Pondasi Mechanical Sampler: A. Data Fondasi Foot Plat

The document discusses the design of a rectangular foundation including calculations for soil bearing capacity, stresses on the soil, and shear forces on the foundation. It provides soil data, foundation dimensions, material properties, and design loads. Equations from Terzaghi, Meyerhof and other methods are used to calculate soil bearing capacity. Shear checks are performed in the x and y directions.

Uploaded by

mustika05
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
134 views10 pages

Pondasi Mechanical Sampler: A. Data Fondasi Foot Plat

The document discusses the design of a rectangular foundation including calculations for soil bearing capacity, stresses on the soil, and shear forces on the foundation. It provides soil data, foundation dimensions, material properties, and design loads. Equations from Terzaghi, Meyerhof and other methods are used to calculate soil bearing capacity. Shear checks are performed in the x and y directions.

Uploaded by

mustika05
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 10

PONDASI MECHANICAL SAMPLER

BENTUK EMPAT PERSEGI PANJANG

A. DATA FONDASI FOOT PLAT

DATA TANAH
Kedalaman fondasi, Df = 1.00 m
Berat volume tanah, g= 17.60 kN/m3
Sudut gesek dalam, f= 34.00
Kohesi, c= 0.00 kPa
Tahanan konus rata-rata (hasil pengujian sondir), ( assumption ) qc = 95.00 kg/cm2
DIMENSI FONDASI
Lebar fondasi arah x, Bx = 3.00 m
Lebar fondasi arah y, By = 2.00 m
Tebal fondasi, h= 0.45 m
Lebar kolom arah x, bx = 0.40 m
Lebar kolom arah y, by = 0.40 m
Posisi kolom (dalam = 40, tepi = 30, sudut = 20) as = 40
BAHAN KONSTRUKSI
Kuat tekan beton, f c' = 30.0 MPa
Kuat leleh baja tulangan, fy = 390 MPa
Berat beton bertulang, gc = 24 kN/m3
BEBAN RENCANA FONDASI
Gaya aksial akibat beban terfaktor, Pu = 50.000 kN
Momen arah x akibat beban terfaktor, Mux = 15.000 kNm
Momen arah y akibat beban terfaktor, Muy = 13.000 kNm

B. KAPASITAS DUKUNG TANAH ( ASSUMSI )

1. MENURUT TERZAGHI DAN PECK (1943)

Kapasitas dukung ultimit tanah menurut Terzaghi dan Peck (1943) :


qu = c * Nc * (1 + 0.3 * B / L) + Df * g * Nq + 0.5 * B * Ng * (1 - 0.2 * B / L)

c = kohesi tanah (kN/m2) c= 0.00


Df = Kedalaman fondasi (m) Df = 1.00 m
g = berat volume tanah (kN/m3) g= 17.60 kN/m3
B = lebar fondasi (m) B = By = 2.00 m
L = panjang fondasi (m) L = By = 3.00 m
Sudut gesek dalam, f= 34.00
f = f / 180 * p = 0.59341195 rad
a = e(3*p / 4 - f/2)*tan f = 4.01140898
Kpg = 3 * tan2 [ 45 + 1/2*( f + 33) ] = 72.4763059
Faktor kapasitas dukung tanah menurut Terzaghi :
Nc = 1/ tan f * [ a2 / (2 * cos2 (45 + f/2) - 1 ] = 52.637
Nq = a2 / [ (2 * cos2 (45 + f/2) ] = Nc * tan f + 1 = 36.504
Ng = 1/2 * tan f * [ Kpg / cos2 f - 1 ] = 35.226
Kapasitas dukung ultimit tanah menurut Terzaghi :
qu = c*Nc*(1+0.3*B/L) + Df*g*Nq + 0.5*B*Ng*(1-0.2*B/L) = 673.01 kN/m2
Kapasitas dukung tanah, qa = q u / 3 = 224.34 kN/m2

2. MENURUT MEYERHOF (1956)


Kapasitas dukung tanah menurut Meyerhof (1956) :
qa = qc / 33 * [ ( B + 0.3 ) / B ]2 * Kd ( dalam kg/cm2)
dengan, Kd = 1 + 0.33 * Df / B harus 1.33

qc = tahanan konus rata-rata hasil sondir pada dasar fondasi ( kg/cm2 )


B = lebar fondasi (m) B = By = 2.00 m
Df = Kedalaman fondasi (m) Df = 1.00 m
Kd = 1 + 0.33 * Df / B = 1.165 < 1.33
diambil, Kd = 1.165
Tahanan konus rata-rata hasil sondir pada dasar fondasi, qc = 95.00 kg/cm2
qa = qc / 33 * [ ( B + 0.3 ) / B ]2 * Kd = 4.435 kg/cm2
Kapasitas dukung ijin tanah, qa = 443.54 kN/m2

3. KAPASITAS DUKUNG TANAH YANG DIPAKAI

Kapasitas dukung tanah menurut Terzaghi dan Peck : qa = 224.34 kN/m2


Kapasitas dukung tanah tanah menurut Meyerhof : qa = 443.54 kN/m2
Kapasitas dukung tanah yang dipakai : qa = 224.34 kN/m2

C. KONTROL TEGANGAN TANAH

Luas dasar foot plat, A = Bx * By = 6.0000 m2


Tahanan momen arah x, Wx = 1/6 * By * Bx2 = 3.0000 m3
Tahanan momen arah y, Wy = 1/6 * Bx * By2 = 2.0000 m3
Tinggi tanah di atas foot plat, z = Df - h = 0.55 m
Tekanan akibat berat foot plat dan tanah, q = h * gc + z * g = 20.480 kN/m2
Eksentrisitas pada fondasi :
ex = Mux / Pu = 0.3000 m < Bx / 6 = 0.5000 m (OK)
ey = Muy / Pu = 0.2600 m < By / 6 = 0.3333 m (OK)
Tegangan tanah maksimum yang terjadi pada dasar fondasi :
qmax = Pu / A + Mux / Wx + Muy / Wy + q = 40.313 kN/m2
qmax < qa AMAN (OK)
Tegangan tanah minimum yang terjadi pada dasar fondasi :
qmin = Pu / A - Mux / Wx - Muy / Wy + q = 17.313 kN/m2
qmin > 0 tak terjadi teg.tarik (OK)

D. GAYA GESER PADA FOOT PLAT

1. TINJAUAN GESER ARAH X

Jarak pusat tulangan terhadap sisi luar beton, d' = 0.075 m


Tebal efektif foot plat, d = h - d' = 0.375 m
Jarak bid. kritis terhadap sisi luar foot plat, ax = ( B x - b x - d ) / 2 = 1.113 m
Tegangan tanah pada bidang kritis geser arah x,
qx = qmin + (Bx - ax) / Bx * (qmax - qmin) = 31.784 kN/m2
Gaya geser arah x, Vux = [ qx + ( qmax - qx ) / 2 - q ] * ax * By = 34.640 kN
Lebar bidang geser untuk tinjauan arah x, b = By = 2000 mm
Tebal efektif footplat, d= 375 mm
Rasio sisi panjang thd. sisi pendek kolom, b c = bx / by = 1.0000
Kuat geser foot plat arah x, diambil nilai terkecil dari V c yang diperoleh dari pers.sbb. :
Vc = [ 1 + 2 / bc ] * fc' * b * d / 6 * 10-3 = 2053.960 kN
Vc = [ as * d / b + 2 ] * fc' * b * d / 12 * 10-3 = 3252.103 kN
Vc = 1 / 3 * fc' * b * d * 10-3 = 1369.306 kN
Diambil, kuat geser foot plat, Vc = 1369.306 kN
Faktor reduksi kekuatan geser, f = 0.75
Kuat geser foot plat, f * Vc = 1026.980 kN
Syarat yang harus dipenuhi,
f * Vc Vux
1026.980 > 34.640 AMAN (OK)

2. TINJAUAN GESER ARAH Y

Jarak pusat tulangan terhadap sisi luar beton, d' = 0.085 m


Tebal efektif foot plat, d = h - d' = 0.365 m
Jarak bid. kritis terhadap sisi luar foot plat, ay = ( B y - b y - d ) / 2 = 0.618 m
Tegangan tanah pada bidang kritis geser arah y,
qy = qmin + (By - ay) / By * (qmax - qmin) = 33.212 kN/m2
Gaya geser arah y, Vuy = [ qy + ( qmax - qy ) / 2 - q ] * ay * Bx = 30.164 kN
Lebar bidang geser untuk tinjauan arah y, b = Bx = 3000 mm
Tebal efektif footplat, d= 365 mm
Rasio sisi panjang thd. sisi pendek kolom, b c = bx / by =
1.0000
Kuat geser foot plat arah y, diambil nilai terkecil dari Vc yang diperoleh dari pers.sbb. :
Vc = [ 1 + 2 / bc ] * fc' * b * d / 6 * 10-3 = 2998.781 kN
Vc = [ as * d / b + 2 ] * fc' * b * d / 12 * 10-3 = 3431.938 kN
Vc = 1 / 3 * fc' * b * d * 10-3 = 1999.187 kN
Diambil, kuat geser foot plat, Vc = 1999.187 kN
Faktor reduksi kekuatan geser, f = 0.75
Kuat geser foot plat, f * Vc = 1499.391 kN
Syarat yang harus dipenuhi,
f * Vc Vux
1499.391 > 30.164 AMAN (OK)

3. TINJAUAN GESER DUA ARAH (PONS)

Jarak pusat tulangan terhadap sisi luar beton, d' = 0.085 m


Tebal efektif foot plat, d = h - d' = 0.37 m
Lebar bidang geser pons arah x, cx = b x + 2 * d = 0.765 m
Lebar bidang geser pons arah y, cy = b y + 2 * d = 0.765 m
Gaya geser pons yang terjadi,
Vup = ( Bx * By - cx * cy ) * [ ( qmax + qmin ) / 2 - q ] = 45.123 kN
Luas bidang geser pons, Ap = 2 * ( cx + cy ) * d = 1.117 m2
Lebar bidang geser pons, bp = 2 * ( c x + c y ) = 3.060 m
Rasio sisi panjang thd. sisi pendek kolom, bc = bx / by = 1.0000
Tegangan geser pons, diambil nilai terkecil dari fp yang diperoleh dari pers.sbb. :
f p = [ 1 + 2 / bc ] * f c ' / 6 = 2.739 MPa
fp = [ as * d / bp + 2 ] * fc' / 12 = 3.091 MPa
fp = 1 / 3 * fc ' = 1.826 MPa
Tegangan geser pons yang disyaratkan, fp = 1.826 MPa
Faktor reduksi kekuatan geser pons, f = 0.75
Kuat geser pons, f * Vnp = f * Ap * fp * 103 = 1529.38 kN
Syarat : f * Vnp Vup
1529.378 > 45.123 AMAN (OK)
f * Vnp Pu
1529.378 > 50.000 AMAN (OK)

E. PEMBESIAN FOOTPLAT

1. TULANGAN LENTUR ARAH X

Jarak tepi kolom terhadap sisi luar foot plat, ax = ( B x - b x ) / 2 = 1.300 m


Tegangan tanah pada tepi kolom,
qx = qmin + (Bx - ax) / Bx * (qmax - qmin) = 30.347 kN/m2
Momen yang terjadi pada plat fondasi akibat tegangan tanah,
Mux = 1/2 * ax2 * [ qx + 2/3 * ( qmax - qx ) - q ] * By = 27.904 kNm
Lebar plat fondasi yang ditinjau, b = By = 2000 mm
Tebal plat fondasi, h= 450 mm
Jarak pusat tulangan thd. sisi luar beton, d' = 75 mm
Tebal efektif plat, d = h - d' = 375 mm
Kuat tekan beton, fc ' = 30 MPa
Kuat leleh baja tulangan, fy = 390 MPa
Modulus elastis baja, Es = 2.00E+05 MPa
Faktor distribusi teg. beton, b1 = 0.85
rb = b1* 0.85 * fc/ fy * 600 / ( 600 + fy ) = 0.03368298
Faktor reduksi kekuatan lentur, f = 0.80
Rmax = 0.75 * rb * fy * [1-*0.75* rb * fy / ( 0.85 * fc ) ] = 7.949
Mn = Mux / f = 34.880 kNm
Rn = Mn * 106 / ( b * d2 ) = 0.12402
Rn < Rmax (OK)
Rasio tulangan yang diperlukan,
r = 0.85 * fc / fy * [ 1 - {1 2 * Rn / ( 0.85 * fc ) } ] = 0.0003
Rasio tulangan minimum, rmin = 0.0025
Rasio tulangan yang digunakan, r= 0.0025
Luas tulangan yang diperlukan, As = r * b * d = 1875.00 mm2
Diameter tulangan yang digunakan, D 16 mm
Jarak tulangan yang diperlukan, s = p / 4 * D * b / As =
2
214 mm
Jarak tulangan maksimum, smax = 200 mm
Jarak tulangan yang digunakan, s= 200 mm
Digunakan tulangan, D 16 - 200
Luas tulangan terpakai, As = p / 4 * D * b / s = 2010.62
2
mm2

2. TULANGAN LENTUR ARAH Y

Jarak tepi kolom terhadap sisi luar foot plat, ay = ( B y - b y ) / 2 = 0.800 m


Tegangan tanah pada tepi kolom,
qy = qmin + (By - ay) / By * (qmax - qmin) = 31.113 kN/m2
Momen yang terjadi pada plat fondasi akibat tegangan tanah,
Muy = 1/2 * ay2 * [ qy + 2/3 * ( qmax - qy ) - q ] * Bx = 16.096 kNm
Lebar plat fondasi yang ditinjau, b = Bx = 3000 mm
Tebal plat fondasi, h= 450 mm
Jarak pusat tulangan thd. sisi luar beton, d' = 85 mm
Tebal efektif plat, d = h - d' = 365 mm
Kuat tekan beton, fc ' = 30 MPa
Kuat leleh baja tulangan, fy = 390 MPa
Modulus elastis baja, Es = 2.00E+05 MPa
Faktor distribusi teg. beton, b1 = 0.85
rb = b1* 0.85 * fc/ fy * 600 / ( 600 + fy ) = 0.03368298
Faktor reduksi kekuatan lentur, f = 0.80
Rmax = 0.75 * rb * fy * [1-*0.75* rb * fy / ( 0.85 * fc ) ] = 7.949
Mn = Muy / f = 20.120 kNm
Rn = Mn * 106 / ( b * d2 ) = 0.05034
Rn < Rmax (OK)
Rasio tulangan yang diperlukan,
r = 0.85 * fc / fy * [ 1 - {1 2 * Rn / ( 0.85 * fc ) } ] = 0.0001
Rasio tulangan minimum, rmin = 0.0025
Rasio tulangan yang digunakan, r= 0.0025
Luas tulangan yang diperlukan, As = r * b * d = 2737.50 mm2
Diameter tulangan yang digunakan, D 16 mm
Jarak tulangan yang diperlukan, s = p / 4 * D * b / As =
2
220 mm
Jarak tulangan maksimum, smax = 200 mm
Jarak tulangan yang digunakan, s= 200 mm
Digunakan tulangan, D 16 - 200
Luas tulangan terpakai, As = p / 4 * D * b / s = 3015.93
2
mm2
3. TULANGAN SUSUT

Rasio tulangan susut minimum, rsmin = 0.0014


Luas tulangan susut arah x, Asx = rsmin* d * Bx = 1050.000 mm2
Luas tulangan susut arah y, Asy = rsmin* d * By = 1533.000 mm2
Diameter tulangan yang digunakan, 12 mm

Jarak tulangan susut arah x, sx = p / 4 * 2 * By / Asx = 215 mm


Jarak tulangan susut maksimum arah x, sx,max = 200 mm
Jarak tulangan susut arah x yang digunakan, sx = 200 mm
Jarak tulangan susut arah y, sy = p / 4 * * Bx / Asy =
2
221 mm
Jarak tulangan susut maksimum arah y, sy,max = 200 mm
Jarak tulangan susut arah y yang digunakan, sy
= 200 mm
Digunakan tulangan susut arah x, 12 - 200
Digunakan tulangan susut arah y, 12 - 200