WEG Guia de Instalacao Mt6050ip Mt8050ip Quick Guide English

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

MT6050iP MT8050iP INSTALLATION INSTRUCTION

1. INSTALLATION AND STARTUP GUIDE 2. Unpacking the Unit Note! 7. Calibration Mode
Unpack and check the delivery. If damage is found, 1. Connect positive DC line to the + terminal and Launch Project Manager, select MT6000/8000 iP Series
Read these instructions carefully before installing, notify the supplier. the DC ground to the - terminal. in Type field, select Ethernet or USB cable, and then
operating or perform maintenance in this equipment. 2. Please do not connect HMI with PLC and PC click Calibrate Touch Panel button to start calibration.
(1) simultaneously to prevent potential difference from
This document covers the installation of destroying USB ports of HMI and PC.
MT6050/8050iP HMI, for the detailed specifications (2) To make a connection, strip about 3/8 of insulation
and operation, please refer to brochure and EasyBuilder off the end of the wire, turn the connector screw
8000 user manual. (3) counterclockwise until the gap is wide open, insert
the wire all the way in, and turn the screw clockwi-
Install environment: (4) se until its tight.
MT6050/8050iP Series HMI is
NEMA Rating 1. Installation Instruction, 2-sided A4 *1 5. System Settings
NEMA 4 rated. 8. Communication Connections
2. Human Machine Interface *1 When HMI powered up and displays image,
MT6050/8050iP Series has Note!
3. Power Connector *1 click the system setting button (default System Pass-
been tested to conform to Only Com1 (RS485 2 W) supports MPI 187.5K.
European CE requirements. 4. Brackets & Screws V3 *1 pack word: 111111). It is necessary to connect the HMI to
This means that the circuitry your network through a RJ45 cable (N/A for MT6050iP).
9 pin, male, Sub-D
is designed to resist the Note!
COM1 (RS232)
Electrical environment effects of electrical noise. Place the operator panel on a stable surface during
This does not guarantee noise COM1 (RS485)
installation. Dropping it or letting it fall may cause
immunity in severe cases. COM3 (RS485)
damage.
Proper wire routing and
grounding will insure proper Go to the Network tab, you may choose to auto get
operation. 3. Installation Instructions
DHCP IP, or designate your own IP. COM1 (RS485)
Secure the operator panel in position, using all the COM1 COM3
(1) Make sure that the PIN# Symbol
fastening holes and the provided brackets and screws: 4 wire 2 wire (RS232) (RS485)
displays are installed correctly
and that the operating limits 1 Rx- Rx- Data-
are followed. Avoid installing
units in environments where (A) 2 Rx+ Rx+ Data+
severe mechanical vibration
3 Tx- Tx-
or shocks are present. Recorte
Cutout
(B)
(2) Do not operate the unit fusvel 4 Tx+ Tx+
in areas subject to explosion
hazards due to flammable 5 GND GND
Environmental gases, vapors or dusts. 6 TxD Transmit
considerations (3) Do not install the unit where 6. EasyBuilder 8000 Software
acid gas, such as SO2 exists. Type A (mm) B (mm)
Settings 7 Data- Data-
(4) This device should be Please use EasyBuilder 8000 V4.65.06 or later versions. 8 Data+ Data+
mounted in the vertical MT6050iP 119 93 Launch EasyBuilder 8000 software, select your
position and for use on the project file, press F7 shortcut key to open the download 9 RxD Receive
MT8050iP 119 93
flat surface enclosure.
dialog box: For MT6050iP, select USB cable/For
(5) Conform to UL508
(ISBN 0-7629-0404-6) MT8050iP, select Ethernet>IP tab>Enter your HMI
machine safety for use
4. Power Connections IP>Click Download to download this project file to HMI
in Pollution Degree 2 (please refer to EasyBuilder 8000 User Manual
Environment. for software operation details).
Software available free-of-charge at www.weg.net.
Cable Different cables are required for various FUSING REQUIREMENTS!
requirement devices. If the display does not come on within
5 seconds of power up, remove power.
Restrict cable length to less than 500
An internal fuse will prevent damage if
(150 m) for RS485/422 devices and
the polarity of the DC power is incorrect.
50 (15 m) for RS232 devices to avoid
Check wiring for proper connections and
communications problems.
try to power up again.
Shielded cable must be used for long
CAUTION! lengths or cables run in an electrically noisy HIGH VOLTAGE!
environment. An Internal fuse will prevent damage for
Do not run cables next to AC power lines overcurrent condition however it isnt
or near sources of electrical noise. guaranteed. DC voltage sources should
Be sure that the cable ends have been provide proper isolation from main AC
inserted all of the way into mating power and similar hazards.
connectors and are secure.
EMERGENCY STOP!
HARDWARE CONSIDERATIONS! A Hard-wired emergency stop should be
The system designer should be aware that fitted in any system using a HMI to comply
devices in controller systems could fail with ICS Safety Recommendations.
and thereby create an unsafe condition.
SUPPLY VOLTAGE CONDITION!
Furthermore, electrical interference in an
Do not power the HMI and inductive DC
operator interface can lead to equipment
loads, or input circuitry to the controller,
start-up, which could result in property
with the same power supply. Note: the
damage and/or physical injury to the
24 V dc output from some controllers
operator.
may not have enough current to power
If you use any programmable control
the HMI.
systems that require an operator, be aware
that this potential safety hazard exists and WIRE ROUTING!
take appropriate precautions. Although 1. Power wire length should be minimized
the specific design steps depend on (max: 500 m shielded, 300 m unshielded).
your particular application, the following 2. Please use twisted pair cables for power
precautions generally apply to installation wire and signal wire and conform to the
of solid-state programmable control impedance matching.
devices, and conform to the guidelines for 3. If wiring is to be exposed to lightning or
installation of Controllers recommended in surges, use appropriate surge suppression
NEMA ICS 3-304 Control Standards. devices.
4. Keep AC, high energy, and rapidly
PROGRAMMING CONSIDERATIONS!
switching DC power wiring separated from
To conform with ICS Safety
signal wires.
Recommendations, checks should be
5. Add a resistor and capacitor in the parallel
placed in the controller to ensure that all
connection between the ungrounded DC
writable registers that control critical parts
power supply and the frame ground. This
of plant or machinery have limit checks
provides a path for static and high frequency
built into the program, with an out-of-limit
dissipation. Typical values to use are 1 M Ohm
safe shut down procedure to ensure safety
and 4,700 pF.
of personnel.
Note!
Make sure that all local and national
CAUTION! electrical standards are met when
installing the unit. Contact your local
authorities to determine which codes
apply.
POWER!
The HMI can be powered by DC power
only, voltage range: 24 20% Volts DC,
compatible with most controller DC systems.
The power conditioning circuitry inside the
unit is accomplished by a switching power
supply. The peak starting current can be as
high as 750 mA.

You might also like