Air System Design Load Summary For FF-AHU-04 W Heat/humidifier

This document summarizes the heating and cooling load design data for an air handling unit serving an office building renovation project. It provides the zone sensible and latent heating and cooling loads in Watts, including from solar gains, transmission, lighting, equipment, occupants, and infiltration. It then calculates the total system loads accounting for ventilation, fans, and duct heat gains/losses. The central cooling and heating coil loads and terminal reheat coil loads are presented to satisfy the total conditioning load.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views

Air System Design Load Summary For FF-AHU-04 W Heat/humidifier

This document summarizes the heating and cooling load design data for an air handling unit serving an office building renovation project. It provides the zone sensible and latent heating and cooling loads in Watts, including from solar gains, transmission, lighting, equipment, occupants, and infiltration. It then calculates the total system loads accounting for ventilation, fans, and duct heat gains/losses. The central cooling and heating coil loads and terminal reheat coil loads are presented to satisfy the total conditioning load.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Design Load Summary for FF- AHU-04 w heat/humidifier

Project Name: DG Affairs- Office rev. 1 08/27/2011


Prepared by: abc 07:34AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 49.2 C / 29.9 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 33 m 5298 - 33 m - -
Wall Transmission 182 m 3042 - 182 m 977 -
Roof Transmission 337 m 9935 - 337 m 2099 -
Window Transmission 33 m 2845 - 33 m 1001 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 19 m 322 - 19 m 0 -
Partitions 174 m 3454 - 174 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 8399 W 7538 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6300 W 6012 - 0 0 -
People 58 3632 3485 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 6312 523 0% 0 0
>> Total Zone Loads - 48391 4007 - 4077 0
Zone Conditioning - 52919 4007 - 2810 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 4674 L/s 0 - 586 L/s 0 -
Ventilation Load 534 L/s 16607 15551 67 L/s 628 0
Supply Fan Load 4674 L/s 2619 - 586 L/s -787 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 484 - 1% 41 -
>> Total System Loads - 72629 19558 - 2691 0
Central Cooling Coil - 74186 19558 - -4202 0
Central Heating Coil - -1557 - - 0 -
Humidification Load - - 0 - - 0
Terminal Reheat Coils - 0 - - 6892 -
>> Total Conditioning - 72629 19558 - 2691 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1