Foam System Calculations
Foam System Calculations
eg
for Projects Services Contracting Email:[email protected]
PROJECT: IBA Hotel Qatar Doha General Input Data (default data)
SYSTEM : Fire Fighting Solution Density [gpm/ft2]
0.16
SUBJECT: Foam System Calculations Discharge Time [min]
10.0
Foame Concentration [%]
3%
Sprinklers Spacing [ft]
100.0
Safety Factor
1.10
G - 35 B Generator Room 8.5 7 4.2 59.5 640.45 249.90 0.16 102.47 1024.72 30.74 33.82 7
Input Input Input Input Input Input Output Output Output Output Output
1 B1 Generator Room 8.5 3.85 3.75 32.725 352.249 122.72 0.16 56.36 563.60
1 Hazard Length = L= 9 m
2 Hazard Width = W= 3.8 m 92%
3 Hazard Area = A= 34.2 m2
4 Hazard Area = A= 368.125736364 ft2
5 Discharge Denisty = d= 0.16 gpm/ft2
6 Discharge Time = T= 10 min 124 4.75001
7 Sprinkler Coverage Area 100 ft2
8 No. of Sprinklers N= 4
9 Total Flow = Qtot = A* d = 58.9001178182 gpm 61.845
10 Concentration = C%= 3%
11 Required Foam Volume = V= 17.6700353455 Gallon 58.90012
12 Flow / Sprinkler = Qsp = Qtot / N = 14.7250294546 gpm 14.72503 2.82 5.221642 27.265542
13 Eductor K-Factor Ke= Qtot / N =
No. of Sprinklers = N= 7 Sp
14 Flow / Sprinkler = Qsp = Qtot / N = 8.4143025455 gpm
15 Discharge Coefficient = K= 5.6 gpm/psi1/2
16 Min. Residule Pressure = Pmin = 2.257668601 psi
16.91 18.60 6