In This Lecture We Will Learn The Following:: Fafewffghjjjj FSD KHJKMKFFJKHG Objectives
In This Lecture We Will Learn The Following:: Fafewffghjjjj FSD KHJKMKFFJKHG Objectives
In This Lecture We Will Learn The Following:: Fafewffghjjjj FSD KHJKMKFFJKHG Objectives
Fsd
khjkmkffjkhg Objectives
When an equipment (e.g. transmission line, transformer, generator, motor) is operating within the rated specifications (speed,
voltage, current etc.), we say that it is in the normal splokpby;ikmhjjulkjijlkitate. Therefore, abnormal state pertains to deviation
from the rated operating point. It may refer to overcurrent, under voltage, over or under frequency. If the apparatus continues
to operate in this state for long enough time, it can lead to damage or reduction in life of the equipment. On the other hand, it
may be also unsafe to operate in this region. A fault refers to a serious abnormality which typically requires immediate
deenergization of the equipment.
Usually, faults are considered dangerous because of overcurrent that they create. This can damage the apparatus and it
endangers the human safety. Three phase faults, Line to Line faults (LL), Single Line to Ground fault (SLG), Line to Line
Ground faults (LLG) are some standard faults considered in our analysis. Three phase faults and Line to Line faults are also
known as phase faults while Single Line to Ground and Double Line to Ground faults are also known asground faults.
However, not all faults create large overcurrents. For example, earth faults which may result due to partial insulation failure
may not create large currents. However, it makes operation of the equipment unsafe from human safety perspective and
further, if the fault is left unattended it can aggravate.
Meshed system or a system with multiple sources require directional relays discussed in subsequent lectures. The first step
in the overcurrent protection is estimation of the fault current. If the system is radial and fed from a single or equivalent
source, this job is simplified. For conservative calculation, utility source impedance should be considered as zero (unlimited
MVA supplying capacity). The reason for this assumption is that, changes in utility system, addition of generators,
strengthening of transmission network etc. can reduce the source impedance. Consequently, the maximum fault current is
limited by the impedance of the distribution transformer. In a single source radial system, typically fault current reduces as we
move away from the source (an exception being a system with large motor loads at the remote ends). The transformer short
circuit current can be calculated from this formula,
An enormous variety of fuses are available today. In terms of quantity, fuses outnumber any other over current protection
devices. They provide economy in protection as well as flexibility in rating and time current characteristic. They are used
for overcurrent protection of transformers, capacitors and lateral taps in distribution systems.
Fig 14.2 shows location of fuses in a distribution system. Each transformer and capacitor bank has fuse protection to
selectively disconnect the device in case of a fault in the device. Transformer fuses can also provide overload protection.
The sectionalizing fuses are used to divide the system into smaller sections which can be then isolated from the rest of the
system. For the fault F1 or F2 it is the responsibility of fuse A to operate. Thus, only customers connected to this line are
affected. In absence of fuse A, fuse B would have to be operated but this would lead to a interruption in service to larger
number of customers. Role of reclosers will be discussed in later lectures.
Total clearing TCC curve (fig 14.4) describes this information. For
lower currents, melting time can be large and arcing time small
The expulsion type fuse is used where expulsion gases cause no problem such as in overhead circuits and equipment.
These fuses can be termed as current awaiting types; and the function of interrupting medium is similar to that of an ac
circuit breaker. The temperature of arc is of the order of 4000-5000K. At this temperature special materials located in close
proximity to fuse element rapidly create gases. Preferred gas generating materials are fiber, melamine, boric acid and
liquids such as oil or carbon tetrachloride. These gases help to create a high pressure turbulent medium surrounding the
arc, thus when the current does reach to zero and the arc channel reduces to a minimum; the ablated gases rapidly mix
with remaining ionized gas and thereby deionize them as well as remove them from arc area'. In turn, this leads to rapid
build up of dielectric strength that can withstand the transient recovery voltage (TRV) and steady state power system
voltage.
TRV for expulsion fuse is shown in fig 14.5. Note that in an inductive circuit, current zero occurs at lag to voltage i.e.
when voltage is at maximum value. The action of interrupting medium causes TRV to be seen in this region.
Suppose that an overcurrent protective element could insert a large resistance in series during fault current. This would then
improve the power factor in the fault circuit which otherwise is more or less inductive. Thus, the zero crossing of the current
and voltage would be in phase. This implies that when the arc is extinguished temporarily at current zero, the applied voltage
across it will also be zero. This should be contrasted with expulsion type or current awaiting type fuse where typically, I(t) = 0,
V = Vm. ( phase lag in an inductive circuit). If at current zero, V(t) = V m, then the presence of a large electric field does
not help in quick de-ionization. In contrast, when the current zero and voltage zero are in phase, then when the temporary arc
is extinguished, the dielectric medium will be quickly de-ionized. (This also reduces TRV. Inclusion of higher resistance also
reduces peak value of current.)
Earc(t) is the arc voltage and V(t) is the source voltage, then
differential equation governing the circuit is:
when
Review Questions
1. Differentiate between abnormal state and faulty state.
b) Interrupting rating.
c) Voltage rating.
5. Explain how does a current limiting fuse, insert a high series resistance in the fault circuit? What benefits does it
achieve?
Recap
Available Fault Current: This is the maximum rms short circuit current that flows to a faulted node or point. The
magnitude is limited by the ac impedance to that specific point. The impedance is the sum of the utility source impedance
and the in-plant circuit impedance.
Continuous Current Rating: As with all overcurrent devices, most fuses are limited to a continuous loading of 80% of
their label rating. This is due to the mutual heating between switch, fuse and adjacent devices.
Current limiting Fuse: First generation fuses, e.g. expulsion type, only limit the duration (time) of the fault. The modern
current-limiting fuse, however, not only limits the duration of the fault, but also limits the magnitude of the fault.
Interrupting Rating: This is the maximum current that overcurrent device can safely interrupt at a stated voltage,
frequency, and short circuit power factor. Interrupting ratings are expressed in rms symmetrical amperes. It is common for a
device rated 200 000 A to have an abbreviated marking such as 200 KA IR.
Voltage Rating: The rms alternating current voltage at which the fuse is designed to operate. Fuses of the 600 V class
will always function safely on a lesser voltage. For example 600 V fuses are typically used on 480 and 208 V.