Rociador Ty L
Rociador Ty L
Rociador Ty L
ESCUTCHEON STYLE 20
WRENCH 1/2"
PLATE SEATING RECESSED
FLANGES NPT
SURFACE ESCUTCHEON
1
WRENCH
AREA 2
2-5/8"
(66,7 mm)
2-5/8"
7/16" 4
(66,7 mm) 3
(11,1 mm)
NOMINAL 2" 5
MAKE-IN (50,8 mm)
7
2-7/8" (73,0 mm) DIA.
FIGURE 1
STANDARD RESPONSE SERIES TY-L UPRIGHT (TY3111) AND PENDENT (TY3211) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON STYLE 30
WRENCH 3/4"
PLATE SEATING RECESSED
FLANGES NPT
SURFACE ESCUTCHEON
1
WRENCH
2-11/16" AREA 2
(68,3 mm)
1/2" 2-11/16" 4
(12,7 mm) (68,3 mm) 3
NOMINAL
2"
MAKE-IN 5
(50,8 mm)
FIGURE 2
STANDARD RESPONSE SERIES TY-L UPRIGHT (TY4111) AND PENDENT (TY4211) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
TFP110 Page 3 of 8
ESCUTCHEON STYLE 20
WRENCH 1/2"
PLATE SEATING RECESSED
FLANGES NPT
SURFACE ESCUTCHEON
1
WRENCH
AREA 2
2-5/8"
(66,7 mm)
2-5/8"
7/16" 4
(66,7 mm) 3
(11,1 mm)
NOMINAL 2" 5
MAKE-IN (50,8 mm)
7
2-7/8" (73,0 mm) DIA.
FIGURE 3
STANDARD RESPONSE SERIES TY-L UPRIGHT (TY4811) AND PENDENT (TY4911) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
SPRINKLER FINISH
K TYPE TEMP. FRAME NATURAL CHROME LEAD WAX WAX OVER
COLOR BRASS PLATED COATED COATED LEAD COATED
RATING CODE
PENDENT (TY3211) 165F/74C Unpainted 1, 2, 3
and 1, 2, 3, 5
212F/100C White
5.6 UPRIGHT (TY3111)
1/2" 280F/138C Blue 1, 2 4 N/A
NPT RECESSED PENDENT 165F/74C Unpainted 1, 2, 3, 5
(TY3211 w/ Style 20) N/A
212F/100C White 1, 2, 3, 5
SPRINKLER FINISH
K TYPE TEMP. FRAME NATURAL CHROME LEAD WAX WAX OVER
COLOR BRASS PLATED COATED COATED LEAD COATED
RATING CODE
PENDENT (TY4211) 165F/74C Unpainted 1, 2, 3
and 1, 2, 3, 5
212F/100C White
8.0 UPRIGHT (TY4111)
3/4" 280F/138C Blue 1, 2 4 N/A
NPT RECESSED PENDENT 165F/74C Unpainted 1, 2, 5
(TY4211 w/ Style 30) N/A
212F/100C White
SPRINKLER FINISH
K TYPE TEMP. FRAME NATURAL CHROME LEAD WAX WAX OVER
COLOR BRASS PLATED COATED COATED LEAD COATED
RATING CODE
PENDENT (TY4911) 165F/74C Unpainted 1, 2, 3
and 1, 2, 3, 5
212F/100C White
8.0 UPRIGHT (TY4811)
1/2" 280F/138C Blue 1, 2 N/A
NPT RECESSED PENDENT 165F/74C Unpainted 1, 2
(TY4911 w/ Style 20) N/A
212F/100C White
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Approved by Factory Mutual Research Corporation (FM) for maximum 150F/68C ambient temperatures.
5. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/03).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
TFP110 Page 5 of 8
MOUNTING
SURFACE 1-3/4" (44,5 mm)
1-1/2" (38,1 mm)
FIGURE 7
W-TYPE 9 SPRINKLER
CLOSURE TY-L
WRENCH
FIGURE 4
SERIES TY-L (TY3211) RECESSED PENDENT SPRINKLER ASSEMBLY WRENCH
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT RECESS
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
ing has been damaged and bare metal sprinkler systems be inspected,
is exposed. The wax coating on the Care and tested, and maintained by a qualified
wrench flats can be retouched by gen- Inspection Service in accordance with
tly applying a heated 1/8 inch diameter Maintenance local requirements and/or national
steel rod to the areas of wax that have codes.
been damaged, to smooth it back over The Series TY-L Sprinklers must be
areas where bare metal is exposed. maintained and serviced in accord-
ance with the following instructions: Limited
NOTES
Only retouching of the wax coating ap- Warranty
plied to the wrench flats and frame NOTES
arms is permitted, and the retouching Before closing a fire protection system Products manufactured by Tyco Fire
is to be performed only at the time of main control valve for maintenance Products are warranted solely to the
the initial sprinkler installation. work on the fire protection system that original Buyer for ten (10) years
it controls, permission to shut down the against defects in material and work-
The steel rod should be heated only to affected fire protection system must be manship when paid for and properly
the point at which it can begin to melt obtained from the proper authorities installed and maintained under normal
the wax, and appropriate precautions and all personnel who may be affected use and service. This warranty will ex-
need to be taken, when handling the by this action must be notified. pire ten (10) years from date of ship-
heated rod, in order to prevent the ment by Tyco Fire Products. No war-
installer from being burned. Absence of an escutcheon, which is ranty is given for products or
used to cover a clearance hole, may components manufactured by compa-
If attempts to retouch the wax coating delay the time to sprinkler operation in
with complete coverage are unsuc- nies not affiliated by ownership with
a fire situation. Tyco Fire Products or for products and
cessful, additional wax can be ordered
in the form of a wax stick (the end of components which have been subject
which is color coded). Only the correct Sprinklers that are found to be leaking to misuse, improper installation, corro-
color coded wax is to be used, and or exhibiting visible signs of corrosion sion, or which have not been installed,
retouching of wrench flats and frame must be replaced. maintained, modified or repaired in ac-
arms is only permitted at the time of cordance with applicable Standards of
Automatic sprinklers must never be the National Fire Protection Associa-
initial sprinkler installation. With the painted, plated, coated or otherwise
steel rod heated as previously de- tion, and/or the standards of any other
altered after leaving the factory. Modi- Authorities Having Jurisdiction. Mate-
scribed, touch the rod to the area re- fied or over-heated sprinklers must be
quiring additional wax with the rod an- rials found by Tyco Fire Products to be
replaced. defective shall be either repaired or
gled downward, and then touch the
wax stick to the rod approximately Care must be exercised to avoid dam- replaced, at Tyco Fire Products sole
one-half inch away from the area re- age to the sprinklers - before, during, option. Tyco Fire Products neither as-
quiring retouching. The wax will melt and after installation. Sprinklers dam- sumes, nor authorizes any person to
and run down onto the sprinkler. aged by dropping, striking, wrench assume for it, any other obligation in
twist/slippage, or the like, must be re- connection with the sale of products or
placed. parts of products. Tyco Fire Products
The Series TY-L Recessed Pendent shall not be responsible for sprinkler
Sprinklers must be installed in ac- Frequent visual inspections are rec- system design errors or inaccurate or
cordance with the following instruc- ommended to be initially performed for incomplete information supplied by
tions. corrosion resistant coated sprinklers, Buyer or Buyers representatives.
after the installation has been com-
Step A. After installing the Style 20 or pleted, to verify the integrity of the cor- IN NO EVENT SHALL TYCO FIRE
30 Mounting Plate, as applicable, over rosion resistant coating. Thereafter, PRODUCTS BE LIABLE, IN CON-
the sprinkler threads and with pipe annual inspections per NFPA 25 TRACT, TORT, STRICT LIABILITY OR
thread sealant applied to the pipe should suffice; however, instead of in- UNDER ANY OTHER LEGAL THE-
threads, hand tighten the sprinkler into specting from the floor level, a random ORY, FOR INCIDENTAL, INDIRECT,
the sprinkler fitting. sampling of close-up visual inspec- SPECIAL OR CONSEQUENTIAL
Step B. Tighten the sprinkler into the tions should be made, so as to better DAMAGES, INCLUDING BUT NOT
sprinkler fitting using only the W-Type determine the exact sprinkler condi- LIMITED TO LABOR CHARGES, RE-
10 Recessed Sprinkler Wrench (Ref. tion and the long term integrity of the GARDLESS OF WHETHER TYCO
Figure 8). With reference to Figure 1, corrosion resistant coating, as it may FIRE PRODUCTS WAS INFORMED
2, or 3, the W-Type 10 Recessed Sprin- be affected by the corrosive conditions ABOUT THE POSSIBILITY OF SUCH
kler Wrench is to be applied to the present. DAMAGES, AND IN NO EVENT
sprinkler wrenching flanges. SHALL TYCO FIRE PRODUCTS LI-
The owner is responsible for the in- ABILITY EXCEED AN AMOUNT
Step C. After the ceiling has been in- spection, testing, and maintenance of EQUAL TO THE SALES PRICE.
stalled or the finish coat has been ap- their fire protection system and de-
plied, slide on the Style 20 or 30 Clo- vices in compliance with this docu- THE FOREGOING WARRANTY IS
sure over the Series TY-L Sprinkler ment, as well as with the applicable MADE IN LIEU OF ANY AND ALL
and push the Closure over the Mount- standards of the National Fire Protec- OTHER WARRANTIES EXPRESS OR
ing Plate until its flange comes in con- tion Association (e.g., NFPA 25), in IMPLIED, INCLUDING WARRANTIES
tact with the ceiling. addition to the standards of any other OF MERCHANTABILITY AND FIT-
authorities having jurisdiction. The in- NESS FOR A PARTICULAR PUR-
stalling contractor or sprinkler manu- POSE.
facturer should be contacted relative to
any questions.
It is recommended that automatic
TFP110 Page 7 of 8
TABLE B
PART NUMBER SELECTION
SERIES TY-L PENDENT AND UPRIGHT SPRINKLERS
Recessed Escutcheon:
Ordering Specify: Style (specify) Recessed Es- Wax Sticks:
cutcheon with (specify finish), P/N (for retouching wrench damaged
Procedure (specify). wax coating)
Specify: (Specify color) color coded
When placing an order, indicate the full 1/2" (15 mm)
Wax Stick for retouching (specify tem-
product name. Refer to the Price List Style 20
Chrome Plated . . . . . . . . . P/N 56-705-9-010 perature rating) temperature rated Se-
for complete listing of Part Numbers. 1/2" (15 mm) ries TY-L Sprinklers, P/N (specify).
Contact your local distributor for avail- Style 20
White Color Red for 165F . . . . . . . . . . . . . P/N 56-065-1-155
ability. Coated . . . . . . . . . . . . . . . P/N 56-705-4-010 Blue for 212F and
1/2" (15 mm) 280F . . . . . . . . . . . . . . . . . P/N 56-065-1-286
Sprinkler Assemblies with NPT Style 20
Thread Connections: Brass Plated . . . . . . . . . . . P/N 56-705-2-010
NOTES
Specify: (Specify Model/SIN), Stand- 3/4" (20 mm)
Style 30 Each wax stick is suitable for retouch-
ard Response, (specify K-factor), Chrome Plated . . . . . . . . . P/N 56-705-9-011 ing up to twenty-five sprinklers.
(specify temperature rating), Series 3/4" (20 mm)
TY-L (specify Pendent or Upright) Style 30 The wax used for 280F sprinklers is
Sprinkler with (specify type of finish or White Color the same as for 212F sprinklers, and,
Coated . . . . . . . . . . . . . . . P/N 56-705-4-011 therefore, the 280F sprinkler is limited
coating), P/N (specify from Table B). 3/4" (20 mm)
Style 30
to the same maximum ceiling tempera-
Brass Plated . . . . . . . . . . . P/N 56-705-2-011 ture as the 212F sprinkler (i.e.,
150F).
Sprinkler Wrench:
Specify: W-Type 9 Sprinkler Wrench,
P/N 56-000-1-849.
Specify: W-Type 10 Sprinkler Wrench,
P/N 56-000-1-948.
Page 8 of 8 TFP110