Engineering Data
Single Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Structural Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Engineering Data
Single Air Inlet Models
Motor HP Weights (lbs) Dimensions Connection Sizes2,3
Internal
Spray Coil
Model Nominal Heaviest Make-Up Pump Volume
FXV Engineering Data
Number Tons5 Fan Pump Operating1 Shipping Section L W H A P Water Coil (GPM) (GAL)
FXV-L421 30 5 7,730 5,050 2,900 46
FXV-L422 41 5 8,190 5,370 3,220 60
FXV-L423 46 5 8,680 5,710 3,560 74
FXV-L424 55 7.5 9,160 6,050 3,900 88
1.5 6 1-1/4 8 5-1/4 13 2-3/4 6 3/4 1 3-3/4 1-1/2 4 190
FXV-421 33 7.5 7,730 5,050 2,900 46
FXV-422 46 7.5 8,190 5,370 3,220 60
FXV-423 52 7.5 8,680 5,710 3,560 74
FXV-424 59 10 9,160 6,050 3,900 88
FXV-L431 53 7.5 11,230 7,160 4,240 69
FXV-L432 68 7.5 11,930 7,650 4,730 90
FXV-L433 75 7.5 12,630 8,140 5,220 112
FXV-L434 86 10 13,380 8,680 5,760 133
2 9 1-1/4 8 5-1/4 13 2-3/4 6 3/4 1 4-1/4 1-1/2 4 290
FXV-431 57 10 11,230 7,160 4,240 69
FXV-432 73 10 11,930 7,650 4,730 90
FXV-433 81 10 12,630 8,140 5,220 112
FXV-434 95 15 13,380 8,680 5,760 133
FXV-L441 83 10 14,200 8,760 5,120 91
FXV-L442 100 10 15,150 9,410 5,770 120
FXV-L443 110 10 16,080 10,060 6,420 149
FXV-L444 130 15 17,070 10,770 7,130 178
1-1/2 4
FXV-441 92 15 14,200 8,760 5,120 91
FXV-442 111 15 15,150 9,410 5,770 120
3 12 1-1/4 8 5-1/4 13 2-3/4 6 3/4 1 8-1/4 500
FXV-443 122 15 16,080 10,060 6,420 149
FXV-444 140 20 17,070 10,770 7,130 178
FXV-LQ440 79 10 15,150 9,410 5,770 124
FXV-LQ441 116 15 17,070 10,770 7,130 182
1-1/2 6
FXV-Q440 88 15 15,150 9,410 5,770 124
FXV-Q441 125 20 17,070 10,770 7,130 182
FXV-L641 126 15 18,560 10,890 6,730 146
FXV-L642 154 15 20,050 11,930 7,770 192
FXV-L643 169 15 21,550 12,980 8,820 238
FXV-L644 193 20 23,050 14,040 9,880 284
1-1/2 4
FXV-641 144 25 18,560 10,890 6,730 146
FXV-642 175 25 20,050 11,930 7,770 192
FXV-643 193 25 21,550 12,980 8,820 238
5 12 1-1/4 11 10 15 10-3/4 8 8-3/4 1 8-3/4 715
FXV-644 215 30 23,050 14,040 9,880 284
FXV-LT642 169 15 21,550 12,980 8,820 284
FXV-T642 192 25 21,650 13,080 8,920 284
FXV-LQ640 118 15 20,050 11,930 7,770 194
1-1/2 6
FXV-LQ641 168 20 23,050 14,040 9,880 286
FXV-Q640 134 25 20,050 11,930 7,770 194
FXV-Q641 186 30 23,050 14,040 9, 880 286
FXV-L661 202 22.5 27,070 15,510 9,690 218
FXV-L662 234 22.5 29,290 17,070 11,250 288
FXV-L663 257 22.5 31,570 18,670 12,850 358
FXV-L664 297 30 33,810 20,280 14,460 429
1-1/2 4
FXV-661 231 40 27,070 15,510 9,690 218
FXV-662 267 40 29,290 17,070 11,250 288
FXV-663 295 40 31,570 18,670 12,850 358
7.5 18 1-1/4 11 10 16 4-1/4 9 2-1/4 2 3/8 900
FXV-664 331 45 33,810 20,280 14,460 429
FXV-LT662 263 22.5 33,790 20,260 14,440 429
FXV-T662 297 40 33,810 20,280 14,460 429
FXV-LQ660 189 22.5 29,290 17,070 11,250 299
1-1/2 8
FXV-LQ661 269 30 33,810 20,280 14,460 439
FXV-Q660 215 40 29,290 17,070 11,250 299
FXV-Q661 299 45 33,810 20,280 14,460 439
Notes:
1. Operating weight is for the tower with the water level in the cold 5. Models shipped with an optional gear drive or low sound fan
water basin at the overflow. may have heights up to 10.5" greater than shown. Models with
2. The actual size of the inlet and outlet connection may vary with Whisper Quiet Fans may have heights up to 5-1/2 greater than
the design flow rate. Consult unit print for dimensions. shown.
6. Nominal tons of cooling represents 3 GPM of water cooled
3. Inlet and outlet connections are beveled for welding.
from 95F to 85F at a 78F entering wet-bulb temperature.
4. Standard make-up, drain and overflow connections are located
7. For FXV-44xx, the riser pipe diameter is 4. For FXV-6xx and all
on the bottom of the unit. Make-up connection is 1-1/2 MPT
dual air inlet models, the riser pipe is 6.
standpipe, drain is 2 FPT and overflow is 3 FPT. On single air-
inlet models, standard make-up, drain and overflow connections 8. Dimensional reference drawings.
are MPT.
3" OVERFLOW
2" DRAIN
6" FLUID IN
dimension in the table below. To support an FXV on columns or in an alternate arrangement not shown
here, consult your local BAC Representative.
Optional Maximum
Model Number D Minimum D* Deflection
FXV - 42x 8 3 5 9 3/16
Maximum
Model Number D Deflection
FXV-288-xxx 23 9-1/8 1/2
Notes:
1. Support steel and anchor bolts to be designed and furnished 4. If vibration isolation rails are to be used between the unit and
by others. supporting steel, be certain to allow for the length of the vibration
rails (by others) when determining the length of the supporting
2. All support steel must be level at the top. steel, as vibration rail length and mounting hole locations may
3. Beams must be selected in accordance with accepted structural differ from those of the unit.
practice. Maximum deflection of beam under unit to be 1/360 5. If point vibration isolation is used with multi-cell units, the isolators
of span, not to exceed 1/2 inch. must be located under the support steel, not between the support
steel and the closed circuit cooling towers.