CBS305
CBS305
CBS305
FOR
CAUTION
Meggers and high potential test equipment should be used
with extreme care. Incorrect use of such equipment could
damage components contained in the device.
CONFIDENTIAL INFORMATION
The following table of information provides a historical summary of changes made to this instruction manual.
RevD/17075 Added UL and CSA marks to front panel drawings in the manual. Added
UL and CSA information to the specifications portion of Section 1. Revised
manual to new format.
GENERAL DESCRIPTION
The Current Boost System (CBS 305) consists of a current boost module and a current transformer (CT).
The system provides an additional current source along with the APR 63-5 voltage regulator which allows
the field to receive full forcing during generator overloading and short circuits.
The CBS 305 allows three-wire and four-wire generators to provide current during sustained single-phase
and multi-phase line-to-line faults. The CBS also permits four-wire generators to support phase A and C
line-to-neutral faults (phase B line-to-neutral faults will have some fault sustaining capabilities since the APR
63-5 regulator input power is taken from the other two unshorted phases).
The Current Boost Module uses the CB+ and CB- outputs of the APR regulator as a control signal. Boost
power to the module is supplied from a CT installed in phases A and C of the generator output. During short
circuits, the CT is the source of all excitation current.
Because the APR 63-5 regulator sensing is the source for the Current Boost System control, the boost
operating level is automatically adjusted to the nominal generator voltage. The CBS control signal also
tracks the regulator~s underfrequency curve to allow the prime mover to pick up large loads in one step.
SPECIFICATIONS
Refer to Table 1-1 for the electrical specifications and to Table 1-2 for the physical specifications.
Table 1-1. Electrical Specifications
a. Refer to Figures 2-4 through 2-8 for the interconnection diagrams and connect as shown therein.
NOTE
Be sure that the two power leads from the two phases pass through
the CT window in opposite directions.
b. The generator leads must be provided with adequate insulation for the generator operating voltage.
Insulated cables or insulated bus bar may be used. Proper support for the cables/bus bar during
short circuit must be provided.
Figure 2-4. CBS 305 Interconnection With 208 to 240 Vac Generators
SELECTION OF CT TURNS-RATIO
The boost system requires current from two phases of the generator output. The interconnect diagrams
illustrate the use of one CT with two phases on the primary or two CT's with one phase on each primary.
The following procedure is used to calculate the number of CT primary turns (generator output lines wound
through the CT window by the installer) for each phase and the secondary turns required.
Step 1. Calculate the exciter field current during a generator short circuit:
E
IField
Where:
Step 2. From the generator manufacturer's short circuit saturation data (plot of exciter field current versus
line amps with generator output short circuited), determine the generator three phase line current
during a short circuit that would result from the exciter field current calculated in Step 1.
Step 3A.
a. Determine the desired acceptable generator three phase line current at short circuit (typical-
ly 300% of nominal). Refer to Table 2-1 or 2-2 (as appropriate) and locate the range that
covers the value in Column 1.
b. Using the generator manufacturer's short circuit data (plot of exciter field current versus line
amps with the generator short circuited), determine the exciter short circuit field current
needed to generate the acceptable generator line current. Refer to Table 2-1 or 2-2 (as
appropriate) and locate the current value equal to this value in column 3. If the field current
desired is in between the column 3 values, go to the next higher value.
c. Check that the rated generator full load line current doesn't exceed the maximum continu-
ous line current. If the generator full load line current does exceed the maximum continu-
ous line current rating, consult the factory.
Column 2 Column 3
3-Phase Line Maximum Exciter Field Current at Rated CBS 305 Output
Current @ Continuous Voltage (90 Vdc)
Short Circuit Line Current
1.8 Adc 3.6 Adc 7.2 Adc Transformer
d. To obtain a reduced field current, place a current limiting resistor in series with the exciter
field. The value of this resistance is calculated as follows:
E
RS
Rf
I2
Where:
I2 = field current required to produce acceptable generator line current at short circuit.
e. Proceed to step 4.
Step 3B.
a. In Table 2-1, Column 1, locate the range of the generator three-phase short circuit line
current that covers the value determined in step 2.
b. In Table 2-1, Column 3, locate the exciter short circuit field current that is closest to the
value determined in step 1. If the calculated field current is between the values in Column
3, go the next higher value.
c. Proceed to step 4.
b. The first numeral of the turns-ratio indicates the number of turns of each generator line that
passes through the CT window. The second numeral indicates the CT secondary turns.
Refer to Table 1-1 and to Figures 2-2 and 2-3 for the terminal numbers corresponding to
the desired secondary turns.
Step 5. Verify that the CT "window" size is sufficient for the generator conductor by comparing the conductor
cross-section (including insulation) with the CT window area.
EXAMPLE 1
Step 1. Determine the field current that will be provided by a Basler CBS 305 during short circuit:
E 90Vdc
IF
6.0 A
R 15ohms
Where:
IF = Field current.
Step 2. From generator manufacturer's data, you determine that the exciter field current of 6.0A from the
CBS 305 would result in a short circuit line current of 525 A - for your generator system you consider
this to be:
Step 3A. You determine that 450 A would constitute an acceptable generator line current at short
circuit. From the generator manufacturer's data, you determine that an exciter field current
of 5.14 A is required for the generator system to deliver an acceptable 450 A at short circuit.
Determine the necessary resistance to be added to the exciter field to achieve the
5.14 A exciter field current as follows:
90Vdc
RS
15
(17.5 15
)
2.5
5.14
In Table 2-1, Column 1, the value of 450 A is between the values of 275 to 55O A.
Draw a horizontal line from this point across the chart.
In Table 2-1, Column 2, the maximum continuous line current of 200 A is greater
than the full load line current of 150 A, therefore, the limits are not exceeded.
In Table 2-1, Column 3, the value of 7.2 A corresponds with the required value of
5.14 A (from step 3A). Draw a vertical line from this point down the chart.
Step 3B. In Table 2-1, Column 1, the value of 525 A (from Step 2) is between the value of 275 -550
A. Draw a horizontal line from this point across the chart.
In Table 2-1, Column 3, the closest value to 6.0 A (from Step l) is 7.2 A. Draw a vertical line
from this point, down the chart.
Step 4. From Table 2-1, the intersection of the two lines (from Step 3B) is the turns-ratio, 4:209.
Step 5. The first numeral of the turns-ratio (4), the number of conductors per phase (1), and the number of
phases (2), multiplied together results in: 8 conductors (through the CT window). From the
generator manufacturer's data, 0.537 is the conductor diameter; therefore, for 8 conductors, the CT
window must be at least 0.537 in. X 4.30 in. Basler CT P/N BE 21331-001 is 0.9 in. X 4.375 in. and
meets the requirements. Selection is complete.
NOTE
This procedure is to be used only for determining the turns-ratio for the
BE 21331-001 current transformer.
a. The turns-ratio indicated in Table 2-1 will provide the CBS with ample operating current. However,
the number of primary turns through the CT may be reduced by using the steps in this paragraph
to more precisely match the CBS to the generator system.
Step 1. Using the exciter short circuit field current obtained from the generator manufacturer's short circuit
data, calculate the required secondary current as follows:
ICT SEC
(IFIELD 1.25)
Where:
Step 2. Calculate the primary ampere-turns required by the CT to provide the secondary current as follows:
PAT
(209 ICT SEC)
Where:
P AT = Primary ampere-turns.
(1.73 ILINE)
Where:
N PRI = Number of primary turns.
P AT = Primary ampere-turns.
I LINE = 3-phase line current at short circuit.
Step 4. Round the result to the next higher whole number. This result is the number of primary turns
required per phase.
Step 5. Verify that the maximum continuous line current rating has not been exceeded by calculating the
following:
CONTINUOUS PAT
NPRI ILINE (Continuous)
Where:
If the result is less than 800 A-T (ampere-turns), the design is acceptable.
If the result is more than 800 A-T, consult the factory.
EXAMPLE 2
I FIELD = 6.0 A
Step 4. Determine the CT secondary current required by the boost system as follows:
ICT SEC
(IFIELD 1.25)
6.0 A
GENERAL
Operation of the Current Boost System is completely automatic and controlled by the APR63-5 voltage
regulator.
INSTALLATION VERIFICATION
Preliminary
(1) Ensure that the prime mover is not turning.
(2) Verify the installation, the turns-ratio selection, and that the interconnection is in accordance
with Section 2.
(3) Verify voltage regulator installation per the appropriate voltage regulator instruction manual.
Testing
(1) With the generator under a "no-load" condition, start-up the prime mover and the generator.
Verify voltage regulator operation.
(2) Connect of a voltmeter configured to read 120Vdc to the current boos module terminals
listed in Table 3-1.
Table 3-1. Voltmeter Connections
Positive (+) P
Negative (-) N
(3) Observe that the voltmeter indicates approximately -1.5 Vdc. (This small negative voltage
will change to a large positive value during boost.)
(4) Connect a load to the generator to cause a 25% or greater dip in rated voltage output.
(5) Observe that the BOOST indicator on the Current Boost Module lights and the voltmeter
indicates a positive voltage of less than or equal to 120 Vdc for the CBS 305.
(7) With a balanced load applied to the generator, measure the generator line current (I L) and
the boost CT secondary current (I SEC).
(8) Verify the calculated turns-ratio (paragraph 2-4) by using the following equation and then
compare the calculated secondary current with the actual measured value
(1.73 N PIL)
ISEC
NSEC
BENCH TEST
Step 3. Close the switch (SWl). The Input light bulb should glow at full brilliance. The BOOST light and
Output light bulb should be off.
Step 4. Open the switch (SWl). The Input light bulb should decrease in intensity and the BOOST light and
Output light bulb should illuminate.
Step 6. Disconnect the switches, light bulbs, and current boost module.