UAT HV Cable Box Assembly
UAT HV Cable Box Assembly
UAT HV Cable Box Assembly
1 2 3 V 4 5 6
673 2x150=
300
6 2
A A
We reserve all rights in this document and in the in-
1
formation contained therein. Reproduction, use or
750
1 CABLE BOX MS 1 SET -
FLEXIBLE CONNECTION
3 COPPER 3 -
(100Wide x8Thk)
CONNECTION FLAT
4 COPPER 3 -
B (100Wide x8Thk) B
5
ALUMINIUM GLAND PLATE 5Thk)
AL 3 -
5
is strictly forbidden.C
9 -
HV LINE BUSHINGS 17.5 kV, 2000 Amps, 3 -
Bushing
3 4
C NOTE: C
1) HV PH CABLE BOXFOR
& 1W 1U,1V
SUITABLE FOR 3 RUNS per phase.
2) MINIMUM CLEARANCE IN CABLE BOX(AIR)FOR 11 kV:
PHASE-PHASE : 130 mm
PHASE-EARTH :80 mm
3) DIMENSIONS SHOWN HAVE A TOLERARANCE OF 5%.
4) EARTH STRIPS WILL BE PROVIDED INSIDE CABLE BOX FOR CABLE SCREEN EARTHING
1330
ItemQuantity
Unit Part ID Dimension Material ID Description Mass Rem
TRAFO_ASSEMBLED 0.032
Prepared HV
Responsible CABLE
department BOX ASSEMBLY
SVR 12.03.2011 PPTR-SPTD
1600 Approved Take over department Language
AKA --
Revision Mass Order Page
AEM 1
Document No. Total
Rev Ind Revision Appd Date ABB LIMITED 1LIN600105-AEM 1
1 2 V 3