730 11
730 11
730 11
HSE 730/11
Paras Heading
1-3 FOREWORD
4-8 INTRODUCTION
9-41 Temporary distribution of electricity
10-13 Primary distribution equipment and installation
14-15 Dockside distribution
16-18 Protective equipment and switchgearProtective equipment and
switchgear
19-22 Generators
23 Liaison with supply authority
24 Shore to ship electrical distribution
24-27 Planning and design of the temporary electrical installation
28-29 Distribution cables and connections
30-31 Electrical supply requirements
32-35 Provision on board the vessel
36-41 Use of vessel's own electrical supplies
42-65 Lighting requirements
42-46 Introduction and definitions
47-50 Normal duty lighting equipment and circuits
51-53 Safe installation of normal duty lighting circuits
54-57 Lighting festoons
58 Confined spaces
59-61 Maintenance of normal duty lighting equipment
62-65 Temporary lighting equipment for use in potentially flammable
atmospheres
66-85 Portable and transportable electrical equipment
66-67 Introduction and definition
68-76 Supply and loading considerations
77-85 Maintaining portable and transportable electrical equipment
86-91 Testing and maintenance of the temporary electrical installation
APPENDIX 1 References
References Technical notes on residual current devices and reduced low voltage
systems
FOREWORD
1 The guidance in this document addresses the provisions made for temporary
electrical installations used in the shipbuilding and ship-repairing industries. It
contains internal guidance which has been made available to the public. The
guidance is considered good practice but is not compulsory. You may find it useful
in deciding what you need to do to comply with the law. However, the guidance may
not be directly applicable in all circumstances and any queries should be directed to
the appropriate enforcing authority.
3 The Health and Safety Executive would welcome comments on this guidance
from shipyard operators or any other interested parties.
INTRODUCTION
4 During the course of work in shipbuilding and ship-repair yards it is likely that
a temporary electrical supply will be required to supplement the build and repair
programmes. An electricity supply is needed for the operation of equipment such as
welding apparatus, extraction systems, and other electrically powered plant and
tools.
5 It is essential that the installed electrical system is safe and without risks to
health during operation, use and maintenance. The arduous nature of the industry
imposes a significant burden on the condition of the temporary electrical installations
used in shipbuilding and repair, this will need to be borne in mind when planning and
designing the electrical system.
11 The cables of these ring main circuits are typically of the steel wire armoured
type which are further protected by placing in ducts, or by similar measures to
prevent inadvertent damage by dockside vehicles or plant.
Dockside distribution
14 Distribution of the electrical supply for work at the building berth or
construction facility should be arranged from these dockside substations.
15 The distribution voltages to the working areas from the dockside substations
are normally at 400 volts ac 3 phase and neutral, 230 volts ac single phase and 110
volts ac single phase. The system protection for these electrical supplies may
include devices such as miniature circuit-breakers and sensitive earth leakage
protection which are typically housed in the distribution substation.
16 Protective equipment refers to items such as fuses, earth fault relays and
overcurrent relays that operate under overload and fault conditions. The rating of
protective equipment and switchgear must be selected to embrace the worse case
fault conditions which are anticipated at that point in the electrical installation. It is
normal for this equipment to be specified to a national and international product
standard, for example, the BS EN 60947 series Specification for low-voltage
switchgear and control gear.
Generators
20 Portable generators which are used in a particular location for short-time work
(eg less than one day) need not be earthed provided that they are only used in
conjunction with Class II (double insulated or all-insulated) tools or apparatus.
21 Small 110 volt portable generators need not be earthed but should be bonded
if all the equipment in use is of double insulated construction or if they supply only
one item of 'earthed' equipment.
23 When use is made of electrical systems and services under the control of
other duty holders, such as a port authority, adequate information which details the
available protective apparatus and any restrictions on the electrical supply, should
be available to allow the temporary electrical installation to be used safely.
25 In grouping and segregating the electrical supply for the various work
activities, eg welding supplies located in one area, it is recommended that electrical
supply cables are located away from areas where damage is foreseeable. This may
involve:
(3) arranging the cable runs on the side of the vessel under repair or
construction to where plant access (craneage, etc) is restricted.
Figures 1 and 2 show practical examples of cable protection for work in shipyards.
(1) allow for extension of the system which minimises disruption and can
be carried out safely;
(2) the capability of the electrical equipment;
(3) the need for maintenance during the lifetime of the programme; and
(4) the placing of cables and distribution outlets on decks and gangways
to prevent obstruction.
30 Electrical equipment used on board the vessel during building and repair,
including plant and tools, is likely to operate at various supply voltages which may be
obtained by direct supply from a dockside substation or by subsequent
transformation via a distribution point. A restriction on auxiliary machinery and plant
operation may occur if 50 Hz and 60 Hz systems are necessary.
35 The earth conductors should be of the same size and rating as the phase
conductors to ensure currents may be safely discharged in the event of a fault
condition.
38 A further shortcoming when making use of the vessel's own electrical supplies
is the available knowledge and expertise with regard to the full extent of the vessel's
sources of electrical supply. Clearly, work should only proceed on this basis if there
is sufficient information available to the yard operators from the ship's crew, for
example in the form of diagrams, schematics and details of protection, to allow for
safe working during the repair activities.
LIGHTING REQUIREMENTS
43 Precautions must be taken against the danger of electric shock and barriers
should be used as appropriate to prevent secondary effects such as falls which may
result from an electric shock injury. In addition, safeguards should be used in cases
of failure of the lighting and from the dangers of electrical fires and explosions which
may include earth leakage monitoring.
44 For the purpose of this guidance, normal duty lighting circuits are those used
to illuminate working areas which do not contain a potentially explosive atmosphere
due to, for example solvent vapours, or escape of gas from welding equipment.
48 This approach has evolved from assessment of the risks of injury to yard
personnel from electric shock and consideration of illumination levels in working
areas. It should be noted that voltage levels of less than 110 volts which would
provide an even greater level of safety are not normally practicable in shipbuilding
and repair due to loads and lengths of supply cables. Lower voltage, eg 25 volt
handlamps may however be necessary in confined conducting locations, supplied
from a step-down transformer close to the point of use.
49 In circumstances which require direct current supplies for lighting purposes,
typically older installations and equipment, the recommended supply voltage is 110
volts dc.
51 A principal safeguard to allow work to proceed on the vessel is that the design
of the temporary electrical installation includes provision for diversity of supply to
lighting circuits. The circuits should be arranged such that failure of a single element
in the electrical distribution scheme will not result in the 'blacking out' of an entire
ship area.
(2) 'safety' lights installed at each hold, tank or other space which is not
serviced by the vessel's emergency lighting system;
Lighting festoons
54 Flexible pvc or elastomeric insulated cables are widely employed for lighting
festoons. These cables should be run in the manner described at paragraphs 24
and 29.
55 Fittings for use with tungsten filament lamps, typically 100 watt rated, for
normal duty lighting should preferably be constructed in polycarbonate or a similar
impact resistent attached wire guard, wherever they are accessible or may be
subject to foreseeable mechanical damage. The wire guard should either be
adequately earthed or fitted in such a way that there is no possibility of it becoming
charged either by contact with live parts or by leakage currents under fault
conditions.
56 It is strongly recommended that only festoon lighting systems with
lampholders bonded or moulded to the cable are used and, where necessary, the
bulb is protected by a wire cage or other means of protection.
Confined spaces
58 The use of lighting circuits supplied at a safe extra low voltage, normally not
exceeding 50 volts ac or 120 volts dc, is recommended for working in confined
spaces, for example, inside double bottoms where workers adopt a cramped
position and contact with temporary electrical equipment may occur. The risk of
damage to cables and equipment in such spaces is increased and consideration
should be given to safe systems of work, including reduced voltage levels, to prevent
danger.
(1) plugs and sockets which are used in hazardous areas should be
suitable for use in that particular zone of risk;
(3) the type of cable should be suitable for rough usage and other adverse
environmental conditions, eg presence of solvents;
(4) the cable should also be suitable for the circuit protective
arrangements, eg where earth monitoring is used, the cable should
include the appropriate number of conductors; and
(5) where the apparatus needs to be earthed, the cable may include an
earthed flexible metallic screen in addition to the earth conductor.
66 During the lifetime of a repair or build project it is likely that numerous items of
portable and transportable electrical equipment will be used to assist in work activity.
This equipment can take many forms including:
(4) grinders.
69 The variation in the quantity and supply requirements of the portable and
transportable electrical equipment will mean that supplies of varying capacity are
included in the specification of the temporary electrical installation. These electrical
loading constraints should be considered during planning (see paragraphs 24-27).
70 Circuit and system protection against overcurrent and earth fault conditions
by adequately constructed and rated fuses, circuit-breakers and isolator switches
should be used, as necessary, to satisfy the duties involved.
73 Portable hand-held electric tools such as drills, linishers and grinders are
normally operated from a low voltage supply. Good practice observed at
shipbuilding and repair yards is a 110 volt single phase supply obtained from a
double wound transformer which conforms with BS 4363: 1991, or an equivalent
standard. Further details of the 110 volt system are given at Appendix 2.
75 Plug and socket connections for portable and transportable apparatus should
be arranged as at paragraph 28.
76 Additional methods which are available to ensure safety of operation and the
safe use of electricity with portable and transportable equipment include:
79 The following faults can be seen easily and will be picked up during formal
visual inspections (and the checks by the user):
(4) damage to plugs and sockets such as cracked casing, bent pins, or
signs of overheating;
80 Users can be given basic training so that they can visually check the
equipment they are using. It is recommended that they look at 230 volt equipment
and RCDs every day or at the start of every shift (if the yard is in use 24 hours/day).
81 Testing can detect faults such as loss of earth continuity, deterioration of the
insulation and internal or external contamination by dust, water etc. All of these
faults are likely to occur at a shipbuilding or repair yard because of the arduous
environment. They could result in electrocution or cause a fire. Therefore, it is
important that testing is carried out by a competent person at a frequency
appropriate to the type of equipment and the risks.
(2) after any repair, modification or similar work to the equipment, when its
integrity needs to be established.
*And when returned from a build/repair project or moved to another build/repair project
location.
**It is recommended that fixed RCDs are tested on a 3-monthly basis, while portable RCDs
are tested monthly.
84 Higher risk equipment (230 volts or above) needs more frequent checking,
inspection and testing than lower risk equipment (110 volts or less).
87 Shipyards will normally have the facilities available to carry out their own
maintenance on practically all aspects of repair, calibration, inspection and test to
both heavy current and electronic equipment.
91 Test and inspection of the completed installation on board the vessel should
be performed in accordance with the reference at Appendix 1 paragraph 3.
March 1996
APPENDIX 1
(paras 12, 22, 41, 50, 52(3), 63, 72, 74, 77, 88 and 91)
REFERENCES
16th Edition of the IEE Wiring Regulations for Electrical Installations 1991 (as amended).
Available from: The Institution of Electrical Engineers, Hitchen, Hertfordshire SG5 1RS.
(Also available as BS 7671: 1992 Requirements for electrical installations. IEE
Wiring Regulations Sixteenth Edition ).
British Standards may be obtained from British Standards Institution, 389 Cheswick
High Road, London, W4 4AL.
2 HS(G) 118 Electrical safety in arc welding HSE Books 1994 ISBN 0 7176
0704 6.
3 BS EN 60529: 1992 Specification for degrees of protection provided by
enclosures (IP code).
6 HS(G)85 Electricity at work - safe working practices HSE Books 1993 ISBN
07176 0442 X.
APPENDIX 2
(para 73)
2 The RCD is sensitive to very small currents. It does not limit the current
flowing in the event of shock, it limits the time for which that current flows thus
minimising injury. If an RCD fails to operate the current will continue flowing,
possibly dangerously.
3 RCDs can also be subject to 'nuisance tripping'. This is where the RCD trips
frequently in the absence of a detectable fault. The cause may be an intermittent
fault, or may be due to 'leakage' currents from items such as information technology
equipment. The resulting loss of supply causes inconvenience to users of the
system, and increases the likelihood of the device being defeated in some way, so
rendering the system without protection.
4 These are electrical supply systems in which the maximum voltage to earth
that can occur in the event of a fault or damage to the system, is reliably limited to a
value which is unlikely to cause danger to persons. Unlike RCDs, reduced low
voltage systems are passive systems in that they do not rely on the operation of a
sensitive electomechanical device to ensure safety.
6 Safety extra low voltage (SELV) systems limit the voltage available to a
maximum of 25 volts. These systems are often used for lighting circuits or similar
low power requirement situations, but the low voltages make the system less useful
for use with power tools and more general application.
7 The reduced low voltage system in most common use at UK shipbuilding and
repair yards for general applications is that which is 110 volt centre tapped to earth.
In this system the source of the electrical supply is usually a double wound
transformer with an earthed screen between the primary and secondary windings of
the transformer. In addition, the star point or neutral of a 3-phase transformer is
connected to earth, and the centre point of a single phase or 2 pole winding is
connected to earth (see figures 1 and 2). It is possible to use generators to supply
these systems and these should be configured to provide the same features.
A system in which the nominal phase-to-earth voltage does not exceed 63.5V and
the nominal phase-to-phase voltage does not exceed 110V.
3 phase
L2
L3
o
Source earth Protective
Conductor
RLV
System phase-to-phase voltage not
exceeding 110 volts Temporary
System phase-to-earth voltage not installation
exceeding 63.5 volts. Distribution
Distribution
All exposed conductive parts are equipment equipment
connected to the protective conductor.
Exposed conductive parts
Figure 1
Single phase
L2
o
Protective
Source earth conductor
RLV
System line-to-line voltage not
exceeding 110 volts Exposed
System line-to-earth voltage not conductive Temporary
exceeding 55 volts parts
installation
All exposed conductive parts are
connected to the protective conductor Distribution equipment
Figure 2
8 The phase to phase (for 3-phase supplies) and the pole to pole (for
single-phase supplies) voltages on the secondary output does not exceed 110 volts.
The corresponding phase to earth and pole to earth voltages will then not exceed
63.5 volts and 55 volts respectively at the transformer output terminals.
9 In this way, the system is able to supply 110 volts to tools or equipment in use
at the yard, whilst technical investigation has shown that the maximum indirect
contact touch voltage from one of these systems does not exceed 40 volts. This can
be a steady state condition and it does not exceed the limits for electric shock
protection set out in the protection curves for normal human body impedance, as
shown in IEC publications 479-1 and 2.