Published by The Institute of Electrical and Electronics Engineers and Titled
Published by The Institute of Electrical and Electronics Engineers and Titled
Published by The Institute of Electrical and Electronics Engineers and Titled
Model
Fuses
Trip
Motors Nominal HP
where Ia = arc fault current in kA; K = -0.153 for open-air arcs and -0.097 for enclosed arcs; Ibf
= 3-phase bolted fault current in kA; V = voltage in kV; G = conductor gap in mm
Working
Equipment class
distance
Low-voltage switchgear 24"
15 kV/5 kV switchgear 36"
Low-voltage MCCs and
18"
panel boards
Cables 18"
(1) E = 4.184(Cf)(En)(t/0.2)(610x/Dx)
where E = incident energy in joules/cm2; Cf is a calculation factor (1.0 for voltages above 1 kV,
and 1.5 for voltages below 1 kV); En = normalized incident energy (from equation (2) below); t
= arc duration in seconds; D = distance from arc in mm; x = distance exponent (see table
below)
where En = energy normalized for distance of 610 mm and arc duration of 0.2 seconds, in
joules/cm2; K1 = -0.792 for open-air arcs and -0.555 for enclosed arcs; K2 = 0 for
ungrounded/high-Z systems and -0.113 for grounded systems; G = arc gap in mm; Ia =
predicted 3-phase arc fault current in kA
DB = [4.184(Cf)(En)(t/0.2)(610x/EB)]1/x
where EB is the desired incident energy at the boundary (usually 1.2 cal/cm2, but occasionally
set at a value matching proposed PPE rating), with other variables defined as for the
incident energy equations above.
* M. Gibbs, "Arc Flash Boundary Calculations Using Computer Software Tools," presented at
IEEE IAS Annual Meeting, Seattle, 2004.