Programming Manual
P/N 270381 Rev 3.0 21OCT99
DOCUMENT HISTORY
Revision Date Reason For Change
1.0 18JUL96 Initial release.
1.11.4 N/A Documentation development releases.
1.5 9MAY97 Update manual to coincide with release of
software version 1.0.
1.61.9 N/A Documentation development releases.
2.0 14DEC98 Update manual to coincide with release of
software version 1.3. Added chapter 15. Major
revisions made to chapters 3, 6, and 9. Updated
various screen captures throughout.
3.0 21OCT99 Update manual to to coincide with release of
software version 1.5. Added glossary and removed
chapters 4-15. The 3-SDU help file, revision 1.5,
includes the user information formerly contained in
chapters 4-15.
Important information iv
About this manual v
The EST3 library vi
Related documentation vii
On 3.50
OnGuard 3.51
Open 3.52
ReleaseDoor (RELEASE) 3.53
RemoteAltSensitivityOff (RASOFF) 3.54
RemoteAltSensitivityOn (RASON) 3.55
Reset 3.56
SlowBlink (SLOW) 3.57
Steady 3.58
TroubleSilence (TS) 3.59
Glossary Y.1
Index Z.1
Important information
Limitation of liability
This product has been designed to meet the requirements of
NFPA Standard 72, 1996 Edition; Underwriters Laboratories,
Inc., Standard 864, 7th Edition; and Underwriters Laboratories
of Canada, Inc., Standard ULC S527. Installation in accordance
with this manual, applicable codes, and the instructions of the
Authority Having Jurisdiction is mandatory. EST shall not under
any circumstances be liable for any incidental or consequential
damages arising from loss of property or other damages or losses
owing to the failure of EST products beyond the cost of repair or
replacement of any defective products. EST reserves the right to
make product improvements and change product specifications
at any time.
While every precaution has been taken during the preparation of
this manual to ensure the accuracy of its contents, EST assumes
no responsibility for errors or omissions.
FCC warning
This equipment can generate and radiate radio frequency energy.
If this equipment is not installed in accordance with this manual,
it may cause interference to radio communications. This
equipment has been tested and found to comply within the limits
for Class A computing devices pursuant to Subpart B of Part 15
of the FCC Rules. These rules are designed to provide
reasonable protection against such interference when this
equipment is operated in a commercial environment. Operation
of this equipment is likely to cause interference, in which case
the user at his own expense, will be required to take whatever
measures may be required to correct the interference.
Intended audience
This manual and the information it contains is intended to be
used by persons who have working knowledge of Windows and
have successfully completed:
The EST3 Self Study Course
The EST3 Programming and Application Course.
Organization
This manual is organized as described below:
Chapter 1 provides a general overview of basic concepts that the
system programmer should understand before attempting to
program system functions.
Chapter 2 provides an alphabetical reference of the input event
types used in the programming language.
Chapter 3 provides an alphabetical reference of the output
commands used in the programming language.
Appendix A provides a quick reference to the information
contained in chapters 2 and 3.
Related documentation
National Fire Protection Association (NFPA)
1 Batterymarch Park
P.O. Box 9101
NFPA
R
Quincy, MA 02269-9101
NFPA 70 National Electric Code
NFPA 72 National Fire Alarm Code
UL
Underwriters Laboratories Inc. (ULI)
R 333 Pfingsten Road
Northbrook, IL 60062-2096
UL 38 Manually Actuated Signaling Boxes
UL217 Smoke Detectors, Single & Multiple Station
UL 228 Door Closers/Holders for Fire Protective Signaling
Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling
Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Visual Signaling Appliances
Summary
This chapter provides a general overview of basic concepts that
the system programmer should understand before attempting to
program system functions.
Content
About the Systems Definition Utility 1.2
Minimum equipment requirements 1.2
Optional equipment but very nice to have 1.3
Programming using rules and objects 1.4
Rules 1.4
Events 1.7
Device types 1.7
Objects 1.7
Labels 1.8
Creating a rules file 1.9
Order is important 1.9
Compiling the rules file 1.12
Developing a labeling plan 1.13
Formatting labels 1.13
Making labels descriptive 1.14
Using common label modifiers 1.15
Using numbers in labels 1.17
Using labels as messages 1.17
Identifying objects in the system 1.18
Priorities 1.21
Advanced programming techniques 1.25
Wildcards 1.25
N-variable 1.25
Mathematical operators 1.26
Programming using logic groups 1.28
Nonalarm logic groups 1.29
Zone groups 1.32
Check-In groups 1.33
Guard Patrol groups 1.33
Service groups 1.34
Programming using time controls 1.35
Manufacturer Model
Creative Technology CT2960 16-bit Audio Card
CT03600 16-bit Advanced Wave
Table Audio Card
Diamond Sound Super Sound Origins Lite
Bravo Sound 16P MT9ATC931
AT&T Jazz 16 Business Audio
Ultra Ultra 32 Audio Card
Manufacturer Model
Zebra Technologies SCANONE
VTI, Inc.
Zebra Technologies Barcode Anything SCAN 97
VTI, Inc.
Rules
A rule is a programming statement that specifies which
commands to execute when a certain event takes place. A rule
consists of a label, an input statement, and an output statement
or statements.
The basic syntax for a rule is:
[Rule_label]
Input_statement:
Output_statement_1, {comments}
Output_statement_2, {comments}
Output_statement_3; {comments}
The rule label can be up to 40 characters in length and enclosed
in brackets. The rule label can be any ASCII character except:
braces { }, the percent symbol %, the number symbol #,
less than and greater than symbols < >, and asterisks *.
The input statement ends with a colon and the output statement
ends with a semicolon. When more than one output statement is
used in a rule, each output statement must end with a comma,
except for the last output statement, which must end with a
semicolon. A rule may contain up to 32 output statements.
When a rule has multiple output statements, each output
command will be executed in the order it is listed in the rule
(from first to last). When the event activating the rule restores,
Input statements
An input statement is the part of a rule that determines what
must happen before the corresponding output statements will be
executed. There are two different syntaxes used in rule input
statements depending on the input event type selected. The two
input statement syntaxes are:
event_type :
event_type device_type 'object_label' :
where:
event_type Specifies the type of input event required for the
rule to execute. When a system input activates,
the resulting change in state creates an event.
Refer to Chapter 2:Input event types for detailed
descriptions of event types and their usage.
device_type Specifies the device type of the input device
initiating the event. The device_type parameter
is optional when using the 'object_label'
parameter. When the device_type parameter is
not included, all devices whose label matches
'object_label' will respond to the command.
'object_label' Specifies the label of the input device or circuit
that must go active for the rule to execute. The
'object_label' parameter is optional when using
the device_type parameter. When the
'object_label' parameter is not included, all
devices with the specified device type will
trigger the rule.
Note: When the device_type and 'object_label' parameters are
optional you must specify one or the other or both.
An input statement must be valid for the rule to be successfully
compiled. This means that the device type of the object
identified by 'object_label' must match that specified by
device_type. Also, the input event specified by event_type must
be applicable for the device_type.
Output statements
An output statement is the part of a rule that determines the
commands that will be executed in response to a given input and
Events
An event is the outcome produced by a panel's CPU module
when an addressable point on the panel changes state. The
information contained in an event includes the logical address of
the point that changed state, the event type, and the event
message.
Device types
A device type is the classification given to objects created in the
database that defines the operating characteristics of the
corresponding device. For example, the PULL device type is
assigned to objects created for manual pull stations.
Refer to Appendix A: Quick Reference for a list of device types
and their use.
Objects
An object is a database entity that represents an addressable
point in the system, such as rail modules, smoke detectors,
switches, and light emitting diodes (LEDs).
Objects can also be:
Logical groups consisting of other objects
Voice messages
Pseudo points designed to monitor card-level and system-
level functions
For example, the Signature controller module is an object as are
any Signature devices connected to it. In contrast, the 3-IDC8/4
module is an object, each of its eight circuits are objects, but any
two-wire smokes connected to the circuits are not.
Labels
A label is a descriptive word or words to identify a specific
object in the project database in order to simplify programming.
Labels are also used to identify a rule in the rules file. Typically,
object labels describe the physical location of the device that the
object represents.
Tip: Excessively long labels are generally harder to read.
Sometimes less is more.
Labels have the following characteristics:
Labels must be unique. Duplicate labels generate compiler
errors and prevent the database from compiling.
Labels are arbitrary except for labels that are automatically
assigned by the system.
Labels are not case sensitive and may contain up to 40
characters. The characters may be any ASCII character
except: braces { } , the percent symbol %, the number
symbol #, less than and greater than symbols < >,
asterisks *, and blank spaces.
The SDU automatically replaces invalid label characters as
shown below to prevent programming errors.
Order is important
When you have more than one rule that uses the same input
requirements to trigger separate output responses, the order in
which the rules appear in the rules file affects how the rules are
executed. The compiler takes multiple rules with like input
statements and executes them as though they were a single rule
containing multiple output statements. The output statements are
executed in the same order that they appear in the rules file.
Say you have a rules file containing the following rules:
[Rule 1]
ALARM SMOKE 'LVL5_SMK1' :
DELAY 30,
FANON 'STAIRWELL_PRESSURE_2';
[Rule 2]
ALARM SMOKE 'LVL5_SMK1' :
FAST 'CAB1_PNL1_LED1';
[Rule 3]
ALARM SMOKE 'LVL5_SMK1' :
ON AUDIBLE 'LVL5_HORN';
After compiling, the rules would be executed as though they
were written as:
[Compiled Rule]
ALARM SMOKE 'LVL5_SMK1' :
DELAY 30,
FANON 'STAIRWELL_PRESSURE_2',
FAST 'CAB1_PNL1_LED1',
ON AUDIBLE 'LVL5_HORN';
Formatting labels
To make your labels more readable, and more understandable,
your labeling plan should include how labels will be formatted.
You should take into consideration that labels will be viewed
online, on printed reports and on the system display panel.
Formatting considerations may include:
How to separate label modifiers
Whether to use all uppercase or all lowercase characters or a
combination of both
How label modifiers may be abbreviated.
Note: Labels are not case sensitive. To the compiler, 'ABCDEF'
and 'abcdef' are duplicate labels, but 'ABC_DEF' is not.
Suppose that you are creating labels for several cabinets in an
industrial park of several buildings. The following shows three
examples using different methods of label formatting for a
cabinet in one of the buildings:
BLDG1CAB BLDG1_CAB Bldg1Cab
The first label may be hard to read because it uses all uppercase
characters and there is no separation between the label modifiers
BLDG1 and CAB. The second label is easier to read because of
the space, represented by an underscore, between the two
modifiers. The third label uses upper and lowercase characters to
differentiate between label modifiers.
Always remember to be consistent and find a comfortable
balance between readability and length when formatting labels.
Consistency is the most important factor in making your labels
easy to use and understand. Notice in the example above that
each label abbreviates Building the same way. You want to
avoid using B1, Bldg_1, and Bldg1 as label modifiers to
reference the same building. Adding extra spaces to separate
Label Description
DMPR_CNTRL Damper control panel.
AMP_LEVEL7 Amplifier for floor designated as the seventh
level in a multi-floor building.
LEDPANEL LED panel used as a point annunciator.
Label Description
SMK Smoke detectors
PULL Pull stations
LED Control/display module LEDs
SW Control/display module switches
Penthouse Level 11
Mezzanine Level 4
Lobby Level 3
Basement Level 2
Sub-basement Level 1
[LEVELS2.CDR]
Stairwell
V1
Elevator Shaft
V4
Pipe Chase
V3
Stairwell
V2
[LEVELS3.CDR]
Output functions
wn
e
ks
tio
tur
tdo
loc
AC
st
sta
e
ap
AC
tur
u
AC
C
rm
hu
HV
a
rc
or
al
VA
HV
ap
h
HV
ala
rs
do
ntr
ex
ato
rH
nt
c
ute
ce
ell
me
tor
or
or
lev
ral
loo
oo
flo
flo
irw
mp
tify
va
ne
.e
se
df
t fl
Ele
3rd
1-3
Sta
Ge
No
Co
Ba
Alt
2n
1s
Input functions
function reveals that they are all devices located on the 2ND
floor. This should signal the designer that a label modifier such
as FLOOR2 or LEVEL2 should be included as part of the
device label for every device on the second floor. This also
implies that the floor number should be included in the labels of
all devices.
The keyword FLOOR2 will be incorporated in the computer
shutdown rule. Any device having FLOOR2 as part of its label
will activate the computer shutdown function. Note that the
elevator lobby detector labeled in the previous example will also
shutdown the second floor computer.
The final object group identified is the 1-3 Floor Exhaust
function. Examination of the inputs that initiate the 1-3 exhaust
function reveals that they are all duct smoke detectors. A label
modifier such as DUCT should be included as part of the
device label for all duct detectors. Notice that the input/output
matrix requires that the basement duct detector does not activate
the 1-3 Exhaust function. This should not affect the choice of
DUCT as a label modifier in the device label, as it is useful to
the designer in determining the device's function.
The keyword DUCT will be incorporated in the 1-3 Exhaust
rule. Because not all detectors with the keyword DUCT in
their labels are required to activate the 1-3 exhaust function, the
additional keywords FLOOR1, FLOOR2, and FLOOR3
will be added to the 1-3 exhaust function rule.
Notice that there are a few matrix entries that are not part of any
group. These functions are activated by a specific device. The
rules used to activate these outputs are written for the specific
function, rather than use by multiple objects.
The matrix for a major project would be very large and detailed.
Many inputs will have only one or two output correlations. The
experienced system designer will quickly recognize the patterns
that develop.
In Figure 1-3, notice that the first, second and third floors are
basically copies of each other. This is typical of high rise
buildings. This duplication of functions permits a designer to
recognize that the floor number will be an important label
modifier when creating labels for devices.
Our example also reveals the importance of well-planned label
modifiers. The proper selection of device labels permits the
designer to account for the common functions throughout the
building by writing only a few rules.
Priorities
The output priority parameter specifies the relative importance
of the output with respect to other rules activating the same
output and is an optional parameter.
Rules and objects programming has the ability to prioritize
output commands. There are two output priority levels, HIGH
and LOW. A high priority command will override a low priority
command. A low priority command can not override a high
priority command. A special priority called LATCH is discussed
later in this section.
Because an output device may be affected by any number of
input devices, each output has two software counters associated
with it to keep track of the output's status. The High priority
counter reflects the number of high priority set and reset
commands issued to the output, and the resulting high priority
status. The low priority counter reflects the number of low
priority set and reset commands issued to the output, and the
resulting low priority status.
An output's status is the result of both the high and low priority
counters as governed by the rules below.
A. Every set command increments the appropriate counter by
one; restoring a set command decrements the appropriate
counter by one.
B. Every reset command decrements the appropriate counter by
one; restoring a reset command increments the appropriate
counter by one.
C. When the high priority counter is equal to or less than
negative one (-1), the output is off.
D. When the high priority counter is equal to or greater than
one (+1), the output is on.
E. When the high priority counter is zero (0) and the low
priority counter is equal to zero (0), the output is off.
F. When the high priority counter is zero (0) and the low
priority counter is equal to or greater than one (+1), the
output is on.
When the input (left) side of a rule references the alarm event
type, the High priority level is the default value automatically
assigned to all output commands on the right side of the rule.
The output priority can be changed for the special cases where
low output priority is required in command to an alarm input.
When the input (left) side of a rule references any event type
except the alarm state, the Low priority level is the default value
Latch priority
The latch priority function is a special output priority level used
to force an output to a specific state and reset the high and low
priority counters. The latch priority is not normally required for
normal system programming.
Some functions such as a scheduled time control with no output
duration specified can cause the priority counters to increment
indefinitely. The latch priority can be used to force the time
control to a known state and reset the counters.
Example: Priority settings
Eight inputs, IN1 through IN9, are issuing commands to an
output. Table 1-1 lists the contents of each counter and the
resultant state of the output.
0 All counters initially start out at zero. The output is off, per
rule E.
1 Input IN1 sets the output with a low priority. The Low
Priority Counter (LPC) increments to 1 per rule A. Output is
on, per rule F.
2 Input IN2 sets the output with a low priority. The LPC
increments to 2 per rule A. The output is still on, per rule F.
3 Input IN3 resets the output with a high priority. The High
Priority Counter (HPC) decrements to -1 per rule B. The
output is now off, per rule C.
4 Input IN4 resets the output with a low priority. LPC
decrements to 1 per rule B. The output is still off, per rule C.
5 Input IN5 sets the output with a low priority. The LPC
increments to 2 per rule A. The output is still off per rule C.
6 Input IN6 sets the output with a low priority. The LPC
increments to 3 per rule A. The output is still off per rule C.
7 Input IN7 sets the output with a low priority. The LPC
increments to 4 per rule A. The output is still off per rule C.
8 Input IN8 sets the output with a low priority. The LPC
increments to 5 per rule A. The output is still off per rule C.
9 Input IN9 resets the output with a high priority. The HPC
decrements to -2 per rule B. The output is still off per rule C.
10 IN3 restores. The HPC increments to -1 per rule B. The
output is still off per rule C.
Wildcards
The asterisk (*) can be used in a rule as a wildcard character to
conditionally select devices based on character patterns. The
asterisk may be substituted for any single character or group of
characters anywhere in the label.
Example Selects
'LVL*' Any devices whose labels begin with "LVL"
'*_SMK' Any devices whose labels end with "_SMK"
'LVL*_SMK' Any devices whose labels begin with "LVL"
and end with "_SMK"
'*_SMK_*' Any devices that have "_SMK_" somewhere
in the label
'*' All devices whose device types are valid for
the specified input event type or output
command
N-variable
The N-variable can be used in a rule to conditionally select
devices based on the numerical indexing used in their object
labels. When using the N-variable, the numbers required to make
the conditional true are specified in the input statement. When
the input statement becomes true, the number is substituted for
the variable N in the output statement.
Example Selects
<N : #> A single number entry
<N : # - #> A range of numbers
<N : #, #, # - #, A combination of single numbers and
# - #> number ranges
Notes:
The N-variable may be any number between 0 and 32767,
inclusive.
The N-variable may only be used in a label once
Wildcards may not be used in place of a number.
Any combination of single number and ranges may be used
"< n: #, #-#, #, #-# >" with the restriction that there must be
less than 255 characters between the single quotes in the
object label.
In the following rule, pressing the switch labeled
'LVL1_PHONE_CNTRL' turns on a module labeled
'LVL1_PHONE_JACK'. The same rule turns on a module
labeled 'LVL5_PHONE_JACK' when the switch labeled
'LVL5_PHONE_CNTRL' is pressed.
[PHONE_SWITCH]
SWITCH 'LVL<N:1,3-5>_PHONE_CNTRL':
ON FIREPHONE 'LVL<N>_PHONE_JACK';
Note: The above rule does not produce an output response when
a switch labeled 'LVL2_PHONE_CNTRL' is pressed.
Mathematical operators
Mathematical operators can be used in conjunction with the N-
variable in the rule output statement to conditionally select
devices based on the numerical indexing used in their object
labels.
When using mathematical operators, the numbers required to
make the conditional true are specified by the N-variable in the
input statement. When the input statement becomes true, the
number is substituted for the variable N in the output statement
and then increased or decreased by the number specified by the
# parameter.
Example Selects
<N + #> A number greater than the number
determined by N in the input statement
<N - #> A number less than the number determined
by N in the input statement
Notes:
The # parameter may be any number between 1 and 32767,
inclusive.
And groups
And groups are a collection of devices that are grouped together
to provide a unique response based on:
a specific number of device activations (changes in state)
the activation type
For example, you can configure an And group of eight smoke
detectors (SMK_1SMK_8) to activate when any three go into
alarm with the exception of SMK_5 which can go into alarm or
trouble.
Notes
Each And group member's change in state produces a
separate event that may be viewed on the 3-LCD in addition
to the And group's activation event.
If a member can have more than one concurrent change in
state, an example being a smoke detector that is in trouble
and then goes into alarm, each change in state counts as 1
activation.
And group activations can be configured for any event type
(alarm, supervisory, trouble, monitor). For example, you can
have an And group that produces a trouble event when it
activates and another that produces an alarm event.
And groups can consist of any of the following device types:
Acknowledge, AlarmSilence, AllCall, AlternateLanguage,
AlternateMsg, AlternateSensitivity, And, Audible,
CardDBIncompatibility, CfgMismatch, CommFailure,
CommonAlarmOutput, CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl, DamperFeedback,
DoorControl, DoorFeedback, Drill, Evacuation,
ExtDBIncompatibility, FailSafe, FanControl, FanFeedback,
Firephone, FirstAlarm, FirstDisable, FirstMonitor,
FirstSupervisory, FirstTrouble, GAInhibit, Gatevalve,
GenAlarm, GroundFault, Heat, Lamptest, LocalAlarm,
LocalMonitor, LocalRelay, LocalTrouble, Matrix, Monitor,
NonsupervisedOutput, Power, Pull, R1, R2, R3, RebootFault,
Reset, Security, ServiceDeviceSupervision,
ServiceGroupActive, Smoke, Smoke Vfy, StageOne, StageTwo,
Startup, SupervisedOutput, Supervisory, Switch, Tamper,
TaskFailure, Temperature, Text, TroubleSilence,
TwoStageTimerActive, TwoStageTimerExpiration,
UserTrouble, Visible, Waterflow, Zone
Matrix groups
Matrix groups are a collection of device types that are grouped
together to provide a unique response similar to the way an And
group operates. In addition to an activation number, a Matrix
group searches a range of devices around the first device in the
group that goes active for a second device to go active in order
to activate the group. Each device within a Matrix group is
assigned a set of x,y coordinates to create a matrix grid
according to their mounting location.
The radius of a Matrix specifies the size of the search radius.
The search radius is the number of devices away from the first
active device that the system will search for a second device.
The activation number of a Matrix group specifies the number of
device activations that must occur to turn on the output of the
Matrix group. Either condition will activate the output of the
Matrix group.
A Matrix group can be configured to generate any activation
type (alarm, supervisory, trouble, monitor) and can consist of
any of the device types found in an And group.
Figure 1-4 illustrates the activation process for a Matrix group
with only alarm activations.
Start
Yes
[2] Is devices in
alarm > or = to the Yes
activation number?
No
No [MTRXACT.CDR]
In the illustration above, the detector at location 3,3 was the first
detector to go into alarm, as indicated by the dark gray box. The
Matrix group creates a search radius around the first active
device, as indicated by the light gray box. Should any additional
detector in the light gray box go into alarm, the Matrix group
will activate its output response.
The following rule activates a device labeled 'HALON' when the
matrix group labeled 'MATRIX_GROUP_A' changes to the
active state and produces an alarm event.
[SampleRule]
Alarm Matrix 'MATRIX_GROUP_A':
ON 'HALON';
Note: The input event type used in rules written for And and
Matrix groups depend on the group's Activation Event setting.
For example, you must use the Trouble event type when the
activation event is set for trouble.
Matrix Group B
Radius = 2
Activation No. = 3
Zone groups
Zone groups are a collection of input devices that are grouped
together to provide a unique response separate from their
individual device responses. For all the devices in the group that
go into alarm, only a single Zone Active event is sent to the
Alarm queue on the 3-LCD. To determine which devices in the
zone are active, select the Zone Active event in the Alarm queue
and press the Details switch.
Zone groups can consist of any of the following device types:
Check-In groups
Check-in groups are a collection of Emergency device types that
are grouped together to provide a unique response when
members of the group fail to check in during a prescribed time
period. If one or more devices do not check in during the allotted
time, a Check-In Active response is generated, indicating those
devices which have failed to check in. Check-in groups are
typically used in senior citizen housing to monitor the wellness
of occupants.
Note: Devices that do not check in are removed from the check-
in list and must be restored in order to be available for the next
check-in period.
If a device connected to a Check-in group is activated outside of
the check-in time window, an Emergency response is activated.
If a device that checked in during the required time period is
activated a second time within the check-in window, an
Emergency activation will also be generated.
Service groups
Service groups are a collection of devices that are grouped
together for testing purposes. When enabled, the Service group
automatically disables the member device's normal alarm
response, and provides a common alternate test response.
Service groups can consist of any of the following device types:
Audible, CommonAlarmOutput, CommonMonitorOutput,
CommonSupervisoryOutput, CommonTroubleOutput,
DamperControl, DamperFeedback, DoorControl, DoorFeedback,
Emergency, FanControl, FanFeedback, Firephone, Gatevalve,
GenAlarm, Guard, Heat, Monitor, Power, Pull, Security, Smoke,
SmokeVfy, StageOne, StageTwo, SupervisedOutput,
Supervisory, Tamper, Temperature, Visible, Waterflow
Summary
This chapter provides an alphabetical reference of the input
event types used to program the system. Optional parameters are
shown in italics.
Content
Acknowledge (ACK) 2.2
Alarm 2.3
AlarmSilence (AS) 2.4
AlarmVerify (AVER) 2.5
AllCall 2.6
CallIn (CI) 2.7
Drill 2.8
Emergency (EMER) 2.9
Evacuation (EVAC) 2.10
FirstAlarm (FA) 2.11
FirstDisable (FD) 2.12
FirstMonitor (FM) 2.13
FirstSupervisory (FS) 2.14
FirstTrouble (FT) 2.15
GroundFault (GNDF) 2.16
GuardPatrol (GPG) 2.17
LocalAlarm (LALM) 2.18
LocalMonitor (LMON) 2.19
LocalTrouble (LTRB) 2.20
Monitor (MON) 2.21
R1 2.22
R2 2.23
R3 2.24
RelayConfirmation (RLYCFG) 2.25
Reset 2.26
Security (SEC) 2.27
ServiceDevice (SERV) 2.28
ServiceGroup (SG) 2.29
ServiceGroupActive (SGA) 2.30
SprinklerSupervisory (SPSUP) 2.31
Startup (STUP) 2.32
StationActivation (STACT) 2.33
Supervisory (SUP) 2.34
Switch (SW) 2.35
TimeControl (TIME) 2.36
Trouble (TRB) 2.37
TwoStageTimerActivation (2STAGEA) 2.38
TwoStageTimerExpiration (2STAGETO) 2.39
Acknowledge (ACK)
Use the Acknowledge event to activate a rule when an operator
acknowledges an event displayed on the 3-LCD module.
The Acknowledge event requires that you specify a device type
or an object label, or both.
Acknowledge device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
And, Audible, CommFailure,
CommonAlarmOutput, CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl,
DamperFeedback, DoorControl, DoorFeedback,
Emergency, ExtDBIncompatibility, Failsafe,
FanControl, FanFeedback, Firephone,
Gatevalve, GenAlarm, GenSmoke, GroundFault,
Guard, GuardPatrol, Heat, LocalAlarm,
LocalMonitor, LocalRelay, LocalTrouble,
LoopControllerResetExt, Matrix, Monitor,
NSCommonAlarmOutput,
NSCommonMonitorOutput,
NSCommonSupervisoryOutput,
NSCommonTroubleOutput, PanelCommFault,
Power, Pull, Security, ServiceDeviceSupervision,
ServiceGroup, ServiceGroupActive, Smoke,
SmokeVfy, SprinklerSupervisory, StageOne,
StageTwo, SupervisedOutput, Supervisory,
Switch, Tamper, TaskFailure, Temperature,
TwoStageTimerActive,
TwoStageTimerExpiration, UserTrouble, Visible,
Waterflow, Zone
'object_label' Specifies the label of the device initiating the
event.
Note: The Acknowledge input event can only be used when the
system is configured as a proprietary fire alarm system, in
accordance with NFPA 72.
Example
{Light LED on control/display module to indicate
message for SMK_1 has been acknowledged}
[ACKMSGON]
ACK SMK 'SMK_1':
STEADY -LOW 'DISPLAY_1_LED1';
Alarm
Use the Alarm event to activate a rule when any point on a panel
or any panel in the same network routing group changes to the
alarm state.
The Alarm event requires that you specify a device type or an
object label, or both.
Alarm device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
And, Failsafe, GenAlarm, GenSmoke, Heat,
Matrix, Pull, Smoke, SmokeVfy, StageOne,
StageTwo, Waterflow, Zone
'object_label' Specifies the label of the device initiating the
event.
Example
{Turn on fan relay when any lobby smoke detector
goes into alarm}
[FAN_ON]
ALARM SMK 'LVL*_LOBBY*':
FANON -HIGH 'FAN_RELAY';
Tip: Use the GenSmoke device type when you want to write a
single rule that applies to devices that can have either Smoke or
SmokeVfy device types.
AlarmSilence (AS)
Use the AlarmSilence event to activate a rule when an operator
presses a switch that starts a panel's Alarm Silence function. The
switch can be the Alarm Silence switch on the 3-LCD module or
a control/display module switch programmed to execute the
AlarmSilence command. Typically, you use the AlarmSilence
event to silence device types in addition to those automatically
silenced by the Alarm Silence function.
The AlarmSilence event does not require a that you specify a
device type or an object label.
AlarmSilence :
Note: Project configuration settings determine if the Alarm
Silence function automatically silences only audible or audible
and visible device types.
Example
{Flash LED on control/display module when
notification devices have been silenced}
[ALARM_SILENCE_ON]
AS:
FAST -LOW 'DISPLAY_1_LED_1';
AlarmVerify (AVER)
Use the AlarmVerify event to activate a rule when a smoke
detector starts its smoke verification cycle. Typically, the
AlarmVerify event is used to provide an indication of potential
alarm or pre-alarm conditions.
The AlarmVerify event requires that you specify a device type
or an object label, or both.
AlarmVerify device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
GenSmoke, SmokeVfy
'object_label' Specifies the label of the device initiating the
event.
Example
{Flash LED on control/display module when any
smoke detector is in its smoke verification
process}
[VERIFY_ON]
AVER GENSMOKE 'SMK_*':
SLOW -LOW 'DISPLAY_1_LED_1';
AllCall
Use the AllCall event to activate a rule when an operator presses
the All Call or All Call Minus switch on the 3-ASU.
The AllCall event does not require that you specify a device type
or an object label.
AllCall :
Example
{Flash LED on control/display module when All
Call in process}
[ALL_CALL_ON]
ALLCALL:
FAST -LOW 'DISPLAY_1_LED_1';
CallIn (CI)
Use the CallIn event to activate a rule when a fire safety
professional plugs a handset into a firefighter's telephone jack.
The CallIn event requires that you specify a device type or an
object label, or both.
CallIn device_type 'object_label':
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
Firephone
'object_label' Specifies the label of the device initiating the
event.
Example
{Flash LED on control/display module when
connection made to firefighter's telephone
circuit}
[CALLIN_ON]
CI FP 'FP_LVL_<N:1-10>':
FAST -LOW 'DISPLAY_1_LED_<N>';
Drill
Use the Drill event to activate a rule when an operator presses a
switch that starts a panel's Drill function. The switch can be the
Drill switch on the 3-LCD module or a control/display module
switch programmed to execute the Drill command. Typically,
you use the Drill event to activate devices in addition to those
automatically activated by the Drill function.
The Drill event does not require that you specify a device type
or an object label.
Drill :
Note: Project configuration settings determine if the Drill
function automatically activates only audible or audible and
visible device types.
Example
[DRILL_RESPONSE]
DRILL:
AMPON 'LEVEL3_AMP' TO 'CH_PAGE_01_08',
MSGON 'DRILL_MESSAGE' TO 'CH_PAGE_01_08';
Emergency (EMER)
Use the Emergency event to activate a rule when a member of a
Check-in group activates their check-in device anytime outside
of their check-in period or a second time during their check-in
period.
The Emergency event requires that you specify a device type or
an object label, or both.
Emergency device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
Emergency
'object_label' Specifies the label of the device initiating the
event.
Example
{Turn on the common distress relay}
[DISTRESS]
EMER '*':
ON SUP 'DISTRESS_RELAY';
Evacuation (EVAC)
Use the Evacuation event to activate a rule when an operator
presses a control/display module switch programmed to execute
a panel's Evacuation function. Typically, you use the Evacuation
event to activate devices in addition to those automatically
activated by the Evacuation function.
The Evacuation event does not require that you specify a device
type or an object label.
Evacuation :
Example
{Flash LED on control/display module when an
Evacuation has been initiated}
[EVACUATION_RESPONSE]
EVAC:
FAST -LOW 'DISPLAY_1_LED_1';
FirstAlarm (FA)
Use the FirstAlarm event to activate a rule the first time that any
point on a panel or any panel in the same network routing group
changes to the alarm state.
The FirstAlarm event does not require that you specify a device
type or an object label.
FirstAlarm :
Example
{Light LED on control/display module when the
first alarm event occurs}
[FIRST_ALARM_ON]
FA :
STEADY -LOW 'FIRST_ALARM_LED';
FirstDisable (FD)
Use the FirstDisable event to activate a rule the first time that
any point on a panel or any panel in the same network routing
group changes to the disabled state.
The FirstDisable event does not require that you specify a device
type or an object label.
FirstDisable :
Example
{Flash LED on control/display module when the
first disable event occurs}
[FIRST_DISABLE_ON]
FD:
SLOW -LOW 'FIRST_DISABLE_LED';
FirstMonitor (FM)
Use the FirstMonitor event to activate a rule the first time that
any point on a panel or any panel in the same network routing
group changes to the monitor state.
The FirstMonitor event does not require that you specify a
device type or an object label.
FirstMonitor :
Example
{Flash LED on control/display module when the
first monitor event occurs}
[FIRST_MONITOR_ON]
FM:
SLOW -LOW 'FIRST_MONITOR_LED';
FirstSupervisory (FS)
Use the FirstSupervisory event to activate a rule the first time
that any point on a panel or any panel in the same network
routing group changes to the supervisory state.
The FirstSupervisory event does not require that you specify a
device type or an object label.
FirstSupervisory :
Example
{Flash LED on control/display module when the
first supervisory event occurs}
[FIRST_SUPERVISORY_ON]
FS:
FAST -LOW 'FIRST_SUPR_LED';
FirstTrouble (FT)
Use the FirstTrouble event to activate a rule the first time that
any point on a panel or any panel in the same network routing
group changes to the trouble state.
The FirstTrouble event does not require that you specify a
device type or an object label.
FirstTrouble :
Example
{Flash LED on control/display module when the
first trouble event occurs}
[FIRST_TROUBLE_ON]
FT:
FAST -LOW 'FIRST_TROUBLE_LED';
GroundFault (GNDF)
Use the GroundFault event to activate a rule when a rail module
detects a ground fault on its field wiring.
The GroundFault event requires that you specify a device type or
an object label, or both.
GroundFault device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
GroundFault
'object_label' Specifies the label of the pseudo point initiating
the event.
Example
{Flash LED on control/display module to indicate
a ground fault}
[GROUNDFAULT_RESPONSE]
GNDF 'Grnd_Fault_Data_Card_1_01_05':
FAST -LOW 'GROUND_FAULT_LED';
GuardPatrol (GPG)
Use the GuardPatrol event to activate a rule when a patrol guard
fails to activate a patrol tour station at the proper time.
Typically, you use the GuardPatrol event to create an output
response for the entire Guard Patrol group.
The GuardPatrol event requires that you specify a device type or
an object label, or both.
GuardPatrol device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
GuardPatrol
'object_label' Specifies the label of the Guard Patrol group
initiating the event.
Example
{Turn on the guard patrol late/out of sequence
horn}
[GUARDPATROL_RESPONSE]
GPG 'GUARD_PATROL_Group1':
ON -HIGH AUD 'GUARD_HORN';
LocalAlarm (LALM)
Use the LocalAlarm event to activate a rule when a rail module's
LocalAlarm pseudo point goes active.
The LocalAlarm event requires that you specify a device type or
an object label, or both.
LocalAlarm device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
LocalAlarm
'object_label' Specifies the label of the pseudo point initiating
the event.
Example
{Light LED on control/display module when
unprogrammed device detected on Signature
controller module}
[LOCAL_ALARM_ACTIVE]
LALM 'Unprogrammed_Device_Data_Card_1_01_05':
STEADY -LOW 'DISPLAY_1_LED_1';
LocalMonitor (LMON)
Use the LocalMonitor event to activate a rule when a rail
module's LocalMonitor pseudo point goes active.
The LocalMonitor event requires that you specify a device type
or an object label, or both.
LocalMonitor device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
LocalMonitor
'object_label' Specifies the label of the pseudo point initiating
the event.
Example
{Flash LED on control/display module when the
Signature controller is identifying the devices
on the loop}
[LOCAL_MONITOR_ACTIVE]
LMON 'Reconstct_Line_Data_Card_1_01_05':
SLOW -LOW 'DISPLAY_1_LED_1';
LocalTrouble (LTRB)
Use the LocalTrouble event to activate a rule when a rail
module's LocalTrouble pseudo point goes active.
The LocalTrouble event requires that you specify a device type
or an object label, or both.
LocalTrouble device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
LocalTrouble
'object_label' Specifies the label of the pseudo point initiating
the event.
Example
{Flash LED on control/display module when a map
fault occurs on the Signature controller module}
[LOCAL_TROUBLE_ACTIVE]
LTRB 'Map_Fault_Data_Card_1_01_05':
FAST -LOW 'DISPLAY_1_LED_1';
Monitor (MON)
Use the Monitor event to activate a rule when any point on a
panel or any panel in the same network routing group changes to
the monitor state.
The Monitor event requires that you specify a device type or an
object label, or both.
Monitor device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
And, DamperFeedback, DoorFeedback,
FanFeedback, Matrix, Monitor
'object_label' Specifies the label of the device initiating the
event.
Example
{Turn on fan status LEDs 1-10}
[FAN_LED]
MON FANFB 'FAN<N:1-10>_STATUS':
STEADY -LOW 'FAN<N>_ON';
R1
Use the R1 event to activate a rule when the first phase of the 3-
phase reset cycle starts after an operator presses the Reset switch
on the 3-LCD.
The R1 event does not require that you specify a device type or
an object label.
R1 :
Note: The R1 event is self-restoring. Any outputs activated by
this event automatically restore at the end of the reset cycle.
Example
{Flash LED on control/display module during
first phase of the reset cycle}
[FIRST_PHASE_RESET]
R1:
SLOW -LOW 'R1_LED';
R2
Use the R2 event to activate a rule when the second phase of the
3-phase reset cycle starts. The second phase starts after the first
phase finishes.
The R2 event does not require that you specify a device type or
an object label.
R2 :
Note: The R2 event is self-restoring. Any outputs activated by
this event automatically restore at the end of the reset cycle.
Example
{Flash LED on control/display during second
phase of the reset cycle}
[SECOND_PHASE_RESET]
R2:
FAST -LOW 'R2_LED';
R3
Use the R3 event to activate a rule when the third phase of the 3-
phase reset cycle starts. The third phase starts after the second
phase finishes.
The R3 event does not require that you specify a device type or
an object label.
R3 :
Note: The R3 event is self-restoring. Any outputs activated by
this event automatically restore at the end of the reset cycle.
Example
{Light LED on control/display module during
third phase of the reset cycle}
[THIRD_PHASE_RESET]
R3:
STEADY -LOW 'R3_LED';
RelayConfirmation (RLYCFG)
Use the RelayConfirmation event to activate a rule when a
control relay indicates that its electrical contacts have switched
positions. Typically, you use the RelayConfirmation event in
applications that require verifying the proper operation of
remote controlled functions.
The RelayConfirmation event requires that you specify a device
type or an object label, or both.
RelayConfirmation device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
Audible, CommonAlarmOutput,
CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl,
DoorControl, FanControl, Firephone, LocalRelay,
NonsupervisedOutput, SupervisedOutput, Visible
'object_label' Specifies the label of the device initiating the
event.
Example
{Light LED on control/display module when relay
confirmation occurs}
[RELAY_OK]
RLYCFG DOOR 'DOOR_CONTROL_RELAY':
STEADY -LOW 'DOOR_RELAY_LED';
Reset
Use the Reset event to activate a rule when an operator presses a
switch that starts a panel's Reset function. The switch can be the
Reset switch on the 3-LCD module or a control/display module
switch programmed to execute the Reset command. Typically,
you use the Drill event to activate output responses in addition
to those automatically activated by the Reset function.
The Reset event does not require that you specify a device type
or an object label.
Reset :
Example
{Flash LED on control/display module during
reset cycle}
[SYSTEM_RESET_ON]
RESET:
FAST -LOW 'RESET_LED';
Note: See also R1, R2, and R3 input event types.
Security (SEC)
Use the Security event to activate a rule when the open input to a
device or circuit that monitors a supervisory or tamper switch
closes.
The Security event requires that you specify a device type or an
object label, or both.
Security device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
Security
'object_label' Specifies the label of the device initiating the
event.
Example
{Light LED on control/display module when relay
confirmation occurs}
[RELAY_OK]
SEC SEC 'CAB1_TAMPER_SW':
STEADY -LOW 'TAMPER_SW_LED';
ServiceDevice (SERV)
Use the ServiceDevice event to activate a rule when an
authorized service technician activates a device in a Service
group under test. The ServiceDevice event is used to program
individual responses for each device in the Service group.
The ServiceDevice event requires that you specify a device type
or an object label, or both.
ServiceDevice device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
Audible, CommonAlarmOutput,
CommonMonitorOutput,
CommonSupervisoryOutput,
CommonTroubleOutput, DamperControl,
DamperFeedback, DoorControl, DoorFeedback,
Emergency, FanControl, FanFeedback,
Firephone, Gatevalve, GenAlarm, GenSmoke,
Guard, Heat, Monitor, Power, Pull, Security,
Smoke, SmokeVfy, SprinklerSupervisory,
StageOne, StageTwo, SupervisedOutput,
Supervisory, Tamper, Temperature, Visible,
Waterflow
'object_label' Specifies the label of the device initiating the
event.
Note: Outputs activated by a rule using the ServiceDevice event
stay latched until the service test is canceled.
Example
{Flash LED on control/display module when device
activates}
[DEVICE_TEST]
SERV PULL 'IDC_RM_CKT<N:1-8>':
FAST 'CDM_1_LED<N>';
ServiceGroup (SG)
Use the ServiceGroup event to activate a rule when an
authorized service technician activates any device in a Service
group under test. The ServiceGroup event is used to program a
single response for the entire Service group in order to perform a
one-man test.
The ServiceDevice event requires that you specify a device type
or an object label, or both.
ServiceGroup device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
ServiceGroup
'object_label' Specifies the label of the service group initiating
the event.
Notes
Outputs activated by a rule using the ServiceGroup event
automatically restore after a programmed delay period.
You must include a delay command at the end of a rule activated
by the ServiceGroup event with a delay value sufficient to
perform the one-man test
Example
{Flash LED on control/display module when
ServiceGroup event occurs}
[SERVICE_GROUP_RESPONSE]
SG 'SERVICE_GROUP_<N:1-8>':
ON VIS 'LVL<N>_STROBES',
DLYR 300;
ServiceGroupActive (SGA)
Use the ServiceGroupActive event to activate a rule when an
authorized service technician starts a test on a service group
from the 3-LCD module.
The ServiceGroupActive event does not require that you
specifya device type or an object label.
ServiceGroupActive :
Example
{Light LED on control/display module when any
service group is in test mode}
[SERVICE_GROUP_ACTIVE_RESPONSE]
SGA:
STEADY 'CDM_1_LED1';
SprinklerSupervisory (SPSUP)
Use the SprinklerSupervisory event to activate a rule when the
open input to a device or circuit that supervises a component of
the sprinkler system closes. Typically, you use the
SprinklerSupervisory event to provide local and off-premises
notification of sprinkler system status.
The SprinklerSupervisory event requires that you specify a
device type or an object label, or both.
SprinklerSupervisory device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
Gatevalve, Power, SprinklerSupervisory,
Tamper, Temperature
'object_label' Specifies the label of the device initiating the
event.
Note: The Supervisory event can be used with a greater number
of device types and should be used in place of the
SprinklerSupervisory event. Any existing rules using the
SprinklerSupervisory event will still function properly and
should not be rewritten.
Example
{Light LED on control/display module when any
tamper switch is activated}
[TAMPER_LED]
SPSUP TAMP 'FLOOR*':
STEADY -LOW 'TAMPER_LED';
Startup (STUP)
Use the Startup event to activate a rule when the panel is
initially powered up or when an operator initiates the Restart
command from the 3-LCD module. Typically, you use the
Startup event to program the initial operating state of system
components or functions.
The Startup event does not require that you specify a device type
or an object label.
Startup :
Example
{Disable HVAC switches on startup}
[STARTUP]
STUP:
DISABLE -LOW SW '*HVAC*';
StationActivation (STACT)
Use the StationActivation event to activate a rule when a patrol
guard activates a patrol tour station. Typically, you use the
StationActivation event to monitor a patrol guard's progress
through the tour.
The StationActivation event requires that you specify a device
type or an object label, or both.
StationActivation device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
Guard
'object_label' Specifies the label of the object triggering the
event.
Example
{Light LED on control/display module when any
tamper guard station is activated}
[GUARD_STATION_OK]
STACT 'STATION<N:1-10>':
STEADY -LOW 'STATION<N>_OK';
Supervisory (SUP)
Use the Supervisory event to activate a rule when any point on a
panel or any panel in the same network routing group changes to
the supervisory state.
The Supervisory event requires that you specify a device type or
an object label, or both.
Supervisory device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
And, Gatevalve, Matrix, Power,
SprinklerSupervisory, Supervisory, Tamper,
Temperature
'object_label' Specifies the label of the object triggering the
event.
Note: The Supervisory event can be used with a greater number
of device types and should be used in place of the
SprinklerSupervisory event. Any existing rules using the
SprinklerSupervisory event will still function properly and
should not be rewritten.
Example
[AND_1_IN_SUP]
SUP AND 'AND_GROUP1':
STEADY -LOW 'DISPLAY_1_LED1';
Switch (SW)
Use the Switch event to activate a rule when an operator presses
a control/display module switch.
The Switch event requires that you specify a device type or an
object label, or both.
Switch device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
Switch
'object_label' Specifies the label of the switch initiating the
event.
Note: Any commands listed in an output statement activated by
the Switch event are automatically assigned a high priority.
Example
{Light all LEDs on control/display module while
lamptest switch is pressed}
[REMOTE_LAMPTEST]
SW 'LAMPTEST_SWITCH':
LAMP;
TimeControl (TIME)
Use the TimeControl event to activate a rule when a specific
combination of days, dates, and/or time of day occurs. Typically,
you use the TimeControl event to program output responses that
hold and release doors or change smoke detector sensitivity.
The TimeControl event requires that you specify a device type
or an object label, or both.
TimeControl device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
TimeControl
'object_label' Specifies the label of the time control initiating
the event.
Example
{Hold all doors at 6:30 PM}
[DOOR_LOCK]
TIME 'LOCKDOORS':
HOLD -LOW DOOR '*DOORLOCKS*';
Trouble (TRB)
Use the Trouble event to activate a rule when any point on a
panel or any panel in the same network routing group changes to
the trouble state.
The Trouble event requires that you specify a device type or an
object label, or both.
Trouble device_type 'object_label' :
Parameter Description
device_type Specifies the device type of the device initiating
the event. Valid device types are:
And, Audible, CommFailure,
CommonAlarmOutput, CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl,
DamperFeedback, DoorControl, DoorFeedback,
Emergency, ExtDBIncompatibility, Failsafe,
FanControl, FanFeedback, Firephone,
Gatevalve, GenAlarm, Gensmoke, Guard, Heat,
LoopControllerResetExt, Matrix, Monitor,
NSCommonAlarmOutput,
NSCommonMonitorOutput,
NSCommonSupervisoryOutput,
NSCommonTroubleOutput, PanelCommFault,
Power, Pull, RebootFault, Security,
ServiceDeviceSupervision, Smoke, SmokeVfy,
SprinklerSupervisory, StageOne, StageTwo,
SupervisedOutput, Supervisory, Tamper,
TaskFailure, Temperature, UserTrouble, Visible,
Waterflow, Zone
'object_label' Specifies the label of the device initiating the
event.
Example
{Energize the remote common trouble relay}
[TROUBLE_LED]
TRB '*':
ON SUP 'TROUBLE_RELAY';
TwoStageTimerActivation (2STAGEA)
Use the TwoStageTimerActivation event to activate a rule when
a panel's two-stage alarm timer starts counting down. Typically,
you use the TwoStageTimerActivation event in jurisdictions that
require some time delay in order to verify the source of the
alarm before sounding a general alarm.
The TwoStageTimerActivation event does not require that you
specify a device type or an object label.
TwoStageTimerActivation :
Note: The project parameters' setting determines the two-stage
timer's count value.
Example
{Flash LED on control/display module when the
two-stage timer starts}
[2STAGE_TIMER_ACTIVE]
2STAGEA:
FAST -LOW '2STAGE_ACTIVE_LED';
TwoStageTimerExpiration (2STAGETO)
Use the TwoStageTimerExpiration event to activate a rule when
a panel's two-stage alarm timer expires. Typically, you use the
TwoStageTimerExpiration event to sound a general alarm in
jurisdictions that require some time delay to verify of the source
of the alarm.
The TwoStageTimerExpiration event does not require that you
specify a device type or an object label.
TwoStageTimerExpiration :
Note: The project parameters setting determines the two-stage
timer's count value.
Example
{Flash LED on control/display module when the
two-stage timer ends}
[2STAGE_TIMER_EXPIRED]
2STAGETO:
FAST -LOW '2STAGE_EXPIRE_LED';
Summary
This chapter provides an alphabetical reference of the
commands used to program the system. Optional parameters are
shown in italics.
Content
AlarmSilence (AS) 3.3
AlternateLanguage (ALTL) 3.4
AlternateMsgOff (ALTMOFF) 3.5
AlternateMsgOn (ALTMON) 3.6
AlternateSensitivityOff (ALTSOFF) 3.7
AlternateSensitivityOn (ALTSON) 3.8
AmpOff 3.9
AmpOn 3.10
Close 3.11
CommonAlarmOff (CAOFF) 3.12
CommonAlarmOn (CAON) 3.13
CommonMonitorOff (CMOFF) 3.14
CommonMonitorOn (CMON) 3.15
CommonSupervisoryOff (CSOFF) 3.16
CommonSupervisoryOn (CSON) 3.17
Delay (DLY) 3.18
DelayActivate (DLYA) 3.19
DelayRestore (DLYR) 3.20
Disable 3.21
Drill 3.22
Enable 3.23
Evacuation (EVAC) 3.24
FanOff 3.25
FanOn 3.26
FastBlink (FAST) 3.27
GAInhibit (GAIN) 3.28
HoldDoor (HOLD) 3.29
LampTest (LAMP) 3.30
LEDOff 3.31
MsgOff 3.32
MsgOn 3.33
NCClose 3.34
NCFanOff 3.35
NCFanOn 3.36
NCHoldDoor (NCHOLD) 3.37
NCOpen 3.38
NCReleaseDoor (NCRELEASE) 3.39
NSCommonAlarmOff (NSCAOFF) 3.40
NSCommonAlarmOn (NSCAON) 3.41
AlarmSilence (AS)
Use the AlarmSilence command to activate a panel's Alarm
Silence function from a control/display module switch. By
programming a control/display module switch to execute the
AlarmSilence command, an operator can silence alarm
notification signals from panels that do not contain a 3-LCD
module.
The AlarmSilence command only requires that you specify a
cabinet label or a routing label.
AlarmSilence 'cabinet_label' ;
or
AlarmSilence 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Notes
You must configure the switch used to execute the AlarmSilence
command as a momentary switch.
Project parameter settings determine whether the Alarm Silence
function silences only audible, or audible and visible notification
appliance circuits.
The system Alarm Silence function treats devices assigned the
CommonAlarmOutput device type as audibles.
Wildcards may be used in the cabinet label but not in the routing
label.
Example
{Initiate the Alarm Silence function from a
remote panel}
[REMOTE_ALARM_SILENCE]
SW 'B1_C1_REM_ALRM_SIL':
AS 'ALL_CABINETS';
AlternateLanguage (ALTL)
Use the AlternateLanguage command to change the language
that the 3-LCD module uses to display text from a
control/display module switch. By programming a
control/display module switch to execute the AlternateLanguage
command, an operator can control bilingual operation of the
panel. You can also use to a time control to automatically switch
between the primary and secondary language.
The AlternateLanguage command does not require that you
specify a device type or an object label.
AlternateLanguage ;
Notes
You must configure the switch used to execute the
AlternateLanguage command as a momentary switch.
The AlternateLanguage command only switches languages on
the panel that contains the switch programmed to execute the
command.
Device event messages are not affected by the Language settings
and are displayed as they are entered in the SDU. You can
customize the SDU to change the target language used for
entering device event messages.
Example
{Change character set on display from
control/display module}
[ACTIVATE_ALTERNATE_LANGUAGE]
SW 'B1_C1_ALT_LANG':
ALTL;
AlternateMsgOff (ALTMOFF)
Use the AlternateMsgOff command to activate the primary
routing settings that a panel uses for routing device event
messages.
The AlternateMsgOff command only requires that you specify a
cabinet label or a routing label.
AlternateMsgOff 'cabinet_label' ;
or
AlternateMsgOff 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Note: Wildcards may be used in the cabinet label but not in the
routing label.
Example
{Change message routing from control/display
module to primary}
[PRIMARY_MSG_ON]
SW 'B1_C1_PRI_MSGON':
ALTMOFF 'All_Cabinets';
AlternateMsgOn (ALTMON)
Use the AlternateMsgOn command to activate the alternate
routing settings that a panel uses for routing device event
messages.
The AlternateMsgOn command only requires that you specify a
cabinet label or a routing label.
AlternateMsgOn 'cabinet_label' ;
or
AlternateMsgOn 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Note: Wildcards may be used in the cabinet label but not in the
routing label.
Example
{Switch to alternate message routing
configuration during non-regular work hours}
[ALTERNATE_MSG_ON]
TIME 'MON_FRI_NONREG_HOURS':
ALTMON 'All_Cabinets';
AlternateSensitivityOff (ALTSOFF)
Use the AlternateSensitivityOff command to load the primary
sensitivity and alarm verification settings into every smoke
detector in the system. Typically, the primary settings are used
during normal business hours when the protected premises is
occupied.
The AlternateSensitivityOff command does not require that you
specify a device type or an object label.
AlternateSensitivityOff ;
Example
{Switch smoke detectors to primary sensitivity
level during regular work hours}
[ALT_SENS_OFF]
TIME 'MON_FRI_REGULAR_HOURS':
ALTSOFF;
Tip: Use the RemoteAltSensitivityOff command for greater
control over smoke detector selection. The
RemoteAltSensitivityOff command allows you to load primary
sensitivity and alarm verification settings into every smoke
detector on selected panels or on a group of panels.
AlternateSensitivityOn (ALTSON)
Use the AlternateSensitivityOn command to load the alternate
sensitivity and alarm verification settings into every smoke
detector in the system. Typically, the alternate settings are used
during off-normal business hours when the protected premises is
unoccupied.
The AlternateSensitivityOn command does not require that you
specify a device type or an object label.
AlternateSensitivityOn ;
Example
{Switch smoke detectors to alternate sensitivity
level setting during non-regular work hours}
[ALT_SENS_ON]
TIME 'MON_FRI_AFTER_HOURS':
ALTSON;
Tip: Use the RemoteAltSensitivityOn command for greater
control over smoke detector selection. The
RemoteAltSensitivityOn command allows you to load alternate
sensitivity and alarm verification settings into every smoke
detector on selected panels or on a group of panels.
AmpOff
Use the AmpOff command to turn off an amplifier's audio
output and remove the connected audio channel from its input.
The AmpOff command contains two parts. The first part of the
command (AmpOff) identifies the amplifier and the second part
(to) identifies the audio channel.
The AmpOff command only works on devices with the Amp
device type. You are required to specify the amplifier label and
the channel label. Specifying a priority value is optional.
AmpOff priority 'amp_label' to 'channel_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'amp_label' Specifies the label of the amplifier module to turn
off.
'channel_label' Specifies the label of the audio channel to
remove from the amplifier input.
Example
{Turn amplifiers off and deselect the page
channel}
[PAGE_OFF_SWITCHES]
SW 'LVL<N:1-10>_PAGE_OFF':
AMPOFF -LOW 'LEVEL<N>_AMP' TO
'CH_PAGE_01_08';
AmpOn
Use the AmpOn command to turn on an amplifier's audio output
and connect an audio channel to its input. The AmpOn command
contains two parts. The first part of the command (AmpOn)
identifies the amplifier and the second part (to) identifies the
audio channel.
The AmpOn command only works on devices with the Amp
device type. You are required to specify the amplifier label and
the channel label. Specifying a priority value is optional.
AmpOn priority 'amp_label' to 'channel_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'amp_label' Specifies the label of the amplifier module to turn
on.
'channel_label' Specifies the label of the audio channel to
connect to the amplifier input.
Example
{Turn amplifiers on and select the page channel}
[PAGE_ON_SWITCHES]
SW 'LVL<N:1-10>_PAGE_ON':
AMPON -LOW 'LEVEL<N>_AMP' TO 'CH_PAGE_01_08';
Close
Use the Close command to turn off an output circuit or relay that
connects to the control mechanism used to close a damper.
The Close command only works on devices with the
DamperControl device type. You are required to specify the
object label. Specifying a priority value is optional.
Close priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit off (nonactive) the control
mechanism closes the damper.
Example
{Close dampers from control/display module
switch}
[DAMPER_CLOSE_SWITCHES]
SW 'LVL<N:1-10>_DMPR_CLOSE':
CLOSE -LOW DAMP 'DMPR_RELAY_LVL<N>';
CommonAlarmOff (CAOFF)
Use the CommonAlarmOff command to turn off a supervised
notification signal output circuit that a panel automatically
activates when the FirstAlarm event occurs.
The CommonAlarmOff command only works on devices with
the CommonAlarmOutput device type. You are required to
specify the object label. Specifying a priority value is optional.
CommonAlarmOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: Active common alarm outputs can not be turned off using
the CommonAlarmOff command.
Example
[COMMON_ALARM_OFF_SWITCHES]
SW 'COM_ALARM_OFF_LVL<N:1-10>':
CAOFF -LOW 'LVL<N>_COM_ALARM_CKT*';
CommonAlarmOn (CAON)
Use the CommonAlarmOn command to turn on a supervised
notification signal output circuit that a panel automatically
activates when the FirstAlarm event occurs.
The CommonAlarmOn command only works on devices with
the CommonAlarmOutput device type. You are required to
specify the object label. Specifying a priority value is optional.
CommonAlarmOn priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
[COMMON_ALARM_ON_SWITCHES]
SW 'COM_ALARM_ON_LVL<N:1-10>':
CAON -LOW 'LVL<N>_COM_ALARM_CKT*';
CommonMonitorOff (CMOFF)
Use the CommonMonitorOff command to turn off a supervised
notification signal output circuit that a panel automatically
activates when the FirstMonitor event occurs.
The CommonMonitorOff command only works on devices with
the CommonMonitorOutput device type. You are required to
specify the object label. Specifying a priority value is optional.
CommonMonitorOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Notes
Active common monitor outputs can not be turned off using the
CommonMonitorOff command.
You can not use any device to turn off a common monitor output
that upon activation produces a monitor event. For example, you
can not use a control/display module switch.
Example
[COMMON_MON_OFF_RESPONSE]
ALARM GENALARM:
CMOFF -LOW 'EVAC_DOOR';
CommonMonitorOn (CMON)
Use the CommonMonitorOn command to turn on a supervised
notification signal output circuit that a panel automatically
activates when the FirstMonitor event occurs.
The CommonMonitorOn command only works on devices with
the CommonMonitorOutput device type. You are required to
specify the object label. Specifying a priority value is optional.
CommonMonitorOn priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
[COMMON_MON_ON_RESPONSE]
ALARM GENALARM:
CMON -LOW 'COM_MON_CKT_LVL*';
CommonSupervisoryOff (CSOFF)
Use the CommonSupervisoryOff command to turn off a
supervised notification signal output circuit that a panel
automatically activates when the FirstSupervisory event occurs.
The CommonSupervisoryOff command works on devices with
the CommonSupervisoryOutput device type. You are required to
specify the object label. Specifying a priority value is optional.
CommonSupervisoryOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: Active common supervisory outputs can not be turned off
using the CommonSupervisoryOff command.
Example
[COMMON_SUP_OFF_SWITCHES]
SW 'COM_SUP_OFF_LVL<N:1-10>':
CSOFF -LOW 'LVL<N>_COM_SUP_CKT*';
CommonSupervisoryOn (CSON)
Use the CommonSupervisoryOn command to turn on a
supervised notification signal output circuit that a panel
automatically activates when the FirstSupervisory event occurs.
The CommonSupervisoryOn command works on devices with
the CommonSupervisoryOutput device type. You are required to
specify the object label. Specifying a priority value is optional.
CommonSupervisoryOn priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
[COMMON_SUP_ON_SWITCHES]
SW 'COM_SUP_ON_LVL<N:1-10>':
CSON -LOW 'LVL<N>_COM_SUP_CKT*';
Delay (DLY)
Use the Delay command to insert a time delay between rule
output command statements when a rule activates and restores.
The Delay command only requires that you specify the delay
value.
Delay delay_value ;
Parameter Description
delay_value Specifies the length of the delay from 1 to 32767
seconds, inclusive.
Example
{Turn amps on at startup to accept the General
channel}
[STARTUP_AMPS]
STUP:
AMPON 'LVL_5_AMP' TO 'CH_GEN_01_08',
DLY 10,
AMPON 'LVL_6_AMP' TO 'CH_GEN_01_08';
DelayActivate (DLYA)
Use the DelayActivate command to insert a time delay between
rule output command statements only when the rule activates.
The delay is not inserted when the rule restores.
The DelayActivate command only requires that you specify the
delay value.
DelayActivate delay_value ;
Parameter Description
delay_value Specifies the length of the delay from 1 to 32767
seconds, inclusive.
Example
{Supply and pressure fan alarm response}
[ALARM_FAN]
ALARM GENSMOKE:
FANOFF 'SUPPLY_FAN',
DLYA 15,
FANON 'PRESSURE_FAN1';
DelayRestore (DLYR)
Use the DelayRestore command to insert a time delay between
rule output command statements only when the rule restores.
The delay is not inserted when the rule activates.
The DelayRestore command only requires that you specify the
delay value.
DelayRestore delay_value ;
Parameter Description
delay_value Specifies the length of the delay from 1 to 32767
seconds, inclusive.
Example
{Supply and pressure fan alarm response}
[ALARMFAN]
ALARM GENSMOKE:
FANON 'PRESSURE_FAN1',
DLYR 15,
FANON 'PRESSURE_FAN2';
Disable
Use the Disable command to inhibit the automatic or manual
control of a system hardware component, circuit, or logic group.
The Disable command requires that you specify a device type or
an object label, or both.
Disable device_type 'object_label' ;
Parameter Description
device_type Specifies the device type of the device
responding to the command. Valid device types
are:
12SW/12LED, 12SW/24LED, 24LED, 3-AADC,
3-ASU, 3-DSDC, 3-FTCU, 3-IDC8/4, 3-OPS,
3SW/3LEDX6, Amp, And, Audible, CheckIn,
CommonAlarmOutput, CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl,
DamperFeedback, DoorControl, DoorFeedback,
Emergency, FanControl, FanFeedback,
Firephone, Gatevalve, GenAlarm, GenSmoke,
Guard, GuardPatrol, Heat, LED, LocalAlarm,
LocalMonitor, LocalRelay, LocalTrouble, Matrix,
Monitor, NonsupervisedOutput,
NSCommonAlarmOutput,
NSCommonMonitorOutput,
NSCommonSupervisoryOutput,
NSCommonTroubleOutput, Power, Pull,
Security, Smoke, SmokeVfy,
SprinklerSupervisory, StageOne, StageTwo,
SupervisedOutput, Supervisory, Switch, Tamper,
Temperature, Text, TimeControl, Visible,
Waterflow, Zone
'object_label' Specifies the label of the output device
responding to the command.
Note: Disabling a Zone group disables the group and all the
devices in the group.
Example
[CIRCUIT_DISABLE]
SW 'PANEL_1_SW1':
DISABLE DSDC 'SIGA_CIRCUIT_1';
Drill
Use the Drill command to activate a panel's Drill function from a
control/display module switch. By programming a
control/display module switch to execute the Drill command, an
operator can turn on alarm notification signals from panels that
do not contain a 3-LCD module.
The Drill command only requires that you specify a cabinet label
or routing label.
Drill 'cabinet_label' ;
or
Drill 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Notes
You must configure the switch used to execute the Drill
command as a momentary switch.
Project parameter settings determine whether the Drill function
activates only audible, or audible and visible notification
appliance circuits. The Drill function activates notification
appliance circuits but does not put the panel into alarm.
Wildcards may be used in the cabinet label but not in the routing
label.
Example
[REM_DRILL_CNTRL]
SW 'B1_CAB<N:1-5>_DRILL':
DRILL 'CAB<N>';
Enable
Use the Enable command to allow automatic or manual control
of a system hardware component, circuit, or logic group.
The Enable command requires that you specify a device type or
an object label, or both.
Enable device_type 'object_label' ;
Parameter Description
device_type Specifies the device type of the device
responding to the command. Valid device types
are:
12SW/12LED, 12SW/24LED, 24LED, 3-AADC,
3-ASU, 3-DSDC, 3-FTCU, 3-IDC8/4, 3-OPS,
3SW/3LEDX6, Amp, And, Audible, CheckIn,
CommonAlarmOutput, CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl,
DamperFeedback, DoorControl, DoorFeedback,
Emergency, FanControl, FanFeedback,
Firephone, Gatevalve, GenAlarm, GenSmoke,
Guard, GuardPatrol, Heat, LED, LocalAlarm,
LocalMonitor, LocalRelay, LocalTrouble, Matrix,
Monitor, NonsupervisedOutput,
NSCommonAlarmOutput,
NSCommonMonitorOutput,
NSCommonSupervisoryOutput,
NSCommonTroubleOutput, Power, Pull,
Security, Smoke, SmokeVfy,
SprinklerSupervisory, StageOne, StageTwo,
SupervisedOutput, Supervisory, Switch, Tamper,
Temperature, Text, TimeControl, Visible,
Waterflow, Zone
'object_label' Specifies the label of the output device
responding to the command.
Example
[CIRCUIT_ENABLE]
SW 'PANEL_1_SW1':
ENABLE 3-DSDC 'SIGA_CIRCUIT_1';
Evacuation (EVAC)
Use the Evacuation command to activate a panel's Evacuation
function from a control/display module switch. By programming
a control/display module switch to execute the Evacuation
command, an operator can put a panel into alarm and force the
panel to activate its programmed alarm responses from panels
that do not contain a 3-LCD module..
The Evacuation command only requires that you specify a
cabinet label or routing label.
Evacuation 'cabinet_label' ;
or
Evacuation 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Note: Wildcards may be used in the cabinet label but not in the
routing label.
Example
[REM_EVAC_CNTRL]
SW 'DISPLAY_1_SW1':
EVAC 'All_Cabinets';
FanOff
Use the FanOff command to turn off an output circuit or relay
that connects to the control mechanism used to turn off a fan.
The FanOff command only works on devices with the
FanControl device type. You are required to specify the object
label. Specifying a priority value is optional.
FanOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit off (nonactive) the control
mechanism turns off the fan.
Example
[SUPPLY_FAN_CNTRL]
SW 'SUPPLY_FAN<N:1,2>_OFF':
FANOFF 'SUPPLY_FAN<N>';
FanOn
Use the FanOn command to turn on an output circuit or relay
that connects to the control mechanism used to turn on a fan.
The FanOn command only works on devices with the
FanControl device type. You are required to specify the object
label. Specifying a priority value is optional.
FanOn priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit on (active) the control mechanism
turns on the fan.
Example
[SUPPLY_FAN_CNTRL]
SW 'SUPPLY_FAN<N:1,2>_ON':
FANON -LOW 'SUPPLY_FAN<N>';
FastBlink (FAST)
Use the FastBlink command to turn a light-emitting diode on a
control/display module on and off at a fast interval.
The FastBlink command only works on devices with the LED
device type. You are required to specify the object label.
Specifying a priority value is optional.
FastBlink priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
{Flash LED on control/display module when second
phase of the system reset process occurs}
[ANN_RESET_2ND_PHASE]
R2:
FAST -LOW 'R2_LED';
GAInhibit (GAIN)
Use the GAInhibit command to stop a panel's two-stage timer
from a control/display module switch. By programming a
control/display module switch to execute the GAInhibit
command, an operator can stop a panel's two-stage alarm timer
before it expires and prevent the panel from sounding a general
alarm.
The GAInhibit command only requires that you specify the
cabinet label or the routing label.
GainInhibit 'cabinet_label' ;
or
GainInhibit 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Notes
You must configure the switch used to execute the GAInhibit
command as a momentary switch.
Wildcards may be used in the cabinet label but not in the routing
label.
Example
{Cancel the two-stage alarm timer}
[GAINHIBIT_CNTRL]
SW 'GAINHIBIT_SW':
GAIN 'ALL_CABINETS';
HoldDoor (HOLD)
Use the HoldDoor command to turn on an output circuit or relay
that connects to the control mechanism used to hold a door.
The HoldDoor command only works with devices assigned the
DoorControl device type. You are required to specify the object
label. Specifying a priority value is optional.
HoldDoor priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit on (active) the control mechanism
holds the door.
Example
{Energize magnetic door holders from panel
control switch}
[MANUAL_DOOR_CNTRL]
SW 'PANEL_1_SW1':
HOLD -HIGH 'DOORCONTROL_*';
LampTest (LAMP)
Use the LampTest command to activate the lamp test function
from a control/display module switch. By programming a
control/display module switch to execute the LampTest
command, an operator can perform a lamp test on panels that do
not contain a 3-LCD module.
The LampTest command does not require that you specify a
device type or an object label.
LampTest ;
Notes
You must configure the switch used to execute the LampTest
command as a momentary switch.
The LampTest command operates only on the panel containing
the switch programmed to execute the command.
Example
[LAMPTEST]
SW 'LAMPTEST_ON':
LAMP;
LEDOff
Use the LEDOff command to turn a light-emitting diode on a
control/display module off.
The LEDOff command only works on devices with the LED
device type. You are required to specify the object label.
Specifying a priority value is optional.
LEDOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
{Turn Damper Open LEDs Off when closed limit
switch is activated}
[DAMPER_LIMIT_LED_OFF]
MON DAMPERFB 'FAN<N:1-5>_DAMP_CLIMIT':
LEDOFF -LOW 'DMPR<N>_OPEN_LED';
MsgOff
Use the MsgOff command to stop broadcasting a voice message
over the selected audio channel. The MsgOff command contains
two parts. The first part of the command (MsgOff) identifies the
message and the second part (to) identifies the audio channel.
The MsgOff command only works on devices with the Msg
device type. You are required to specify the message label and
the channel label. Specifying an ASU label or priority value is
optional.
MsgOff priority 'msg_label' from 'asu_label' to
'channel_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'msg_label' Specifies the label of the voice message to stop
broadcasting.
'asu_label' Specifies the label of the audio source unit
providing the voice message.
'channel_label' Specifies the label of the audio channel
broadcasting the voice message.
Note: Only use the from 'asu_label' parameter with systems
containing multiple audio source units.
Example
[EVAC_MSG_OFF_TEST]
SW 'FLOOR1_TEST':
MSGOFF 'TEST_MESSAGE' FROM '3-ASU1' TO
'CH_EVAC_01_08';
MsgOn
Use the MsgOn command to start broadcasting a voice message
over a selected audio channel. The MsgOn command contains
two parts. The first part of the command (MsgOn) identifies the
message and the second part (to) identifies the audio channel.
The MsgOn command only works on devices with the Msg
device type. You are required to specify the message label and
the channel label. Specifying an ASU label or priority value is
optional.
MsgOn priority 'msg_label' from 'asu_label' to
'channel_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'msg_label' Specifies the label of the voice message to start
broadcasting.
'asu_label' Specifies the label of the audio source unit
providing the voice message.
'channel_label' Specifies the label of the audio channel
broadcasting the voice message.
Notes
The MsgOn command must be placed after the AmpOn
command in a rule and selected to the same audio channel as the
amplifier.
Only use the from 'asu_label' parameter with systems containing
multiple audio source units.
Example
{Send test message to Floor 1 on EVAC channel
from panel control switch}
[EVAC_MSG_ON_TEST]
SW 'FLOOR1_TEST':
AMPON 'LEVEL3_AMP' TO 'CH_EVAC_01_08',
MSGON 'TEST_MESSAGE' FROM '3-ASU1' TO
'CH_EVAC_01_08';
NCClose
Use the NCClose command to turn on an output circuit or relay
that connects to the control mechanism used to close a damper.
The NCClose command only works on devices with the
DamperControl device type. You are required to specify the
object label. Specifying a priority value is optional.
NCClose priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit on (active) the control mechanism
closes the damper.
Example
{Close dampers from control/display module
switch}
[DAMPER_CLOSE_SWITCHES]
SW 'LVL<N:1-10>_DMPR_CLOSE':
NCCLOSE -LOW 'DMPR_RELAY_LVL<N>';
NCFanOff
Use the NCFanOff command to turn on an output circuit or relay
that connects to the control mechanism used to turn off a fan.
The NCFanOff command only works on devices with the
FanControl device type. You are required to specify the object
label. Specifying a priority value is optional.
NCFanOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit on (active) the control mechanism
turns off the fan.
Example
[SUPPLY_FAN_CNTRL]
SW 'SUPPLY_FAN<N:1,2>_OFF':
NCFANOFF -LOW 'SUPPLY_FAN<N>';
NCFanOn
Use the NCFanOn command to turn off an output circuit or relay
that connects to the control mechanism used to turn on a fan.
Example
[SUPPLY_FAN_CNTRL]
SW 'SUPPLY_FAN<N:1,2>_ON':
NCFANON -LOW 'SUPPLY_FAN<N>';
NCHoldDoor (NCHOLD)
Use the NCHoldDoor command to turn off an output circuit or
relay that connects to the control mechanism used to hold a
door.
The NCHoldDoor command only works with devices with the
DoorControl device type. You are required to specify the object
label. Specifying a priority value is optional.
NCHoldDoor priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit off (nonactive) the control
mechanism holds the door.
Example
{Energize magnetic door holders from panel
control switch}
[MANUAL_DOOR_CNTRL]
SW 'PANEL_1_SW1':
NCHOLD -HIGH 'DOORCONTROL_*';
NCOpen
Use the NCOpen command to turn off an output circuit or relay
that connects to the control mechanism used to open a damper.
The NCOpen command only works on devices with the
DamperControl device type. You are required to specify the
object label. Specifying a priority value is optional.
NCOpen priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit off (nonactive) the control
mechanism opens the damper.
Example
{Open dampers from control/display module
switch}
[MANUAL_DAMPER_CNTRL]
SW 'PANEL_1_SW1':
NCOPEN -HIGH 'DAMPERCONTROL_*';
NCReleaseDoor (NCRELEASE)
Use the NCReleaseDoor command to turn on an output circuit or
relay that connects to the control mechanism used to release a
door.
The NCReleaseDoor command only works on devices with the
DoorControl device type. You are required to specify the object
label. Specifying a priority value is optional.
NCReleaseDoor priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit on (active) the control mechanism
releases the door.
Example
{Release door locks from panel control switch}
[DOOR_RELEASE_CNTRL]
SW 'PANEL_1_SW1':
NCRELEASE -HIGH 'DOORCONTROL_*';
NSCommonAlarmOff (NSCAOFF)
Use the NSCommonAlarmOff command to turn off a
nonsupervised output relay that a panel automatically activates
when the FirstAlarm event occurs.
The NSCommonAlarmOff command only works on devices
with the NSCommonAlarmOutput device type. You are required
to specify the object label. Specifying a priority value is
optional.
NSCommonAlarmOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Notes
Active nonsupervised common alarm outputs can not be turned
off using the NSCommonAlarmOff command.
The NSCommonAlarmOff command does not affect the
operation of the Form C common alarm relay on the 3-CPU1
module.
Example
[NSCOMMON_ALARM_OFF_SWITCHES]
SW 'NSCOM_ALARM_OFF_LVL<N:1-10>':
NSCAOFF -LOW 'LVL<N>_NSCOM_ALARM_CKT*';
NSCommonAlarmOn (NSCAON)
Use the NSCommonAlarmOn command to turn on a
nonsupervised output relay that a panel automatically activates
when the FirstAlarm event occurs.
The NSCommonAlarmOn command only works on devices with
the NSCommonAlarmOutput device type. You are required to
specify the object label. Specifying a priority value is optional.
NSCommonAlarmOn priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
[NSCOMMON_ALARM_ON_SWITCHES]
SW 'NSCOM_ALARM_ON_LVL<N:1-10>':
NSCAON -LOW 'LVL<N>_NSCOM_ALARM_CKT*';
NSCommonMonitorOff (NSCMOFF)
Use the NSCommonMonitorOff command to turn off a
nonsupervised output relay that a panel automatically activates
when the FirstMonitor event occurs.
The NSCommonMonitorOff command only works on devices
with the NSCommonMonitorOutput device type. You are
required to specify the object label. Specifying a priority value is
optional.
NSCommonMonitorOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Notes
Active nonsupervised common monitor outputs can not be
turned off using the NSCommonMonitorOff command.
You can not use any device to turn off a nonsupervised common
monitor output that upon activation produces a monitor event.
For example, you can not use a control/display module switch.
Example
[NSCOMMON_MON_OFF_RESPONSE]
ALARM GENALARM:
NSCMOFF -LOW 'NSCOM_MON_CKT_LVL*';
NSCommonMonitorOn (NSCMON)
Use the NSCommonMonitorOn command to turn on a
nonsupervised output relay that a panel automatically activates
when the FirstMonitor event occurs.
The NSCommonMonitorOn command only works on devices
with the NSCommonMonitorOutput device type. You are
required to specify the object label. Specifying a priority value is
optional.
NSCommonMonitorOn priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
[COMMON_MON_ON_RESPONSE]
ALARM GENALARM:
CMON -LOW 'COM_MON_CKT_LVL*';
NSCommonSupervisoryOff (NSCSOFF)
Use the NSCommonSupervisoryOff command to turn off a
nonsupervised output relay that a panel automatically activates
when the FirstSupervisory event occurs.
The NSCommonSupervisoryOff command only works on
devices with the NSCommonSupervisoryOutput device type.
You are required to specify the object label. Specifying a
priority value is optional.
NSCommonSupervisoryOff priority 'object_label';
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Notes
Active nonsupervised common supervisory outputs can not be
turned off using the NSCommonSupervisoryOff command.
The NSCommonSupervisoryOff command does not affect the
operation of the Form C common supervisory relay on the
3-CPU1 module.
Example
[NSCOMMON_SUP_OFF_SWITCHES]
SW 'NSCOM_SUP_OFF_LVL<N:1-10>':
NSCSOFF -LOW 'LVL<N>_NSCOM_SUP_CKT*';
NSCommonSupervisoryOn (NSCSON)
Use the NSCommonSupervisoryOn command to turn on a
nonsupervised output relay that a panel automatically activates
when the FirstSupervisory event occurs.
The NSCommonSupervisoryOn command only works on
devices with the NSCommonSupervisoryOutput device type.
You are required to specify the object label. Specifying a
priority value is optional.
NSCommonSupervisoryOn priority 'object_label';
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
[NSCOMMON_SUP_ON_SWITCHES]
SW 'NSCOM_SUP_ON_LVL<N:1-10>':
NSCSON -LOW 'LVL<N>_NSCOM_SUP_CKT*';
NSCommonTroubleOff (NSCTOFF)
Use the NSCommonTroubleOff command to turn off a
nonsupervised output relay that a panel automatically activates
when the FirstTrouble event occurs.
The NSCommonTroubleOff command only works on devices
with the NSCommonTroubleOutput device type. You are
required to specify the object label. Specifying a priority value is
optional.
NSCommonTroubleOff priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Notes
Active nonsupervised common trouble outputs can not be turned
off using the NSCommonTroubleOff command.
The NSCommonTroubleOff command does not affect the
operation of the Form C common trouble relay on the 3-CPU1
module.
Example
[NSCOMMON_TRB_OFF_SWITCHES]
SW 'NSCOM_TRB_OFF_LVL<N:1-10>':
NSCTOFF -LOW 'LVL<N>_NSCOM_TRB_CKT*';
NSCommonTroubleOn (NSCTON)
Use the NSCommonTroubleOn command to turn on a
nonsupervised output relay that a panel automatically activates
when the FirstTrouble event occurs.
The NSCommonTroubleOn command only works on devices
with the NSCommonTroubleOutput device type. You are
required to specify the object label. Specifying a priority value is
optional.
NSCommonTroubleOn priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
[NSCOMMON_TRB_ON_SWITCHES]
SW 'NSCOM_TRB_ON_LVL<N:1-10>':
NSCTON -LOW 'LVL<N>_NSCOM_TRB_CKT*';
Off
Use the Off command to turn a system hardware component,
circuit, or logic group off.
The Off command requires that you specify a device type or an
object label, or both. Specifying a priority value is optional.
Off priority device_type 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
device_type Specifies the device type of the device
responding to the command. Valid device types
are:
Audible, CheckIn, CommonAlarmOutput,
CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl,
DoorControl, FanControl, Firephone, LED,
NonsupervisedOutput, NSCommonAlarmOutput,
NSCommonMonitorOutput,
NSCommonSupervisoryOutput,
NSCommonTroubleOutput, ServiceGroup,
SupervisedOutput, Visible
'object_label' Specifies the label of the output device
responding to the command.
Example
{Turn off all horns in the building from
control/display module}
[REMOTE_HORN_OFF]
SW 'PANEL_1_SW1':
OFF -LOW AUD 'HORN*';
OffGuard
Use the OffGuard command to cancel a specific guard patrol
tour. The OffGuard command contains two parts. The first part
of the command (OffGuard) identifies the GuardPatrol group
and the second part (Route) identifies the route number.
The OffGuard command only works on devices with the
GuardPatrol device type. You are required to specify the guard
label and the route identifier number.
OffGuard 'guard_label' Route route_id
Parameter Description
'guard_label' Specifies the label of the Guard Patrol group
responding to the command.
route_id Specifies the route number of the guard patrol
tour.
Example
{Deactivate individual guard patrol route from
remote panel toggle switch}
[GUARDPATROL_ROUTE_OFF]
SW 'PANEL_2_SW1':
OFFGUARD 'GUARD_PATROL_GROUP1' ROUTE 1;
On
Use the On command to turn a system hardware component,
circuit, or logic group on.
The On command requires that you specify a device type or an
object label, or both. Specifying a priority value is optional.
On priority device_type 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
device_type Specifies the device type of the device
responding to the command. Valid device types
are:
Audible, CheckIn, CommonAlarmOutput,
CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl,
DoorControl, FanControl, Firephone, LED,
NonsupervisedOutput, NSCommonAlarmOutput,
NSCommonMonitorOutput,
NSCommonSupervisoryOutput,
NSCommonTroubleOutput, ServiceGroup,
SupervisedOutput, Visible
'object_label' Specifies the label of the output device
responding to the command.
Example
{Turn on all horns in the building from
control/display module}
[REMOTE_HORN_ON]
SW 'PANEL_1_SW2':
ON -HIGH AUD 'HORN*';
OnGuard
Use the OnGuard command to start a specific guard patrol tour.
The OnGuard command contains two parts. The first part of the
command (OnGuard) identifies the GuardPatrol group and the
second part (Route) identifies the route number.
The OnGuard command only works on devices with the
GuardPatrol device type. You are required to specify the guard
label and the route identifier number.
OnGuard 'guard_label' Route route_id
Parameter Description
'guard_label' Specifies the label of the Guard Patrol group
responding to the command.
route_id Specifies the route number of the guard patrol
tour.
Example
{Activate guard patrol route from
control/display module switch }
[Group1GuardPatrolRoutesOn]
SW 'Panel_1_SW1':
OnGuard 'GUARD_PATROL_Group1' Route 1;
Open
Use the Open command to turn on an output circuit or relay that
connects to the control mechanism used to open a damper.
The Open command only works on devices with the
DamperControl device type. You are required to specify the
object label. Specifying a priority value is optional.
Open priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit on (active) the control mechanism
opens the damper.
Example
{Open dampers from control/display module
switch}
[MANUAL_DAMPER_CNTRL]
SW 'PANEL_1_SW1':
OPEN -HIGH 'DAMPERCONTROL_*';
ReleaseDoor (RELEASE)
Use the ReleaseDoor command to turn off an output circuit or
relay that connects to the control mechanism used to release a
door.
The ReleaseDoor command only works on devices with the
DoorControl device type. You are required to specify the object
label. Specifying a priority value is optional.
ReleaseDoor priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Note: The output circuit must be wired to the control mechanism
so that with the output circuit off (nonactive) the control
mechanism releases the door.
Example
{Release door locks from panel control switch}
[DOOR_RELEASE_CNTRL]
SW 'PANEL_1_SW1':
RELEASE -HIGH 'DOORCONTROL_*';
RemoteAltSensitivityOff (RASOFF)
Use the RemoteAltSensitivityOff command to load the primary
sensitivity and alarm verification settings into every smoke
detector on selected panels or on a group of panels. Typically,
the primary settings are used during normal business hours when
the protected premises is occupied.
The RemoteAltSensitivityOff command only requires that you
specify a cabinet label or a routing label.
RemoteAltSensitivityOff 'cabinet_label' ;
or
RemoteAltSensitivityOff 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Note: Wildcards may be used in the cabinet label but not in the
routing label.
Example
{Automatically switch smoke detectors only on
Cab2 to primary sensitivity level during regular
work hours}
[PRIMARY_SENSITIVITY_CAB2]
TIME 'MON-FRI_REGULAR_HOURS':
RASOFF 'CAB_2';
RemoteAltSensitivityOn (RASON)
Use the RemoteAltSensitivityOn command to load the alternate
sensitivity and alarm verification settings into every smoke
detector on selected panels or on a group of panels. Typically,
the alternate settings are used during normal business hours
when the protected premises is unoccupied.
The RemoteAltSensitivityOn command only requires that you
specify a cabinet label or a routing label.
RemoteAltSensitivityOn 'cabinet_label' ;
or
RemoteAltSensitivityOn 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Note: Wildcards may be used in the cabinet label but not in the
routing label.
Example
{Automatically switch smoke detectors to
alternate sensitivity level only on Cab2 during
non-regular work hours}
[ALTERNATE_SENSITIVITY_CAB2]
TIME 'MON-FRI_AFTER_HOURS':
RASON 'CAB_2';
Reset
Use the Reset command to activate a panel's Reset function from
a control/display module switch. By programming a
control/display module switch to execute the Reset command, an
operator can reset the system from panels that do not contain a
3-LCD module.
The Reset command only requires that you specify a cabinet
label or a routing label.
Reset 'cabinet_label' ;
or
Reset 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Notes
You must configure the switch used to execute the Reset
command as a momentary switch.
Wildcards may be used in the cabinet label but not in the routing
label.
Example
[REMOTE_RESET]
SW 'REM_RESET_SWITCH':
RESET 'All_Cabinets';
SlowBlink (SLOW)
Use the SlowBlink command to turn a light-emitting diode on a
control/display module on and off at a slow interval.
The SlowBlink command only works on devices with the LED
device type. You are required to specify the object label.
Specifying a priority value is optional.
SlowBlink priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
{Flash LED on control/display module to indicate
FirePhone device type is activated}
[ANN_RESET_2ND_PHASE]
R2:
SLOW -LOW 'R2_LED';
Steady
Use the Steady command to turn a light-emitting diode on a
control/display module LED on and have it remain on.
The Steady command only works on devices with the LED
device type. You are required to specify the object label.
Specifying a priority value is optional.
Steady priority 'object_label' ;
Parameter Description
priority Specifies the order of importance this command
has over other commands affecting the same
output device. Valid priority levels are:
-low, -high, -latch, -set
'object_label' Specifies the label of the output device
responding to the command.
Example
{Light LED on control/display module to indicate
Firephone device type is activated}
[PHONE_CONNECT_REQ]
CALLIN:
STEADY -LOW 'DISPLAY_1_LED_1';
TroubleSilence (TS)
Use the TroubleSilence command to activate a panel's Trouble
Silence function from a control/display module switch. By
programming a control/display module switch to execute the
TroubleSilence command, an operator can turn off a panel's
trouble buzzer from panels that do not contain a 3-LCD module.
The TroubleSilence command only requires that you specify a
cabinet label or a routing label.
TroubleSilence 'cabinet_label' ;
or
TroubleSilence 'routing_label' ;
Parameter Description
'cabinet_label' Specifies the label of the panel responding to the
command.
'routing_label' Specifies the label of the network routing group
responding to the command.
Note: You must configure the switch used to execute the
TroubleSilence command as a momentary switch.
Example
[REMOTE_TROUBLE_SILENCE]
SW 'B1_C1_REM_TRBL_SIL':
TS 'ALL_CABINETS';
Summary
This appendix provides a quick reference to the information
contained in chapters 2 and 3.
Content
Table A-1: Fire alarm system input events A.2
Table A-2: Fire alarm system commands A.4
Table A-3: Fire alarm system device types A.7
AllCall device type Classification used for the system pseudo point that changes to
the active state when an operator presses the All Call or All Call
Minus switch on the 3-ASU.
AllCall event Event produced when an operator presses the All Call or All
Call Minus switch on the 3-ASU.
AlternateLanguage Command used to change the language setting on a panel.
command Abbreviation: ALTL.
AlternateMsgOff command Command used to toggle the event message routing from the
alternate setting to the primary setting. Abbreviation:
ALTMOFF.
AlternateMsgOn command Command used to toggle the event message routing from the
primary setting to the alternate setting. Abbreviation: ALTMON.
AlternateSensitivityOff Command used to load the primary alarm sensitivity and alarm
command verification settings into every smoke detector in the system.
Abbreviation: ALTSOFF.
AlternateSensitivityOn Command used to load the alternate alarm sensitivity and
command alarm verification settings into every smoke detector in the
system. Abbreviation: ALTSON.
Amp device type Classification used for a zoned amplifier module.
AmpOff command Command used to turn off an amplifier's audio output and
removes the connected audio channel from its input.
AmpOn command Command used to turn on an amplifier's audio output and
connect an audio channel to its input.
And device type Classification used for an And logic group.
And group A group of devices in the database combined to provide a
unique response based on a number of device activations.
application code Program file that controls the way a rail module performs fire-
related functions.
Audible device type Classification used for a notification appliance circuit that
produces a signal able to be perceived by the sense of hearing.
Abbreviation: AUD.
bootloader code Program file that controls the way a rail module performs
system-level functions like startup tests, downloading, and rail
bus communications.
bus A set of conductive paths used for transferring data between
electronic components.
cabinet number 1. Index used to classify a cabinet when it is added to the
database. 2. Panel number.
CallIn event Event produced when someone plugs a handset into a
firefighter's telephone jack. Abbreviation: CI.
CardDBIncompat device Classification used for a pseudo point that the system changes
type to the active state when the CPU module's database contains
different information than a rail module's database.
Abbreviation: DBIN.
CheckIn device type Classification used for a Check-In logic group. Abbreviation:
CIG.
Close command Command used to turn off an output circuit or relay that
connects to the control mechanism used to close a damper.
COM port I/O port on desktop and laptop computers used for connecting
RS-232 serial devices. In most cases, COM1 (I/O range
03F8H-03FFH, IRQ4) is used to connect a mouse while COM2
(I/O range 02F8H-02FFH, IRQ3) is used to connect a modem
or other serial device.
CommFailure device type Classification used for a pseudo point that the system changes
to the active state when a CPU module can not communicate
with other CPU modules on the network. Abbreviation: CFAIL.
CommonAlarmOff command Command used to turn off a supervised notification signal
output circuit that a panel automatically activates when the
FirstAlarm event occurs. Abbreviation: CAOFF.
CommonAlarmOn command Command used to turn on a supervised notification signal
output circuit that a panel automatically activates when the
FirstAlarm event occurs. Abbreviation: CAON.
CommonAlarmOutput device Classification used for a supervised notification signal output
type circuit that a panel automatically activates when the FirstAlarm
event occurs. Abbreviation: CAO.
CommonMonitorOff Command used to turn off a supervised notification signal
command output circuit that a panel automatically activates when the
FirstMonitor event occurs. Abbreviation: CMOFF.
CommonMonitorOn Command used to turn on a supervised notification signal
command output circuit that a panel automatically activates when the
FirstMonitor event occurs. Abbreviation: CMON.
CommonMonitorOutput Classification used for a supervised notification signal output
device type circuit that a panel automatically activates when the
FirstMonitor event occurs. Abbreviation: CMO.
CommonSupervisoryOff Command used to turn off a supervised notification signal
command output circuit that a panel automatically activates when the
FirstSupervisory event occurs. Abbreviation: CSOFF.
CommonSupervisoryOn Command used to turn on a supervised notification signal
command output circuit that a panel automatically activates when the
FirstSupervisory event occurs. Abbreviation: CSON.
CommonSupervisoryOutput Classification used for a supervised notification signal output
device type circuit that a panel automatically activates when the
FirstSupervisory event occurs. Abbreviation: CSO.
DamperControl device type Classification used for an output circuit or relay that connects to
a control mechanism used for opening or closing a damper.
The output circuit may be supervised or nonsupervised
depending on the type and placement of the module used for
the circuit. Abbreviation: DAMP.
DamperFeedback device Classification used for a non-latching input circuit that monitors
type the operation of a damper control circuit. Abbreviation:
DAMPFB.
FirstDisable event Event produced when the first point on a panel or any panel in
the same network routing group changes to the disable state.
Abbreviation: FD.
FirstMonitor device type Classification used for the system pseudo point that changes to
the active state when the first point on a panel or any panel in
the same network routing group changes to the monitor state.
FirstMonitor event Event produced when the first point on a panel or any panel in
the same network routing group changes to the monitor state.
Abbreviation: FM.
FirstSupervisory device type Classification used for the system pseudo point that changes to
the active state when the first point on a panel or any panel in
the same network routing group changes to the supervisory
state.
FirstSupervisory event Event produced when the first point on a panel or any panel in
the same network routing group changes to the supervisory
state. Abbreviation: FS.
FirstTrouble device type Classification used for the system pseudo point that changes to
the active state when the first point on a panel or any panel in
the same network routing group changes to the trouble state.
FirstTrouble event Event produced when the first point on a panel or any panel in
the same network routing group changes to the trouble state.
Abbreviation: FT.
GAInhibit command Command used to stop a panel's two-stage timer and prevent
the panel from sounding a general alarm. Abbreviation: GAIN.
Gatevalve device type Classification used for an active-latching input circuit that
supervises a gate valve to determine when the valve is not fully
open. Abbreviation: GATE.
GenAlarm device type Classification used for an alarm input circuit that connects to
normally-open dry contact initiating devices, non-retarded
waterflow alarm switches, or to devices used in applications
that must differentiate between shorted and alarm conditions.
Abbreviation: GENA.
GenSmoke Artificial device type that replaces using the Smoke and
SmokeVfy device types in a rule. Abbreviation: GENS.
GroundFault device type Classification used for the pseudo point that a rail module
changes to the active state when the rail module detects a
ground fault. Abbreviation: GNDF.
GroundFault event Event produced when a rail module detects a ground fault on its
field wiring. Abbreviation: GNDF.
Guard device type Classification used for an input device that connects to a guard
patrol tour station.
GuardPatrol device type Classification used for a Guard Patrol logic group. Abbreviation:
GPG.
GuardPatrol event Event produced when patrol guard fails to activate a patrol tour
station at the proper time. Abbreviation: GPG.
Heat device type Classification used for input circuit that changes to the alarm
state when it detects the heat generated by a fire.
HoldDoor command Command used to turn on an output circuit or relay that
connects to the control mechanism used to hold a door.
Abbreviation: HOLD.
label Descriptive word or phrase used to identify a specific system
component in the database.
LampTest command Command used to activate the lamp test function from a
control/display module switch. Abbreviation: LAMP.
LED 1. Semiconductor device that converts electrical energy into
light. 2. Acronym for a light-emitting diode.
LED device type Classification used for a light-emitting diode on a control/display
module.
LEDOff command Command used to turn a control/display module LED off.
local Close at hand or restricted to a particular area.
local panel A panel that can be operated directly rather than over the
network.
LocalAlarm device type Classification used for a pseudo point that a loop controller
changes to the active state when an unprogrammed device
goes into alarm. Abbreviation: LALM.
LocalAlarm event Event produced when a rail module's LocalAlarm pseudo point
goes active. Abbreviation: LALM.
LocalMonitor device type Classification used for a pseudo point that monitors the activity
of rail module functions. Abbreviation: LMON.
LocalMonitor event Event produced when a rail module's LocalMonitor pseudo
point goes active. Abbreviation: LMON.
LocalRelay device type Classification used for a pseudo point that monitors a channel
selection relay on a zoned amplifier module. Abbreviation:
LRLAY.
LocalTrouble device type Classification used for a pseudo point that monitors fault
conditions on a rail module that could compromise the
operation of the rail module. Abbreviation: LTRB.
LocalTrouble event Event produced when a rail module's LocalTrouble pseudo
point goes active. Abbreviation: LTRB.
logic group A database object used to provide a single response for a set of
devices
LoopControllerResetExt Classification used for the system pseudo point changes to the
device type active state when a loop controller stays in the reset mode
longer than normally expected. Abbreviation: LCREXT.
Matrix device type Classification used for a Matrix logic group.
mechanism 1. A machine or mechanical appliance. 2. The arrangement of
connected parts in a machine.
Monitor device type Classification used for a non-latching input circuit that monitors
switch closures. Abbreviation: MON.
Monitor event Event produced when any point on a panel or any panel in the
same network routing group changes to the monitor state.
Abbreviation: MON.
MSG device type Classification used for the recorded audio messages stored in
the 3-ASU.
MsgOff command Command used to stop broadcasting a voice message over the
selected audio channel.
MsgOn command Command used to start broadcasting a voice message over a
selected audio channel.
NCClose command Command used to turn on an output circuit or relay that
connects to the control mechanism used to close a damper.
NCFanOff command Command used to turn on an output circuit or relay that
connects to the control mechanism used to turn off a fan.
NCFanOn command Command used to turn off an output circuit or relay that
connects to the control mechanism used to turn on a fan.
NCHoldDoor command Command used to turn off an output circuit or relay that
connects to the control mechanism used to hold a door.
Abbreviation: NCHOLD.
NCOpen command Command used to turn off an output circuit or relay that
connects to the control mechanism used to open a damper.
NCReleaseDoor command Command used to turn on an output circuit or relay that
connects to the control mechanism used to release a door.
Abbreviation: NCRELEASE.
NonsupervisedOutput Classification used for a notification appliance circuit that does
device type not monitor its output for open or shorted wiring. Abbreviation:
NSO.
nonactive Condition of a circuit when the circuit is turned off.
normal state Condition of a circuit when there are no alarms or troubles on
the system. May be active or nonactive.
notification appliance Fire alarm system component such as a bell, horn, speaker, or
light that provides audible or visible outputs. Audible notification
appliances produce a signal that can be heard while visibles
produce a signal that can be seen.
NSCommonAlarmOff Command used to turn off a nonsupervised output relay that a
command panel automatically activates when the FirstAlarm event occurs.
NSCommonAlarmOn Command used to turn on a nonsupervised output relay that a
command panel automatically activates when the FirstAlarm event occurs.
NSCommonAlarmOutput Classification used for a nonsupervised output relay that a
device type panel automatically activates when the FirstAlarm event occurs.
Abbreviation: NSCAO.
NSCommonMonitorOff Command used to turn off a nonsupervised output relay that a
command panel automatically activates when the FirstMonitor event
occurs.
R1 device type Classification used for the system pseudo point that changes to
the active state when the first phase of the 3-phase reset cycle
starts.
R1 event Event produced when the first phase of the 3-phase reset cycle
starts.
R2 device type Classification used for the system pseudo point that changes to
the active state when the second phase of the 3-phase reset
cycle starts.
R2 event Event produced when the second phase of the 3-phase reset
cycle starts.
R3 device type Classification used for the system pseudo point that changes to
the active state when the third phase of the 3-phase reset cycle
starts.
R3 event Event produced when the third phase of the 3-phase reset
cycle starts.
rail location Area in a cabinet enclosure used for mounting chassis rail
assemblies. Rail 1 refers to the location closest to the top of the
enclosure, Rail 2 the next lower, and Rail 3 the next lower after
that.
rail-slot position Physical connection where the module is installed in the cabinet
enclosure.
RebootFault device type Classification used for the pseudo point that the system
changes to the active state when a panel restarts unexpectedly.
Abbreviation: RBF.
RelayConfirmation event Event produced when a control relay indicates that its electrical
contacts have switched positions. Abbreviation: RLYCFG.
ReleaseDoor command Command used to turn off an output circuit or relay that
connects to the control mechanism used to release a door.
remote panel A panel that can be operated over the network rather than
directly. In a network, all panels that are not the local panel.
RemoteAltSensitivityOff Command used to load the primary sensitivity and alarm
command verification settings into every smoke detector on selected
panels or on a group of panels.
RemoteAltSensitivityOn Command used to load the alternate sensitivity and alarm
command verification settings into every smoke detector on selected
panels or on a group of panels.
Reset command Command used to clear a panel.
Reset device type Classification used for the system pseudo point that changes to
the active state when an operator presses a switch that
executes the Reset command.
Reset event Event produced when an operator presses a switch that
executes the Reset command.
StageOne device type Classification used for the first address (pre-alarm stage) of a
circuit that connects to a 2-stage pull station. Abbreviation:
STAGE1.
StageTwo device type Classification used for the second address (alarm stage) of a 2-
stage pull station. Abbreviation: STAGE2.
Startup device type Classification used for the system pseudo point that changes to
the active state when the panel is energized or an operator
initiates a Restart from the 3-LCD module.
Startup event Event produced when the panel is energized or an operator
initiates a Restart from the 3-LCD module. Abbreviation: STUP.
StationActivation event Event produced when a patrol guard activates a patrol tour
station. Abbreviation: STACT.
Steady command Command used to turn a control/display module LED on and
have it remain on.
SupervisedOutput device Classification used for a notification appliance signaling circuit
type that monitors its output for open or shorted wiring. Abbreviation:
SUP.
Supervisory device type Classification used for an input circuit used for supervising
switch closures. Abbreviation: SUP.
Supervisory event Event produced when any point on a panel or any panel in the
same network routing group changes to the supervisory state.
Abbreviation: SUP.
Switch device type Classification used for a control/display module switch.
Abbreviation: SW.
Switch event Event produced when an operator presses a control/display
module switch.
Tamper device type Classification used for an input circuit that supervises a secured
component of the sprinkler system to determine when someone
tries to gain access to it. Abbreviation: TAMP
TaskFailure device type Classification used for the pseudo point that the system
changes to the active state when a CPU module takes too long
to complete a task. Abbreviation: TFAIL.
Temperature device type Classification used for an input circuit that supervises the
temperature surrounding a component of the sprinkler system
to determine when freezing temperatures exist. Abbreviation:
TEMP.
Text device type Classification used for an Instruction Text logic group.
TimeControl device type Classification used for a time control. Abbreviation: TIME.
TimeControl event Event produced when a specific combination of days, dates,
and/or time of day occurs. Abbreviation: TIME.
Trouble event Event produced when any point on a panel or any panel in the
same network routing group changes to the trouble state.
TroubleSilence command Command used to activate the system Trouble Silence
response from a control/display module switch.
TroubleSilence device type Classification used for the pseudo point that the system
changes to the active state in order to produce the
TroubleSilence event. Abbreviation: TS.
TwoStageTimerActivation Event produced when a panel's two-stage alarm timer starts.
event Abbreviation: 2STAGEA.
TwoStageTimerActive device Classification used for the system pseudo point that changes to
type the active state when a panel's two-stage alarm timer starts.
Abbreviation: 2STAGEA.
TwoStageTimerExpiration Classification used for the system pseudo point that changes to
device type the active state when a panel's two-stage alarm timer expires.
Abbreviation: 2STAGETO.
TwoStageTimerExpiration Event produced when a panel's two-stage alarm timer expires.
event Abbreviation: 2STAGETO.
upload 1. The process of transferring a copy of a file from a remote
computer to a local computer over a network or modem. 2. To
transfer a copy of a file from a remote computer to a local
computer over a network or modem.
UserTrouble device type Classification used for the system pseudo point that changes to
the active state
Visible device type Classification used for a notification appliance circuit that
produces a signal able to be perceived by the sense of sight.
Abbreviation: VIS.
Waterflow device type Classification used for an input circuit that changes to the alarm
state when it detects water flowing through the fire protection
sprinkler system. Abbreviation: FLOW.
Zone device type Classification used for a Zone logic group.
1 C
12SW/12LED device type 3.21, 3.23 CallIn event 2.7
12SW/24LED device type 3.21, 3.23 CheckIn device type 3.21, 3.23, 3.48, 3.50
Check-In Group description 1.33
2 Check-In logic groups 1.28
Close command 3.11
24LED device type 3.21, 3.23 CommFailure device type 2.2, 2.37
CommonAlarmOff command 3.12
3 CommonAlarmOn command 3.13
CommonAlarmOutput device type 2.2,
3-AADC device type 3.21, 3.23 2.25, 2.28, 2.37, 3.21, 3.23, 3.48, 3.50
3-ASU device type 3.21, 3.23 CommonMonitorOff command 3.14
3-DSDC device type 3.21, 3.23 CommonMonitorOn command 3.15
3-FTCU device type 3.21, 3.23 CommonMonitorOutput device type 2.2,
3-IDC8/4 device type 3.21, 3.23 2.25, 2.28, 2.37, 3.21, 3.23, 3.48, 3.50
3-OPS device type 3.21, 3.23 CommonSupervisoryOff command 3.16
3SW/3LEDX6 device type 3.21, 3.23 CommonSupervisoryOn command 3.17
CommonSupervisoryOutput device type
A 2.2, 2.25, 2.28, 2.37, 3.21, 3.23, 3.48,
3.50
About the Systems Definition Utility 1.2
CommonTroubleOutput device type 2.28
Acknowledge event 2.2
Compiling the rules file 1.12
Alarm event 2.3
Alarm logic groups 1.28
AlarmSilence command 3.3 D
AlarmSilence event 2.4 DamperControl device type 2.2, 2.25, 2.28,
AlarmVerify event 2.5 2.37, 3.21, 3.23, 3.48, 3.50
AllCall event 2.6 DamperFeedback device type 2.2, 2.21,
AlternateLanguage command 3.4 2.28, 2.37, 3.21, 3.23
AlternateMsgOff command 3.5 Delay command 3.18
AlternateMsgOn command 3.6 DelayActivate command 3.19
AlternateSensitivityOff command 3.7 DelayRestore command 3.20
AlternateSensitivityOn command 3.8 Device types 1.7
Amp device type 3.21, 3.23 used with And groups 1.29
AmpOff command 3.9 used with Instruction Text groups 1.32
AmpOn command 3.10 used with Service groups 1.34
And device type 2.2, 2.3, 2.21, 2.34, 2.37, used with Zone groups 1.32
3.21, 3.23 Disable command 3.21
AND Group description 1.29 DoorControl device type 2.2, 2.25, 2.28,
Audible device type 2.2, 2.25, 2.28, 2.37, 2.37, 3.21, 3.23, 3.48, 3.50
3.21, 3.23, 3.48, 3.50 DoorFeedback device type 2.2, 2.21, 2.28,
2.37, 3.21, 3.23
B Drill command 3.22
Drill event 2.8
Bar code readers 1.3
E I
Emergency device type 2.2, 2.9, 2.28, 2.37, Input statement syntax 1.5
3.21, 3.23 Input vs Output matrix chart 1.18
Emergency event 2.9 Instruction Text Group description 1.32
Enable command 3.23 Interleaved 2 of 5 1.3
EST3 library vi
Evacuation command 3.24 L
Evacuation event 2.10
Event 1.7 Label modifiers
ExtDBIncompatibility device type 2.2, 2.37 used in numberless floors 1.15
used in vertical applications 1.16
F used to describe device type 1.14
used to describe function 1.14
Failsafe device type 2.2, 2.3, 2.37 used to describe location 1.14
FanControl device type 2.2, 2.25, 2.28, using as message 1.17
2.37, 3.21, 3.23, 3.48, 3.50 using numbers to make unique 1.17
FanFeedback device type 2.2, 2.21, 2.28, Labeling plan
2.37, 3.21, 3.23 developing 1.13
FanOff command 3.25 important considerations 1.13
FanOn command 3.26 Labels
FastBlink command 3.27 characteristics of 1.8
FCC warning iv formatting 1.13
Firephone device type 2.2, 2.7, 2.25, 2.28, making descriptive 1.14
2.37, 3.21, 3.23, 3.48, 3.50 using as the message 1.17
FirstAlarm event 2.11 using common modifiers 1.15
FirstDisable event 2.12 using numbers in 1.17
FirstMonitor event 2.13 LampTest command 3.30
FirstSupervisory event 2.14 Latch priority description 1.22
FirstTrouble event 2.15 LED device type 3.21, 3.23, 3.48, 3.50
LEDOff command 3.31
G Limitation of liability iv
LocalAlarm device type 2.2, 2.18, 3.21,
GAInhibit command 3.28 3.23
Gatevalve device type 2.2, 2.28, 2.31, 2.34, LocalAlarm event 2.18
2.37, 3.21, 3.23 LocalMonitor device type 2.2, 2.19, 3.21,
GenAlarm device type 2.2, 2.3, 2.28, 2.37, 3.23
3.21, 3.23 LocalMonitor event 2.19
GenSmoke device type 2.2, 2.3, 2.5, 2.28, LocalRelay device type 2.2, 2.25, 3.21,
2.37, 3.21, 3.23 3.23
GroundFault device type 2.2, 2.16 LocalTrouble device type 2.2, 2.20, 3.21,
GroundFault event 2.16 3.23
Guard device type 2.2, 2.28, 2.33, 2.37, LocalTrouble event 2.20
3.21, 3.23 Logic group parameters 1.28
Guard Patrol Group description 1.33 Logic group types 1.28
Guard Patrol logic groups 1.28 LoopControllerResetExt device type 2.2,
GuardPatrol device type 2.2, 2.17, 3.21, 2.37
3.23
GuardPatrol event 2.17 M
H Mathematical operators 1.26
Matrix device type 2.2, 2.3, 2.21, 2.34,
Heat device type 2.2, 2.3, 2.28, 2.37, 3.21, 2.37, 3.21, 3.23
3.23 Matrix group
HoldDoor command 3.29 activation number setting 1.31
radius setting 1.31
T V
Tamper device type 2.2, 2.28, 2.31, 2.34, Visible device type 2.2, 2.25, 2.28, 2.37,
2.37, 3.21, 3.23 3.21, 3.23, 3.48, 3.50
TaskFailure device type 2.2, 2.37
Temperature device type 2.2, 2.28, 2.31, W
2.34, 2.37, 3.21, 3.23
Text device type 3.21, 3.23 Waterflow device type 2.2, 2.3, 2.28, 2.37,
TimeControl device type 2.36, 3.21, 3.23 3.21, 3.23
TimeControl event 2.36 Wildcards 1.10, 1.25
Trouble event 2.37
Trouble logic groups 1.28 Z
TroubleSilence command 3.59 Zone device type 2.2, 2.3, 2.37, 3.21, 3.23
TwoStageTimerActivation event 2.38 Zone Group description 1.32
TwoStageTimerActive device type 2.2
TwoStageTimerExpiration device type 2.2
TwoStageTimerExpiration event 2.39