The MP range valve regulated lead acid batteries are used as standby
power for communication, power, military and broadcast and television
system. They possess precise ABS heat seal technology between
container and lid and patented post seal structure.
The design float life is12 years at 25 (77 ).
Dimensions-mm[inch]
283 [11.14]
559 [22.01]
125 [4.92]
Specifications
Battery Model 6-GFM-155F
Terminal M6 Female
Terminal Hardware Torque 8 1.0Nm
Container Material ABS (V0 optional)
1.60V 504 271 164 119 96.1 55.1 43.2 33.1 28.9 25.0 19.4 16.0 13.6 8.43 7.04
1.67V 473 261 161 118 95.6 54.8 42.4 32.9 28.7 24.9 19.2 15.7 13.4 8.36 6.98
1.70V 469 257 159 117 94.9 54.4 42.2 32.8 29.3 24.9 19.2 15.8 13.3 8.34 6.98
1.75V 431 249 158 116 93.5 53.0 41.7 32.4 28.8 24.7 19.0 15.7 13.3 8.32 6.97
1.80V 386 232 151 112 91.1 52.6 41.4 32.3 28.1 24.2 18.9 15.5 13.2 8.24 6.96
1.83V 368 212 148 108 87.1 51.9 40.1 30.8 27.2 23.3 18.4 14.9 12.7 8.22 6.85
1.85V 345 206 137 104 84.4 50.0 39.0 30.4 26.5 22.8 17.8 14.8 12.6 8.06 6.79
O O
Discharge Data with Constant Power UnitsWatts per cell (25 C, 77 F)
End voltage
per cell 5min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 12h 20h 24h
1.60V 842 476 297 223 181 104 82.1 63.6 57.1 48.0 37.7 30.9 26.3 16.7 14.0
1.67V 811 467 294 222 180 104 81.0 63.5 56.8 48.0 37.3 30.7 26.1 16.6 14.0
1.70V 806 462 294 221 179 103 81.0 63.2 56.2 48.0 37.2 30.5 25.8 16.6 14.0
1.75V 752 458 293 221 177 103 80.2 63.2 55.9 47.8 36.8 30.4 25.8 16.6 14.0
1.80V 703 433 286 216 176 103 79.9 63.0 54.7 47.4 36.8 30.3 25.7 16.6 13.9
1.83V 678 397 283 209 169 101 78.1 60.7 53.5 46.0 36.4 29.5 25.2 16.5 13.8
1.85V 642 388 263 201 164 98.0 76.0 59.9 52.2 45.1 35.3 29.3 25.0 16.2 13.7
Terminal Voltage(V) Vs. Discharge Time (25OC, 77OF) Battery Voltage Vs. Charge Time
Capacity
Current
Voltage
Charge
Charge
Charge
13
Charge Characteristic
Discharge Voltage(V)
12
(%) (CA) (V) Constant Charge At 0.20CA-14.1V(25)
120
11 Charge Charge
0.05CA 14 Voltage Capacity
0.1CA 100
10 0. 25CA
0. 6CA
1CA 80 0.20 13
9 100%Charge
60 0.15
12 50%Charge
8
40 0.10
11
20 0.05
0 2 6 12 30 60 3 10 20 Charge
Current
Min h 0 0 0 2 4 6 8 10 12
Time(hour)
13.0
100
Capacity(%)
OCV (V)
12.5 75 O O
10 C(50 F)
12.0 50
40 OC (104 OF) 30 OC (86 OF) O
20 C(68 F)
O
25
11.5
11.0 3 6 9 12 15 18 21 24 27
0 10 20 30 40 50 60 70 80 90 100
6-GFM-155F-03-N-EN (Ver.03 July 2012) Subject to revision without prior notice. E.& O.E.
Storage Time(month)
Remained Capacity(%)
Final
Max. Discharge
Set Allowable 1.80 1.70 1.55 1.30
Application Temperature Charge Voltage
Point Range Current V/Cell
NARADA POWER SOURCE CO.,LTD. NARADA ASIA PACIFIC PTE.LTD. NARADA EUROPE (UK) LIMITED
9F, Building A, No. 50 Zijinghua Road, Hangzhou, China 65 Ubi Crescent #07-05 Hola centre, Singapore Spectrum House, Dunstable Road, Redbourn,
Tel:+86-571-28827013 Fax:+86-571-28828290 Tel: +65-6848 1191 Fax: +65-6749 3498 St. Albans, Herts AL3 7PR
Website:www.naradabattery.com E-mail: [email protected] E-mail: [email protected] Tel: +44 (0)845 371 7095 Fax:+44 (0)845 612 2031
E-mail: [email protected]