NFPA13 - Pt1 - Handout Cambios Nfpa 13
NFPA13 - Pt1 - Handout Cambios Nfpa 13
NFPA13 - Pt1 - Handout Cambios Nfpa 13
DISCLAIMER
This webinar and its content is not a formal interpretation
issued pursuant to NFPA regulations. Any opinion expressed is
the personal opinion of the author and presenter and does
not necessarily present the official position of the NFPA and
its Technical Committees.
NFPA 13 Changes from the 2013 Edi9on to the 2016 Edi9on, Part 1
1
2/15/16
A.1.6.3 Some dimensions used in this standard require a tight precision and other do
not. For example when performing hydraulic calculations more precision is required
than when specifying a nominal dimension. An example is pipe sizes, where we
typically refer to a nominal diameter rather than the exact diameter. The metric
equivalents also have a set of generally accepted nominal measurements and they are
not a precise conversion from the "English Unit" nominal dimension. Throughout the
standard the generally accepted nominal pipe sizes have been used. For example 1"
pipe = 25 mm, 1" pipe = 32 mm, 1" pipe = 40 mm, etc. In other cases rounding is
used and the number of significant digits taken into account. For example a 30 ft
ceiling would be 9.144 meters. This implies a level of precision that is higher than used
for the original dimension and a conversion to 9.1m or even 9m is more appropriate.
Another example is that in the standard, 1 inch (in.) has been converted to 25mm and
not 25.4mm, 2 in. to 50mm, 6 in. to 150mm etc. Finally, locally available material may
have different characteristics in countries that use metric units than are typically found
in the US. Examples are things like standard door or window sizes, rack dimensions,
etc. In these cases a soft conversion may also be used. Where soft conversions have
been used, it is acceptable for a designer or installer to use an exact or "hard"
conversion rather than the soft conversion used in the standard.
2
2/15/16
Small Openings 7
No Definition 8
3
2/15/16
Deleted 11
4
2/15/16
Change description 13
Definition 14
5
2/15/16
5.6.1.1.1
Commodity classification and the corresponding
protection requirements shall be determined based on the
makeup of individual storage units (i.e., unit load, pallet
load).
5.6.1.1.1.1 The type and amount of materials used as
part of the product and its primary packaging as well as
the storage pallet shall be considered in the classification
of the commodity.
Class IV Definition 18
18
6
2/15/16
Should be
Unexpanded
Should be
Cartoned 19
20
Group A Plastics 21
7
2/15/16
Group B Plastics 22
Group C Plastic 23
Compatibility 24
8
2/15/16
6.3.9.2 When nonmetallic pipe is used in combination systems utilizing steel piping
internally coated with corrosion inhibitors and nonmetallic piping , the steel pipe coating
shall be investigated listed for compatibility with the nonmetallic piping by a testing
laboratory pipe materials .
6.3.9.3 When nonmetallic pipe is used in combination systems utilizing steel pipe that is
not internally coated with chemical corrosion inhibitors, no additional evaluations shall be
required.
6.3.9.4* When nonmetallic pipe is used in combination systems utilizing steel pipe, cutting
oils and lubricants used for fabrication of the steel piping shall be compatible with the
nonmetallic pipe materials in accordance with 6.1.1.6 .
6.3.9.5 Fire-stopping materials intended for use on nonmetallic piping penetrations shall
be investigated for compatibility compatible with the nonmetallic pipe materials in
accordance with 6.1.1.6 .
6.3.9.6 Pipe or tube listed for light hazard occupancies shall be permitted to be installed in
ordinary hazard rooms of otherwise light hazard occupancies where the room does not
exceed 400 ft2 (37 m2).
6.3.9.6.1 Pipe or tube installed in accordance with 6.3.7.8.2 shall be permitted to be
installed exposed, in accordance with the listing.
9
2/15/16
10
2/15/16
Light Hazard 32
EC 33
11
2/15/16
12
2/15/16
Hip Roof 39
13
2/15/16
Hip Roof 40
14
2/15/16
2013 EdiCon
15
2/15/16
8.7.4.1.4* Soffits and Cabinets. Where soffits are used for the
installation of sidewall sprinklers, the sprinklers and soffits shall be
installed in accordance with 8.7.4.1.4.1 , 8.7.4.1.4.2 , or 8.7.4.1.4.3 .
8.7.4.1.4.1 Where soffits exceed more than 8 in. (203 mm) in width or
projection from the wall, pendent sprinklers shall be installed under
the soffit.
8.7.4.1.4.2 Sidewall sprinklers shall be permitted to be installed in the
face of a soffit located directly over cabinets, without requiring
additional sprinklers below the soffit or cabinets, where the soffit does
not project horizontally more than 12 in. (305 mm) from the wall.
8.7.4.1.4.3 Where sidewall sprinklers are more than 3 ft (0.91 m)
above the top of cabinets, the sprinkler shall be permitted to be
installed on the wall above the cabinets where the cabinets are no
greater than 12 in. (305 mm) from the wall.
3 J (0.91
m) or
greater
8 in. (203
mm) or less
&
16
2/15/16
49
50
Polling Question
How many people are listening/
viewing todays presentation from
your computer site?
51
Questions?
QuesCons will be answered in the order they are received.
If we do not get to your quesCon, we apologize in advance. Your
quesCon will be answered by email aJer the program.
17
2/15/16
EC SW 53
18
2/15/16
EC Sidewalls in Residential 56
19
2/15/16
EC SW 58
EC SW 59
ECSW Obstructions 60
20
2/15/16
Residential 62
21
2/15/16
64
ESFR 65
22
2/15/16
Combustible Concealed 67
23
2/15/16
24
2/15/16
Cloud Ceilings 73
Sprinkler Omission 74
Sprinkler-Protected Glazing 75
25
2/15/16
Sprinkler-Protected Glazing 76
Heat Tracing 78
26
2/15/16
Air Venting 79
FDC 80
8.17.2.3* Size. The size of the pipe for the fire department connection shall be
in accordance with one of the following:
(1) Pipe size shall be a minimum of 4 in. (100 mm) for fire engine
connections.
(2) Pipe size shall be a minimum of 6 in. (150 mm) for fire boat
connections.
(3) For hydraulically calculated systems, the fire department
connection pipe size shall be permitted to be less than 4 in. (100
mm) and no , but not less than the size of system riser, where
serving one system riser largest riser being served by that
connection .
8.17.2.6* Drainage. The piping between the check valve and the outside hose
coupling shall be equipped with an approved automatic drip drain valve in areas
subject to freezing.
8.17.2.6.1 The automatic drain valve shall be installed in a location that permits
inspection and testing as required by NFPA 25 .
Backflow Prevention 81
27
2/15/16
Chapter 10 84
28
2/15/16
Chapter 11 85
Inside Hose 86
29
2/15/16
Relocated 11.2.3.1.4(4) 88
(7) Concealed spaces over isolated small compartments rooms not exceeding 55
ft 2 (5.1 m 2 ) in area.
(8) Vertical pipe chases under 10 ft 2 (0.93 m 2 ), provided that in multifloor
buildings the chases are firestopped at each floor using materials equivalent to
the floor construction, and where such pipe chases shall contain no sources of
ignition, piping shall be noncombustible, and pipe penetrations at each floor shall
be properly sealed.
(9) Exterior columns under 10 ft 2 (0.93 m 2 ) in area formed by studs or wood
joists, supporting exterior canopies that are fully protected with a sprinkler system.
(10) * Light or ordinary hazard occupancies where noncombustible or limited-
combustible ceilings are attached to the bottom of composite wood joists either
directly or on to metal channels not exceeding 1 in. (25.4 mm) in depth, provided
the adjacent joist channels are firestopped into volumes not exceeding 160 ft 3
(4.5 m 3 ) , using materials equivalent to 1 2 (14) 12 in.(12.7 mm) gypsum
board, and at least 3 1 2 (15) 312 in. (90 mm) of (16) batt insulation is installed
at the bottom of the joist channels when the ceiling is attached utilizing metal
channels.
30
2/15/16
QR Reduction 91
Residential design 92
11.3.1.3
Unless the requirements of 11.3.1.4 are met, the minimum
required discharge from each of the four hydraulically most
demanding sprinklers design area sprinkler shall be the greater
of the following:
(1) In accordance with minimum flow rates indicated in individual the
sprinkler listings
(2) Calculated based on delivering a minimum of 0.1 gpm/ft 2 (4.1
mm/min) over the design area in accordance with the provisions of
8.5.2.1 or 8.6.2.1.2 In rooms or compartments greater than 800 ft
(74.3 m 2 ), calculated based on delivering a minimum of 0.1 gpm/ft
2 (4.1 mm/min) over the design area in accordance with the
provisions of 8.5.2.1
(3) In rooms or compartments 800 ft 2 (74.3 m 2 ) or less calculated
based on delivering a minimum of 0.1 gpm/ft 2 (4.1 mm/min) over
the room or the compartment using the area of the room divided by
the number of sprinklers in the room
Residential design 93
31
2/15/16
Sprinkler-Protected Glazing 94
Annex 95
Final Questions? 96
32
2/15/16
Instructor 97
James Golinveaux
[email protected]
Cell 1(407) 463-8511
NFPA 13 Changes from the 2013 Edi9on to the 2016 Edi9on, Part 1
Thank You
98
NFPA 13 Changes from the 2013 Edi9on to the 2016 Edi9on, Part 1
Instructions
Receive Certificate of CE Credit
To receive CEUs for todays program, you must have registered online for the live
webinar, then complete an evaluaCon form aJer the program.
To complete the evaluaCon go to: h\ps://fs8.formsite.com/AFSA/form194/index.html
CerCcates will go out within 2 weeks.
Thank you!
99
33