QUT Digital Repository
QUT Digital Repository
http://eprints.qut.edu.au/
Majumder, Ritwik and Ghosh, Arindam and Ledwich, Gerard and Zare, Firuz (2010)
Load frequency control for rural distributed generation. Electric Power Components and
Systems, 38(6). pp. 637-656.
ABSTRACT: In rural low voltage networks, distribution lines are usually highly resistive.
When many distributed generators (DGs) are connected to such lines, power sharing amongst them
is difficult using conventional droop control as the real and reactive power have strong coupling
with each other. A high droop gain can alleviate this problem, but may lead the system to instability.
To overcome this, two droop control methods are proposed for accurate load sharing with frequency
droop controller. The first method considers no communication among the DGs and regulates the
output voltage and frequency ensuring acceptable load sharing. The droop equations are modified
with a transformation matrix based on the line R/X ratio for this purpose. The second proposed
method, with minimal low bandwidth communication, modifies the reference frequency of the DGs
based on the active and reactive power flow in the lines connected to the points of common coupling
(PCC). The performance of these two proposed controllers is compared with that of a controller
simulation of a test system. The magnitude of errors in power sharing between these three droop
Keywords: Autonomous microgrid, Load frequency droop, Active and reactive Power
1. Introduction
Decentralized power sharing among distributed generators (DG) can be achieved in a microgrid
using droop control method. The real and reactive power outputs of the DGs are controlled by frequency
and voltage droop characteristics [1, 2]. Rural electrification should ensure the availability of electricity
irrespective of the technologies, sources and forms of generation, but many cannot afford it due to a
shortage of resources. Distributed generation is one of the best available solutions for rural microgrids. But
the locations of the micro sources are very important. The success and failure of the rural electrification
activities in a developing country invariably depend on the extent to which the relevant issues have been
systematically analyzed and addressed [3]. In [4] a power electronic converter solution is introduced that is
capable of providing rural electrification at a fraction of the current electrification cost for weaker
A highly resistive line typical of low or medium voltage rural network challenges the power
sharing controller efficacy. The strong coupling of real and reactive power in the network leads to an
inaccurate load frequency control. High values of droop gains are required to ensure proper load sharing,
especially under weak system conditions. However, high droop gains have a negative impact on overall
stability of the system. Unfortunately however, proper load sharing cannot be ensured even with a high
gain if the lines are highly resistive. In such cases, the main assumption of the droop control that active and
reactive powers are decoupled is violated and the conventional droop control [1] is not able to provide an
At Anangu Solar Station of South Australia [5], with the off grid renewable connection, 220 kW
power is distributed covering 10,000 square km among number of communities up to 500 people. The
minigrid connection at Hermannsburg in central Australia [5] supplies three communities, each with
several hundred household (720 kW total power consumption). These are some of the examples of the
scenario under consideration where the micro sources and loads are geographically far from each other in a
Two methods have been proposed in this paper for power sharing with both inertial (rotary) and
converter interfaced DGs. The first method considers a decentralized operation and the conventional
frequency droop control is modified to accommodate the highly resistive line. A transformation matrix is
derived for the control parameter and feedback gains taking in consideration of the R-by-X ratio of the
lines. The second method requires a low bandwidth communication (100byte/s), where the reference
frequency of each DG output is modified based on the desired active and reactive power flow and the line
impedances. A low-cost web-based communication system [6-7] is used in this paper to serve this purpose.
In [6] it is shown how a distributed measuring system is able to monitor a number of power-quality indices
on every load connected to the same PCC and transmit the measured values to a master device that
The main contribution of the paper lies in the proposed set of droop control algorithm to support
the microgrid with particular emphasis on highly resistive lines. The proposed methods overcome the
shortcoming of the conventional droop control in a rural network. The accuracy of the controllers is shown
in different weak system conditions where the conventional droop fails to share the power as desired.
Mathematical derivations and time domain simulations are used to illustrate the methodologies.
To show the power sharing with frequency droop, a system of two DGs with a load is considered as
shown in Fig. 1. The conventional frequency droop equation [1] of the DGs are given by
1 1rated m1 P1 P1rated
(1)
2 2 rated m2 P2 P2 rated
where the rated power of the DGs are denoted by P1rated and P2rated . The droop coefficients are chosen to
m2 P1rated
m1 P2 rated
mostly resistive (high R/X ratio) and the values of the line resistance are not negligible. In that case, the
conventional load frequency droop control is not able to ensure a proper sharing of load. This is because
the conventional droop control assumes that the lines are inductive in nature so the real and reactive power
can be independently controlled with frequency and voltage respectively. But in rural netwrok with high
R/X ratio network this is not valid due to high real and reactive power coupling. Fig. 1 is redrawn without
the output inductances of the DGs as shown in Fig. 2. Here the line reactance value XD is chosen to be the
same as line resistance value RD. The line impedance values are shown in Table-I. In this sub-section a
modified droop control is proposed without any communication for the control of the resistive lines. In the
next sub-section it is shown with a low cost minimum communication, the controller performance can be
improved significantly.
where
V11 R 2 D1 X 2 D1
From the above equation, multiplying Q1 by RD1 and subtracting the product from the multiplication of P1
It is to be noted that DG-1 does not have any control over the load voltage magnitude and angle.
Hence they can be assumed as constant. Thus the linearization of (2) and (3) around the nominal values of
where indicates the perturbed value from the nominal values that are indicated by the subscript 0. From
(4) and (5), the output voltage magnitude and angle of a DG-1 can be written in terms of real and reactive
power as,
X D1 RD1
Z
11 Z1 P1 P
V K 1 KT 1 (6)
11 X D1 RD1 Q1 Q1
Z1 Z1
1
V V 110V
Z1 R X
2 2
K Z1 110
2V110 V
D1 D1
0
It can be seen that in (6), the output voltage angle and magnitude are influenced both by real and
reactive power output. So they can not be independently controlled as in conventional droop.
P1 P1
Q T Q
1 1
11 P1
V K Q (7)
11 1
The above equation forms the basis of modified droop sharing. A similar equation can be derived for DG-2
as well.
where the rated powers (P1rated, Q1rated) are also represented after multiplying the conversion matrix [T].
Similar transformation is also used for the rated powers of DG-2 as well. The droop gains of the both the
m1 m1 m2 m2
n T n and n T n (9)
1 1 2 2
m2 P1rated n Q
and 2 1rated (10)
m1 P2 rated n1 Q2 rated
It is to be noted that in this case we need to regulate the voltage V11, which is assumed to be DG output
voltage. This can be done by changing the converter output filter from LCL to LC structure and so the DG
output inductance is not present in this case. The converter structure and control is discussed in detail in
the Section 3.
In this sub-section, a droop control is proposed that requires minimal communication. The system in Fig.
1 is considered here and the DGs are connected to the microgrid with their output inductances. For small
angle difference between the DGs and their respective local buses shown in Fig. 1, the power flow
1 11 1 P1
(11)
2 22 2 P2
the terminal voltages, the PCC voltages of the DGs can be expressed as,
11 D1Q1 D1 P1
(12)
22 D 2Q2 D 2 P2
1 1 P1 D1Q1 D1 P1
(13)
2 2 P2 D 2Q2 D 2 P2
Since the = d/dt, taking derivative on both sides of the above equation, we get
m2 P1rated
m1 P2 rated
P1 m2 P1rated
m1P1 m 2 P2 (18)
P2 m1 P2 rated
It can be seen that the power sharing of the DGs are proportional to their rating. This control technique
shown with above simple example can be extended to multiple DG system, as well.
Fig. 3 shows the multiple DG system where three DGs are connected at different location of the
microgrid. DG-1 and DG-2 is assumed to be inertia less and converter interfaced while DG-3 is a
synchronous machine. This is to ensure that the proposed control work even with the presents of inertial
DGs in a microgrid (As in most of cases the inertial DGs limits the control law for the converter interfaced
DGs in a microgrid). The four loads of the microgrid are shown as Load_1, Load_2, Load_3 and Load_4.
The real and reactive power supply from the DGs are denoted by Pi, Qi, i = 1,,3. The real and reactive
power flow for different line sections and load demand are shown in Fig. 3. The line impedances are
denoted as ZDi (= RDi + jXDi), i = 1,, 6. Each of the DG controllers needs to measure its local quantities
only and hence, the real and reactive power flow measurements into and out of the DG local bus are
required. It is to be noted all the line impedances and loads are assumed to be lumped.
3 L 4 3 P3 D 6Q3 R D 6 P3 R (19)
2 L 3 2 P2 D 4Q2 R D 4 P2 R (20)
It is to be noted that in (22) and (23), all the active and reactive power quantities, except the first
term, are not locally measureable. The angle difference shown in (21) can be measured by DG-3 and then
communicated to DG-2 and DG-1. As these quantities only modify the reference angle to ensure better
load sharing, updates can be done using slower sample rates with a low bandwidth communication
channel. This can be done since the frequency droop, given by (1), is always active. The primary control
action is instantaneous and ensures a rough load sharing among the DGs. The longer time allow us to use
web based communication for this purpose [6-7]. The reference frequency deviation is then controlled with
1 L 4 1 p 11 12 13 (24)
where,
1 p 1P1 , 11 D 2Q1R 2 D P1R
12 3 DQ2 L 3 D P2 L D 4Q2 R D 4 P2 R
13 D 5Q3 L D 5 P3 L D 6Q3 R D 6 P3 L
A low bandwidth (100 bytes/s) web based data transfer method is used for the minimal
communication droop control. The web-based measurement system is shown in Fig. 4. The real and
reactive power outputs, measured at each DG unit, are communicated to a dedicated website or company
intranet with the help of a modem. Assuming that the PQ measurement units are already installed at each
DG location, the additional equipment needed for each DG unit are a computer to collect the
measurements from local and remote units, and a modem to transmit the measurements to the dedicated
website, or to download remote measurements from it. Fig. 4 (a) shows the web connection of all the DGs,
while the communication in each DG is shown in Fig. 4 (b). The power monitoring unit sends the real and
reactive power measurement to the computer to calculate 11 for DG-1, as shown in (24). The other angle
component 12 and 13 are received by the modem and communicated to the DG control unit through the
computer. The change in frequency reference is calculated from these measurements as discussed in
Section 2.2.1. As mentioned before, the main load sharing is based on local measurement frequency droop
and so even in case of communication failure a rough load sharing is ensured among the DGs.
It is to be noted that the optimum power sharing could be different from proportional to the power
rating in many scenarios. It could be cost based, generation based or based on other criteria. However this
paper aims to share power proportional to the rating of the DGs, which is very common in rural distributed
generation system. Moreover, with droop control power sharing can be achieved in a desired ratio by the
proper selection of the droop gains as per (8). The proposed control methods in this paper ensure that the
real and reactive power output can be controlled in presence of a strong coupling in a high R/X ratio line.
DG-1 and DG-2 are assumed to be an ideal dc voltage source supplying a voltage of Vdc to the
voltage source converters (VSCs). The structure of the VSC is shown in Fig. 6. It contains three H-bridges
that are supplied from the common dc bus. The outputs of the H-bridges are connected to three single-
phase transformers that are connected in wye for required isolation and voltage boosting [9]. The
resistance RT represents the switching and transformer losses, while the inductance LT represents the
leakage reactance of the transformers. The filter capacitor Cf is connected to the output of the transformers
to bypass switching harmonics, while Lf represents the output inductance of the DG source. The voltages
across the filter capacitors, the currents through them and the currents inject to the microgrid are denoted
xT i2 icf vcf (25)
x Ax Bu (26)
uc K x xref (27)
where K is the gain matrix and xref is the reference vector for the states given by (25). The gain matrix, in
this paper, is obtained through linear quadratic regulator (LQR) design. Based on this control law, the
The control law discussed so far is for the system in which the DGs have an output inductor. It can
be seen from Fig. 5 that this implies the converter output stage has LCL (or T) filter structure.
Alternatively, when the DGs do not have an output inductance, the inductance Lfi is removed and the
output filter is a simple LC filter. The system states are then modified as
xT icf vcf
However the state space is similar to (26) and the control law (27) and switching logic (28) remain the
same. This control strategy is applied to DG-1 and DG-2, when operating without any communication of
Section 2.1.
It is evident from (27) that a reference for all the elements of the states, given in (26), is required
for state feedback. The reference for the capacitor voltage and current are given by
For the LCL filter, the reference for the current i2 can be calculated as
P2 Q2
I 2 ref and 2 ref tan 1 Q / P
Vcf
Since V and are obtained from the droop equation, to calculate the reference in (29)-(31), the
value of has to be obtained. The voltage angle controller of the converter generates a rotating angle 1*
t0 2 t1
Therefore we have
t1 t0 (32)
It is to be noted that the converters are current limited at twice of their rated current [12, 13].
During a fault or in case of excessively high load demand, the output current reaches limit. The reactive
power capability of the DGs are also limited by the current limit and controlled by the voltage droop as
shown in (8).
The DG-3 is assumed to be a synchronous machine. The synchronous machine model given in [14]
is used in this paper. The generator field is supplied by a static exciter and automatic voltage regulator
e fd Ke
(33)
err sTe 1
where efd is the field voltage and err is the error in voltage given by Vtref |V2|. Ke and Te are the AVR gain
and time constant, respectively. A mini hydraulic turbine is used as the prime mover [15]. The real and
reactive power output of the synchronous machine is controlled by the load frequency droop and voltage
Simulation studies are carried out in PSCAD/EMTDC (version 4.2). Different configurations of
load and power sharing of the DGs are considered. To consider the web based communication, a delay of 5
ms is incorporated in the control signals which are not locally measureable. As only one measurement is
taken in one main cycle, a 100 byte/s communication is needed (which is a very low speed communication
compared to any of the high bandwidth communication). The system parameters are shown in Table-I
In this case, all the three DGs are connected to the microgrid and supplying Load_2 and Load_3.
While the system in steady state, DG-2 is disconnected from the microgrid at 0.5 s. Fig. 6 (a) shows the
power output of the DGs and Fig. 6 (b) shows the power sharing ratios with conventional frequency droop
controller. It can be seen that due to high line impedance, the power sharing of the DGs are not as desired.
Fig. 7 shows the system response with proposed controller 1. The error in power sharing is reduced
significantly (Table-II). Fig. 8 shows the system response with proposed controller 2. The power sharing
ratio of the DGs, shown in Table-II, are much closer to the desired sharing and the system reaches steady
state within 4-5 cycles as in the case with the conventional controller. Fig 9 shows the operating
frequencies of the DGs. It is to be noted that the deviation in frequency depends on the droop gain and
limited by the system regulations. It can be seen that the system is running within a very narrow frequency
band in all the cases. As the frequency droop share the power by droping the frequency, in a continuous
load changing situation frequency regulation could be a problem in some other senerios. This could be
solved by operating one generator in isochronous mode. The other way could be integrating the reset of
frequency reference function in the droop control of all the DGs [16].
Fig. 10 shows the reactive power output and the output voltages of the DGs with conventional
controller. Due to the high reactive power demand from the loads the voltage droop coefficients are chosen
small to ensure the voltage drops are within regulation. The reactive power outputs of the DGs with the
proposed controller are shown in Fig. 11. It can be seen that reactive power demand is distributed among
the DGs and after loss of DG-2, DG-1 and DG-3 supply the total reactive power demand.
It is assumed all the DGs are connected to the microgrid and they are supplying Load_1 and
Load_4. The system response shown in Fig 12 is with the conventional controller. Load_1 is disconnected
at 0.5s and the DGs supply Load_4 only. It can be seen from Table-II that the power sharing ratio deviates
much after Load_1 is disconnected. Fig. 13 shows the power sharing with proposed Controller-1 and after
Load_1 is disconnected, the power sharing ratio of DG-1 and DG-3 falls to 1.1. The system response with
proposed minimal communication (Controller-2) is shown in Fig. 14. It can be seen that an acceptable
power sharing is achieved with the proposed controllers. The high line impedance (and high R/X ratio)
between the DGs and load makes the power sharing difficult and the power sharing with conventional
The performance of the two proposed controllers is compared with that of a controller equipped
with a high bandwidth communication channel. In such a scheme, the droop control becomes redundant
since all load and control parameters are measurable from any DG connecting of the network without any
significant time delay. With the similar condition as in Case-2, the system is simulated and this results in
very accurate load sharing with error of 0.3% or less, which are not shown here. However as mentioned
before, the cost involved in a high bandwidth communication is much higher compared to the proposed
The mean percentage errors in the above-mentioned three different control techniques are
compared, along with that of a conventional droop controller. The results are shown in Fig. 15 for the two
cases discussed above. Note that these cases were chosen for weak system conditions, where the micro
sources and loads are not symmetrically distributed throughout the network. This results in high values of
power sharing error with conventional droop controller. However it can be seen that, with the proposed
control methods, the error can be reduced significantly. While Controller-1 can reduce the error below
4.1%, the web based Controller-2 has an error below 1.78%. Though the error in case with an advanced
communication system is much lower, the cost involved is likely to be prohibitively high. Therefore the
proposed controllers can provide an economical solution in a low voltage, high resistive network.
6. Conclusions
In this paper, two load frequency control strategies are proposed with special emphasis on highly
resistive line in an autonomous microgrid. The first method requires no communication and the feedback
quantities and droop controller gain matrix are transformed with a transformation matrix based on the line
resistance reactance ratio of the line for proper power sharing of the DGs. In the second method, a low
bandwidth web based communication system is used and the frequency references are modified based on
the active and reactive power flow in the line connected at PCC. It is shown that a more economical and
acceptable power sharing solution is possible with the proposed control methods. The difference in error
margin between proposed control schemes and a costly high bandwidth based communication system is
not significant. Therefore, considering the cost involved, the implementation of a controller based on a
high bandwidth communication system may not be justifiable, especially in rural systems that span over a
The current limiting operation of the converters is shown in this appendix. A three phase fault is
simulated at the DG-1(Fig. 3) terminal and cleared after 2 cycles. The converter is controlled by state
feedback given in (25-27). Also the reference voltage is set from droop equations. However during the
fault, the magnitude of the output current is limited and its angle can be chosen arbitrarily. If the fault is
not cleared within 4-5 cycles, the converter is blocked, which is not considered here. Fig. 16 shows the
terminal voltage and output current of the DG. It can be seen that the DG is current limited during the
fault. Once the fault is cleared the output current comes down to its initial value.
Acknowledgement
The authors thank the Australian Research Council (ARC) for the financial support for this project
References
[1] M. C. Chandorkar, D. M. Divan and R. Adapa, Control of parallel connected inverters in standalone
ac supply systems, IEEE Trans. On Industry Applications, Vol. 29, No. 1, pp. 136-143, 1993.
[2] A.M. Salamah, S.J. Finney, B.W. Williams, Autonomous controller for improved dynamic
[3] M. Munasinghe, Rural electrification in the Third World, Power Engineering Journal, Vol. 4, No.
[4] S. Thiel, C.H. Mostert, J.H.R Enslin, Universal power electronic solution to low-cost rural
Instrumentation and Measurements, Vol. 51, No. 4, pp. 776 - 781, August 2002.
[7] L. Nian, Z. Jianhua, L. Wenxia, A Security Mechanism of Web Services-Based Communication for
Wind Power Plants, IEEE Trans. Power Delivery, Vol. 23, No. 4, pp. 1930-1938, 2008.
[8] Lynn Powell, Power System Load Flow Analysis, McGraw-Hill Professional Publishing, November
2004.
[9] A. Ghosh and A. Joshi, A new approach to load balancing and power factor correction in power
distribution system, IEEE Trans. on Power Delivery, Vol. 15, No. 1, pp. 417-422, 2000.
[10] A. Ghosh and G. Ledwich, Power Quality Enhancement using Custom Power Devices, Kluwer
[11] R. Majumder, A. Ghosh, G. Ledwich and F. Zare, Control of parallel converters for load sharing
with seamless transfer between grid connected and islanded modes, Power and Energy Society
[12] M. Brucoli, T. C. Green, and J. D. F. McDonald, Modelling and analysis of fault behaviour of
inverter microgrids to aid future fault detection, System of Systems Engineering, SoSE '07. IEEE
[13] H. Nikkhajoei and R. H. Lasseter, Microgrid protection, Power Engineering Society General
[14] K. R. Padiyar, Power System Dynamics: Stability and Control, Anshan Publisher, August 2004.
[15] Working Group on Prime Mover and Energy Supply, Hydraulic turbine and turbine control models
for system dynamic studies, IEEE Trans. In Power Systems, Vol. 7, No. 1, Feb. 1992 Page(s):167
179.
[16] F. Katiraei and M. R. Iravani, Power Management Strategies for a Microgrid With Multiple
Distributed Generation Units IEEE Trans. on Power Systems, Vol.. 21, No. 4, November 2006
1821-1831.
TABLE-I: NOMINAL SYSTEM PARAMETERS
Systems frequency 50 Hz
Feeder impedance
ZD1 1.0 + j 1.0
ZD2 0.4 + j 0.4
ZD3 0.5 + j 0.5
ZD3 0.4 + j 0.4
ZD3
0.4 + j 0.4
Load ratings
Load1 11.8 kW and 7.5 kVAr
Load2 16.8 kW and 13.5 kVAr
Load3 26.25 kW and 16.0 kVAr
Load4 26.25 kW and 16.0 kVAr
DG ratings (nominal)
DG-1 18 kVA, 0.3 to0.95 pf
DG-2 27 kVA, 0.3 to0.95 pf
DG-3 27 kVA, 0.3 to0.95 pf
Output inductances
Lf1 7.5 mH
Lf2 5.0 mh
DGs and VSCs
DC voltages (Vdc1 to Vdc4) 0.220 kV
Transformer rating 0.220 kV/0.440 kV, 0.5
VSC losses (Rf) MVA, 2.5% Lf
Filter capacitance (Cf) 1.5
Hysteresis constant (h) 50 F
10-5
Droop Coefficients
Powerangle
m1 25 rad/s/MW
m2 16.67 rad/s/MW
m3 16.67 rad/s/MW
VoltageQ
n1 0.6 V/KVAr
n2 0.4 V/KVAr
n3 0.4 V/KVAr
Synchronous Machine
Inertia constant, H 0.2 s
Damping constant D 1.0
Direct axis transient time constant 1.497 s
Td0
Quadrature axis transient time 0.223 s
constant Tq0
Armature resistance Ra 0.01 pu
Direct axis reactance Xd 0.8 pu
Quadrature axis reactance Xq 0.752 pu
Direct axis transient reactance 0.16 pu
Xd
Quadrature axis transient 0.325
reactance Xq
Synchronous speed s 100 rad/s
Exciter
Gain Ke 12.0
Time constant Te 0.05 s
Fig. 10. Reactive power output and output voltages of the DGs
Fig. 11. Reactive power output of the DGs with proposed controllers
Fig. 12. Power sharing with conventional controller: Case-2.
12
10
Conventional Control
8
Prposed Decentralized
% Error 6 Control
Proposed Minimum Com.
4 Control
High Bandwidth Control
2
0
1
Control Methods