Insulators for indoor use

ISA 5

IPA 6

DC - DCP 8

DCL 10

SF - SC 12

SCD - SCB - SDY 14

IPAN 16

PSE/PSL 18

PRC 20

PRB 22

IPAR - ISOF - IPA 24

4
Type ISA
Low voltage post insulators for indoor installation

General characteristics
Post insulators made of epoxy resin (EP UL94V0) or
polyesther reinforced with fiberglass (UP FG), suitable for
indoor application with internal metal fitting. These insulators
are particularly suitable to be used as single supports for
bus-bars, fuses and for other equipment.

Application
For indoor applications with working condition at max.
operating temperature of 160 C (epoxy resin - EP UL94V0)
and 130 C (polyesther - UP FG)

Working voltage
From 0,4 up to 2 kV

Reference standards
IEC 216 - DIN 53452 - DIN 53455

Identification Technical data


Maximum Ultimate Ultimate
Fig. Type Drawing operating bending tensile Material Color Weight
voltage stress stress
kV N ( 10%) N ( 10%) kg.
1 ISA 20/20 M5 U2215 0,4 1500 2500 EP UL 94V0 RAL 9005 0,01
2a ISA 30/30 M8 U3306
2 4000 8000 EP UL 94V0 RAL 9005 0,06
U3308
2b ISA 30/30 M6
P3308 0,75 3000 6000 UP FG RAL 7030 0,05
U4410 2 7000 12000 EP UL 94V0 RAL 9005 0,13
3 ISA 40/40 M10
P4410 1 5000 10000 UP FG RAL 7030 0,11

Fig. 1 Fig. 2a Fig. 2b Fig. 3

5
Type IPA
post insulators for indoor installation

General characteristics
Epoxy resin post insulators, for indoor application, with internal metal fitting.
These insulators are particularly suitable to be used as single supports for conductors, for
fuses and for other equipment (as switchgears).

Application
For indoor installation with working condition at T max. 100 C.

Working voltage
From 12 up to 36 kV
(40,5 kV available on request)

Reference standards
IEC 60273 (CEI 36/12) - CENELEC HD 578 S1
IEC 60660 (Fascicolo S/663)
IEC 60137

Commercial code
1G101 + drawing (example IPA 7,2/4000 commercial code = 1G10107204)

Identification Electrical data Mechanical data Technical data


Ultimate
bending Maximum
stress deflection
Lightning Dry power difference
Reference to Maximum frequency
IEC Type Drawing operation
impulse between 20% Creepage Fins Weight
voltage voltage and 50% of distance
designation voltage whitstand
whitstand the specifield
load

kV kV kV N mm mm N kg.
JO 4 - 60 IPA 7,2/4000 07204 4000
7,2 60 28 1,5 >150 3 0,6
JO 8 - 60 IPA 7,2/8000 07208 8000
JO 4 - 75 IPA 12/4000 10010 4000 >235 0,7
JO 8 - 75 IPA 12/8000 10020 12 75 35 8000 2 >175 4 0,8
JO 16 - 75 IPA 12/16000 10025 16000 >230 1,5
JO 8 - 95 IPA 17,5/8000 20020 8000 >260 1,1
17,5 95 45 2,7 5
JO 16 - 95 IPA 17,5/16000 20026 16000 >300 2,2
IPA 24/4000
Standard 24210 >360 1,1
JO 4 Enel DJ1053
125 IPA 24/3000 4000 8
Standard 24220
Enel DJ1056 24 125 55 3,2 >370 1,2
IPA 24/4000 24225
JO 8 - 125 IPA 24/8000 30030 8000 >350 1,6
7
JO 10 - 125 IPA 24/10000 30026 10000 >400 2,6
JO 4 - 170 IPA 36/4000 40010 4000 >520 13 1,8
JO 8 - 170 IPA 36/8000 40012 36 170 75 8000 5 >520 12 2,9
JO 10 - 170 IPA 36/10000 40026 10000 >570 10 3,4

6
AccessorIes
Nichel-plated male reduction.

Drawing 3012 Drawing 3016

Technical data
h D d1 t1 d2 t2 L d3 t3 d D1 D2

Distance
Maximum Auxiliary Distance
Upper Base between
nominal Hole Hole upper Hole between Maximum Maximum
Isnulator threaded threaded base face
diameter of centre depth depth threaded depth threaded diameter diameter
height hole centre hole and lower
insulating d1 d2 hole d3 holes base face upper face
(tapped) (tapped) threaded
part (tapped) d3
end

mm. (+-1) mm. mm. (min.) mm. (min.) mm. mm. (min.) mm. mm. mm.
M12 0 55
95 82 M12 18 25 70
M16 18 M8 15 46 70
83 14 70 65
130 M12 18 M16 25 M6 15 36
75 18 75 65
116 M16 25 M20 32 36 M10 20 46 100 91
175 83 M12 18 M16 25 35 M6 15 36 76 62
118 M16 25 M20 32 36 M10 20 46 100 91
210
25 0
80 80 54,5
M12 M16 25 M6 15 36
225 35
18
93 18 77 70
110 M16 25 M20 32 42 M10 20 46 100 90
80 32 80 55
M12 18 M16 25 M6 15 36
310 98 60 94 76
110 M16 25 M20 32 42 M10 20 46 100 90

7
Type DC - DCP
Capacitive insulators with low voltage lower reading connection

General characteristics
Epoxy resin post insulators with capacitive devider for the reading of the voltage.
Manufactured with internal metal fitting, they can be equipped with couplings and low
voltage light signal box.
These insulators are mainly suitable to be used as insulated supports of equipment, bus bar
or fuses.

Safety information
The insulators can be equipped with:
- S afety valve type ATS drawing 4500 that, in case of incoming voltage higher than 600 V,
connect to earth the system;
- S ignal box type SF 5600, SC 5583, SCD 5500, and SCB 5590 that, through a gas arrester
installed inside, in case of incoming voltage higher than 600 V, automatically connect to
earth the system.The heart connection system is self-resetting.

Application
Indoor installation at max working temperature of 85 C.

Working voltage
From 12 to 36 kV.
(40,5 available on request)

Reference standards
IEC 60137

Commercial code
1G103 + drawing (example DC 10 commercial code = 1G10350010)

Mechani-
Identification Electrical data H D1 D2 D Technical data
cal data
Maximum
Maximum Lightning Dry power Ultimate nominal
Diameter Diameter diameter
Type Drawing operation impulse frequency Capaci- bending Insilator of base of upper Creepage Fins Weight
voltage voltage voltage tance stress height of distance
face face
whitstand whitstand (PO) insulating
part
kV kV kV pF N mm. mm. mm. mm. mm. N kg.
DC 10 50010 12 75 35 220 3000 130 75 65 75 175 4 0,8
DC 15 50012 17,5 95 45 150 3000 175 76 62 83 260 5 1,1
DC 20 50013 24 125 55 150 3000 225 69 62 78 355 7 1,3
DC 30 50021 36 170 75 75 3000 310 80 55 80 520 13 1,8
DCP 10 50015 12 75 35 220 5000 130 70 65 75 175 4 0,8
DCP 15 50017 17,5 95 45 150 5000 175 76 62 83 260 5 1,1
DCP 20 50018 24 125 55 150 5000 225 76 69 85 350 7 1,6
DCP 30 50019 36 170 75 75 5000 310 94 76 98 520 12 2,9

8
type DC type DCP

Upper

Base

Connection type ATS 4482

Insulator gaps
type ATS
Drawing 4500
Washer

Steework hole
Grow 16,5 mm

Screw M12/14

Grow Safety valve for


overvoltage protection

Tc M4

Voltage presence indicators

Standard
ENEL
DY 811

type SF type SC type SCB type SCD type SDY


drawing 5600 drawing 5583 drawing 5590 drawing 5500 drawing 5811

9
Type DCL
Capacitive insulators with low voltage side reading connection

General characteristics
Epoxy resin post insulators with capacitive devider for the
reading of the voltage
Manufactured with internal metal fitting, they can be
equipped with couplings and low voltage light signal box.
These insulators are mainly suitable to be used as insulated
supports of equipment, bus bar or fuses.

Safety information
The insulators can be equipped with:
- Safety valve type ALS drawing 4700 that, in case of
incoming voltage higher than 600 V, connects to earth the
system;
- Signal box type SF 5600, SC 5583, SCD 5500 and SCB
5590 that, through a gas arrester installed inside, in case of
incoming voltage higher than 600 V, automatically connect
to earth the system.The heart connection system is
self-resetting.
The DCL 24/I capacitive insulator, that utilise epoxy resin as
dielectric; it has low capacitance condenser and low voltage
outlet.

Application Reference standards


Indoor installation at max working temperature of 85 C. IEC 60137 (electrical tests)
Enel standard DJ 1054 - DJ 1550 (DCL 24/I)

Working voltage Commercial code


From 12 to 36 kV 1G105 + drawing (example DCL 10 commercial code =
1G10550030)

Identification Electrical data Technical data

Maximum Lightning Dry power Model of


Type Outlet Type Drawing operation impulse voltage frequency Capacitance Cable type comatible
voltage whitstand voltage signal box
whitstand
kV kV kV 20% pF
A 50030
DCL 10 B 50032 12 75 35 220
C 50031 SF 5600
A 50070 SC 5583
DCL 15 B 50072 17,5 95 45 150 standard SCB 5590
C 50071 SCD 5500
A 50040 SDY 5811
DCL 24 B 50041 24 125 55 150
C 50042
A 52054 SCB 5590
DCL 24/I
Standard B 52050 24 125 55 7 RG 58 SCD 5500
Enel DJ 1054
C 52055 SDY 5811
SF 5600
A 50310 SC 5583
DCL 30 B 50311 36 170 75 75 standard SCB 5590
C 50312 SCD 5500
SDY 5811

10
With type C outlet it is possible to connect
safety valve type ALS drawing 4700 for over-
voltage protection

L.V. Side reading connection type

Connection 1G10604580
Voltage presence indicators

Standard
ENEL
DY 811

type SF type SC type SCB type SCD type SDY


drawing 5600 drawing 5583 drawing 5590 drawing 5500 drawing 5811

Mechanical
Identification H D1 D2 D3 Technical data
data

Ultimate
bending
stress
Outlet Diameter Diameter
Type Drawing Insilator Quote Creepage
type of base of upper Fins Weight
height D3 distance
face face

N mm. mm. mm. mm. mm. N kg.


A 50030
DCL 10 B 50032 4000 130 74 53 87 165 5 0,9
C 50031
A 50070
DCL 15 B 50072 4000 175 74 53 87 245 7 1,1
C 50071
A 50040
DCL 24 B 50041 3500 225 74 55 87 350 9 1,4
C 50042
A 52054
DCL 24/I
Standard B 52050 3500 225 74 55 87 350 9 1,75
Enel DJ 1054
C 52055
A 50310
DCL 30 B 50311 3000 310 80 55 90 490 13 2,2
C 50312

11
Type SF - SC
Voltage presence indicators

General characteristics
The voltage presence indicators are devices used to supply information about the main
circuit status inside the equipment where the devices are installed. To each lamp placed
inside the indicator (L1 L2 L3) corresponds one phase of the input line. The line voltage
presence is indicated by switching of the relevant lamp. The signal of voltage presence
necessary to switch the lamps is sourced out by a capacitive coupling with an insulator
equipped with capacitive output.

Application
In MV cubicles for operating voltages from 1 to 36 kV.

Type SF Type SC
The indicator SF is a light signal device made of one single The indicator SC is a light signal device made of one fix part
fix part. The indicator is equipped with a safety system, and one mobile and removable part.The lamps are placed
composed of one gas arrester for each phase, which in the mobile part. The indicator is equipped with a safety
connects the system to ground in case of overvoltage system, composed of one gas arrester for each phase, which
> 600 V. The arresters are self-resetting, this means that at connects the system to ground in case of overvoltage > 600
the end of the discharge the device will start again to function V. The arresters are self-resetting, this means that at the
normally. end of the discharge the device will start again to function
normally.

Capacitive source Indicator SF 5600 - SC 5583


Voltage on indicator at
Maximum Nominal Pulsating lamp Fix lamp
Insulator type max. operating
operation voltage capacitance lightning at lightning at voltage
kV pF 20% kV kV V
DC - DCP - DCL 10 12 220 1,2 2 150
DC - DCP - DCL 15 17,5 150 1,1 2 130
DC - DCP - DCL 20/24 24 150 2 12 100
DCL 24/I 24 7 5 75
DC - DCP - DCL 30 36 75 1 10 145

The above mentioned values were reached by using a standard cable (3 meters length) to connect the capacitive insulator and the voltage indicator.
The values have a 20% variability.

12
type SF 5600

Steelwork Lay-Out

Front side Back side

type SC 5583

Back side Steelwork Lay-Out

Back side

Mobile part

Back side
Complete set

13
Type SCD - SCB - SDY
Voltage presence indicators

General characteristics
The voltage presence indicators are devices used to supply
information about the main circuit status inside the equipment
where the devices are installed. To each lamp placed inside
the indicator (L1 L2 L3) corresponds one phase of the input
line. The line voltage presence is indicated by switching of the
relevant lamp. The signal of voltage presence necessary to
switch the lamps is sourced out by a capacitive coupling with
an insulator equipped with capacitive output.

Application
In MV cubicles for operating voltages from 1 to 36 kV.

Type SCD Type SCB


The indicator SCD is a light signal device made of one single The indicator SCB is a light signal device made of one fix part
fix part. Below each lamp there are relevant contact holes and one mobile and removable part.The lamps are placed
which allow to verify the phase accordance between two or in the mobile part. The indicator is equipped with a safety
more equipments, through the use of a phase accordance system, composed of one gas arrester for each phase, which
device DCF 6500. The indicator is equipped with a safety connects the system to ground in case of overvoltage > 600
system, composed of one gas arrester for each phase, which V. The arresters are self-resetting, this means that at the The
connects the system to ground in case of overvoltage > signal box SCB is used to read a low input signal.
600 V. The arresters are self-resetting, this means that at the
end of the discharge the device will start again to function
normally. The signal device SCD can be used even to read a
low input signal.

Phase accordance device DCF 6500 Type SDY


Thanks to the phase accordance device DCF 6500 it The signal device SDY is realized according to ENEL (National
is possible to verify if the lamps L1 (or L2 or L3) of two Power Company) specification DY 811. It is made of 1 front
indicators SCD 5500 placed on two different equipments board base and of 3 mobile parts, one for each phase,
are connected to the same phase. When the phases are in equipped with removable and separated light indicators.
accordance the lamp of the device DCF 6500 is off, while in The fix part is suitable to be connected with RG DAT
case of non accordance of the phases the lamp is on. monitoring device, according to Enel specification DY 1059.

Capacitive source Indicator SCD 5500 - SCB 5590 - SDY 5811


Voltage on indicator at
Maximum Nominal Pulsating lamp Fix lamp
Insulator type max. operating
operation voltage capacitance lightning at lightning at voltage
kV pF 20% kV kV Volts
DC - DCP - DCL 10 12 220 1 2,5 50
DC - DCP - DCL 15 17,5 150 1 5 45
DC - DCP - DCL 20/24 24 150 1 13 38
DCL 24/I 24 7 3(*) 36
DC - DCP - DCL 30 36 75 1 8 50

The above mentioned values were reached by using a standard cable (3 meters length) to connect the capacitive insulator and the voltage indicator.
The values have a 20% variability.
(*) To reach the pulsation level required by DY 811 homologation it is necessary to use a screened RG 58 cable to connect the capacitive insulator DCL
24/I and the voltage indicator SDY 5811.

14
type SCD 5500 tipe SCB 5590

Back side Steelwork Lay-Out

Back side

Mobile part
Steelwork lay-out
Back side
Front side

Complete set

serie SDY

Steelwork Lay-Out

Back side

15
Type IPAN
Bushing for indoor use

General characteristics
12 36 kV epoxy resin bushing insulators.The insulators can be fitted with copper bars
designed from 250 up to 2000 A.
They are equipped with internal metal fittings for installation on the relevant frame and with
brass nuts and washers for fastening of phase connectors.

Application
Indoor installation at max working temperature of 85 C.

Working voltage
From 12 to 36 kV.

Reference standards
IEC 60137 (electrical tests).

Commercial code
1G107 + drawing (example IPAN 10/250 commercial code = 1G10781010)

Identification Electrical data Technical data


Dry power Lightning
Maximum Nominal frequency impulse
Type Drawing operation Creepage
current voltage voltage distance Fins Weight
voltage whitstand whitstand
kV A kV kV mm. N kg.
IPAN 10/250 81010 250 2,3
IPAN 10/400 81011 400 220 3+3 2,5
IPAN 10/630 81012 630 2,8
IPAN 10/800 81240 12 800 35 75 6
IPAN 10/1000 81014 1000 7
230 4+4
IPAN 10/1500 81015 1500 8,2
IPAN 10/2000 81016 2000 9
IPAN 15/250 82010 250 3,1
IPAN 15/400 82011 400 390 3,4
IPAN 15/630 82012 630 3,8
IPAN 15/800 82240 17,5 800 45 95 6+6 6,8
IPAN 15/1000 82014 1000 8
330
IPAN 15/1500 82015 1500 9,5
IPAN 15/2000 82016 2000 10,4
IPAN 20/250 83010 250 3,5
IPAN 20/400 83011 400 480 3,8
IPAN 20/630 83012 630 4,5
IPAN 20/800 83240 24 800 55 125 8+8 7,5
IPAN 20/1000 83014 1000 9
440
IPAN 20/1500 83015 1500 10,9
IPAN 20/2000 83016 2000 12
IPAN 30/250 84010 250 9,8
IPAN 30/400 84011 400 10,4
IPAN 30/630 84012 630 11,2
IPAN 30/800 84013 36 800 75 170 620 8+8 12,3
IPAN 30/1000 84014 1000 14,1
IPAN 30/1500 84015 1500 16,2
IPAN 30/2000 84016 2000 17,9

16
Steelwork holes Lay-Out

Identification Dimensional data


R
Type Drawing A B C D F G H L M
Diameter Pitch Lenght
IPAN 10/250 81010 12 1,5
IPAN 10/400 81011 140 140 280 106 75 87 380 16 1,5 45
IPAN 10/630 81012 20 1,5
IPAN 10/800 81340 8,5 M8x20 24 2
IPAN 10/1000 81014 30 2
175 175 350 134 110 126 470 55
IPAN 10/1500 81015 36 2
IPAN 10/2000 81016 42 3
IPAN 15/250 82010 12 1,5
IPAN 15/400 82011 205 205 410 106 75 87 510 16 1,5 45
IPAN 15/630 82012 20 1,5
IPAN 15/800 82240 8,5 M8x20 24 2
IPAN 15/1000 82014 30 2
215 215 430 134 110 126 550 55
IPAN 15/1500 82015 36 2
IPAN 15/2000 82016 42 3
IPAN 20/250 83010 12 1,5
IPAN 20/400 83011 106 75 87 620 16 1,5 45
IPAN 20/630 83012 20 1,5
IPAN 20/800 83240 260 260 520 8,5 M8x20 24 2
IPAN 20/1000 83014 30 2
134 110 126 670 70
IPAN 20/1500 83015 36 2
IPAN 20/2000 83016 42 3
IPAN 30/250 84010 12 1,5
IPAN 30/400 84011 940 16 1,5 60
IPAN 30/630 84012 20 1,5
IPAN 30/800 84013 405 405 810 10,5 160 120 118 M10x20 24 2
IPAN 30/1000 84014 30 2
960 70
IPAN 30/1500 84015 36 2
IPAN 30/2000 84016 42 3

17
Type PSE - PSL
Bushing for indoor/outdoor use

General characteristics
12 36 kV cicloaliphatic resin bushing insulators.The insulators can be fitted with copper
bars designed from 250 up to 1000 A. They are equipped with internal metal fittings for
installation on the relevant frame and they are supplied completed with:
B rass nuts and washer for fastening of phase connectors
O-Ring gasket
Screws and nuts for assembling of the bushing on the metallic frame

Application
Outdoor installation at max working temperature of 85 C.

Working voltage
From 12 to 36 kV.

Reference standards
IEC 60137 (electrical tests).

Commercial code
1G110 + drawing (example PSE 10/250 commercial code = 1G11071010)

Identification Electrical data Technical data


Dry power Lightning Creepage
Maximum Nominal frequency
Type Drawing operation impulse voltage distance Weight
current voltage whitstand side (B)
voltage whitstand
kV A kV kV mm. kg.
PSE 10/250 71010 250 3,2
PSE 10/400 71011 400 3,4
12 35 75 350
PSE 10/630 71012 630 3,8
PSE 10/800 71013 800 4,2
PSE 15/250 72010 250 4,5
PSE 15/400 72011 400 4,8
17,5 45 95 540
PSE 15/630 72012 630 5,3
PSE 15/800 72013 800 5,8
PSE 20/250 73010 250 5,7
PSE 20/400 73011 400 6
24 55 125 740
PSE 20/630 73012 630 6,7
PSE 20/800 73013 800 7,3
PSE 30/250 74010 250 10,7
PSE 30/400 74011 400 11,2
PSE 30/630 74012 36 630 75 170 860 12
PSE 30/800 74013 800 13
PSE 30/1000 74014 1000 14,7
PSl 20/400
73016 24 400 55 125 740 9,6
Standard Enel

18
Steelwork holes Lay-Out

Identification Dimensional data


R
Type Drawing A A1 B C D E F G H L M Threded
Diameter Pitch lenght
mm. mm. mm. mm. mm. mm. mm. mm. mm. mm. mm. mm. mm. mm.
PSE 10/250 71010 12 1,5
PSE 10/400 71011 16 1,5
96 20 164 280 8,5 130 114 88 87 380 M8x20 45
PSE 10/630 71012 20 1,5
PSE 10/800 71013 24 2
PSE 15/250 72010 12 1,5
PSE 15/400 72011 16 1,5
163 20 232 415 8,5 130 114 88 87 510 M8x20 45
PSE 15/630 72012 20 1,5
PSE 15/800 72013 24 2
PSE 20/250 73010 12 1,5
PSE 20/400 73011 16 1,5
235 20 305 560 8,5 130 114 88 87 660 M8x20 45
PSE 20/630 73012 20 1,5
PSE 20/800 73013 24 2
PSE 30/250 74010 12 1,5
PSE 30/400 74011 940 16 1,5 60
PSE 30/630 74012 365 40 405 810 10,5 159 160 120 118 M10x20 20 1,5
PSE 30/800 74013 24 2
960 70
PSE 30/1000 74014 30 2
PSl 20/400
73016 235 325 305 865 8,5 130 114 88 87 965 M8x20 16 1,5 45
Standard Enel

19
Type PRC
Protection insulators

General characteristics
Epoxy resin protection insulators, bell shaped, with internal metal fitting.

Application
Indoor application with working condition at T max. 100 C.

Working voltage
From 12 to 36 kV.

Commercial code
1G123 + drawing (example PRC 12 commercial code = 1G12386010)

Technical data PRC 12 PRC 17 PRC 24 PRC 36


Drawing 86010 87015 88020 89030
H (mm.) 170 230 290 350
H1 (mm.) 275 335 395 455
D (mm.) 145 140 135 130
Creepage
Maximum operation voltage (kV) 12 17,5 24 36 distance
Dry power frequency 38 50 50 75
voltage whitstand (kV)

Lightning impulse voltage 75 95 125 170


whitstand (kV)
Creepage distance (mm.) 210 280 345 430
Fins (N) 2 3 4 5
Weight (kg.) 6 7 8 9
Tightening torque M10 (Nm) 30 30 30 30

Steelwork holes Lay-Out

20
21
Type PRB 24-36 kV
Air-air bushing for indoor use

General characteristics
The PRB bushings can be used as medium voltage inlet for indoor air insulated devices
such as switchgears, in particular for applications in quite small machines.
The bushings are realized on the one side with a coupling interface in accordance with
EN 50180-50181 (DIN 47636; HN 52-S-61) standards. This type of interface allows a
connection with the relevant moving connector. On the other part the sheded side allows a
bare electrical wire connection.

Accessories
Plastic cap for coupling interface protection.
Only on request, alluminium flange suitable to fix the bushing to the steelwork.
The fixing flange is necessary for the 400A version for mobile connector fastening.

Working voltage
24-36 kV

Reference standards
IEC 60137 (electrical tests)
EN 50180-50181 (DIN 47636; HN 52-S-61)

Commercial code
1G1240 + drawing (example PRB 24/400 commercial code = 1G12402430)

Identification Electrical data Standards


Lightning Dry power
Maximum Nominal impulse frequency Coupling Electrical Connection Creepage
Fig. Type Drawing operation Weight
current voltage voltage type tests type distance
voltage whitstand whitstand
kV A kV kV mm. kg.
EN 50180 Sliding
1 PRB 24/400 2430 24 400 125 55 EN 50181 IEC 137 380 2,65
contact
DIN 47636
EN 50180
2 PRB 24/630 2431 24 630 125 55 EN 50181 IEC 137 M16 380 2,65
DIN 47636
EN 50180
3 PRB 36/630 3670 36 630 170 75 EN 50181 IEC 137 M16 730 4,2
DIN 47636

22
Assembling instructions
Bushing insulator PRB
Prepare the holes on the body of the tank as indicated in the steelwork holes Lay-out. Remove the paint, or any insulating coat
in the area of fixing holes, in order to guarantee a correct earth connection of the bushing.
Moreover, make sure that the surface where the bushing is placed is without any type of roughness or unevenness. It must be
completely clean in order to guarantee a perfect tightness. It is recommended to use the fixing flange in order to strengthen the
area where the bushing is fixed to the tank. For 400A version the use of the flange is necessary for mobile connector fastening.
Place the flange, when used, and tighten the 3 fixing screws M6, together with their relevant washers, with a tightening force
value of 911 Nm. The tightening operation must be done crosswise. The lower connection (M16) must be fastened with a
tightening force value of 90100 Nm.
During mounting operations the plastic protective cap must be fitted and pressed right down on the bushing, in order to avoid
faults caused by dirt or accidental scratching of the interface.

Fig. 1 Fig. 2

Color RAL 3013 Color RAL 3013

23
Type IPAR - ISOF - IPA
Epoxy resin insulators for rotative switchgear 24 kV

IPAR
Three phase rotating bushing block with recessed
metal fitting for assembling on the steelwork.

Commercial code
1G108 + drawing (example IPAR 65012 commercial code = 1G10865012)

ISOF
Drawing: 69020
Conductor connection insulator with air room for arc estinguishing.
Its equipped with internal metal fitting for the assembling on the steelwork and of the upper
contact.

Reference standards
1G10869020

IPA
Drawing: technical at page 6
Conductor connection insulator with internal metal fitting for the assembling on the
steelwork and of the upper contact.

Application
For indoor use, vertical and horizontal installation.

IPA

IPAR

ISOF

24
Identification Dimensional data Standards

Maximum Lightning Dry power


Nominal impulse frequency Creepage
Fig. A Type Drawing L B operation Weight
current voltage voltage distance
voltage
whitstand whitstand
20 mm. mm. mm. W A kV kV mm. kg.
Alluminium 65012 400
Copper - and 690 210 12 75 35 >350 11
silver plated 67012 630
alluminium
Alluminio 65017 400
1 Copper - and IPAR 770 250 17,5 95 55 >350 12
silver plated 67017 630
alluminium
Alluminium 65021 400
Copper - and 870 300 24 125 55 >350 13
silver plated 67021 630
alluminium
Copper - and
2 silver plated ISOF 69020 24 125 55 2,3
alluminium

Fig. 1 IPAR
Three phase rotating bushing block type IPAR Special bushing
block IPAR for small
switchgears (500 mm).

Drawing 65016

Fig. 2
insulator with air room type
ISOF

25
26
Insulators for outdoor use

IPAE 28

PRG 24 30

PRG 36 32

PGS 24-36 34

BSL 36

27
Type IPAE
Post insulator for outdoor installation

General characteristics
Cicloaliphatic resin post insulators, for outdoor application, with internal metal fitting.
These insulators are mainly indicated to be used as insulating supports for bus
bar, fuses and other equipment (as outdoor switchgears).

Application
For outdoor installation with heavy (III) pollution level, according to IEC 60815, 71-2.
Working condition temperatures: max 90 C.

Working voltage
From 12 to 36 kV.
(40,5 kV available on request)

Reference standards
IEC 60273 (CEI 36/12) - CENELEC HD 578 S1
IEC 60660 (File S/663)
IEC 60815, 71-2.

Commercial code
1G102 + drawing (example IPAE 10 commercial code = 1G10270100)

Identification Electrical data Mechanical data Technical data


Ultimate
bending Maximum
stress deflection
Lightning Dry power
Maximum difference
impulse frequency Creepage
Type Drawing operation between 20% Fins Weight
voltage voltage distance
voltage and 50% of
whitstand whitstand the specifield
load

kV kV kV N mm mm N kg.
IPAE 10 70100 12 75 35 10000 2 320 4 1,4
IPAE 15 70200 17,5 95 45 8000 2,7 520 7 2,3
IPAE 20 70300 24 125 55 6000 3,2 730 10 3,2
IPAE 30 70400 36 170 75 4000 5 910 13 3,9

28
Identification Technical data
h D d1 t1 d2 t2 L d3 t3 d D1 D2

Distance
Maximum Base Auxiliary Distance Maximum Maximum
Upper between
nominal Hole threaded Hole upper Hole between
Insulator threaded base face threaded diameter diameter
Type Drawing height diameter of centre depth centre depth threaded depth
hole and lower base upper
insulating (tapped) d1 hole d2 hole d3 holes
threaded face face
part (tapped) (tapped) d3
end

IPAE 10 70100 130 130 M12 18 M16 26 27 M6 15 36 90 70


IPAE 15 70200 210 130 M12 18 M16 26 27 M6 15 36 90 70
IPAE 20 70300 295 130 M12 18 M16 26 27 M6 15 36 90 70
IPAE 30 70400 360 130 M12 18 M16 26 27 M6 15 36 90 70

Accessories
Nichel-plated male reduction.

Drawing 3012 Drawing 3016

29
Type PRG 24 kV
SF6 - Air silicon rubber bushing

General characteristics
The PRG bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for outdoor applications. The external side is made by silicon rubber
with internal core made by epoxy resin. The body guarantee solidity to the complex and
perfect seal of SF6 gas filled in the inner part of electrical device.
Is equipped with galvanized copper conductor and it is supplied completed with:
- Top fixing cap made by galvanized brass brass;
- Top connection fixing screw & nuts made by galvanized brass;
- O-Ring gasket made by EPDM for SF6 gas seal;
- Upon request, aluminium flange, screw & nuts for assembling of the bushing on the
metallic frame.

Application
For outdoor application and connection with bare electrical wire. The PRG bushings can be
assembled in any position with the exception of the situation where the sheds are turned
upside down, even if slightly

Working voltage
Up to 24 kV

Reference standards
IEC 60137(eletrical test) - Enel unification chart DY 1806 Cap. 4
IEC 60507 (1991): salinity salt fog test (type test)
IEC 61109 (1992-03) 5000 hours accelerated ageing test (type test)

Technical data Mod. 1998 Mod. 2400


Nominal current 400 A 630 A
Maximum operation voltage 24 kV 24 kV
Frequency withstand voltage 55 kV 55 kV
Impulse withstand voltage 125 kV 125 kV
Creepage distance 780 mm. 780 mm.
Weight 3,3 kg. 4,5 kg.
Commercial code 1G11701998 1G11702400

Pos. Components Kit


1 Top connection fixing screw and nuts
2 Fixing cap
3 Silicon bushing
4 O-Ring gaskit
5 Aluminium insulator fixing flange
6 Lower connection fixing screws and nuts
7 Steelwork holes Lay-Out

The highlighted items are included in the


supplied Kit

The highlighted items can be supplied on


request

30
Assembling instructions
- P repare the holes on the body of the tank as indicated (item 7).
- Remove the paint, or insulating coat, in the area of fixing holes in order to guarantee a correct earth connection of the
bushing.
- More over make sure that the surface where the bushing hods is without any type of roughness, or unevenness and it must
be perfectly clean in order to guarantee a perfect tightening-up of the flat gaskets (item 4).
- Place the bushing (item 3) on the tank after having positioned the gasket (item 4).
- Place the aluminium flange (item 5) inside the tank and tighten the six fixing screws (item 6) together with the relevant
washers with a tightening force value of 911 Nm. The tighting of the screws must be done crosswise.
- The lower connection to the M10 threaded hole must be fixed with a tightening force value of 3035 Nm.

Mod. 1998 Mod. 2400

Color RAL 7030 Color RAL 7030

Steelwork holes Lay-Out

31
Type PRG 36 kV
SF6 - Air silicon rubber bushing

with internal core made by epoxy resin

General characteristics
The PRG bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for outdoor applications. The external side is made by silicon rubber
with internal core made by epoxy resin. The body guarantee solidity to the complex and
perfect seal of SF6 gas filled in the inner part of electrical device.
Is equipped with galvanized copper conductor and it is supplied completed with:
- Top fixing cap made by galvanized brass brass;
- Top connection fixing screw & nuts made by galvanized brass;
- O-Ring gasket made by EPDM for SF6 gas seal;
- Upon request, aluminium flange, screw & nuts for assembling of the bushing on the
metallic frame.

Application
For outdoor application and connection with bare electrical wire. The PRG bushing can be
assembled in any position with the exception of the situation where the sheds are turned
upside down, even if slightly

Working voltage
Up to 36 kV

Reference standards
IEC 60137(eletrical test) Enel unification chart DY 1806 Cap. 4
IEC 60507 (1991): salinity salt fog test (type test)
IEC 61109 (1992-03) 5000 hours accelerated ageing test (type test)

Dati tecnici Mod. 3600


Nominal current 630 A
Maximum operation voltage 36 kV
Frequency withstand voltage 75 kV
Impulse withstand voltage 170 kV
Creepage distance 1050 mm.
Weight 5,1 kg.
Commercial code 1G11703600

Pos. Components Kit


1 Top connection fixing screw and nuts
2 Fixing cap
3 Silicon bushing
4 O-Ring gaskit
5 Aluminium insulator fixing flange
6 Lower connection fixing screws and nuts
7 Steelwork holes Lay-Out

The highlighted items are included in the


supplied Kit

The highlighted items can be supplied on


request

32
Mod. 3636
Assembling instruction
Prepare the holes on the body of the tank as indicated
(item 7).
Remove the paint, or insulating coat, in the area of fixing
holes in order to guarantee a correct earth connection of
the bushing.
Moreover make sure that the surface where the bushing
holds is without any type of roughness, or unevenness and
it must be perfectly clean in order to guarantee a perfect
tightening-up of the flat gaskets (item 4).
Place the bushing (item 3) on the tank after having
positioned the gasket
(item 4).
Place the aluminium flange (item 5) inside the tank and
tighten the six fixing screws (item 6) together with the
relevant washers with a tightening force value of 911 Nm.
The tighting of the screws must be done crosswise.
- The lower connection to the M10 threaded hole must be
fixed with a tightening force value of 3035 Nm.

Steelwork holes Lay-Out Color RAL 7030

33
Type PGS 24-36 kV
SF6 - Air silicon rubber bushing

General characteristics
A
The PGS bushings can be used as a fixed part for medium voltage input on SF6 gas or
oil insulated machines. It is provided with a coupling interface according to DIN 47636
standard that allows a connection with the relevant movable connectors. It is forbidden to
use the bushing in outdoor applications without the relevant movable connectors or without
the silicon rubber protection (B).

A+B
The PGS bushing with the silicon rubber protection can be utilized outdoor for connections
with bare electrical wire. The PGS can be assembled in any position except for the situation
where the sheds of silicon rubber protection are turned upside down, even if slightly.

Working voltage
Up to 36 kV

Reference standards
IEC 60137 (electrical tests)
IEC 60507 (1991): Salinity salt fog test (type test)
IEC 61109 (1992-03) C: 5000 hours accelerated ageing test (type test)

Technical data A 1990 + A 1996 +


A 1990 A 1996 B 2000 B 3000
Normal current 630 A 630 A 630 A 630 A
Maximum operation voltage 24 kV 36 kV 24 kV 36 kV
Frequency whitstand voltage 55 kV 75 kV 55 kV 75 kV
Impulse whitstand voltage 125 kV 170 kV 125 kV 170 kV
Creepage dustance 780 mm. 1050 mm.
Weight 2,4 kg. 2,9 kg. 4,1 kg. 5,1 kg.
Color RAL 3013 RAL 3013 RAL 7030 RAL 7030
Commercial code 1G11701990 1G11701996 1G11702000 1G11703000

Pos. Components Kit


1 Top connection fixing screw and nuts
2 Fixing cap
3 Silicon bushing
4 Plastic protective cover
5 Grease poket
6 Connection intarface DIN 47636
7 Epoxy resin bushing
8 O-Ring gaskit
9 Steelwork holes Lay-Out
10 Aluminium insulator fixing flange
11 Lower connection fixing screws and nuts

The highlighted items are included in the


supplied Kit

The highlighted items can be supplied on


request

34
Assembling instruction Fig. 1

PGS bushing (Fig. 1 and 2):


Drill the holes on the body of the tank as indicated (9).
Remove the paint, or insulating coat, in the area of the
fixing fastener holes in order to guarantee a correct earth
connection of the bushing.
M oreover make sure that the surface where the bushing

H - 290 mm - Mod. 2000 - 24 kV


H - 356 mm - Mod. 3000 - 36 kV
holds is without any type of roughness, or unevenness and
it must be perfectly clean in order to guarantee a perfect
tightness of the flat gaskets.
Place the bushing (7) on the metal structure after having
positioned the gasket (8). Place the aluminium flange Fig. 2
(10) inside the tank and tighten the six fixing screws (11)
together with the relevant washers with a tightening force
value of 911 Nm. The tighting of the screws must be done
crosswise.The lower connection to the M10 threaded hole
must be fixed with a tightening force value of 3035 Nm.

Silicon rubber protection (Fig. 3 and 4):


R emove the plastic protective cover (4) from the bushing.
The plastic protective cover must be fitted and pressed
right down on the bushing always when:
the bushing is not connected to the movable connector;
Fig. 3
 the bushing does not have silicon rubber protection.

L - 108,5 mm - Mod. 1996 - 36 kV


T his prevents faults caused by dirty or incidental scratching

L - 68,5 mm - Mod. 1990 - 24 kV


of the interface (6).
C lean with alcohol the interface (6) and the area of contact
with the silicon rubber protection (3).
After the complete evaporation of the solvent, spread
evenly over the connection interface (6) the grease
contained in the enclosed pocket (5).
P ull the silicon rubber protection (3) on the bushing (7)
and screw down tightly until maximum torque is obtained
(90100 Nm). This can be done with the aid of a 20
mm spanner used on the top cap (2). The silicon rubber
protection is correctly clamped if the bushing is totally Fig. 4
covered with it.
Turn the silicon rubber protection slightly to the left and to
the right to distribuite grease evenly over the connection
interface (6).

35
Type BSL
Composite insulators for line switches

General characteristics
The composite insulators type BSL are suitable to be used in MV line switches.
These insulators are realized with a fiberglass and epoxy resin core and aluminium end
fittings and covered by silicon rubber. This material gives best performances for an outdoor
use: abrasion resistance against UV rays, in environements with very high pollution level and
with high salinity concentration. Silicon is unbreakable and hidrophobic. It is not necessary
to plan any maintenance operation, even in particularly difficult environement conditions.

Application
Outdoor line switches.

Reference standards
IEC 60815

Identiification Dimensional characteristics Eletrical data Mechanical data Technical data


A D D1

Dry impulse Theorical Theorical Minimum


Fig. Drawing Drawing Drawing Drawing withstand tensile compressive creepage Fins weight
voltage (BIL) stress stress distance

mm. kV N N mm. N kg.


2501 333 75 kV 450 6 0,5
2502 393 95 kV 600 8 0,6
2503 423 125 kV 675 9 0,72
80
2504 543 170 kV 975 13 0,93
1 2505 663 250 kV 1275 17 1,15
10000 12000
2506 873 325 kV 1800 24 1,45
2507 873 325 kV 1935 18 2,1
2508 673 115 250 kV 1400 13 1,55
2509 643 170 kV 1120 10 1,15
2 34341 860 145 110 325 kV 10+9 2,4

36
Fig. 1 Fig. 2

37
38
Products for SF6 insulated
switchgear

INV - PPC/PPT - PPS - PTS/IPC - IPF - INV 40

PPC - PPT - PPE 42

PTC 44

PTS 46

PRI 48

39
Type INV - PPC/PPT - PPS - PTS
IPC - IPF - INV
Fuse holder, bushings and accessories for SF6 insulated devices

INV
Drawing: 1745 - 1736
Epoxy resin fuse holder completed with lower and central contacts for fuse and silicon
gasket for bushings assembling.

PPC/PPT
Drawing: 3236 - 3220
SF6 gas tight type, it is equipped with innen coupling type
EN 50180-50181 (DIN 47637).

PPS
Drawing: 1945 - 1521
No SF6 tight type, it is equipped with external coupling type EN 50180-50181
(DIN 47636) and connection for L.V. reading.

PTS
Drawing: 1921
SF6 gas tight type, it is equipped with external coupling type EN 50180-50181
(DIN 47636) DIN 47636 and connection for L.V. reading.

IPC
Drawing: 1830
Wire-test SF6 gas tight bushing completed with O-Ring type gasket.

IPF
Drawing: 1730
Fuse holder SF6 gas tight support bushings completed with O-Ring type gasket.

INV
Drawing: 1760
Fuse holder cover completed of upper contact, mechanism for fuse and silicon gasket for fuse holder coupling.

Application
For indoor use, vertical and horizontal installation.

PPC/PPT 3236/3220

PPS 1945/1521

PTS 1921

INV 1745/1736

IPC 1830

INV 1760

IPF 1730

40
Fuse holder type INV 24 kV 36 kV with cover drawing n. 1760
Drawing: 1745 Drawing: 1736
Fig. 1A A = 592 mm. A = 687 mm.
Fig. 1B B = 90 mm. B = 185 mm.

Fig. 2 Fig. 3A Fig. 3B

Bushing type IPF - Drawing: 1730 Bushing type PPS - Drawing: 1945 Bushing type PPS - Drawing: 1521

Identification Electrical data kg.

Maximum operating Lightning impulse Dry power frequency


Fig. Type Drawing Nominal current Weight
voltage voltage whitstand voltage whitstand
1A 1745 - 1760 24 kV 200 A 125 kV 55 kV 14
INV
1B 1736 - 1760 36 kV 200 A 170 kV 75 kV 15
2 IPF 1730 24 kV 250 A 125 kV 55 kV 1
3A 1945 1,1
PPS 24 kV 250 A 125 kV 55 kV
3B 1521 1,78
4 IPC 1830 24 kV 500 A 125 kV 55 kV 1

Silicon rubber extension for bushing type Fig. 4


IPC - Drawing: 1840
Bushing type IPC
Drawing: 1830

41
Type PPC - PPT - PPE
Bushing with internal plug connection

General characteristics
The PPC, PPT and PPE epoxy resin bushings can be used as medium voltage inlet
connections for oil or SF6 insulated device, such as transformers or switchgears.
They are equipped with internal coupling type DIN 47637 to be coupled with relevant mobile
connectors.
The PPC-DC 400-630 A bushing is equipped with a connection for the reading of L.V. by a
light signal box.

Application
Indoor installation at max working temperature of 85 C

Reference standards
IEC 60137

Identification Electrical data Reference standards kg.


Lightning Dry power
Maximum Nominal impulse frequency
Fig. Type Drawing operating current voltage voltage Coupling type Weight
voltage whitstand whitstand
PPC 20/250 3236 24 kV 250 A 125 kV 55 kV DIN 47637 / ENEL DJ 1115 2,4
1
PPC-DC 30/630 3206 24-36 kV 400-630 A 170 kV 75 kV DIN 47637 / ENEL DJ 1113 2,5
PPT 20/250 3220 24 kV 250 A 125 kV 55 kV DIN 47637 / ENEL DJ 1115 1,9
2
PPT 30/630 3195 24-36 kV 400-630 A 170 kV 75 kV DIN 47637 / ENEL DJ 1113 2
3 PPE 20/1250 3227 24 kV 1250 A 125 kV 55 kV DIN 47637 / ENEL DJ 1153 5,8

PPC 20/250 PPC-DC 30/630

drawing nr. 3236 drawing nr. 3206

42
PPT 20/250 PPT 30/630

drawing nr. 3220 drawing nr. 3195

PPE 20/1250

drawing nr. 3227

Color RAL 3013

PPC PPC/DC PPT PPT PPE


Pos. Technical data
20/250 30/6330 20/250 30/630 20/1250
1 Mobile connector fastening
2 Fastening insulator insert
3 Earth socket or outlet of the capacitive potential divider
4 Threaded central conductor
5 Epoxy resin insulated part
6 Connection socket
7 Electrical field deflector
8 Coupling type DIN 47637
9 Equipotential screen
10 Gasket O-ring
11 Gasket O-ring
12 Insulator fixing flange
13 Insulator screws and nuts
14 Screws plastic pretective cover
15 Coupling plastic pretective cover
16 Insulated insert
17 Screw M5

The highlighted items are included in the supplied kit.

43
Type PTC
Bushing with external plug connection

General characteristics
The PTC bushings can be used as a fixed part in medium voltage
inlet for oil or SF6 insulated devices, such as transformers or switchgears.
They are equipped with a connection for the reading of low voltage by a light signal box.

Application
For indoor application, suitable for vertical or horizontal installation.

Working voltage
24 - 36 kV

Reference standards
IEC 60137 (electrical tests)
DIN 47636/HN 52-S-61 (coupling interface)

Identification Electrical data Standards C M kg.

Lightning Dry power


Maximum Nominal impulse frequency Coupling Connetion Threded
Fig. A H Type Drawing operation current voltage voltage type type hole Weight
voltage whitstand whitstand

1922 DIN 47636 Sliding


105 184 PTC 24/250 24 kV 250 A 125 kV 55 kV M8 1,3
I-6284-02 HN 52-S-61 contact
1
PTC 24/250-R 1930 DIN 47636 Sliding
60 140 24 kV 250 A 125 kV 55 kV M8 1,1
Corto I-7113-02 HN 52-S-61 contact

1933 EN 50180 Sliding


105 228 PTC 36/400 36 kV 400 A 170 kV 75 kV contact M10 2,3
I-6274-02 HN 52-S-61

PTC 24/400-R 1935 EN 50181 Sliding


60 183 Corto 24 kV 400 A 125 kV 55 kV M10 1,9
NI-959 HN 52-S-61 contact
2
1923 EN 50181
105 230 PTC 36/630 36 kV 630 A 170 kV 75 kV M16 M10 2,3
I-6250-2 DIN 47636

PTC 24/630-R 1936 EN 50181


60 184,5 Corto 24 kV 630 A 125 kV 55 kV M16 M10 1,9
I-7094-04 DIN 47636

We recommend the use of flange

44
Fig. 1 Fig. 2

250 A 400-630 A

Pos. Components
1 Lower connection
2 Epoxy resin insulated part
3 O-Ring gasket
4 Coupling interface DIN 47636
5 Copper bar
6 Insulator fixing flange
7 Fastening insulator screws
8 Plastic protective cover

All items are included in the supplied kit

45
Type PTS
Bushing with external plug connection

General characteristics
The PTS bushings can be used as a fixed part in medium voltage inlet for oil or SF6
insulated devices, such as transformers or switchgears .
They are equipped with a copper conductor and is supplied completed with O-ring gasket,
aluminium flange and screws and nuts for assembling operations on the metallic tank.

Application
For indoor application, suitable for vertical or horizontal installation.

Working voltage
24-36 kV

Reference standards
IEC 60137 (eletrical test)
EN 50180-50181 (DIN 47636 / HN 52-S-61) coupling interface.

Identification Electrical data C M H L


Lightning Dry power
Maximum Nominal impulse frequency Contact Threded
Fig. Type Drawing operation current voltage voltage type hole Weight
voltage whitstand whitstand
kV A mm. (min.) mm. ( 1) mm. kg.
1 PTS 24/250 1921 250 Lamellare M8 222 150 1,4
24 125 kV 55 kV
PTS 24/630 1925 M 630 M16x29 mm. M12 239 120 2,2
2 PTS 36/400 1942 400 Lamellare M8 266,5 150 2,4
36 170 kV 75 kV
PTS 36/630 1925 630 M16x29 mm. M12 269 150 2,4
3 PTS 24/630 1929 24 630 125 kV 55 kV M16x29 mm. M12 234 120 3,2

46
Fig. 1 Fig. 2 Fig. 3

Pos. Components
1 Lower connection
2 Epoxy resin insulated part
11
3 Earth socket or outlet of the capacitive potential divider
4 O-Ring gasket
5 Coupling interface DIN 47636
9 6 Copper bar
7 Upper connection
10 8 Insulator fixing flange
9 Fastening insulator screws
10 Mobile connector fastening 25 e 400 A.
11 Plastic protective cover
8
7 5
All the items are included in the supplied kit
6

47
Type PRI 24 kV
SF6 - air bushing for indoor use

General characteristics
The PRI bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for indoor applications.
They are equipped with nichel-plated copper conductor and it is supplied completed with
O-Ring gasket made by EPDM for SF6 gas seal.

Application
For indoor application and connection with bare electrical wire.

Working voltage
Up to 24 kV

Reference standards
IEC 60137

Commercial code
1G12185024

Assembling instructions Technical data Mod. 85024


Bushing insulator PRI. Nominal current 630 A
Prepare the holes on the body of the tank as indicated in the Max operating voltage 24 kV
steelwork holes Lay-out. Remove the paint, or any insulating Frequency withstand voltage 55 kV
coat in the area of fixing holes, in order to guarantee a Impulse withstand voltage 125 kV
correct earth connection of the bushing. Creepage distance 380 mm.
Moreover, make sure that the surface where the bushing is Weight 1,95 kg.
placed is without any type of roughness or unevenness. It
must be completely clean in order to guarantee a perfect
tightness.
Connect to earth, when not used as capacitive outlet, the M5
thread (A) connected to the equipotential screen.
Tighten the 6 fixing screws M6, together with their relevant
washers, with a tightening force value of 9 11 Nm. The
tightening operation must be done crosswise. The lower
connection (M10) must be fastened with a tightening force
value of 30 35 Nm.

48
Steelwork holes Lay-Out

49
50
51
Note

52