Magrini Galileo Cat Gen
Magrini Galileo Cat Gen
Magrini Galileo Cat Gen
Instrument
Tr a n s f o r m e r s
page
Main characteristics 2
A certified quality system 3
Current transformers 4
Current transformers types 4
Specifications 6
Standardized current transformers 8
Order form 34
Voltage transformers 35
Voltage transformers types 35
Specifications 36
Standardized voltage transformers 38
Order form 53
c Their standard shape, top electric performance, c Extremely good ageing behaviour both to heat mass ageing according to IEC 216
reduced weight and overall dimensions make these (over 20 years at 120 C) and to surface ageing obtained in salty mist
devices suitable for use in:
v metalclad units c In case of fire, no toxic substances are released in accordance with standards
v metal enclosed units IEC 20-37, IEC 20-22 and ASTM D 3286.
v large motor terminal strips
v environments with potentially explosive c Extremely effective behaviour in tropical climates.
atmosphere (Eex).
c High strength even at the highest working temperatures
(Martens point exceeding 105 C).
F2 Forces applied
not simultaneously
up to 100C
F1 F1 = 500 daN
F2 = 300 daN
Quality is obtained by planning and implementing Magrini Galileo, brand of Schneider Electric can prove its Guaranteed Quality via:
every phase, from the initial design all through c documentations explaining the company quality policy
production and testing to product delivery and c the planning of each individual product development phase
after-sales service. c continuous assessment of special indicators showing any possible quality faults
This means operating in full application of the Quality throughout the production process
Guarantee. By this procedure it is possible to supply a c a set of technical/quality papers providing evidence of what has been done all
product with all the design characteristics on the one through the production and testing process in order to guarantee the required
hand, and to show the Customer all that is planned quality level.
and implemented in order to come up with a good
product on the other hand. Production process applies standard Guarantee and Quality Control methods.
Quality Control Plans ensure that established procedures are applied to product
checking from construction material reception all the way to product delivery.
The earliest phases of product design and industrialization are also set up and
verified according to Guaranteed Quality principles.
CSQ is an independent
organisation for the
certification of company
management system,
member of the CISQ
(Italian Certifiers of
Company Quality Systems),
its active within the scope
of IMQ with the support of
CESI, these being
internationally
acknowledged boards in the
electrical engineering
industry.
Post type
type reference short-circuit max possible refer notes
voltage thermal current primary number to
(kV) in multiple of rated of CT page
Ipn x 1 s current cores (n)
(max 60 kA x 1s) (A) (no.)
ARM1 7.2 - 12 100400 SR 800 1-2 8
ARM1 ARM2 ARQ1 17.5 - 24 DR 800-400 compact
ARM2 7.2 - 12 100630 SR 800 1-2-3 9 size
ARQ2 17.5 - 24 DR 800-400
ARM6 ARM7
Note
(1) SR = single ratio - DR = double ratio,
(2) All the apparatus have a 120% extended range, which means that the transformers can
be overloaded 20%beyond their rated current without exceeding the class.
ARM9
Support type
type reference short-time max possible reter notes
voltage thermal current primary number to
(kV) (A) rated current of CT page
cores (n)
ARO1a 7.2-12 max 60 kA x Ipn SR 5000 1-2-3 24 without
primary for
ARO1b 17.5 DR 5000-2500 mounting
ARO2 24-36 max 60 kA x 1s SR 4000 1-2-3 25 directly on
ARO1 ARO2 busbar
DR 4000-2000
Warning:
This equation is only guaranteed during CT selection phase.
266 160
Dimensions (mm)
8
8
Type A B C
ARM1 250 290 310
14
50
P1
P2
220
P1
VA = nominal output
Isn = secondary rated current
Ze = measuring instrument impedance (ohm)
Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM2, ARM3, ARM4,ARM8
Dimensions (mm)
Type ARQ1/N1-N2 Type ARM1/N1-N2
Weight 13.5 kg Weight 14 kg
50 N4 fixing holes 50
M 8 x 12 86
110 43 M 12
GROUPE SCHNEIDER
287
282
279
75
274
248
243
GROUPE SCHNEIDER
240
235
P2
5
130
158
110
85
20
P1
65
115
115 97 200
N4 holes
158 225 11
M6 screw type 212 M6 screw type
secondary and earthing terminals
secondary and earthing terminals
Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM3, ARM4, ARM8
If such point should fall within the grey area, choose a smaller CT type:
ARM1.
Dimensions (mm)
Type ARQ2/N1-N2-N3 Type ARM2/N1-N2-N3
Weight kg 19 Weight kg 19.5
N4 fixing holes
M 8 x 12 50
50 110 86
43 M 12
287
279
248
240
20
110
P2
130
158
282
274
85
5
243
GROUPE SCHNEIDER
235
90
P1
145
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2.
If such point should fall within the white area, a larger CT type
should be used: ARM4 - ARM8.
50 N4 fixing holes 86 50 43 M 12
M 8 x 12
110
P1
GROUPE SCHNEIDER
82
P2
338
330
333
325
300
292
295
110
287
23
120
90
225
5
N4 holes
11
260
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area..
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2 - ARM3.
If such point should fall within the white area, a larger CT type
should be used: ARM8.
50 N4 fixing holes 86 50 43 M 12
M 8 x 12
110
P1
GROUPE SCHNEIDER
175
200
52
GROUPE SCHNEIDER
P2
82
338
333
330
325
300
295
292
287
110
23
225
90
N4 holes
5
148
11
260
1000
1200
1250
800-400
1000-500
1200-600
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARJP3/N1-N2-N3
Weight kg 22
72 M 12 x 23
P2
20
120
148
270
240
120
185 137 184
175 100 N4 slot
11
322 295
M6 screw type
secondary and earthing terminals
1000
1200
1250
1600
800-400
1000-500
1200-600
1500-750
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARJM3/N1-N2-N3
Weight kg 25
M 12 x 23
NUOVA MAGRINI GALILEO
260
20
178
P2
120
148
P1
185 137
120
322
M6 screw type 184 N4 slot
secondary and earthing terminals 11
175 100
295
1200
1250
1500
1600
1800
2000
2500
1000-500
1500-750
2000-1000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARJP3.
Dimensions (mm)
type ARJA1/N1-N2-N3
Weight kg 30
P2
175
200
P1
40
45
160 148
58
70
M6 screw type
secondary and earthing terminals 120
308
60
184 60
N4 holes 70
225 11
260
Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.
Dimensions (mm)
TypeAD12/N1-N2-N3
Weight kg 20
12.5
11
C1
P1
C1
P1
C1
P1
223
GROUPE SCHNEIDER
C2
C2
P2
C2
P2
P2
P1
P2
125
100
148
DIN 1030
M8 c c
Pg 16
18.5
254
184
20
177 150
270
350
1000
1200
1250
800-400
1000-500
1200-600
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type AD13/N1-N2-N3
Weight kg 20
M12 x 23
DIN 40430
M8
Pg 16 GROUPE SCHNEIDER
223
125
148
K
L
100
P1
P2
31
M5 screw type
secondary and earthing terminals
177 150
20
120 N4 holes 11
350
184
270
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the white area, a larger CT type should be
used: AD22.
Dimensions (mm)
type AD21/N1-N2
Weight kg 23
P1
P1
11
280
P2
P2
C2
C2
M8
P1
178
DIN 40430
150
100
Pg 16 18.5
319
P2
184
163 160
20
280
370
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
AD21.
Dimensions (mm)
type AD22/N1-N2-N3
Weight kg 28
1 x Ipn 2 x Ipn
GROUPE SCHNEIDER
280
C1
C1
P1
P1
P1
P2
150
178
100
DIN 40430 M8
Pg 16
C2
C2
P2
P2
311
184
178 160
20
280
370
1000
1200
1250
1500
1600
2000
2500
DR
800-400
1000-500
1200-600
1500-750
1600-800
2000-1000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type AD23/N1-N2-N3
Weight kg 30
178
100
P2
P1
40
31
45
58
70
M5 screw type
178 160 120 secondary and earthing terminals
20
60
370 184 N4 holes 14 60
70
280
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM7 - ARM8.
Dimensions (mm)
type ARM6/N1-N2
Weight kg 22
86 50 43 M 12
P1
175
200
GROUPE SCHNEIDER
52
P2
408
400
370
362
225
N4 holes
23
11
260
5
122 102
M6 screw type
secondary and earthing terminals
224
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM6
If such point should fall within the white area, a larger CT type
should be used: ARM8.
Dimensions (mm)
type ARM7/N1-N2-N3
Weight kg 30
86 50 43 M 12
P1
175
200
GROUPE SCHNEIDER
52
GROUPE SCHNEIDER
P2
408
400
370
362
225 N4 holes
11
23
260
157 150
M6 screw type
secondary and earthing terminals
307
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2 - ARM3 - ARM4 for Um 24 kV;
ARM6 - ARM7 for Um = 36 kV.
Dimensions (mm)
type ARM8/N1-N2-N3
Weight kg 45
86 50 43 M 12
GROUPE SCHNEIDER
P1
175
200
249
52
GROUPE SCHNEIDER
P2
408
400
370
362
23
225 N4 holes
5
11
260
152 150
M6 screw type
secondary and earthing terminals
302
1200
1250
1500
1600
1800
2000
2500
1000-500
1500-750
2000-1000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARM9/N1-N2-N3
Weight kg 35
GROUPE SCHNEIDER
Ipn Ipn
800 1600 A 1800 2500 A
200
P2
175
362
P1
40
45
23
70
120
5
184
70
225 N4 holes
157 150 M6 screw type 260 11 70
secondary and earthing terminals
307
1200
1500
2000
3000
4000
5000
2000-1000
3000-1500
4000-2000
5000-2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARO1a/N1-N2-N3 and ARO1b/N1-N2-N3
Weight kg 27
L
175
200
P1 P2
369
230
23
GROUPE SCHNEIDER
225
5
N4 holes
11
260
c type ARO1a/N1-N2-N3
M6 screw type secondary
L = 238 mm = 110 mm and earthing terminals
c type ARO1b/N1-N2-N3
Connection between primary
L = 248 mm = 130 mm and shielding (lenght 300 mm)
1200
1500
2000
3000
4000
2000-1000
3000-1500
4000-2000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARO2/N1-N2-N3 248
Weight kg 32
110
175
200
P1 P2
420
280
225 N4 holes
23
GROUPE SCHNEIDER
11
5
260
400 400-800
600 600-1200
800 800-1600
1000 1000-2000
1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15
3) In case of double (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF1/N1-N2
Weight kg 8
85
25
100
M6 secondary
terminals
140
170
198
GROUPE SCHNEIDER
7
P1
170
N4 slot
198 9 x 11
130
229
400 400-800
600 600-1200
800 800-1600
1000 1000-2000
1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15
If such point should fall within the grey area, choose a smaller CT type:
ARF1.
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF2/N1-N2-N3
Weight kg 12
85
25
150
M6 secondary
140
170
198
7
GROUPE SCHNEIDER
terminals
P1
170 N4 slot
198 9 x 11
130
229
100 200-100 * **
150 300-150 * ** *
200 400-200 ** **** **
300 600-300
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1200
1500
2000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF3/N1
Weight kg 7
105
30
S2
S1 S3
100
M6 secondary P1
terminals
198
GROUPE SCHNEIDER
83
113
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF4/N1-N2
Weight kg 14
105
25
100
M6 secondary
terminals
140
200
238
7
GROUPE SCHNEIDER
P1
200
238 N4 slot
9 x 11
152
271
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF5/N1-N2
Weight kg 12
125
25
100
M6 secondary
terminals
140
200
238
GROUPE SCHNEIDER
7
P1
200
238 N4 slot
9 x 11
152
271
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF6/N1-N2
Weight kg 10
150
25
100
M6 secondary
terminals
140
200
238
GROUPE SCHNEIDER
7
P1
200
238 N4 slot
9 x 11
152
271
Schneider Instrument Transformers
Electric Merlin Gerin 31
Toroidal type Current transformers
AOP-C/N1 - AOP-C/N2
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500 3000-1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs15 ** cl. 0.5 Fs15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type AOP-C/N1-N2
Weight kg 15
200
GROUPE SCHNEIDER
25
100
M6 secondary
terminals
373
7
P1
140
290
330
225
N4 slot
264 9 x 11
208
800 1600-800
1000 2000-1000
1250 2500-1250
1500 3000-1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARL4/N1-N2
Weight kg 30
25
100
220
90
GROUPE SCHNEIDER
M6 secondary
terminals
400
557
Part 1
Type: _________________________________________________________________________________________________________
Number of secondaries: 1 2 3
2nd secondary Output: ________________ Class: ___________ Security factor/Accuracy limit factor ______________________
3rd secondary Output: ________________ Class: ___________ Security factor/Accuracy limit factor ______________________
Capacitive tap:
Frequency: 60 Hz Others
Others:
Note
Apparatus with the following features are defined as standard:
electrical features, max. reference voltage, rated current, output and class strictly as indicated in the table of option from page 8 to 33
primary contacts and terminals, if requested, are tin plated
pickled copper secondary terminals
fixtures, if any, are zinc-plated steel.
VRCR VRC3
produce resonance.
in the immediate vicinity of the VT. We suggest to use 10A/500V fuses for "earth
70 pole" devices and 6A/500V fuses for "insulated poles" devices.
Fairleadbush 12
Fixing slots 20 x 8
20
120
354
Rated performance calculation one secondary (instrument or protection) double primary ratio (with tap at secondary)
a1 - b small ratio; a2 - b high ratio
table
Power absorbed by measuring instruments and Maximum Single (grounded) pole Two (insulated) poles
protection relays reference
(alternating current 50 to 60 Hz) voltage for
Type of instrument or relay insulation
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRFRn/S1-S2
VRFR/S1-S2
Weight kg 15
M 10
125
148
A
221
270
5
N4 holes
M6 screw type secondary 11
and earthing terminals 300
140 117
257
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRF1n/S1-S2
VRF1/S1-S2-S3
Weight kg 21
M 10 170
155
180
A
240
30
155
NUOVA MAGRINI GALILEO
N4 holes
11
225
177 155
M6 screw type secondary
and earthing terminals
332
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRF2n/S1-S2
VRF2/S1-S2
Weight kg 29
M 10 186
175
200
A A
300
30
225 N4 holes
5
11
260
177 155
M6 screw type secondary
332 and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRQ1n/S1-S2-S3
VRQ1n/S1-S2-S3
Weight kg 30
M 10 158 N4 holes M 6 x 8
A
144
82
275
25
GROUPE SCHNEIDER
180
187 170
M6 screw type secondary
357 and earthing terminals
VRQ2n
VRQ2
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary and
separate operation for 3rd secondary.
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRQ2n/S1-S2-S3
VRQ2/S1-S2-S3
Weight kg 19
M 10 170 N4 holes
M6x8
A
265
135
82
25
115
160 138
M6 screw type secondary
298 and earthing terminals
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRF3n/S1-S2-S3
VRF3/S1-S2-S3
VRF/S1-S2-S3
Weight kg 45
M 10 230
225
255
A
390
300
30
N4 holes
11
5
GROUPE SCHNEIDER
325
192 170
M6 screw type secondary
362 and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRF3Zn/S1-S2-S3
VRF3Z/S1-S2-S3
Weight kg 65
M 10
230
225
255
A
390
300
30
N4 holes
11
5
GROUPE SCHNEIDER
325
197 175
M6 screw type secondary
372 and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VDF11/S1-S2
VDF11n/S1-S2
Weight kg 15
M 10
A
100
125
148
DIN 40430
Pg 16 M8
221
GROUPE SCHNEIDER
270 N4 holes 11
M5 screw type secondary
31
168 150
20
VRQ2n
VRQ2
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VDF21/S1-S2-S3
VDF21n/S1-S2-S3
Weight kg 21
M 10
DIN 40430
M8
A
Pg 16
100
150
178
280
280
n 4 holes 14
370
20
31
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRCR/S1-S2
Weight kg 15
100 110 A
125
148
M 10
B
270
221
N4 holes
30
11
5
300
257
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRC1/S1-S2
Weight Kg 23
M 10 195
150
155
180
30
A B
155 N4 holes
240
300
M6 screw type secondary
and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRC2/S1-S2
Weight Kg 28
M 10 270
210
175
200
30
A B
5
300
225 N4 holes
NUOVA MAGRINI GALILEO
11
260
177 155
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRC3/S1-S2
Weight Kg 45
M 10 380
320
225
255
A B
390
30
300
GROUPE SCHNEIDER
N4 holes
11
192 170 325
M6 screw type secondary
362 and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VDC11/S1-S2
Weight Kg 15
100 110
M 10
DIN 40430
A
Pg 16 M8
100
125
148
221
GROUPE SCHNEIDER
B
31
270 N4 holes 11
M5 screw type secondary
168 150 350 and earthing terminals
20
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VDC21/S1-S2
Weight Kg 21
165 130
M 10
A
DIN 40430
Pg 16 M8
100
150
178
280
GROUPE SCHNEIDER
B
280 N4 holes 14
31
Part 1
Type: _________________________________________________________________________________________________________
Number of secondaries: 1 2 3
Frequency: 60 Hz Others
Others:________________________________________________________________________________________________
Note
Apparatus with the following features are defined as standard:
electrical features, max. reference voltage, rated voltages, output and classes strictly as indicated in the table of options from page 38
to page 52
pickled copper primary holds and secondary terminals
fixtures, if any, are zinc-plated steel.
04/2000