Dunham Bush Fault Codes
Dunham Bush Fault Codes
Dunham Bush Fault Codes
Booklet
R410a Non Inverter and Inverter
R22 Fixed Speed
2016 Version
1.2
Products That PerformBy People Who Care
FAULT CODE BOOKLET
Index
2016
Version
1.2
2016
Version
1.2
Page 1
of 25
FAULT CODE BOOKLET
R22 Fixed Speed
Cassette Split
2016
Version
1.2
The standard value for E7 No over zero signal/EEPROM error Cut Out 0C
Cut In 5C
the three sensors is E8 Water level alarm
10k at 25C.
Page 2
of 25
FAULT CODE BOOKLET
R22 Fixed Speed
Ducted Split
2016
Version
1.2
Page 3
of 25
FAULT CODE BOOKLET
R22 Fixed Speed
Ducted Split
2016
Version
1.2
Page 4
of 25
FAULT CODE BOOKLET
R22 Fixed Speed
Under Ceiling Split
2016
Version
1.2
Page 5
of 25
FAULT CODE BOOKLET
R22 Fixed Speed
Rooftop Package
2016
Version
1.2
Page 6
of 25
FAULT CODE BOOKLET
R410A Non Inverter
High Wall Split
2016
Version
1.2
Check CN8
YES connection
Page 7
of 25
FAULT CODE BOOKLET
R410A Non Inverter
Cassette Split
2016
Version
1.2
Page 8
of 25
FAULT CODE BOOKLET
R410A Non Inverter
Ducted Split
2016
Version
1.2
Page 9
of 25
FAULT CODE BOOKLET
R410A Non Inverter
Under Ceiling Split
2016
Version
1.2
Page 10
of 25
FAULT CODE BOOKLET
R410A Non Inverter
Rooftop Package
2016
Version
1.2
Page 11
of 25
FAULT CODE BOOKLET
R410A Inverter
High Wall Split
2016
Version
1.2
TX (C) K
Min: 210VAC/50Hz
20 68.66 Communication Error:
21 65.62 Max: 240VAC/50Hz
22 62.73 Measure between N and S. Voltage readings will fluctuate between negative and P-N: 277356 VDC
23 59.98 positive AC readings, if it is not fluctuating in positive readings the indoor PCB must
24 57.37 be inspected. If the voltage fluctuates only in positive values the outdoor PCB must Ref. Charging Table:
25 54.89
be inspected.
26 52.53
27 50.28 Pipe Refrigerant
Refrigerant Leak Detected:
28 48.14 Size per Meter
29 46.11 Check refrigerant charge, is there any gas leaks present. Ensure that T2 coil sensor is
30 44.08 fixed in its sleeve, please note that an imbalance in R410A 1/4 23g per m
refrigerant due to vapour charging or gas leak can cause this fault. 3/8 60g per m
1/2 120g per m
IPM/EGBT Module Protection:
T3 High Temperature
1. Check the IPM continuity from P to UVW, all readings must be equal and N The unit is pre-
Cut Out 65C to UVW. Place the black test lead on P and red test lead on U, V or W. Use charged for a 5m pipe
Cut In 52C the red test lead for N and the black test lead for U,V or W. run if the piping ex-
ceeds 5m use the
2. Ensure that the IPM PC board is securely installed on the heat sink, ensure
T4 Ambient Temperature table above for cor-
that sufficient heat past is used and that the heat sink is clean.
rect charging values.
Cut Out <-7C/>43C 3. Check if the condenser fan motor rotation is correct and if it is turning freely.
Cut In >-7C/<43C Test the running capacitor of the fan motor, ensure that the macro fared
Please do not charge
reading do not exceed the allowed over/under tolerance as indicated on the
HDT Pipe Temperature vapour, only liquid
capacitor.
and use a charging
4. Check compressor windings, resistance must be equal across U-V, U-W and scale
Cut Out 115C
Cut In 90C V-W. Resistance will be between 0.5 and 5.9
Page 13
of 25
FAULT CODE BOOKLET
R410A Inverter
High Wall Split
2016
Version
1.2
Page 14
of 25
FAULT CODE BOOKLET
R410A Inverter
High Wall Split
2016
Version
1.2
Page 15
of 25
FAULT CODE BOOKLET
R410A Inverter
High Wall Split
2016
Version
1.2
Check refrigerant charge, is there any gas leaks present. Ensure that T2 coil sensor is
fixed in its sleeve, please note that an imbalance in R410A
refrigerant due to vapour charging or gas leak can cause this fault. T3 High Temperature
Check whether there is any damage to the reactor and the wire connections. Test the
capacitor micro fared reading and test if the ohm reading is around zero .
Ensure that the wiring connections on the compressor is correct and secure, the
connection sequence must be in a clockwise direction. Inspect the outdoor fan
connections and check the fan capacitor micro fared readings.
Page 16
of 25
FAULT CODE BOOKLET
R410A Inverter
Cassette Split
2016
Version
1.2
T5 Sensor Resistance Table Run Timer Fault Description 1Phase Power Supply:
Page 17
of 25
FAULT CODE BOOKLET
R410A Inverter
Cassette Split
2016
Version
1.2
Page 18
of 25
FAULT CODE BOOKLET
R410A Inverter
Cassette Split
2016
Version
1.2
Cut Out <-7C/>43C 8 Flashes On off Flash On Over current of IPM output
Note:
Cut In >-7C/<43C
9 Flashes On On On On Low voltage protection
HDT Pipe Temperature 10 Flashes On On On On High voltage protection
Ref. Charging Table:
12 Flashes On Flash On On Control chip failure
Cut Out 115C
Cut In 90C 13 Flashes On On Flash On Zero speed of compressor Pipe Refrigerant
Size per Meter
15 Flashes On On Flash On Lack of phase or speed fluctuates
Page 19
of 25
FAULT CODE BOOKLET
R410A Inverter
Ducted Split
2016
Version
1.2
The standard value for Flash Slow Off Off Inverter compressor drive protection
T1, T2, T3 and T4 is Flash Off On Off Compressor discharge sensor abnormal
10K at 25C T5 is
54.89K at 25C
New Low Static Ducted 12 000Btu Split Type
1Phase Power Supply: Run Timer Fault Description T5 Sensor Resistance Table
Page 20
of 25
FAULT CODE BOOKLET
R410A Inverter
Ducted Split
2016
Version
1.2
Page 21
of 25
FAULT CODE BOOKLET
R410A Inverter
Ducted Split
2016
Version
1.2
Page 22
of 25
FAULT CODE BOOKLET
R410A Inverter
Ducted Split
2016
Version
1.2
Page 23
of 25
FAULT CODE BOOKLET
R410A Inverter
Under Ceiling Split
2016
Version
1.2
TX (C) K
E0 EEPROM error
20 68.66
E2 Communication error 21 65.62
22 62.73
E3 Communication error between IPM and main PC board 23 59.98
E4 Outdoor coil /ambient temperature sensor abnormal 24 57.37
25 54.89
E5 Voltage protection 26 52.53
P0 Compressor top temperature sensor abnormal 27 50.28
28 48.14
P1 High pressure protection 29 46.11
P2 Low pressure protection 30 44.08
Page 24
of 25
FAULT CODE BOOKLET
R410A Inverter
Under Ceiling Split
2016
Version
1.2
Cut Out <-7C/>43C 8 Flashes On off Flash On Over current of IPM output
Note:
Cut In >-7C/<43C
9 Flashes On On On On Low voltage protection
HDT Pipe Temperature 10 Flashes On On On On High voltage protection
Ref. Charging Table:
12 Flashes On Flash On On Control chip failure
Cut Out 115C
Cut In 90C 13 Flashes On On Flash On Zero speed of compressor Pipe Refrigerant
Size per Meter
15 Flashes On On Flash On Lack of phase or speed fluctuates
Page 25