Na2xseyby 3 X (35-300) MM

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NA2XSEYBY 3 x (35-300) mm 2

12/20
NA2XSEYBY 3 x (35-300) mm 12/20
2
kV kV
Al / XLPE / CWS / PVC / STA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Wire Screen, PVC Innersheath
Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : SPLN 43-5-4 : 1995
Aluminium Conductor with
Construction Data Water Blocking Material

Application : Conductor Screen


Nom. Overall Cable For installation indoor, in ground direct burried, for XLPE Insulation
Cross Diameter Weight power station and switchgear, if there is a risk that Insulation Screen
Section
approx. approx. low mechanical damage may occur.
Area Semi Cond. Water
Blocking Tape
mm mm kg/km Special Features on Request ID Tape
- Oil Resistance Copper Wire Screen
35 / 16 64.0 4,943 - UV Resistance Copper Tape Screen
- Flame Retardant Cat. A, B, C
50 / 16 67.0 5,361 - Flame Retardant Non Category Non Cond. Water
Blocking Tape
70 / 16 71.5 6,083 - Heat Resistance
PVC Inner Sheath
- Anti Termite
95 / 16 75.5 6,759 - Anti Rodent Galvanized Steel
- Low Smoke Zero Halogen Tape Armor
120 / 16 79.0 7,411 PVC Sheath
Note :
150 / 25 84.0 9,179 Conductor Shaped
185 / 25 88.5 10,067 35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

240 / 25 94.0 11,329 Standard Packing


35 - 300 sqmm will be suplied in wooden drum on available length
300 / 25 99.0 12,612 Length Tolerance per drum 2%

Electrical Data
Conductor Current-Carrying Short
Inductance Capacity circuit current
Nom. DC AC
at 30oC * at 1 sec
Cross Resistance Resistance
Sect. at 20oC at 90oC in air in ground Conductor Screen **
Max. Max. Max. Max. Max. Max.
(mm) (/km) (/km) (mH/km) (A) (A) (kA) (kA)

35 / 16 0.868 1.113 0.424 150 135 3.29 1.60


50 / 16 0.641 0.822 0.406 178 159 4.70 1.60
70 / 16 0.443 0.568 0.381 220 194 6.58 1.60
95 / 16 0.320 0.411 0.363 265 231 8.93 1.60
120 / 16 0.253 0.325 0.350 303 262 11.28 1.60
150 / 25 0.206 0.265 0.341 340 290 14.10 2.50
185 / 25 0.164 0.211 0.328 387 327 17.39 2.50
240 / 25 0.125 0.161 0.316 448 374 22.56 2.50
300 / 25 0.100 0.130 0.307 505 417 28.20 2.50
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
** With short circuit screen condition at 90 oC operating temperature and 160 oC final short circuit temperature
26804-01 Rev. 0. 0 / 2013

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification