Epoxy Resin Insulators and Silicon Rubber Insulators Industrial Trading
Epoxy Resin Insulators and Silicon Rubber Insulators Industrial Trading
Epoxy Resin Insulators and Silicon Rubber Insulators Industrial Trading
ISA 5
IPA 6
DC - DCP 8
DCL 10
SF - SC 12
IPAN 16
PSE/PSL 18
PRC 20
PRB 22
4
Type ISA
Low voltage post insulators for indoor installation
General characteristics
Post insulators made of epoxy resin (EP UL94V0) or
polyesther reinforced with fiberglass (UP FG), suitable for
indoor application with internal metal fitting. These insulators
are particularly suitable to be used as single supports for
bus-bars, fuses and for other equipment.
Application
For indoor applications with working condition at max.
operating temperature of 160 C (epoxy resin - EP UL94V0)
and 130 C (polyesther - UP FG)
Working voltage
From 0,4 up to 2 kV
Reference standards
IEC 216 - DIN 53452 - DIN 53455
5
Type IPA
post insulators for indoor installation
General characteristics
Epoxy resin post insulators, for indoor application, with internal metal fitting.
These insulators are particularly suitable to be used as single supports for conductors, for
fuses and for other equipment (as switchgears).
Application
For indoor installation with working condition at T max. 100 C.
Working voltage
From 12 up to 36 kV
(40,5 kV available on request)
Reference standards
IEC 60273 (CEI 36/12) - CENELEC HD 578 S1
IEC 60660 (Fascicolo S/663)
IEC 60137
Commercial code
1G101 + drawing (example IPA 7,2/4000 commercial code = 1G10107204)
kV kV kV N mm mm N kg.
JO 4 - 60 IPA 7,2/4000 07204 4000
7,2 60 28 1,5 >150 3 0,6
JO 8 - 60 IPA 7,2/8000 07208 8000
JO 4 - 75 IPA 12/4000 10010 4000 >235 0,7
JO 8 - 75 IPA 12/8000 10020 12 75 35 8000 2 >175 4 0,8
JO 16 - 75 IPA 12/16000 10025 16000 >230 1,5
JO 8 - 95 IPA 17,5/8000 20020 8000 >260 1,1
17,5 95 45 2,7 5
JO 16 - 95 IPA 17,5/16000 20026 16000 >300 2,2
IPA 24/4000
Standard 24210 >360 1,1
JO 4 Enel DJ1053
125 IPA 24/3000 4000 8
Standard 24220
Enel DJ1056 24 125 55 3,2 >370 1,2
IPA 24/4000 24225
JO 8 - 125 IPA 24/8000 30030 8000 >350 1,6
7
JO 10 - 125 IPA 24/10000 30026 10000 >400 2,6
JO 4 - 170 IPA 36/4000 40010 4000 >520 13 1,8
JO 8 - 170 IPA 36/8000 40012 36 170 75 8000 5 >520 12 2,9
JO 10 - 170 IPA 36/10000 40026 10000 >570 10 3,4
6
AccessorIes
Nichel-plated male reduction.
Technical data
h D d1 t1 d2 t2 L d3 t3 d D1 D2
Distance
Maximum Auxiliary Distance
Upper Base between
nominal Hole Hole upper Hole between Maximum Maximum
Isnulator threaded threaded base face
diameter of centre depth depth threaded depth threaded diameter diameter
height hole centre hole and lower
insulating d1 d2 hole d3 holes base face upper face
(tapped) (tapped) threaded
part (tapped) d3
end
mm. (+-1) mm. mm. (min.) mm. (min.) mm. mm. (min.) mm. mm. mm.
M12 0 55
95 82 M12 18 25 70
M16 18 M8 15 46 70
83 14 70 65
130 M12 18 M16 25 M6 15 36
75 18 75 65
116 M16 25 M20 32 36 M10 20 46 100 91
175 83 M12 18 M16 25 35 M6 15 36 76 62
118 M16 25 M20 32 36 M10 20 46 100 91
210
25 0
80 80 54,5
M12 M16 25 M6 15 36
225 35
18
93 18 77 70
110 M16 25 M20 32 42 M10 20 46 100 90
80 32 80 55
M12 18 M16 25 M6 15 36
310 98 60 94 76
110 M16 25 M20 32 42 M10 20 46 100 90
7
Type DC - DCP
Capacitive insulators with low voltage lower reading connection
General characteristics
Epoxy resin post insulators with capacitive devider for the reading of the voltage.
Manufactured with internal metal fitting, they can be equipped with couplings and low
voltage light signal box.
These insulators are mainly suitable to be used as insulated supports of equipment, bus bar
or fuses.
Safety information
The insulators can be equipped with:
- S afety valve type ATS drawing 4500 that, in case of incoming voltage higher than 600 V,
connect to earth the system;
- S ignal box type SF 5600, SC 5583, SCD 5500, and SCB 5590 that, through a gas arrester
installed inside, in case of incoming voltage higher than 600 V, automatically connect to
earth the system.The heart connection system is self-resetting.
Application
Indoor installation at max working temperature of 85 C.
Working voltage
From 12 to 36 kV.
(40,5 available on request)
Reference standards
IEC 60137
Commercial code
1G103 + drawing (example DC 10 commercial code = 1G10350010)
Mechani-
Identification Electrical data H D1 D2 D Technical data
cal data
Maximum
Maximum Lightning Dry power Ultimate nominal
Diameter Diameter diameter
Type Drawing operation impulse frequency Capaci- bending Insilator of base of upper Creepage Fins Weight
voltage voltage voltage tance stress height of distance
face face
whitstand whitstand (PO) insulating
part
kV kV kV pF N mm. mm. mm. mm. mm. N kg.
DC 10 50010 12 75 35 220 3000 130 75 65 75 175 4 0,8
DC 15 50012 17,5 95 45 150 3000 175 76 62 83 260 5 1,1
DC 20 50013 24 125 55 150 3000 225 69 62 78 355 7 1,3
DC 30 50021 36 170 75 75 3000 310 80 55 80 520 13 1,8
DCP 10 50015 12 75 35 220 5000 130 70 65 75 175 4 0,8
DCP 15 50017 17,5 95 45 150 5000 175 76 62 83 260 5 1,1
DCP 20 50018 24 125 55 150 5000 225 76 69 85 350 7 1,6
DCP 30 50019 36 170 75 75 5000 310 94 76 98 520 12 2,9
8
type DC type DCP
Upper
Base
Insulator gaps
type ATS
Drawing 4500
Washer
Steework hole
Grow 16,5 mm
Screw M12/14
Tc M4
Standard
ENEL
DY 811
9
Type DCL
Capacitive insulators with low voltage side reading connection
General characteristics
Epoxy resin post insulators with capacitive devider for the
reading of the voltage
Manufactured with internal metal fitting, they can be
equipped with couplings and low voltage light signal box.
These insulators are mainly suitable to be used as insulated
supports of equipment, bus bar or fuses.
Safety information
The insulators can be equipped with:
- Safety valve type ALS drawing 4700 that, in case of
incoming voltage higher than 600 V, connects to earth the
system;
- Signal box type SF 5600, SC 5583, SCD 5500 and SCB
5590 that, through a gas arrester installed inside, in case of
incoming voltage higher than 600 V, automatically connect
to earth the system.The heart connection system is
self-resetting.
The DCL 24/I capacitive insulator, that utilise epoxy resin as
dielectric; it has low capacitance condenser and low voltage
outlet.
10
With type C outlet it is possible to connect
safety valve type ALS drawing 4700 for over-
voltage protection
Connection 1G10604580
Voltage presence indicators
Standard
ENEL
DY 811
Mechanical
Identification H D1 D2 D3 Technical data
data
Ultimate
bending
stress
Outlet Diameter Diameter
Type Drawing Insilator Quote Creepage
type of base of upper Fins Weight
height D3 distance
face face
11
Type SF - SC
Voltage presence indicators
General characteristics
The voltage presence indicators are devices used to supply information about the main
circuit status inside the equipment where the devices are installed. To each lamp placed
inside the indicator (L1 L2 L3) corresponds one phase of the input line. The line voltage
presence is indicated by switching of the relevant lamp. The signal of voltage presence
necessary to switch the lamps is sourced out by a capacitive coupling with an insulator
equipped with capacitive output.
Application
In MV cubicles for operating voltages from 1 to 36 kV.
Type SF Type SC
The indicator SF is a light signal device made of one single The indicator SC is a light signal device made of one fix part
fix part. The indicator is equipped with a safety system, and one mobile and removable part.The lamps are placed
composed of one gas arrester for each phase, which in the mobile part. The indicator is equipped with a safety
connects the system to ground in case of overvoltage system, composed of one gas arrester for each phase, which
> 600 V. The arresters are self-resetting, this means that at connects the system to ground in case of overvoltage > 600
the end of the discharge the device will start again to function V. The arresters are self-resetting, this means that at the
normally. end of the discharge the device will start again to function
normally.
The above mentioned values were reached by using a standard cable (3 meters length) to connect the capacitive insulator and the voltage indicator.
The values have a 20% variability.
12
type SF 5600
Steelwork Lay-Out
type SC 5583
Back side
Mobile part
Back side
Complete set
13
Type SCD - SCB - SDY
Voltage presence indicators
General characteristics
The voltage presence indicators are devices used to supply
information about the main circuit status inside the equipment
where the devices are installed. To each lamp placed inside
the indicator (L1 L2 L3) corresponds one phase of the input
line. The line voltage presence is indicated by switching of the
relevant lamp. The signal of voltage presence necessary to
switch the lamps is sourced out by a capacitive coupling with
an insulator equipped with capacitive output.
Application
In MV cubicles for operating voltages from 1 to 36 kV.
The above mentioned values were reached by using a standard cable (3 meters length) to connect the capacitive insulator and the voltage indicator.
The values have a 20% variability.
(*) To reach the pulsation level required by DY 811 homologation it is necessary to use a screened RG 58 cable to connect the capacitive insulator DCL
24/I and the voltage indicator SDY 5811.
14
type SCD 5500 tipe SCB 5590
Back side
Mobile part
Steelwork lay-out
Back side
Front side
Complete set
serie SDY
Steelwork Lay-Out
Back side
15
Type IPAN
Bushing for indoor use
General characteristics
12 36 kV epoxy resin bushing insulators.The insulators can be fitted with copper bars
designed from 250 up to 2000 A.
They are equipped with internal metal fittings for installation on the relevant frame and with
brass nuts and washers for fastening of phase connectors.
Application
Indoor installation at max working temperature of 85 C.
Working voltage
From 12 to 36 kV.
Reference standards
IEC 60137 (electrical tests).
Commercial code
1G107 + drawing (example IPAN 10/250 commercial code = 1G10781010)
16
Steelwork holes Lay-Out
17
Type PSE - PSL
Bushing for indoor/outdoor use
General characteristics
12 36 kV cicloaliphatic resin bushing insulators.The insulators can be fitted with copper
bars designed from 250 up to 1000 A. They are equipped with internal metal fittings for
installation on the relevant frame and they are supplied completed with:
B rass nuts and washer for fastening of phase connectors
O-Ring gasket
Screws and nuts for assembling of the bushing on the metallic frame
Application
Outdoor installation at max working temperature of 85 C.
Working voltage
From 12 to 36 kV.
Reference standards
IEC 60137 (electrical tests).
Commercial code
1G110 + drawing (example PSE 10/250 commercial code = 1G11071010)
18
Steelwork holes Lay-Out
19
Type PRC
Protection insulators
General characteristics
Epoxy resin protection insulators, bell shaped, with internal metal fitting.
Application
Indoor application with working condition at T max. 100 C.
Working voltage
From 12 to 36 kV.
Commercial code
1G123 + drawing (example PRC 12 commercial code = 1G12386010)
20
21
Type PRB 24-36 kV
Air-air bushing for indoor use
General characteristics
The PRB bushings can be used as medium voltage inlet for indoor air insulated devices
such as switchgears, in particular for applications in quite small machines.
The bushings are realized on the one side with a coupling interface in accordance with
EN 50180-50181 (DIN 47636; HN 52-S-61) standards. This type of interface allows a
connection with the relevant moving connector. On the other part the sheded side allows a
bare electrical wire connection.
Accessories
Plastic cap for coupling interface protection.
Only on request, alluminium flange suitable to fix the bushing to the steelwork.
The fixing flange is necessary for the 400A version for mobile connector fastening.
Working voltage
24-36 kV
Reference standards
IEC 60137 (electrical tests)
EN 50180-50181 (DIN 47636; HN 52-S-61)
Commercial code
1G1240 + drawing (example PRB 24/400 commercial code = 1G12402430)
22
Assembling instructions
Bushing insulator PRB
Prepare the holes on the body of the tank as indicated in the steelwork holes Lay-out. Remove the paint, or any insulating coat
in the area of fixing holes, in order to guarantee a correct earth connection of the bushing.
Moreover, make sure that the surface where the bushing is placed is without any type of roughness or unevenness. It must be
completely clean in order to guarantee a perfect tightness. It is recommended to use the fixing flange in order to strengthen the
area where the bushing is fixed to the tank. For 400A version the use of the flange is necessary for mobile connector fastening.
Place the flange, when used, and tighten the 3 fixing screws M6, together with their relevant washers, with a tightening force
value of 911 Nm. The tightening operation must be done crosswise. The lower connection (M16) must be fastened with a
tightening force value of 90100 Nm.
During mounting operations the plastic protective cap must be fitted and pressed right down on the bushing, in order to avoid
faults caused by dirt or accidental scratching of the interface.
Fig. 1 Fig. 2
23
Type IPAR - ISOF - IPA
Epoxy resin insulators for rotative switchgear 24 kV
IPAR
Three phase rotating bushing block with recessed
metal fitting for assembling on the steelwork.
Commercial code
1G108 + drawing (example IPAR 65012 commercial code = 1G10865012)
ISOF
Drawing: 69020
Conductor connection insulator with air room for arc estinguishing.
Its equipped with internal metal fitting for the assembling on the steelwork and of the upper
contact.
Reference standards
1G10869020
IPA
Drawing: technical at page 6
Conductor connection insulator with internal metal fitting for the assembling on the
steelwork and of the upper contact.
Application
For indoor use, vertical and horizontal installation.
IPA
IPAR
ISOF
24
Identification Dimensional data Standards
Fig. 1 IPAR
Three phase rotating bushing block type IPAR Special bushing
block IPAR for small
switchgears (500 mm).
Drawing 65016
Fig. 2
insulator with air room type
ISOF
25
26
Insulators for outdoor use
IPAE 28
PRG 24 30
PRG 36 32
PGS 24-36 34
BSL 36
27
Type IPAE
Post insulator for outdoor installation
General characteristics
Cicloaliphatic resin post insulators, for outdoor application, with internal metal fitting.
These insulators are mainly indicated to be used as insulating supports for bus
bar, fuses and other equipment (as outdoor switchgears).
Application
For outdoor installation with heavy (III) pollution level, according to IEC 60815, 71-2.
Working condition temperatures: max 90 C.
Working voltage
From 12 to 36 kV.
(40,5 kV available on request)
Reference standards
IEC 60273 (CEI 36/12) - CENELEC HD 578 S1
IEC 60660 (File S/663)
IEC 60815, 71-2.
Commercial code
1G102 + drawing (example IPAE 10 commercial code = 1G10270100)
kV kV kV N mm mm N kg.
IPAE 10 70100 12 75 35 10000 2 320 4 1,4
IPAE 15 70200 17,5 95 45 8000 2,7 520 7 2,3
IPAE 20 70300 24 125 55 6000 3,2 730 10 3,2
IPAE 30 70400 36 170 75 4000 5 910 13 3,9
28
Identification Technical data
h D d1 t1 d2 t2 L d3 t3 d D1 D2
Distance
Maximum Base Auxiliary Distance Maximum Maximum
Upper between
nominal Hole threaded Hole upper Hole between
Insulator threaded base face threaded diameter diameter
Type Drawing height diameter of centre depth centre depth threaded depth
hole and lower base upper
insulating (tapped) d1 hole d2 hole d3 holes
threaded face face
part (tapped) (tapped) d3
end
Accessories
Nichel-plated male reduction.
29
Type PRG 24 kV
SF6 - Air silicon rubber bushing
General characteristics
The PRG bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for outdoor applications. The external side is made by silicon rubber
with internal core made by epoxy resin. The body guarantee solidity to the complex and
perfect seal of SF6 gas filled in the inner part of electrical device.
Is equipped with galvanized copper conductor and it is supplied completed with:
- Top fixing cap made by galvanized brass brass;
- Top connection fixing screw & nuts made by galvanized brass;
- O-Ring gasket made by EPDM for SF6 gas seal;
- Upon request, aluminium flange, screw & nuts for assembling of the bushing on the
metallic frame.
Application
For outdoor application and connection with bare electrical wire. The PRG bushings can be
assembled in any position with the exception of the situation where the sheds are turned
upside down, even if slightly
Working voltage
Up to 24 kV
Reference standards
IEC 60137(eletrical test) - Enel unification chart DY 1806 Cap. 4
IEC 60507 (1991): salinity salt fog test (type test)
IEC 61109 (1992-03) 5000 hours accelerated ageing test (type test)
30
Assembling instructions
- P repare the holes on the body of the tank as indicated (item 7).
- Remove the paint, or insulating coat, in the area of fixing holes in order to guarantee a correct earth connection of the
bushing.
- More over make sure that the surface where the bushing hods is without any type of roughness, or unevenness and it must
be perfectly clean in order to guarantee a perfect tightening-up of the flat gaskets (item 4).
- Place the bushing (item 3) on the tank after having positioned the gasket (item 4).
- Place the aluminium flange (item 5) inside the tank and tighten the six fixing screws (item 6) together with the relevant
washers with a tightening force value of 911 Nm. The tighting of the screws must be done crosswise.
- The lower connection to the M10 threaded hole must be fixed with a tightening force value of 3035 Nm.
31
Type PRG 36 kV
SF6 - Air silicon rubber bushing
General characteristics
The PRG bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for outdoor applications. The external side is made by silicon rubber
with internal core made by epoxy resin. The body guarantee solidity to the complex and
perfect seal of SF6 gas filled in the inner part of electrical device.
Is equipped with galvanized copper conductor and it is supplied completed with:
- Top fixing cap made by galvanized brass brass;
- Top connection fixing screw & nuts made by galvanized brass;
- O-Ring gasket made by EPDM for SF6 gas seal;
- Upon request, aluminium flange, screw & nuts for assembling of the bushing on the
metallic frame.
Application
For outdoor application and connection with bare electrical wire. The PRG bushing can be
assembled in any position with the exception of the situation where the sheds are turned
upside down, even if slightly
Working voltage
Up to 36 kV
Reference standards
IEC 60137(eletrical test) Enel unification chart DY 1806 Cap. 4
IEC 60507 (1991): salinity salt fog test (type test)
IEC 61109 (1992-03) 5000 hours accelerated ageing test (type test)
32
Mod. 3636
Assembling instruction
Prepare the holes on the body of the tank as indicated
(item 7).
Remove the paint, or insulating coat, in the area of fixing
holes in order to guarantee a correct earth connection of
the bushing.
Moreover make sure that the surface where the bushing
holds is without any type of roughness, or unevenness and
it must be perfectly clean in order to guarantee a perfect
tightening-up of the flat gaskets (item 4).
Place the bushing (item 3) on the tank after having
positioned the gasket
(item 4).
Place the aluminium flange (item 5) inside the tank and
tighten the six fixing screws (item 6) together with the
relevant washers with a tightening force value of 911 Nm.
The tighting of the screws must be done crosswise.
- The lower connection to the M10 threaded hole must be
fixed with a tightening force value of 3035 Nm.
33
Type PGS 24-36 kV
SF6 - Air silicon rubber bushing
General characteristics
A
The PGS bushings can be used as a fixed part for medium voltage input on SF6 gas or
oil insulated machines. It is provided with a coupling interface according to DIN 47636
standard that allows a connection with the relevant movable connectors. It is forbidden to
use the bushing in outdoor applications without the relevant movable connectors or without
the silicon rubber protection (B).
A+B
The PGS bushing with the silicon rubber protection can be utilized outdoor for connections
with bare electrical wire. The PGS can be assembled in any position except for the situation
where the sheds of silicon rubber protection are turned upside down, even if slightly.
Working voltage
Up to 36 kV
Reference standards
IEC 60137 (electrical tests)
IEC 60507 (1991): Salinity salt fog test (type test)
IEC 61109 (1992-03) C: 5000 hours accelerated ageing test (type test)
34
Assembling instruction Fig. 1
35
Type BSL
Composite insulators for line switches
General characteristics
The composite insulators type BSL are suitable to be used in MV line switches.
These insulators are realized with a fiberglass and epoxy resin core and aluminium end
fittings and covered by silicon rubber. This material gives best performances for an outdoor
use: abrasion resistance against UV rays, in environements with very high pollution level and
with high salinity concentration. Silicon is unbreakable and hidrophobic. It is not necessary
to plan any maintenance operation, even in particularly difficult environement conditions.
Application
Outdoor line switches.
Reference standards
IEC 60815
36
Fig. 1 Fig. 2
37
38
Products for SF6 insulated
switchgear
PTC 44
PTS 46
PRI 48
39
Type INV - PPC/PPT - PPS - PTS
IPC - IPF - INV
Fuse holder, bushings and accessories for SF6 insulated devices
INV
Drawing: 1745 - 1736
Epoxy resin fuse holder completed with lower and central contacts for fuse and silicon
gasket for bushings assembling.
PPC/PPT
Drawing: 3236 - 3220
SF6 gas tight type, it is equipped with innen coupling type
EN 50180-50181 (DIN 47637).
PPS
Drawing: 1945 - 1521
No SF6 tight type, it is equipped with external coupling type EN 50180-50181
(DIN 47636) and connection for L.V. reading.
PTS
Drawing: 1921
SF6 gas tight type, it is equipped with external coupling type EN 50180-50181
(DIN 47636) DIN 47636 and connection for L.V. reading.
IPC
Drawing: 1830
Wire-test SF6 gas tight bushing completed with O-Ring type gasket.
IPF
Drawing: 1730
Fuse holder SF6 gas tight support bushings completed with O-Ring type gasket.
INV
Drawing: 1760
Fuse holder cover completed of upper contact, mechanism for fuse and silicon gasket for fuse holder coupling.
Application
For indoor use, vertical and horizontal installation.
PPC/PPT 3236/3220
PPS 1945/1521
PTS 1921
INV 1745/1736
IPC 1830
INV 1760
IPF 1730
40
Fuse holder type INV 24 kV 36 kV with cover drawing n. 1760
Drawing: 1745 Drawing: 1736
Fig. 1A A = 592 mm. A = 687 mm.
Fig. 1B B = 90 mm. B = 185 mm.
Bushing type IPF - Drawing: 1730 Bushing type PPS - Drawing: 1945 Bushing type PPS - Drawing: 1521
41
Type PPC - PPT - PPE
Bushing with internal plug connection
General characteristics
The PPC, PPT and PPE epoxy resin bushings can be used as medium voltage inlet
connections for oil or SF6 insulated device, such as transformers or switchgears.
They are equipped with internal coupling type DIN 47637 to be coupled with relevant mobile
connectors.
The PPC-DC 400-630 A bushing is equipped with a connection for the reading of L.V. by a
light signal box.
Application
Indoor installation at max working temperature of 85 C
Reference standards
IEC 60137
42
PPT 20/250 PPT 30/630
PPE 20/1250
43
Type PTC
Bushing with external plug connection
General characteristics
The PTC bushings can be used as a fixed part in medium voltage
inlet for oil or SF6 insulated devices, such as transformers or switchgears.
They are equipped with a connection for the reading of low voltage by a light signal box.
Application
For indoor application, suitable for vertical or horizontal installation.
Working voltage
24 - 36 kV
Reference standards
IEC 60137 (electrical tests)
DIN 47636/HN 52-S-61 (coupling interface)
44
Fig. 1 Fig. 2
250 A 400-630 A
Pos. Components
1 Lower connection
2 Epoxy resin insulated part
3 O-Ring gasket
4 Coupling interface DIN 47636
5 Copper bar
6 Insulator fixing flange
7 Fastening insulator screws
8 Plastic protective cover
45
Type PTS
Bushing with external plug connection
General characteristics
The PTS bushings can be used as a fixed part in medium voltage inlet for oil or SF6
insulated devices, such as transformers or switchgears .
They are equipped with a copper conductor and is supplied completed with O-ring gasket,
aluminium flange and screws and nuts for assembling operations on the metallic tank.
Application
For indoor application, suitable for vertical or horizontal installation.
Working voltage
24-36 kV
Reference standards
IEC 60137 (eletrical test)
EN 50180-50181 (DIN 47636 / HN 52-S-61) coupling interface.
46
Fig. 1 Fig. 2 Fig. 3
Pos. Components
1 Lower connection
2 Epoxy resin insulated part
11
3 Earth socket or outlet of the capacitive potential divider
4 O-Ring gasket
5 Coupling interface DIN 47636
9 6 Copper bar
7 Upper connection
10 8 Insulator fixing flange
9 Fastening insulator screws
10 Mobile connector fastening 25 e 400 A.
11 Plastic protective cover
8
7 5
All the items are included in the supplied kit
6
47
Type PRI 24 kV
SF6 - air bushing for indoor use
General characteristics
The PRI bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for indoor applications.
They are equipped with nichel-plated copper conductor and it is supplied completed with
O-Ring gasket made by EPDM for SF6 gas seal.
Application
For indoor application and connection with bare electrical wire.
Working voltage
Up to 24 kV
Reference standards
IEC 60137
Commercial code
1G12185024
48
Steelwork holes Lay-Out
49
50
51
Note
52