Transformer Stability Test Example Procedure #2
Transformer Stability Test Example Procedure #2
Transformer Stability Test Example Procedure #2
The transformer stability test used to conform the CT connections for Differential and REF protection. This test
also used as a primary injection test for HV & LV side BCT's.
PRIMARY SIDE : -
HV side full load current = Power / 3 x Voltage = 10010^3 = 100000000 = 251 Amps
3 230 1000 399050
HV side Impedence/ Phase = HV side Impedence X % Impedence = 916 X 12.24 = 112 Ohms
100
LV side SIDE : -
Note : -
To make this condition open any one of CT FT fingers and short by insert the FT jack.
Test connection: Three phase short circuit outside protected zone on LV side. Three phase voltage injected on
HV side = 380V
Test connection : The shorting and grounding bar was removed from the Delta winding and current was injected
with Severker Test Kit and secondary currents were measured in the Transformer LCP panel.