Corrosion and CP - USBR PDF
Corrosion and CP - USBR PDF
Corrosion and CP - USBR PDF
14. ABSTRACT
This document provides field personnel the principles they need for a clearer understanding of basic corrosion processes and
methods to deal with them. It further describes some simple situations in which they might design and install a cathodic
protection system using site forces. The document also describes general cathodic protection monitoring procedures. In most
circumstances, however, field personnel should seek some level of participation and assistance from corrosion professionals.
15. SUBJECT TERMS
Corrosion, corrosion mitigation, corrosion principles and concepts, oxidizer, oxidation, reduction, polarization,
depolarization, passive, corrosion cell, galvanic series, concentration cell, pH cell, stray current corrosion, attenuation,
cathodic protection, coatings, galvanic anode cathodic protection, impressed current cathodic protection, anodes, rectifier,
test station, junction box, bond box, service life.
16. SECURITY CLASSIFICATION OF: 17. LIMITATION 18. NUMBER 19a. NAME OF RESPONSIBLE PERSON T
This written material consists of general information for internal use only by
Bureau of Reclamation operations and maintenance staff. Information contained
in this document regarding commercial products or firms may not be used for
advertising or promotional purposes and is not to be construed as an endorsement
or depreciation of any product or firm by the Bureau of Reclamation.
Acronyms and Abbreviations
AC Alternating current
CP Cathodic protection
CSE Copper sulfate electrode
DC Direct current
D&S Directive and Standard
ERI Electrical resisting imaging
FIST Facilities Instruction, Standards, and Techniques
HMWPE High molecular weight polyethylene
HSCI High-silicon cast iron
ICCP Impressed current cathodic protection
IR Infrared
PPM Parts per million
SOP Standard Operating Procedures
TSC Technical Service Center
UV Ultraviolet
iii
iv
Corrosion and Cathodic Protection
Table of Contents
Page
v
Corrosion and Cathodic Protection
vi
Corrosion and Cathodic Protection
Tables
Table 1 Galvanic Series of Metals Exposed to Seawater .................................. 12
Table 2 Typical Current Requirements for Bare Steel....................................... 27
Table 3 Properties of Magnesium and Zinc Anodes .......................................... 29
Table 4 Galvanic Anode Grounding Resistances Used for FIST 4-5 ................ 32
Table 5 Estimated Specific Coating Resistances for Pipe Grounding Resistance
Calculations......................................................................................................... 34
Table 6 Maximum Allowed Current Per Galvanic Anode ................................ 43
Table 7 GACP Inspection and Maintenance Checklist...................................... 56
Table 8 ICCP Inspection and Maintenance Checklist ....................................... 61
Figures
Figure 1 The corrosion cell .................................................................................. 9
Figure 2 Anode to cathode area ratio ................................................................ 14
Figure 3 The use of isolating joints to prevent galvanic corrosion .................... 16
Figure 4 Installation of galvanic anode .............................................................. 37
Figure 5 Typical test station with board exposed .............................................. 39
Figure 6 Typical junction box ............................................................................ 39
Figure 7 Typical galvanic anode cathodic protection system installation ......... 43
Figure 8 Typical galvanic anodes ...................................................................... 45
Figure 9 Typical ICCP system installation ........................................................ 45
Figure 10 Typical ICCP anodes ......................................................................... 46
Figure 11 Typical rectifier cabinet ..................................................................... 47
Figure 12 Typical rectifier board inside a cabinet ............................................. 47
Figure 13 Wasps occupying a junction box ....................................................... 50
Figure 14 Copper/copper sulfate reference cell and components ...................... 51
vii
Corrosion and Cathodic Protection
vi
Corrosion and Cathodic Protection
1.0 Introduction
The Bureau of Reclamation operates and maintains multiple hydroelectric power
plants, switchyards, pumping plants, and associated facilities in the 17 Western
United States. These facilities are critical to the electric power and water delivery
systems on which many rely. Operating and maintaining the complex electrical
and mechanical equipment which these facilities house is essential to ensure
reliability. In fulfilling this responsibility, Power Operation Managers must
ensure the safe and sound operation of all structures and equipment.
1.1 Purpose
This volume provides basic information concerning:
1.2 Scope
This document provides field personnel the principles they need for a clearer
understanding of basic corrosion processes and methods to deal with them. It
further describes some simple situations in which they might design and install a
cathodic protection system using site forces. The document also describes general
cathodic protection monitoring procedures. In most circumstances, however, field
personnel should seek some level of participation and assistance from corrosion
professionals.
1
Corrosion and Cathodic Protection
2.0 General
The reader may also see other classifications such as microbial-induced corrosion
or stray current corrosion. In addition, many of the types described above have
2
Corrosion and Cathodic Protection
A full treatment of each type of corrosion and its intricacies is beyond the scope
of this document.
3
Corrosion and Cathodic Protection
[Report pipe corrosion damage using the form at the end of Technical
Memorandum No. MERL-2011-35, Guidelines for Reporting Corroded Pipe.2
A copy of this form is reproduced at the end of this document in
Appendix B.]
Water
Oxidizers
Ionizable chemicals
These components of the electrolyte can have a strong influence on corrosion rate.
However, temperature and the chemical that corrosion itself causes are also
important. These factors will be explored further in the following paragraphs.
3.1.1 Water
Bare ferrous pipe kept in a dry storage area will suffer little or no significant
corrosion, but will show rust shortly after immersion or exposure to rain or dew.
This is because a significant amount of dissolved oxygen in the water has rapidly
reacted with the metal. Even though there is plenty of oxygen in the air around a
pipe, it generally reacts with the metal at a very slow or even negligible rate under
ambient dry conditions. The water allows oxygen and other corrosives to readily
interact with the metal in ways they cannot otherwise.
4
Corrosion and Cathodic Protection
3.1.2 Oxidizers
The component of an electrolyte that does the actual corrosion damage is called
an oxidizer. Among this class of dissolved chemical, oxygen is very commonly
encountered. Oxidizers like oxygen in solution steal electrons away from the
metal atom, and having done so, the oxidizer acquires a negative charge and is
said to be reduced. A reduced oxidizer is spent and will not react with additional
metal. The attacked metal atom, having lost one or more electrons, acquires a
positive charge and is said to become oxidized, and it is thereby freed from its
position in a rigid metal structure. Because of this mechanism, the corrosion
reaction in an electrolyte is described as an oxidation-reduction, or a redox
reaction. In this manner, a buried or immersed structure corrodes atom by atom.
The corrosion reaction products of iron or steel with oxygen accumulate as rust.
Since the reacted oxidizer, like oxygen that has formed rust, is no longer available
to do further damage, fresh oxidizer must constantly be replenished at the metal
surface to keep corrosion going. Hence, anything that blocks or makes the
migration of an oxidizer to the metal surface more difficult, such as certain
corrosion products, will slow down corrosion. Whatever brings oxidizers to the
surface, such as a flowing electrolyte, will accelerate corrosion.
Oxygen is not the only oxidizer dispersed in water. Carbon dioxide in the air
forms carbonic acid when it enters water, and acids can also oxidize iron and
steel. Likewise, dissolved air pollutants such as oxides of sulfur and nitrogen will
also form corrosive acids, as can decomposing organic matter. Fortunately,
naturally occurring dissolved acids are often too dilute to significantly corrode
ferrous metal. The corrosion products formed when acid attacks ferrous metals
are hydrogen gas and a metal salt, such as iron carbonate which forms when
carbonic acid attacks ferrous pipe. Dissolved oxygen in combination with an acid
can be particularly corrosive. There are many other soluble materials in soil, and
some may also be oxidizers that can cause corrosion. Dissolved chemicals will
tend to be at equilibrium concentrations in rain, lakes, streams, ground water, and
the like and will tend to return to equilibrium as those components are consumed.
Hence, there should always be a ready supply of some level of oxidizers in the
electrolyte.
Charge balance is central to redox reactions. For every electron given up by the
corroding metal, an oxidizer must take in an electron. Furthermore, nature
requires that charge balance must be maintained at every point in the electrolyte;
positive charges and negative charges cannot accumulate at separate locations.
Ionizable chemicals are important in maintaining this charge balance.
5
Corrosion and Cathodic Protection
negative charges canceling out. Even pure water itself dissociates to a small
extent. The fact that water has a pH of 7 reflects this dissociation. These charged
particles are called ions or radicals, and the materials from which they came are
said to be ionizable. Ions and radicals that carry a positive charge are called
cations while those carrying a negative charge are called anions.
The more ionizable chemicals in soil moisture or water, the more conductive it is
(i.e., the lower its resistivity) and often the more corrosive it may be. A good
comparison is sea water versus fresh water. The former is highly conductive and
typically much more corrosive than the latter. However, there are exceptions to
the resistivity/corrosivity correlation, as in the case of concrete and similar
cementitious materials.
3.1.4 Temperature
Temperature can have a significant impact on corrosion. Elevating the
temperature generally accelerates corrosion, everything else being constant. It
can even determine whether particular forms of corrosion will develop. However,
raising the temperature sufficiently can reduce the solubility of gasses such as
oxygen in an electrolyte and may even dry out a metallic surface in extreme
situations. If this occurs, corrosion may actually slow down or halt.
Temperatures on buried or immersed Reclamation structures are typically not
elevated or too variable.
6
Corrosion and Cathodic Protection
that resists further corrosion, as explained further below. Hence, corrosion rates
are typically greatest at the onset.
Anything that reduces these chemical changes at anodic or cathodic sites is said to
depolarize that site. A simple way of depolarizing a surface is by agitating a
solution, which will sweep reaction products away and refresh the reactants.
Increasing the temperature or introducing certain chemicals can have a similar
impact.
If a more noble metal and a more active one are electrically connected together
(e.g., through a wire or by direct contact) in an electrolyte:
The more active metal will tend to provide at least some of the electron
oxidizer demand at the surface of the noble metal.
The more active metal will supply some additional electrons to oxidizers
at its own surface.
As a result, the anodic metal corrodes more rapidly while protecting the noble
metal. This is typical of galvanic corrosion and, as will be seen, is the basis for
galvanic anode cathodic protection. This differing tendency to lose electrons
demonstrates itself as a voltage difference between the two metals.
7
Corrosion and Cathodic Protection
sufficient quantity will induce passive film breakdown of iron or steel in concrete,
as will carbonation of the concrete by dissolved carbon dioxide.
Gray cast iron and ductile cast iron corrosion products behave somewhat
differently from the rust on steel. Gray cast iron composed of iron in an
interconnected network of graphite flakes. As a result, when a gray cast iron pipe
buried in soil corrodes, it often suffers selective leaching; the iron corrodes while
the graphite flake network remains intact. This is called graphitic corrosion. The
corroded iron may dissolve away, but rust will more often remain in the voids of
the graphite flake network. Little or no corrosion product expansion results. The
corroded pipe has essentially the same dimensions as the original metal, but with
very little strength. A screw driver or shovel can easily break through graphitic
corrosion products. Ductile iron is also composed of iron and graphite, but the
graphite is in discrete nodules. Unlike gray cast iron, the graphite network is not
interconnected and continuous; the corrosion products are essentially graphite
spheres floating in a continuous network of rust. Nonetheless, a corroded ductile
iron pipe will also often suffer severe corrosion while retaining the looks of an
uncorroded pipe, until one cleans out the pockets of corrosion.
Anode
Cathode
An electrolyte for ion flow between these electrodes
An external metal path for current flow between these electrodes
8
Corrosion and Cathodic Protection
The following discussion will refer to these components. The principles of this
simple model are also useful when considering cathodic protection.
Even general corrosion of a single metal has been described using this model.
The term mixed potential theory was coined to describe it. At any point in time,
mixed potential theory visualizes anodic points and cathodic points on a single
piece of metal in an electrolyte; the locations of these anodes and cathodes
randomly change over time. The result is more or less an even metal loss over the
surface.
Corrosion cells in which tiny anodes and cathodes are in close proximity to each
other are termed microcells. In addition to general corrosion of a metal, pitting
corrosion and intergranular corrosion are other examples of microcells.
Similarly, larger discrete cells can exist and develop a voltage difference. These
are often referred to as macrocells. Examples of macrocells include:
9
Corrosion and Cathodic Protection
Two distinct metals connected together and in the same soil or water a
galvanic cell.
A large metallic structure in different electrolytes or soil conditions a
concentration cell.
As discussed previously, the reactions at anodic and cathodic sites change the
surrounding chemistry and can affect corrosion. These changes are also reflected
in the voltage difference between anodes and cathodes. The voltage difference
between anodic sites and cathodic sites becomes less as the result of anodic sites
becoming less anodic and cathodic sites becoming less cathodic.
a) Buried iron or steel will be anodic to copper ground mats or to brass bolts
or other copper alloy parts.
b) An immersed or buried steel plate with mill scale may suffer accelerated
corrosion at metal exposed through the scale because the steel anodic to
mill scale.
c) Weld areas of a welded pipe may suffer accelerated corrosion because the
weld metal is of slightly different composition or may contain impurities
that make them anodic to nearby base metal.
d) The bottom of a pipeline may corrode while the top remains largely
undamaged because higher oxygen concentration in the soil moisture
(electrolyte) at the top of the pipe creates an oxygen concentration cell
with the bottom of the pipe being the anode.
e) A pipe passing through different types of soil develops voltage
differences, suffering areas of greater and lesser corrosion.
f) The soil side of buried iron steal areas passing through concrete may
suffer accelerated corrosion because the ferrous metal in concrete is at a
more noble potential than the ferrous metal in the soil.
10
Corrosion and Cathodic Protection
Note that in Table 1, graphite, a form of carbon and non-metal, will also develop a
potential in an electrolyte. It is quite noble and can induce galvanic corrosion of a
number of metals or alloys.
A galvanic series must not be confused with the electromotive series. The latter
provides potentials for pure metals and other materials referenced to standard
reversible conditions. While the electromotive series can be valuable research
tool, its use in engineering applications is somewhat limited.
11
Corrosion and Cathodic Protection
(-) Magnesium
Magnesium Alloys
| Zinc
| Galvanized Steel
| Aluminum 1100
| Aluminum 6053
| Alclad
| Cadmium
| Aluminum 2024
| Mild Steel
| Wrought Iron
| Cast Iron
| 410 SS (Active)
| 304 SS (Active)
| 316 SS (Active)
| Lead-Tin Solders
| Lead
| Tin
| Muntz Metal
| Manganese Bronze
| Naval Brass
| Nickel (Active)
| Yellow Brass
| Admiralty Brass
| Red Brass
| Copper
| Silicon Brass
| 70-30 Cupro Nickel
| G-Bronze
| M-Bronze
| Silver Solder
| Nickel (Passive)
| 67Ni-33Cu (Monel)
| 410 SS (Passive)
| Titanium
| 304 SS (Passive)
| 316 SS (Passive)
| Silver
| Graphite
Gold
(+) Platinum
Noble or Passive End
rd
Table 1. Extracted from NACE Corrosion Engineers Reference Book, 3 Ed.;
R. Baboian (Editor).
conditions could yield different orderings. The only way to be certain is to devise
a galvanic series for a specific environment, or to perform confirming tests.
Nonetheless, one can often gain a general idea from a series as to which metal or
alloy is likely to be more active or more noble in a couple and how substantial this
difference may be.
Zinc provides a good case example for this warning. This metal is considerably
more active than steel in the galvanic series of Table 1 and should sacrificially
protect steel. However, elevating the temperature about 180oF, such as in a
domestic hot water tank, or introducing nitrates, bicarbonates, or carbonates can
cause the potential of zinc to become nobler than that of steel.5 When this
happens, the steel will sacrificially protect zinc.
Table 1 is a typical galvanic series tabulation. Like most galvanic series, it was
experimentally developed for typical sea water at a given temperature, flow rate,
and other specific conditions.
13
Corrosion and Cathodic Protection
14
Corrosion and Cathodic Protection
NACE SP 0286 describes the equipment and principles for electrical isolation of
cathodically-protected pipelines.6 This specialized equipment includes flange
isolation kits (incorporate an isolating gasket, isolating washers, and bolt sleeve
isolators), monolithic isolation units for weld applications, and isolating unions
for threaded applications. Isolation materials, especially buried or immersed, can
absorb moisture, which will reduce their electrical resistance. As a minimum,
coatings must be applied to resist moisture absorption. Thick coating systems
such as wax tapes have been used in some Reclamation buried applications.
Placing the isolation in a vault instead of direct burial is ideal as it prevents
deterioration of isolating materials and improves access should repairs be needed.
15
Corrosion and Cathodic Protection
soil corrosion. Since the magnesium anode is the least noble of the three metals
(magnesium, steel, and copper) in the ground (electrolyte), it could have been
used even without the electrical isolation. However, without isolation, the copper
would have demanded current from the anode in addition to the steel pipe. As a
result of using isolation, less anode material is required for this application.
In some instances, there may be a need for alternating current (AC) grounding
that conflicts with the need for electrical isolation. For instance, if in Figure 3 had
there been some AC-induced current on the pipeline or some requirement that the
pipe be grounded against AC or fault currents, then an isolation device would
have prevented this safety feature. Direct current (DC) decoupling devices
provide an alternate solution in such cases. These devices block the flow of DC
current while allowing the flow of AC. In this instance, placing a DC decoupling
device between the motor and the ground mat instead of a flange isolation kit, or
across the isolated flange, would block the draining of cathodic protection current
while allowing any AC pick up by the pipeline to drain to the grounding mat. DC
decouplers can allow the passage of steady-state AC, AC fault currents, and even
lightning currents. Solid state DC decouplers are more popular these days,
displacing polarization cells that were formerly used for a similar purpose.
16
Corrosion and Cathodic Protection
potential or voltage difference will develop between the two regions. A similar
effect occurs when buried pipe passes through different soils; potential differences
develop at different points on the pipe. These differing potentials can accelerate
corrosion at the more anodic points. A common concentration cell effect involves
iron or steel partially encased in cementitious material like concrete or mortar and
partially in soil.
The alkalinity of cementitious materials has two major impacts on iron and steel
corrosion. First, embedded iron and steel can undergo passivation at high pH,
stifling the corrosion process. This is commonly observed in concrete, which has
a typical pH around 12.5. Secondly, carbonic acid or other environmental acids
dissolved in groundwater will react with the alkalies in the cementitious material.
This reaction neutralizes their acidity so that they are no longer corrosive.
Unfortunately, this neutralization can slowly consume the alkalinity of the
cementitious material, eventually destroying the passivity of encased iron and
steel, especially if the cementitious covering is shallow.
Carbon dioxide, which forms carbonic acid in water, can react with the calcium
hydroxide to form calcium carbonate, which has an equilibrium pH of 9.4 at 77oF
(25oC).7 This process is called carbonation, and the resulting pH is too low to
develop and maintain passivation on iron or steel. The thicker and less porous the
layer of cementitious material over the iron or steel, and the more buffering
capability it contains, the longer it is able to neutralize acids and maintain a low
corrosion rate.
17
Corrosion and Cathodic Protection
While cathodic protection can be employed without isolating the encased metal
from that in the soil, the encased metal may needlessly drain a considerable
amount or current. Coating the encased metal will minimize the cathode to anode
area ration and reduce cathodic protection current requirements. Isolation joints
and measures previously described to control galvanic couples are also often
useful in dealing with concentration cells like pH cells. Isolating within the
cementitious material can minimize the amount of coupled metal within the
concrete that will draw CP current; but subsequent testing and repair of the
isolation joint will be difficult. Isolating at or just outside the encasement
eliminates these problems, but may leave a stub projecting from the concrete to
the point of isolation. This stub may still suffer pH cell corrosion at any holidays
in the coating, and the isolating material may absorb moisture and deteriorate.
A thick coating system such as a wax filler and wax tape has sometimes been
used to eliminate such holidays and protect the isolating material. Isolating
within a vault has the benefit of minimizing the amount of encased metal needing
to be cathodically protected while helping to keep the isolating materials dry and
readily available for testing or replacement if needed.
pH cell corrosion may also occur where a structure rises from concrete into the
air. This is particularly a concern when there is puddling at that location due to
condensation, precipitation, etc. Sloping concrete or mortar up to a vertical
ferrous structure may help prevent such puddling. Coating the concrete as well as
the metal around the area where the metal emerges may be helpful, especially if a
layer of carbonated concrete is not yet present. Carbonation of concrete at the air
interface can eliminate the passivating ability of that concrete. As a result, bare
metal just below the surface may start to rust. Coating the metal for a distance
into the concrete when that metal is first installed may able be helpful.
18
Corrosion and Cathodic Protection
charge and is opposite from the flow of electrons or negative charge. To draw
electrons out of the metal, the current must produce a reduction reaction in the
electrolyte at the point of entry. The reduction reaction is normally hydrogen
evolution or oxygen reduction in aqueous electrolytes. Because the metallic
structure in question is not connected to the original source of the current, the
current has to re-enter the electrolyte in order to complete its path. To re-enter the
electrolyte, the current must produce an oxidation reaction at the point. This
oxidation reaction will be corrosion of the ferrous structure, which releases
positive metal ions into the electrolyte and the electrons needed by the reduction
reaction where the current enters. This type of corrosion is called stray current
corrosion. Note that stray current corrosion is not a function of the corrosivity of
the environment. A metal can be made to corrode by this method even in a
benign environment.
High-voltage AC may also cause stray current corrosion. This sometimes occurs
when a three-phase overhead transmission system parallels a buried metallic
pipeline. Corrosion, if it is to occur, is normally in the area where the
transmission line and the pipeline paths eventually diverge. Because of canceling
effects, a buried high-voltage cable containing the three conductors is very
unlikely to cause high-voltage AC stray current corrosion. Fault currents, as from
lightning strikes, are also considered under the topic of stray AC currents.
Telluric currents resulting from sun spot activity are a special case of stray current
corrosion. These currents cause problems especially nearer northern and southern
regions of the globe and near the equator. Solar activity associated with telluric
currents is approximately on an 11-year cycle.9
The structure passes near the anode bed of a foreign structure, placing it in
the anode voltage gradient field.
19
Corrosion and Cathodic Protection
20
Corrosion and Cathodic Protection
2004-1 (Corrosion Considerations for Buried Metallic Water Pipe).11 The first
document uses raw field resistance data that has been computer processed using
an electrical resistivity imaging (ERI) inversion routine; this provides the geo-
electric structure along the pipeline alignment. A statistical treatment is then
applied to the layer resistivity readings along the run of pipe; the end result is
termed the 10 percent probability. Resistivities along a pipeline will typically
vary randomly by 3 or 4 orders of magnitude from location to location along the
alignment. [Do not use the Barnes Layer Method of determining layer soil
resistivities unless a TSC geophysicist or corrosion professional recommends
doing so in a particular situation.] The second document recommends
minimum corrosion mitigation measures based on the 10 percent probabilities
determined in the first document. A corrosion specialist may also employ
experience with similar materials in the same or similar soil, if available. At
times, additional data (e.g., chloride or sulfate concentration, etc.) may be useful.
Soil resistivity readings along the structure and at anode locations are also
essential in designing cathodic protection systems. These resistivities are
determined separate from the 10 percent probability value.
Indicators such as the Langelier Index have sometimes been used to help assess
water corrosivity. The belief was that the tendency of water to form scale on the
surface of a metal indicated that it would not be corrosive. However, this is not
always true, and the use of such indices for natural waters in not reliable.
Due to the geometric variety of anodes that might be used for protecting
immersed structures, this document will not provide basic design algorithms for
that situation. [Seek the assistance of a TSC corrosion specialist or similar
when assessing water corrosivity and designing cathodic protection systems
for immersed structures.] As in soil, reliable resistivity (conductivity) readings
are essential when designing a cathodic protection system for water.
Galvanizing, a zinc coating, isolates the ferrous metal beneath from exposure to
atmospheric corrosives. Furthermore, during periods of wetness (e.g., rain or
dew) it can act galvanically (see galvanic table above) to protect substrate metal at
scratches and nicks in the galvanizing. Galvanizing used in atmospheric
exposures can often provide 30 to 50 years of service life. Performance in
immersion or buried service often does not provide nearly as much service life
and is quite variable. Galvanizing may even passivate in some waters, causing it
to accelerate corrosion of exposed ferrous metal.
Mortar coatings can help the ferrous metal beneath to passivate. However, such
coatings are somewhat fragile and thin. Damage at a mortar coating can lead to
pH cell corrosion at the metal exposed to soil. Problem areas for mortar-coated
pipe are often found at girth weld seams. Such welds are performed in the field
after installation, and the mortar coating is repaired at that time. Field repairs may
not be as effective as shop mortar coatings.
Organic coatings isolate the ferrous metal from a corrosive environment. Unlike
galvanizing and mortar coatings, organic coatings are commonly electrically
isolating barriers and are often called bonded dielectric coatings. If the barrier is
intact, corrosion cannot progress since the metal does not see the corrosive
electrolyte. However, bonded dielectric coatings, especially thin coatings (e.g.,
less than 0.040 in.), are usually not perfect. They typically have pores and defects
as applied and may be damaged during installation or in service; stray currents
22
Corrosion and Cathodic Protection
such as lightning arc strikes can create major defects in them. They also
deteriorate at varying rates with time. Defects in a coating are called holidays.
Short-cuts have ruined many a coating that otherwise would have provided many
years of service. Coating manufacturers are well aware of this and usually
provide detailed instructions for coating applications. Employing trained and
experienced personnel helps ensure good coating performance. Having an
inspector separate from the application vendor helps as well.
Given the importance of a good coating system, the significance associated with
the details of its application, and the developments that are ongoing, site
personnel are strongly advised to work with a TSC coatings specialist for proper
selection and application.
23
Corrosion and Cathodic Protection
However, the coating system must be compatible with cathodic protection and the
level of cathodic protection must not be excessive. For instance, the normal
elevated pH produced on a structure by cathodic protection can damage zinc-rich
primers, and these primers may also lead to inaccurate corrosion monitoring
readings. [Zinc-rich primers must therefore be avoided on cathodically
protected structures.] However, even normally compatible coatings may
disband due to excessive levels of cathodic protection. Corrosion can then take
place at the disbondments where cathodic protection currents may not reach. As
described later, Reclamation employs protection criteria that limit the polarized
potential of a protected structure to prevent cathodic disbondment.
24
Corrosion and Cathodic Protection
This document will explain how to properly use this equipment to accomplish
common cathodic protection tasks.
These standards generally include either of two main criteria for protection of
ferrous metal that Reclamation usually employs for ensuring effective cathodic
protection, especially when the protected structure cannot be observed:
25
Corrosion and Cathodic Protection
These criteria were derived semi-empirically and have served the industry well
for many years. Note that these values involve determining polarized
electrochemical potential values (i.e., with extraneous voltage drop errors
eliminated). IR drop, a major voltage drop error, results when measuring voltage
in a resistive soil or water medium with current flowing.
Special instances may require adjustments to the usual criteria. For instance,
microbial-induced corrosion calls for a minimum -0.950V(CSE) polarized potential
criterion instead of the usual -0.850V(CSE). With some higher strength steels, the
0.100V of polarization may not be usable as it may subject a structure to stress
corrosion cracking. Too negative a potential may also cause either hydrogen
embrittlement or high pH corrosion of some metals.
Reclamation primarily uses the first criterion. The latter is typically used when
structures are poorly coated and protecting them to the primary criterion is not
economically justifiable. The second is also sometimes used for ferrous structures
embedded in concrete. Additionally, Reclamation generally limits polarized
potentials to a value no more negative than -1.100V(CSE) to prevent damage to
coatings.
This is fairly intuitive. The more exposed metal in an environment, the more
corrosion (oxidation) will be taking place. The more readily oxidizers can reach
the surface of a metal and reaction products can be removed, the more rapidly
exposed metal corrodes. Therefore, current requirements for cathodic protection
are normally stated in units of current per area (e.g., mA/ft2), and they can vary
significantly with conditions. Table 2 is a partial list of typical current
requirement values for exposed steel.19
26
Corrosion and Cathodic Protection
For most soils, a current density between 1 and 3 mA/ft2 of bare steel is usually
effective. Water tends to require more current, in part due to the depolarizing
action of eddies and flow. Obviously, if a structure is already in the soil,
performing a current requirement test will provide a more accurate estimate of the
current needed at that time. One can then augment this amount to compensate for
additional coating deterioration in the future. It is a relatively simple matter to
reduce the current on a cathodic protection system that has some excess capacity;
it is often not possible to increase the current on an undersized system.
Pipe is usually considered a smooth cylinder. Determining its surface area in that
instance is then a simple exercise in geometry. However, in some instances a
surface may be textured, uneven, or otherwise rough. Centrifugally cast ductile
iron pipe is a good example; it has a bumpy textured surface, unlike smooth sand
cast ductile iron fittings. A 1 foot by 1 foot textured surface may effectively
expose more than a square foot of metal. A rough or textured surface may also be
more difficult to coat as compared to a smooth surface. When faced with such
surfaces, a cathodic protection designer may need to make more conservative
assumptions than those suggested in this document. Examples in this document
assume a smooth surface condition unless otherwise noted.
27
Corrosion and Cathodic Protection
coatings normally have very high resistivities, the electrical current path through
the coating can usually be ignored, unless there is extensive coated surface area.
A newly installed structure with an excellent coating needs very little current for
cathodic protection. However, coatings deteriorate over time due to soil stresses
and other such factors. In order to supply sufficient current over the long term,
Reclamation cathodic protection designs anticipate this deterioration. A design
that assumes 2 percent exposed metal is typical; however, in some instances as
little as a 1 percent exposure and as much as 5 percent exposure have been
assumed. The exact number depends upon how conservative the designer wants
to be. The amount of effectively coated surface is termed the coating efficiency
2 percent exposed metal is equivalent to a 98 percent efficiency.
To provide an example, assume a designer wanted to protect 100 feet (l) of newly
coated 2-foot diameter (d) standard wall pipe being buried in a wet, moderately
corrosive soil. Based on past experience, the designer feels that the cathodic
protection system should protect for a 98 percent coating efficiency. Based on
Table 2, the designer should need about 2.5 mA/ft2 of exposed metal. Therefore,
the cathodic protection system should provide as a minimum:
or
2.5 2.5
() (0.02) = ( 2 100) (0.02)
2 2
= 31.4
E/R = I
or
R = E/I
or
E = IR
28
Corrosion and Cathodic Protection
Galvanic anode literature from suppliers normally provides the open circuit
potential of their anode materials. The amount of driving voltage in a working
galvanic circuit is then the difference in potentials between the anode and the
minimum polarized potential of the protected structure (e.g., -0.850V(CSE)).
Designers sometimes employ the anode open circuit potential when taking this
difference. A more conservative approach is to account for polarization of the
anode by reducing that potential by 0.05V to 0.10V. For iron or steel, the driving
voltage differences with various types of anodes in soil or water are approximate
as given in Table 3.
Thus, for the pipe example above, the designer would need to achieve a circuit
resistance of no more than:
29
Corrosion and Cathodic Protection
Thus, designing a cathodic protection system with minimum circuit resistance can
determine whether a galvanic anode system can be used; and circuit resistance is
key to designing an impressed current system that will perform economically.
30
Corrosion and Cathodic Protection
31
Corrosion and Cathodic Protection
Note that any outer plastic or other dielectric packaging around the inner
water permeable packaging must be removed before burying an anode!]
For anodes under these circumstances, site personnel will still need to obtain the
soil resistivity () in ohm-cm at the location of the anode bed. They may then
conservatively estimate the anode bed grounding resistance from Table 4 below.
Hence, a single magnesium anode in 2,000 ohm-cm soil would have a grounding
resistance of:
While a single zinc anode in the same soil would have a grounding resistance of:
[For any other installation, the site must hire a NACE-certified Cathodic
Protection Specialist, or a Corrosion Specialist with a strong background in
cathodic protection, or a professional engineer qualified in cathodic
protection to provide the design and assist with installation.]
1 0.00467 0.00479
2 0.00242 0.00248
3 0.00170 0.00174
4 0.00132 0.00135
5 0.00109 0.00111
6 0.00093 0.00095
Table 4. Galvanic Anode Grounding Resistances Used for FIST 4-5. Note: is soil
resistivity around the pre-packaged anode(s).
32
Corrosion and Cathodic Protection
The designer obviously needs to make electrical contact with the pipe through test
stations or the like in order to make this determination. However, if a design is
needed for a new section of coated pipe being installed, this technique is not
usually practical. Furthermore, the pipe grounding resistance will decrease over
time due to coating deterioration.
Studies, as might be expected, have shown that areas of pipe with a superior
coating application have greater electrical grounding resistance. The exact
resistance, however, varies with the soil resistivity, since more current will leak
into a low-resistivity soil. By taking the resistance of a coated pipe, multiplying
that number by the area, and normalizing the result to 1000 -cm soil, corrosion
professionals have developed characteristic numbers for coated pipe of varying
coating quality. These quantities are termed the average specific coating
resistance (rc). The inverse is called the average specific coating conductance
(g). Given a coating efficiency, one can review past findings and get a general
idea as to what the average specific coating conductance is for a pipe in question.
With this quantity, knowledge of the soil resistivity around the pipe in question,
and knowing the surface area of the pipe (As), one can estimate the grounding
resistance of that structure. The pipe grounding resistance may be calculated by
this method as:
=
1000
Hence, if the 100 feet of 2-foot diameter pipe noted above is in 2,000 ohm-cm soil
and a cathodic protection system is to be designed to protect it even when there is
2 percent coating damage (98 percent coating efficiency), then the pipe grounding
resistance for design purposed could be estimated as:
33
Corrosion and Cathodic Protection
99 1 1076
98 2 538
97 3 359
96 4 269
95 5 229
90 10 127
80 20 63.3
34
Corrosion and Cathodic Protection
If our example welded pipe described above is connected to an anode via 50 feet
of #12 cable and 20 feet of #6 cable, then the circuit resistance of the wiring is:
1.62
#12 = 50. = 0.081
1000
0.4030
#6 = 20. = 0.008
1000
= 0.089
= /
Thus if the 100-foot welded pipe used in this example has a wall thickness of
0.375 in., the resistance between the ends of the pipe is:
(1.344 105 ) 100 30.5
= = 0.000453
2
[(24 . ) (23.625) ] 4 6.45 2
2 2
[Buried or immersed cable or wiring must have insulation that will resist
moisture and deterioration.] Reclamation employs cables with high molecular
weight polyethylene (HMWPE) insulation in these instances. HMWPE resists
water intrusion and soil abrasion. For impressed current applications, anode
cable insulation often combines an HMWPE outer insulation with an inner
fluropolymer insulation layer (Halar or Kynar) to resist damage by chlorine
generation at the anode.
35
Corrosion and Cathodic Protection
In soil, galvanic anodes employ a chemical backfill and impressed current anodes
use a carbonaceous backfill to reduce the contact resistance between the anode
and the surrounding soil. A sacrificial anode chemical backfill typically consists
of bentonite clay, gypsum, and sometimes sodium sulfate. Galvanic anodes for
soil use are usually ordered prepackaged with the chemical backfill in a cloth bag
around the anode, and impressed current anodes for similar use are more often
supplied bare. [Note that any outer impermeable bag (e.g., plastic) must be
removed before bedding a prepackaged anode.] If anodes that are not pre-
packaged are used in soil, chemical backfill for galvanic anodes or coke breeze
for impressed current anodes must be tamped around the anodes as shown
typically in Figure 4 (disregard the dimensions). Earth backfill should be placed
over the chemical backfill or coke breeze and well tamped in 6-inch to 1-foot lifts
to ensure good contact. [An installed galvanic anode must not be wetted until
there is at least a foot of well-tamped soil over the chemical backfill. If the
anode does not already have compacted soil around it, the backfill will
expand and may later shrink back from the surrounding soil.]
Reclamation typically buries anode leads a minimum of 2.5 feet below ground
surface, surrounded on all sides by at least 6 inches of sand, and with a warning
tape 1 foot above the leads. For added reliability, these leads should be
continuous (no splices) until they reach a junction box, test station, or other
similar protected point above ground. [All leads must be installed with slack so
as not to apply stress to the connection at the anode or at the structure.]
[Once they come above ground, leads must be protected against damage by a
conduit, test station pipe, or the like.] Conduits also serve to protect leads in
immersed situations. For immersed situations, PVC conduit will normally resist
corrosion better than metal conduit.
Relative to a protected structure, there are two basic placement styles for anodes:
36
Corrosion and Cathodic Protection
37
Corrosion and Cathodic Protection
additively doubling the protection at that limit and equalizing the protection
across the structure.
Space these anodes 4 feet, 8 inches from the surface of the structure to
be protected.
Space these anodes 16 feet from one another.
Place the first and last anodes at the limits of the protected structure.
Perform previously described calculations to confirm that the anode
array will provide the needed amount of current.]
A large, buried pipe, tank, or similar structure may require strings of distributed
anodes on each side and at multiple locations around the structure to achieve an
even current distribution and adequate cathodic protection everywhere. With
anodes spaced 4 feet, 8 inches from a structure, a site may expect any part of a
structure 8 feet away from an anode to have about half the protection seen directly
under than anode.
38
Corrosion and Cathodic Protection
39
Corrosion and Cathodic Protection
[Junction boxes and bond boxes must be 16-gauge galvanized steel and meet
NEMA 3R requirements as a minimum.]
7.4.7 Attenuation
As discussed previously, a cable from a cathodic protection system supplies
electrons to a protected structure. These electrons support reduction reactions at
exposed metal sites. If a long pipeline has a poor coating, has high linear
resistance, and is in low-resistivity soil, the electrons will have difficulty traveling
down the pipeline; they will instead leak out to the soil soon after entering the
protected structure and be rapidly consumed in producing reduction reactions.
As a result, cathodic protection levels near the lead connected to the structure will
be acceptable, but will rapidly drop off the further one gets from that point. This
effect is called attenuation.
Increase protection levels near the connection to the structure (these levels
may soon exceed prudent limits).
Improve protection further down the pipeline only by a small amount.
Such structures require additional rectifiers and/or anode beds if recoating and
reducing linear resistance are not options. These rectifiers/anode beds need to be
spaced so that each cathodic protection system adds to the needed amount of
supplemental protection at the limit of the adjacent system.
40
Corrosion and Cathodic Protection
Large anode bed designs must also consider attenuation. One can reach a point at
which an additional anode provides no increase in protective current.
MgMg+2 + 2e-
Knowing this stoichiometry and the amount of time (t) a current (I) flowed, one
can apply Faradays Law to determine the mass (W) of anode consumed as a
result of this current. Faradays Law may be stated as:
=
where M is the atomic mass of the anode material, n is the number of electrons in
the reaction, and F is Faradays constant (96,500 coulombs per equivalent;
equivalents being M/n). Note that each amp of current is equivalent to 1 coulomb
per second.
Knowing this relationship, the theoretical consumption rate (Cr) due to galvanic
action for magnesium will be 8.76 lb/A-yr., while that of zinc will be 23.5 lb/A-yr.
However, in addition to galvanic action, some anode material also gets used up
due to direct reaction with the environment. This latter corrosion is termed self-
corrosion or autogenous corrosion.
The percent of galvanic anode consumed by galvanic action alone is termed anode
efficiency (E). Magnesium anodes are about 50 percent efficient if the anode
current density (current flow divided by the surface area of the anode metal) is
20 mA/ft2 or greater. This means that, under these current density conditions,
about twice as much magnesium anode material is needed for a given service life
than Faradays Law would predict. Zinc anodes are much more efficient,
providing 90 percent efficiency when their current density is 5 mA/ft2 or greater.
Galvanic anode efficiency is zero when no current is passing and all corrosion is
autogenous. Assuming linear efficiency relationships between zero current
41
Corrosion and Cathodic Protection
density and the limits stated previously provide conservative estimates of anode
efficiency when galvanic current is low.
Utilization (U) is another factor that determines the service life of an anode.
Utilization is the percent or fraction of the original mass that will be considered
the end of a service life. A utilization factor allows some margin of error to help
ensure that an anode will be refreshed before it is completely used up.
Reclamation usually applies an 85 percent utilization factor; however, 90 percent
has sometimes been used as well.
Combining this information, the service life (L) of a sacrificial anode weighing
W pounds and passing A amps, may be calculated as:
(32)(0.5)(0.85)
= = 25.0
8.76
(0.062)
42
Corrosion and Cathodic Protection
Table 6. Maximum allowed current per galvanic anode. Note: Assumes utilization factor
of 85 percent, magnesium efficiency of 50 percent, and zinc efficiency of 90 percent.
43
Corrosion and Cathodic Protection
[Only galvanic anode material specifically alloyed for that use must be used
for cathodic protection.] ASTM B843 (Standard Specification for Magnesium
Alloy Anodes for Cathodic Protection) lists three groups of magnesium alloys
the AZ63, the AZ31, and M1.21 The M1 alloy is a high-potential material that is
about 200 mV higher in potential than other magnesium anode alloys. The
standard potential magnesium anode has an open circuit potential of about
-1.55 V (CSE). Either alloy is applicable to soil or fresh water. ASTM B418
(Standard Specification for Cast and Wrought Galvanic Zinc Anodes) lists two
types of zinc anodes Type I and Type II.22 Type I, along with a Mil Spec.
A-18001K anode, is intended for use in seawater and brackish water at
temperatures less than 50oC. Type II and high-purity zinc anode is intended for
soil and fresh water. Zinc anodes have an open circuit potential of about
-1.100 V (CSE). Aluminum anodes are available in a Type I for open seawater and
Type II for seawater/mud applications. Because of the high saline environments
required when using aluminum and their rarity within Reclamation, nothing
further will be mentioned here regarding aluminum anodes.
Sacrificial anodes for immersion service expose bare metal to the electrolyte
while anodes for buried service are pre-packaged in, or otherwise surrounded by,
a chemical backfill (see 7.4.5 above, Installation and Placement of Anodes).
Low-resistivity environments.
Small surface areas of metal to be protected.
44
Corrosion and Cathodic Protection
Figure 8. Typical galvanic anodes; note the bagged anode for buried installation.
ICCP systems usually introduce current into the electrolyte through anodes made
of corrosion-resistant material such as graphite, high-silicon cast iron (HSCI),
platinized titanium (Ti) or niobium (Nb), or mixed metal oxide on Ti or Nb.
45
Corrosion and Cathodic Protection
The typical ICCP rectifier operates on 110 V AC or greater input power. This can
present personnel safety concerns not relevant with low-power galvanic anode
systems. Allowing too great a power input from an ICCP system can damage the
coating on a structure, a phenomenon called cathodic disbondment. Too much
current can also produce enough hydrogen at a structure to cause hydrogen
embrittlement of some metals. This is usually an issue with high-strength steels
and certain alloys. Furthermore, while not commonly observed, misconnecting
the positive and negative sides of an ICCP system can make the structure the
anode and result in highly accelerated corrosion of that structure. This is not even
possible with galvanic anode systems. Impressed current systems have more parts
that can break down and generally require more maintenance and upkeep than
galvanic systems. They can be accidentally turned off and may be susceptible to
lightning strikes and power outages.
The most common DC current source for impressed current cathodic protection is
a rectifier. However, if electrical power is not available, other DC power sources
are available. These include:
46
Corrosion and Cathodic Protection
9.2 Rectifiers
The typical rectifier has two basic components. The first component is a step-
down transformer to control the driving voltage. The second component is a
rectification section, most commonly a diode bridge, to convert the AC input
current to DC output current. In addition, there are gauges, connectors, fuses, taps
to adjust the secondary output on the transformer, and other accessories to make
the system safe and workable. Figure 11 shows a typical rectifier cabinet as it
might appear in the field. Figure 12 shows a typical board inside the cabinet.
47
Corrosion and Cathodic Protection
The most often used rectifier within Reclamation is a simple air-cooled, single-
phase AC input rectifier with full-wave DC output. However, rectifiers are
available in a variety of configurations, including:
Most constant voltage rectifiers have exposed taps on the secondary side of the
rectifier transformer. Taps allow the output voltage to be increased or decreased
in increments. Some rectifiers have knobs that allow varying the voltage
continuously anywhere within the operating range. These accessories allow
48
Corrosion and Cathodic Protection
setting a voltage that will provide the necessary current for adequate cathodic
protection without exceeding prescribed electrochemical potential limits. In
setting this voltage, one normally starts at the lowest setting, increasing it in small
steps. The impact on structure potential is measured in between increases until
the desired effect is achieved.
[The design and installation of an impressed current system can call for
specialized knowledge and considerable cathodic protection experience. Site
personnel must employ a NACE-certified Cathodic Protection Specialist, or a
Corrosion Specialist with a strong background in cathodic protection, or a
P.E. qualified in cathodic protection.]
10.1 General
Cathodic protection systems require periodic attention to ensure that they function
properly. Some checks only require visual observations. Others require a
portable high-impedance voltmeter, leads in good condition, and a calibrated
reference cell (usually a copper/copper sulfate reference cell). Timely
inspections, good record keeping, and acting on the recommendations of the
qualified cathodic protection professional who has reviewed the records can head
off problems. Operation and maintenance of cathodic protection systems, coating
systems requirements, as well as record keeping are covered further in NACE
International SP 0169.13
49
Corrosion and Cathodic Protection
Figure 13. Wasps occupying a junction box. Note the failure to properly connect the
conduit at the bottom, providing easy access for the wasps.
50
Corrosion and Cathodic Protection
10.2 Personnel
Individuals performing maintenance and testing of cathodic protection systems
must, as a minimum, have a general understanding of such systems. Maintenance
and testing of impressed current systems in particular require a higher level of
appreciation for electrical and electronic components and associated hazards.
[Only trained and qualified personnel are to perform the required
maintenance and testing on cathodic protection systems.]
51
Corrosion and Cathodic Protection
CSEs or copper sulfate reference cells are fairly stable and quite rugged for field
use. However, [precautions must be taken to ensure they remain in
calibration:]
Sunlight or other ultraviolet (UV) shining through a clear tube has been
shown to affect the readings; hence it is best to put opaque tape over areas
of clear tube when taking readings.
If the solution becomes cloudy, clean the reference cell, replace the
solution, and recalibrate.
Disassemble the cells and drain any remaining copper sulfate solution
and crystals, and properly dispose.
Using inert grit paper (do not use steel wool or grit paper
contaminated by foreign metals), abrade the surface of the copper
rods from the centers of the cells to obtain a bright surface. When
completed, rinse the rods with distilled or deionized water.
52
Corrosion and Cathodic Protection
Of the two reference cells within the 5 mV range, set one aside as a
reference standard and use the other in the field. Keep the reference
standard at least at the end of each work period (e.g., a shift) to
ensure that the field reference is not drifting excessively due to
contamination, temperature extremes, etc. Keep the porous cell tips
from plugging with salt deposits by placing a few drops of water in the
protective end caps, or by keeping the tips in a container of water.]
In addition, soil conditions may change somewhat over time, anodes may be
consumed, and structure coatings will deteriorate. These conditions may require
adjustments. [The following procedures must there be followed for GACP
systems.]
53
Corrosion and Cathodic Protection
3. Connect the structure (e.g., accessed through the test station test lead)
to the positive terminal of the typical digital voltmeter for correct sign
convention. Connect the negative voltmeter terminal to the CSE.
4. Press the ceramic plug of the CSE into the soil or immerse in the
water above or near the structure. It is desirable and sometimes
essential to wet the soil before applying the CSE to reduce contact
resistance.
5. Since currents in the electrolyte can cause voltage drop errors called
IR drop, galvanic anode connections to the structure need to be
momentarily interrupted while taking readings. However,
interrupting cathodic protection current for more than a few seconds
at a time could result in some depolarization of the structure and
readings that are somewhat in error. A current interrupter may be
useful when taking these readings, but potentials on sacrificial anode
systems are often taken while manually interrupting the current. Any
other currents flowing through the soil in the area of a reading must
also be interrupted while taking potential readings. This could
54
Corrosion and Cathodic Protection
.
= .
.
The tester records the actual millivolt reading, the resistance value of the
resistor, and the current obtained after the application of Ohms Law.
55
Corrosion and Cathodic Protection
What ICCP systems have that sacrificial anode systems do not have is a rectifier
or similar DC power source (see 9.1 General Description (of impressed current
systems)). Although rectifiers are relatively simple and generally reliable
equipment, they are subject to power interruptions and failure of electrical
components that are not an issue with sacrificial anode systems. Rectifiers can be
put out of service by someone simply tripping the circuit breaker supplying AC
power, or by lightning strike. In spike of lightning arrestors normally installed in
rectifiers, lightning strikes can still damage rectifier components or completely
56
Corrosion and Cathodic Protection
destroy the unit. [The following procedures must therefore be followed for
ICCP systems.]
10.5.1 Safety
Most Reclamation rectifiers are single-phase 120 V AC input voltage; some could
be 3-phase and higher voltage. Personnel dealing with ICCP systems must
therefore be more safety conscious than when working with GACP systems.
Rectifiers, junction boxes, and the like are normally kept padlocked to prevent
unauthorized tampering. [They must be relocked following testing or
maintenance work. In some instances, it may be desirable to fence in a
rectifier and lock the area to prevent unauthorized access altogether.]
[Wasps and other insects may next in CP enclosures (see 10.1.2 above),
especially those that havent been properly sealed. CP workers must be
ready for them.]
Verifying that the rectifier tap settings are in the positions recorded
on the last inspection sheet.
57
Corrosion and Cathodic Protection
Looking for scorch marks and indications of excess heat that could
indicate present or imminent component failure.
Cleaning out any debris found in the rectifier cabinet, test stations,
junction boxes, and bond boxes.
*Note: DC voltage and amperage gauges on the panel are usually not very
accurate and sometimes fail. A gauge that indicates current flow may simply
have failed in that position and may not be indicating actual current flow. These
gauges tend to last longer if there is a switch to take them out of the circuit when
not needed and if this switch is left in the off position following readings. This
switch can sometimes be used to determine if the gauge is frozen in place. A
portable voltmeter is normally more reliable. A voltage reading across the DC
output terminals with a portable voltmeter is informative but will not indicate if
current is flowing. A rectifier can hold a voltage across its terminals even when
one or both leads are broken and no DC current is flowing.
58
Corrosion and Cathodic Protection
4. Connect the structure (e.g., accessed through the test station test lead)
to the positive terminal of the typical digital voltmeter for correct sign
convention. Connect the negative voltmeter terminal to the CSE.
5. Press the ceramic plug of the CSE into the soil or immerse in the
water above or near the structure. It is desirable and sometimes
essential to wet the soil before applying the CSE to reduce contact
resistance.
59
Corrosion and Cathodic Protection
.
= .
.
The tester records the actual millivolt reading, the resistance value of the
resistor, and the current obtained after the application of Ohms Law.
1. Record the coarse and fine tap settings. If the rectifier has an
infinitely variable knob, record the knob setting.
2. Record the voltage and the amperage from the gauges on the rectifier
panel. If these gauges are supplied with an on/off switch, turn them
on to take readings and off again when done; this will help ensure
their reliability when needed. (See note in 10.5.2 regarding panel
gauges.)
4. Measure and record the voltage across the rectifier shunt connections
with a portable voltmeter and convert to amperage. Rectifier shunts
are normally rated in A/mV; therefore, multiply the shunt rating by
the millivolts read to obtain the total rectifier DC amperage output.
For instance, with a 10A/50 mV rectifier shunt a millivolt reading of
10 mV across the shunt would mean that the rectifier is passing 2A.
The total rectifier amperage should be in close agreement with the
sum of anode currents.
60
Corrosion and Cathodic Protection
The reviewer must be provided the record of previous inspection results with
which to compare to the latest findings. The reviewer may then recommend
adjustments if needed.
61
Corrosion and Cathodic Protection
62
Appendices
General Considerations
The designer of a cathodic protection system needs to consider a number of
factors, including:
The following examples are for small, simple, buried structures that might be
protected using either the 32-pound magnesium anode or the 15-pound zinc anode
previously described in this document. In keeping with previous editions of this
document, the examples are intended for site personnel who may wish to attempt
in-house cathodic protection for such structures. Note, however, that there is no
short-cut for obtaining reliable soil resistivity readings and that these readings are
crucial to a correct design. The simplified calculations use conservative
assumptions associated with the data tabulated herein. Given the low voltage
nature of galvanic anode systems, interference corrosion on other structures while
possible is unlikely. Site personnel may nonetheless find it useful to have a
63
Appendices
[For cathodic protection of larger structures requiring the use of more than
six anodes, an impressed current rectifier system, or for immersed
applications, site personnel must obtain the specialized assistance of a
corrosion professional.]
Problem 1:
A new 4-inch (D) schedule 40 (0.237 inch wall thickness) coated welded steel
pipe 150 feet long will be buried 6 feet below ground in a sandy clay soil. The
new pipe will be electrically isolated at both ends. Determine if site personnel
can use the galvanic anodes described in this document to protect this pipe. If so,
design the system. The anodes need to provide the usual Reclamation 20-year
life.
Required data:
Soil resistivity in ohm-centimeters for possible anode locations and around
the structure.
Pipe protective coating efficiency or percent bare design basis.
Current density needed for protection.
Solution:
1. The responsible site engineer first determines the amount of current that
will be needed given the data and base assumptions. The cathodic
protection current (I) required is the product of estimated area of bare steel
(Abare) in square feet times the required current per square foot. If:
= ()(0.02)
64
Appendices
Then
2
=
.
2 4
= (150)(0.02) = 6.28 0.00628
. 12/
2. The engineer next determines the individual resistances that make up the
cathodic protection circuit. Indications are that there is a likely anode bed
site on the northwest side of the pipe that has low resistivity, which should
minimize the anode grounding resistance. Knowing the area, the engineer
also knows that this location is also about 10 feet from a building and that
the test station and/or junction box could be placed near the building for
protection. The engineer therefore decides to place an anode bed in that
location and proceeds to estimate the cathodic protection system circuit
resistance.
2019 cm
1000 cm (538 sq. ft)
= = 6.92
4in
12in 150ft
ft
B. Anode grounding resistance:
The engineer is not certain which anode to use and will therefore
consider either magnesium or zinc. The grounding resistances based
on Table 4 above are:
Or
65
Appendices
C. Cable resistances:
Since the tentative location of the test station and/or junction box is
about 40 feet from the pipe and the engineer needs to bring the
structure cable up about 5 feet, in addition to some slack, the engineer
decides to allow for 50 feet of #6 AWG cable from the pipe. Since
plans are to have the anode bed near the test station, 20 feet of #12
AWG cable will be assumed from either anode. Total cable resistance
is calculated as:
0.4030 1.6200
= 50ft + 20ft = 0.0526
1000ft 1000ft
D. Pipe metal resistance:
The engineer plans to connect the cathodic protection to one end of the
pipe, leaving a maximum of 150 feet for the cathodic protection
current to travel through steel. A quick estimate shows that this
resistance will be negligible:
(1.344105 ) 15030.5
= = 0.003
((4.5)2 (4.026)2 ) 6.45. .
4 . .
= + + +
= 6.92 + 7.34 + 0.0526 + 0.003
= 14.3
The alternative zinc anode would provide a total circuit resistance of:
= + + +
= 6.92 + 7.53 + 0.0526 + 0.003
= 14.5
66
Appendices
0.650
= 0.0455
14.3
Hence, the engineer has plenty of capacity with a single 32-pound anode,
magnesium anode. A variable resistor should be installed in the circuit to
control the structure potential. If instead a single 15-pound zinc anode
were used, the amount of current the system could supple would be:
0.200
= 0.0138
14.5
This system would still have the capacity to generate about twice the
current needed. Note too that either one of these anodes will provide in
excess of 20 years of service life since the maximum current output for
that longevity has not been exceeded (see Table 6).
Problem 2:
Determine the cathodic protection requirements, including the amount of current
needed and the type and number of anodes, to cathodically protect 80 feet (L) of
new 4-inch (D) schedule 40 (0.237 inch wall thickness) coated welded steel pipe
buried in the ground. There is a retaining wall 10 feet to one side of the pipe and
a road 15 feet on the other; the anodes must be kept between these features. Road
salts used to deal with icing in the winter have made the soil in the area severely
corrosive. The pipe is buried 6 feet below ground and is electrically isolated at
both ends.
Required data:
Soil resistivity in ohm-centimeters for possible anode locations and around
the structure.
Pipe protective coating efficiency or percent bare design basis.
Current density needed for protection.
67
Appendices
Solution:
1. The site engineer knows a remote anode system cannot be employed since
anodes cannot be placed at least 28 feet from the pipe; a distributed anode
system will therefore be considered. The engineer first determines the
amount of current needed given the data on hand and the base
assumptions. The cathodic protection current (I) required is the product of
estimated area of bare steel (Abare) in square feet times the required current
per square foot. If:
= ()(0.02)
Then
6
=
.
6 4
= (80)(0.02) = 10.1 0.0101
. 12/
2. In order to protect 80 feet of pipe with anodes every 16 feet, the engineer
must employ 6 anodes (one at either end, each covering the first 8 feet of
pipe from the ends and 4 more anodes between these). Given that the pipe
is only 4 inches in diameter, anodes should not be needed on both sides of
the pipe; they will, however, be staggered. The engineer next determines
the individual resistances that make up the cathodic protection circuit.
68
Appendices
538 2 760
= = 4.88
1000
4
12 80
C. Cable resistances:
The tentative location of the test station/junction box will be near the
center of the pipe, where the 6 anode leads will connect to about
10 feet of #6 AWG cable from the pipe. The engineer assumes an
average of 25 feet of #12 AWG cable from each anode (some will
actually be shorter and some will be longer). Since these short runs of
cable are in parallel, the engineer estimates the combined resistance of
the cables to be 1/6 the resistance of one anode cable, so that the
combined cable resistance is approximately:
0.4030 1 1.6200
= 10ft + 25ft = 0.0108
1000ft 6 1000ft
D. Pipe metal resistance:
(1.344105 ) 4030.5
= 1/2{ }
((4.5)2 (4.026)2 ) 6.45. .
. .
4
= 0.0004
69
Appendices
The alternative zinc anodes would provide a total circuit resistance of:
E/Rtotal = I
Hence, since only 0.0101 A is needed to protect the pipe, the engineer has
plenty of capacity and adequate service life with 32-pound standard
potential magnesium anodes; variable resistors will be installed in the
circuit to control the structure potential.
If instead six 15-pound zinc anodes were used, the amount of current the
system could supply and the individual current per anode would be
(see Table 3):
Since only 0.0101 A is needed to protect the pipe, the engineer again
would have plenty of current and the design would meet a minimum 20-
year service life. The engineers recommendation, therefore, calls for a
close distributed zinc anode cathodic protection system with 6 anodes
spaced 4 feet, 8 inches from the pipe and spaced 16 feet apart. Since there
are only 6 anodes, all the cables will be run to a junction box where each
anode will pass through a 0.100 shunt resistor and a variable resistor for
balancing anode currents. A separate test lead will be provided on the
junction box board. The junction box will be placed near the retaining
wall where it should be out of harms way.
70
Appendices
71
Appendices
72
Appendices
73
Appendices
74
Appendices
75
Appendices
76
Appendices
Appendix C References
1. NACE/ASTM G193-10b Standard Terminology and Acronyms Relating to
Corrosion, NACE International/ASTM International 2010.
77
Appendices
19. L.L. Shrier, R.A. Jarman, G.T. Burstein. Corrosion Control, Volume 2.
Newness-John Wiley and Sons, Inc., New York, 1963.
21. ASTM B843-07, Standard Specification for Magnesium Alloy Anodes for
Cathodic Protection.
22. ASTM B418-08, Standard Specification for Cast and Wrought Galvanic Zinc
Anodes.
22. FIST 1-1, Hazardous Energy Control Program. U.S. Bureau of Reclamation,
January 2012.
78
Appendices
Appendix D Definitions
Anion
Negatively charged ions in the electrolyte. Anions are attracted to and move
toward the anode under influence of a potential gradient. Some may react at the
anode.
Anode
The electrode of an electrochemical cell at which oxidation occurs. The metal
that corrodes in a galvanic cell or the positive terminal of an electrolytic cell.
Cathode
The electrode of an electrochemical cell at which reduction is the principle
reaction. The metal which is protected by an anode of a galvanic cell; the
negative terminal of an electrolytic cell.
Cathodic protection
A technique to reduce the corrosion rate of a metal surface by making that surface
the cathode of an electrochemical cell.
Cation
Positivity charged ion in an electrolyte. Cations are attracted to and move toward
the cathode under influence of a potential gradient. Some may react at the
cathode.
Coating
A liquid, liquefiable, or mastic composition that, after application to a surface, is
converted into a solid protective, decorative, or functional adherent film.
Concentration cell
A corrosion cell whose voltage gradient is the result of inhomogeneities or
differential chemical conditions at sites on the structure within the electrolyte.
Corrosion
The deterioration of a material, usually a metal, that results from a chemical or
electrochemical reaction with its environment.
Corrosion cell
Consists of an anode and a cathode which are electrically connected for electron
flow and immersed for ion flow. Dry and wet cell batteries are common
examples (when shorted across the terminals).
79
Appendices
Current interrupter
A device installed in the output circuit of a rectifier which provides a means of
opening and closing the circuit at programmable intervals.
Electrical resistivity
The resistance offered to the passage of current between the opposite faces of a
unit cube of the material. Units are resistance times distance, such as ohm-
centimeters, ohm-meters, ohm-feet, or the like.
Electrolyte
The medium (such as an aqueous solution, moist soil, or solution of chemicals)
through which the current (positive charge) of a corrosion cell flows (i.e., from
the anode to the cathode by migration of anions and cations).
Electron flow
Flow of electrons in the external circuit; in the opposite direction to
conventional current flow.
External circuit
The part of a corrosion cell circuit in which electrons flow through the metal of
the anode, cathode, and metallic conductor between them (the metallic part of the
circuit).
Galvanic cell
A corrosion cell in which there is an anode made of a different material than the
cathode.
Galvanic series
A list of conductive materials, especially metals and alloys, arranged according to
their corrosion potentials in a given environment.
Galvanic-type corrosion
Corrosion similar to that produced by a galvanic cell.
Internal circuit
The part of a corrosion cell circuit in which the current flows through the
electrolyte via ions or radicals (the solution part of the circuit).
80
Appendices
Ion
An electrically charged atom (e.g., Na+, Cl-, etc.); sometimes used when speaking
of radicals as well.
Long-line corrosion
Current flowing through the earth between an anodic and a cathodic area that
returns along an underground metallic structure. (Usually used only where the
areas are separated by considerable distance and where the current flow results
from concentration cell action).
Mill scale
The oxide layer formed during hot fabrication or heat treatment of metals.
Mixed potential
A potential resulting from two or more electrochemical reactions occurring
simultaneously on one metal surface.
Noble metal
A metal with a standard electrode potential more positive than that of hydrogen.
Of two metals in a corrosion cell, the one with a potential more in the noble
direction will be the cathode.
Polarization
The change from the corrosion potential as a result of current flow across the
electrode/electrolyte interface.
Potential
In cathodic protection work, the voltage difference between a structure and a
reference electrode, all in a continuous electrolyte.
Radical
An electrically charged group of atoms (e.g., OH-, SO4-2, etc.); sometimes loosely
referred to as ions.
Reference electrode
An electrode having a stable and reproducible potential, which is used in the
measurement of other potentials.
81
Appendices
Shunt resistor
A calibrated resistor placed within a circuit to determine the current flow;
calibration is typically expressed in ohms or amperage/millivolt.
Static potential
The potential of a metal before any polarization and with no current flowing
through the electrolyte where the potential is measured; sometimes also called
native potential.
Structure
In cathodic protection work, an item that could be monitored and/or cathodically
protected (e.g., buried pipeline, submerged pump column, etc.) or an item foreign
to such an article (i.e. a foreign structure).
Test station
A location with electronic connection to a structure for cathodic protection
testing.
Tuberculation
The formation of localized corrosion products scattered over the surface in the
form of knob-like mounds called tubercles.
82
Appendices
83
Appendices
84
Appendices
85
Appendices
86