Bakers Surge Tester - ST 203a
Bakers Surge Tester - ST 203a
Bakers Surge Tester - ST 203a
Surge/DC HiPot/Tester
Models ST103A/ST106A/ST112A
ST203A/ST206A/ST212A
12/2/2009 | 71-002-V5 EN 1
ST103A, ST106A, ST112A
Warranties; Disclaimers
Limited Warranty as to Baker/SKF Brand Products.
1) Baker/SKF warrants that Baker/SKF brand Products, if any, that are sold under the
Agreement shall be of the kind and quality described in Baker/SKF's acknowledgment of
Buyer's Order, and shall be free of material defects in workmanship and material for a
period from the date of shipment equal to (i) twelve (12) months in the case of new
Products (including factory-installed circuit boards, accessories and options purchased
concurrently with the applicable Product), (ii) six (6) months in the case of used or
refurbished Products, and new circuit boards, accessories and options delivered separately
from the applicable Product, (iii) a period of ninety (90) days from the date of shipment in
the case of used or refurbished circuit boards. If any such Product , accessory or option
is not as warranted, Buyer must notify Baker/SKF thereof in writing within the applicable
warranty period.
2) Baker/SKF's sole obligation, and Buyer's sole remedy, under the foregoing warranty shall
be to provide the parts and labor for the repair or replacement (at Baker/SKF's sole
option) of defective parts, recalibration of any portions of a product that could reasonably
have been affected by the repair, and functional verification to affirm proper operation.
When, subject to the next sentence, the Buyer returns Products, accessories or options
to the Baker/SKF factory for warranty service, Baker/SKF will bear the cost of return
packaging, and shipping , and insurance ,on the return shipment. For Products,
accessories or options that Baker/SKF designates as on-site service only due to their
size, the permanence of their installation pr otherwise, travel expenses (including labor
costs for time spent traveling) for warranty services are covered to the location of
original shipment and installation. Products, accessories and options that are capable of
being returned to the factory for service may receive warranty service on site, but all
travel expenses (including labor charges for time spent traveling) shall be the
responsibility of Buyer.
3) For warranty coverage of on-site service only items, Buyer must make available to
Baker/SKF a knowledgeable operator to assist with preliminary diagnosis prior to a
service trip being scheduled. Buyer, in connection with a request for on-site service,
must be capable of authorizing charges for the service visit in the event the issues
discovered are not covered by warranty, such as application errors or installation errors.
If Buyer, having elected to perform installations without Baker/SKFs participation and
having encountered irresolvable problems, shall be charged for an installation if on-site
assistance is necessary, except when defective product is determined to be the cause.
Warning: Baker Instrument Company, an SKF Group Company assumes no liability for
damages consequent to the use of this product. No part of this document may be reproduced
in part or in full by any means such as photocopying, photographs, electronic recording,
videotaping, facsimile, etc., without written permission from Baker Instrument Company, an
SKF Group Company, Fort Collins, Colorado.
12/2/2009 | 71-002-V5 EN 2
ST103A, ST106A, ST112A
Table of Contents
Warranties; Disclaimers....................................................................................................................... 2
Limited Warranty as to Baker/SKF Brand Products. .................................................................... 2
1.......................................................................................................................................................................... 7
PREFACE ........................................................................................................................................................... 7
Important safety information..................................................................................................................... 7
General Safety Precautions................................................................................................................. 7
Safety term definition .......................................................................................................................... 7
Other Important Safety warnings ....................................................................................................... 7
Power Source Precautions .................................................................................................................. 8
Ground the product.............................................................................................................................. 8
Operation notes .................................................................................................................................... 8
Symbols on equipment ........................................................................................................................ 9
Other Information........................................................................................................................................ 9
Cleaning & decontamination ............................................................................................................... 9
Technical assistance / Authorized Service Centers ........................................................................... 9
Intermittent operation limits ............................................................................................................... 9
Installation requirements..................................................................................................................... 9
Unpacking the unit ............................................................................................................................... 9
Power and utility ................................................................................................................................10
Environmental ....................................................................................................................................10
Storage (indoor/outdoor) ...................................................................................................................10
Shipment.............................................................................................................................................10
2........................................................................................................................................................................11
INSTRUMENT OVERVIEW ............................................................................................................................11
Front panel controls ..................................................................................................................................11
3........................................................................................................................................................................15
TEST PROCEDURES AND VOLTAGES........................................................................................................15
General user cautions and notices..........................................................................................................15
Initial tester power-up and check-out .............................................................................................15
Recommended voltages.....................................................................................................................16
Recommended Standards .................................................................................................................17
4........................................................................................................................................................................19
DC HIPOT TESTING.......................................................................................................................................19
Principles of DC High-Potential (HiPot) testing ....................................................................................19
Other Important Safety warnings .....................................................................................................21
7) Repair Parts Warning : Defective, damaged, or broken test leads must be replaced with
factory-authorized parts to ensure safe operation and maintain performance specifications. ..21
DC HiPot test and set-up ..................................................................................................................22
HiPot overcurrent trip........................................................................................................................24
HiPot application tips .........................................................................................................................24
Resistance temperature compensation............................................................................................25
5........................................................................................................................................................................27
SURGE TESTING ............................................................................................................................................27
Principles of Surge testing .......................................................................................................................27
Other Important Safety warnings .....................................................................................................28
17) Repair Parts Warning : Defective, damaged, or broken test leads must be replaced with
factory-authorized parts to ensure safe operation and maintain performance specifications. ..29
Surge comparison testing..................................................................................................................29
Examples of Surge comparison testing ............................................................................................30
Surge comparison testing against a standard or master coil ........................................................31
Single coil Surge test and set-up .....................................................................................................31
Three phase motor Surge comparison test and set-up .................................................................33
Surge voltage measurement.............................................................................................................34
Notes for Surge and Surge comparison tests .................................................................................35
Factors affecting the Surge testers output......................................................................................35
12/2/2009 | 71-002-V5 EN 3
ST103A, ST106A, ST112A
Table of Contents
12/2/2009 | 71-002-V5 EN 4
ST103A, ST106A, ST112A
Table of Contents
12/2/2009 | 71-002-V5 EN 5
ST103A, ST106A, ST112A
Table of Contents
12/2/2009 | 71-002-V5 EN 6
ST103A, ST106A, ST112A
1
Preface
Important safety information
General Safety Precautions
Note: The general safety information presented here will be for both operating and service
personnel. Specific warnings and cautions will be found throughout this manual where they
apply.
Note: If the equipment is used in any manner not specified by Baker Instrument Company,
an SKF Group Company, the protection provided by the equipment may be impaired.
WARNING: Indicates a hazardous situation which, if not avoided, could result in death or
serious injury.
CAUTION: Indicates a hazardous situation, which, if not avoided, could result in minor or
moderate injury.
NOTICE: NOTICE is the preferred signal word to address practices not related to personal
injury.
Danger
High Voltage
To prevent serious injury or death:
- Do not use in explosive atmospheres.
- Do not contact test leads or device being testing
while test is in progress or during discharge period.
- Do not connect test leads to live circuits.
Read and follow safety precautions and safe operating
practices in operator manual. Do not exceed maximum
operating capabilities of this instrument.
1) Never attempt a two-party operation. Always know what test is being performed and
when. FOR EXAMPLE: DO NOT adjust test leads when footswitch is being operated.
Leads will have live voltage and severe electric shock may result.
12/2/2009 | 71-002-V5 EN 7
ST103A, ST106A, ST112A
Safety Precautions & Notices
4) Make sure the tester leads are disconnected before the motor is energized or powered
up.
5) Do not remove the product covers or panels or operate the tester without the covers
and panels properly installed. Components on inside of tester carry voltage for operation
and if touched can render a shock.
6) Use appropriate safety equipment required by your organization, including high voltage
globes and eye protection.
7) Repair Parts Warning : Defective, damaged, or broken test leads must be replaced
with factory-authorized parts to ensure safe operation and maintain performance
specifications.
8) Ground the product : This product is grounded through the grounding conductor of the
power cord. To avoid electrical shock, plug the power cord into a properly
wired/grounded receptacle before connecting the product test leads.
10) The unit is for indoor use. If used outdoors, the unit must be protected from rain, snow
and other contaminants.
Operation notes
Irregularities, particularly vertical peaks, may be seen in the first cycle of the wave
pattern. These occur most frequently on large, high voltage motors. Do not interpret
these as faults in the winding. Any winding fault will be seen through the entire wave
pattern.
Do not change the Test Lead Select, if so equipped, switch setting during a test.
When increasing the applied voltage, switch to a higher Volts/Div setting so the entire
wave pattern remains visible on the display.
12/2/2009 | 71-002-V5 EN 8
ST103A, ST106A, ST112A
Safety Precautions & Notices
Always return the Output Voltage control to Min when a test is complete. Begin each
test at the Min voltage setting. Failure to do so may result in damage to the test winding
and/or the tester.
Symbols on equipment
Protective conductor terminal. Located beside black ground test lead
on front panel of instrument.
Other Information
Installation requirements
The unit may be operated
12/2/2009 | 71-002-V5 EN 9
ST103A, ST106A, ST112A
Safety Precautions & Notices
Users Manual
Environmental
The tester should only be operated in temperatures ranging from 0 to 100 degrees
Fahrenheit (-17.8 to 37.8 degrees Celsius).
As with all insulation dielectric and resistivity measurements, humidity will affect the condition
of the instruments components over time. Relative humidity of the storage environment
should be less than 50 percent.
Storage (indoor/outdoor)
This instrument should not be stored in any location where water entry to the instrument
could occur. Also, humidity will affect the operation of the instrument.
Shipment
All Baker testers are shipped using factory foam-filled containers. Should the tester be
returned to Baker Instrument Company, an SKF Group Company for any reason, we
recommend using the original packaging the unit came in or the following factory specified
packaging:
12/2/2009 | 71-002-V5 EN 10
ST103A, ST106A, ST112A
2
Instrument overview
2) Line in
The external AC power supply plug wire is inserted here.
3) On/off
The On/Off switch contains a circuit breaker and a green On indicator lamp.
4) Focus
Rotate this control to adjust the clarity of the trace on the display from a wide, thick line to a
narrow, fine line.
5) Intensity
This control will adjust the intensity or brightness of the display. Clockwise (CW) will increase
intensity. Counterclockwise (CCW) will decrease intensity. Intensity has a slight effect on the
focus. It can be adjusted to a blank screen.
6) Horizontal position
Rotate this control to adjust the side-to-side position of the surge wave pattern. A trace that
begins at the far left is suggested for surge testing.
7) Vertical position
This control adjusts the up or down position of the surge wave pattern. The optimum
positioning is usually on center or one major graticule line below center for the surge test.
Two or more graticule lines below center is usually optimum for the HiPot test.
8) Sweep
The sweep adjusts the seconds per division, or sweep rate, or the trace on the display. This
control will have the effect of expanding or contracting the wave pattern when surge testing.
12/2/2009 | 71-002-V5 EN 11
ST103A, ST106A, ST112A
Instrument Overview
There are six markings corresponding to 5, 10, 20, 50, 100, and 200 microseconds per
division. The lower values represents the slowest rate and higher numbers represent the
fastest. Markings on the face panel indicate approximate sweep rates. The sweep rate is not
calibrated and should be used for indication only.
NOTICE
During the surge test, with the SWEEP control at the lowest possible setting, the
ringing pattern must be at least one division in length for one full cycle. Less than
one division for the first cycle indicates a very low inductive load. DAMAGE to the
instrument is possible when operated for an extended period of time with a low
inductive load.
9) Function selector
This control selects the type of test to be performed and the sensitivity of the DC HiPot
leakage current display. There are four primary positions as follows:
Note: The Zero Start Interlock is disabled when this function is selected.
10) Volts/div
This control sets the sensitivity of the display or scale factor in volts per division for both the
surge and HiPot test traces. There are four settings corresponding to 250, 500, 1000, 2500
volts per division.
Note: The volts/Division setting values may not be valid using some accessories.
Note: This control does not affect or limit the output voltage of the tester!
13) HiPot current select switch and light (12kV testers only)
This push-button and indicator light combination on ST112 and ST212 testers selects either
Internal or External HiPot display functions. This switch has two positions as follows:
12/2/2009 | 71-002-V5 EN 12
ST103A, ST106A, ST112A
Instrument Overview
Internal For stand alone operation of the tester, this button should be in the out
position, with its indicator light off. The unit will then display Internal HiPot readings of
voltage and leakage current taken from the testers own test leads.
External When this button is depressed and the indicator light is on, the display will
show the readings of HiPot readings obtained from external units, such as a 24 kV
Power Pack (See Appendix D: PP124/PP224 Power Pack).
Note: A Zero Start Interlock is used with this control during surge and HiPot tests. The user
must return the Output Control to MIN for each test. In other words, if the Test button is
pressed while the Output Control is rotated above MIN the testers output is disabled until the
Output Control is rotated to MIN. The Zero Start Interlock is disabled for AT101 testing.
NOTICE
When testing a highly inductive coil (high turns counts), it is possible to develop
voltages in excess of the testers rated output. Damage may occur to the tester. Use
caution to limit the output to no more than the instruments rating. Monitor the
voltage by observing the display.
16) Test
The Test button activates the high voltage output of the tester. One of the selected modes,
surge or HiPot, will be enabled and a voltage will be impressed on the device being tested.
This button automatically disengages when released.
Settings 1-2, 2-3, 3-1 are for surge testing. The red Test Leads (20) are numbered and
correspond to these settings. The lead number setting indicates which test leads are Hot
or energized.
The HiPot position energizes test lead #1 and opens test leads #2 and #3.
The Leads Ground position holds all three red leads at the same grounded potential as
the black Ground lead. It is a safety feature that should always be used whenever the
operator touches the testers leads to change their position. Use the chart below as a
reference for TLS positions and lead potential.
12/2/2009 | 71-002-V5 EN 13
ST103A, ST106A, ST112A
Instrument Overview
12/2/2009 | 71-002-V5 EN 14
ST103A, ST106A, ST112A
3
Test procedures and voltages
Throughout this manual, Baker Instrument Company, an SKF Group Company will
recommend various procedures that should be followed for the most efficient and safe use of
your tester. These procedures have been developed through constant feedback from you, the
user.
Baker Instrument Company, an SKF Group Company recommends that you perform the DC
HiPot test first, in order to determine if a windings ground wall insulation has failed. If this
occurs, it is not necessary to proceed with any further testing the winding is bad. If the test
piece passes the DC HiPot test, it is then appropriate to proceed with the Surge test.
12/2/2009 | 71-002-V5 EN 15
ST103A, ST106A, ST112A
Test Procedures, Voltages & Applicable Standards
2) Connect the tester power cord to a 110-120 VAC outlet (or 220-240 VAC outlet for
203, 206, 212 machines). The tester will work on either 60 Hz (103, 106, 112) or 50 Hz
(203, 206, 212).
4) Turn the tester On/Off switch to On. Allow a brief period for CRT warm-up. A display
trace should appear in seconds.
5) If the CRT does not display anything, turn the unit Off immediately and recheck the steps
above. Also, check that the Intensity is not turned fully counterclockwise. Turn the tester
On to obtain a display on the CRT. If no display is noticed, turn the unit Off and call Baker
Instrument Company, an SKF Group Companys Service Department. Refer to Warranty
Notes and Appendix B: Troubleshooting for calling information.
Recommended voltages
A recommended value for DC High Potential (HiPot) and Surge voltage to test a motor,
generator, or transformer in service is twice the line voltage plus 1000 volts. This test voltage
value is consistent with NEMA MG-1, ANSI/IEEE 95-1977 (test voltages greater than 5000V)
and IEEE 43-1974 (test voltages less than 5000V).
For new windings or rewound motors, this potential is sometimes increased by a factor of
1.2 or as much as 1.7. This provides for a higher level of quality control on the work
performed. For the above 460 V motor, the test voltage may be:
Note: Although the CRT display is accurately calibrated, it is not possible to discern small or
minor voltage increments. It is suggested that the formula answers be rounded off, or more
specifically, rounded to the nearest minor graticule division discernible.
12/2/2009 | 71-002-V5 EN 16
ST103A, ST106A, ST112A
Test Procedures, Voltages & Applicable Standards
Recommended Standards
12/2/2009 | 71-002-V5 EN 17
ST103A, ST106A, ST112A
Test Procedures, Voltages & Applicable Standards
12/2/2009 | 71-002-V5 EN 18
ST103A, ST106A, ST112A
4
DC HiPot Testing
Principles of DC High-Potential (HiPot) testing
DC HiPot Testing has proved to be a useful tool to evaluate, non-destructively the dielectric
strength of ground insulation. No insulation is perfect and all have some conductivity, so some
current flows or leaks along or through the insulation to ground. By charging the winding to
a specific test voltage and holding the frame at ground, leakage current can be monitored.
Insulation resistance can be measured and dielectric strength assured with a DC HiPot Test.
The resistance is determined by dividing the voltage impressed on the coil by the leakage
current measured. Both are monitored with the DC HiPot test.
Determining resistance via voltage impressed and leakage current can be understood with the
analogy of a water pipe. Two tests of the pipe are possible. Imagine a water pipe, which has
no leaks and is capable of withstanding a maximum pressure. If a small hole is drilled in the
pipe, a certain amount of water would escape and cause leakage. An increase of water
pressure in the pipe would cause a measurable increase in the leakage of water, but it would
not necessarily rupture the pipe. In the second test, if a pipe with no holes were worn thin
and the pressure increase to test the pipes strength, at some pressure it may rupture,
allowing all the water to be released.
In an electrical conductor, the pipe would be an insulator and the water pressure would be
the voltage impressed on it. Leakage current in the insulator would be comparable to water
flowing through the hole in the pipe. As voltage is increased on the leaking insulator there
would be a corresponding increase in leakage current. Higher leakage currents (a larger hole
in the pipe) corresponds to lower resistance of the insulation to the flow of current. A perfect
insulator (pipe with no holes) is said to have high resistance.
The second test, where the pipe is subjected to rupturing, is comparable to measuring the
dielectric strength or dielectric limit of the insulation. The possibility of rupturing is
measured in an electrical conductor with a high potential (HiPot) test. The point of rupture is
called the dielectric limit of the insulation material. In HiPot Testing, the voltage (water
pressure on the pipe) is increased on the coil. However, the DC HiPot test does not
breakdown the insulation. Good insulation has a dielectric strength value much higher than
the operating voltage of the apparatus and common field test voltages. The HiPot Test is used
to ensure that the insulation DOES NOT breakdown or rupture at a prescribed test value. The
test voltage should be less than the rated dielectric strength of the insulation. If the insulation
does fail under the test, the insulation to ground is unreliable and the apparatus is unusable.
Knowledge of the real behavior of resistors, not just ideal resistors, will help the operator to
test the winding insulation to a point before the insulation is broken down.
12/2/2009 | 71-002-V5 EN 19
ST103A, ST106A, ST112A
DC HiPot Testing
For an ideal resistor, good or poor, as the voltage is increased, the leakage current will
increase proportionately and indefinitely (Fig 4-1). However, insulation resistance in the real
world rarely behaves in this manner. Instead, the current in a typical resistor will increase
proportionately with voltage until the voltage is within as little as 5% of the breakdown
voltage. Just before insulation breakdown, the current will rise faster than the voltage.
At still higher voltage, the insulation will completely breakdown and the current will rise
extremely fast.
The key to DC HiPot testing is to look for leakage current that is rising faster than the
increase in voltage that is applied to the winding. The test can then be stopped before the
insulation is damaged. (For more information on DC HiPot tests refer to IEEE-95-1977 which
describes test procedures, voltages, safety, and interpretation.)
The HiPot test is considered the mainstay of motor testing. HiPot tests can be performed in
one of two ways, AC or DC. Although the Surge test will test for grounds, it does not
uniformly test all the ground wall insulation as thoroughly a the HiPot test. Nor does the
Surge test give a quantitative value of the leakage current to ground
The HiPot brings the entire motor winding up to the same potential. Since all the windings
are at the same potential, there is no turn-to-turn, or phase-to-phase insulation stress.
There is uniform voltage stress applied between the winding insulation and the ground wall.
As discussed before the theory behind the test is based on simple leak current. Given any
good insulation, the current leakage through the insulation should be very low and therefore
the insulation resistance very high, and vise versa. The formula associated with this test is R =
E/I. This formula states that resistance is equal to voltage divided by current, or put another
way, resistance is inversely proportional to current for a given voltage.
The HiPot tester provides a voltage variable up to some limit. The resistance is that of the
ground wall to ground or the motor frame. Using the formula, the higher the resistance for a
given voltage, the lower the leakage current, and vise versa.
Baker Instrument Company, an SKF Group Company testers provide the DC HiPot test as a
separate and added function to the Surge testing unit. The Baker tester provides a variable
voltage source to apply to motor windings and a state of the art CRT display for both voltage
and current readings.
During a typical DC HiPot test, all motor output leads are tied together and connected to test
lead #1. The tester ground lead is connected to the motor frame. The output voltage is raised
to some predetermined test voltage and a current reading is measured. The lower the
leakage current reading for the given voltage, the better the ground wall insulation.
12/2/2009 | 71-002-V5 EN 20
ST103A, ST106A, ST112A
DC HiPot Testing
Danger
High Voltage
To prevent serious injury or death:
- Do not use in explosive atmospheres.
- Do not contact test leads or device being testing
while test is in progress or during discharge period.
- Do not connect test leads to live circuits.
Read and follow safety precautions and safe operating
practices in operator manual. Do not exceed maximum
operating capabilities of this instrument.
1) Never attempt a two-party operation. Always know what test is being performed
and when. FOR EXAMPLE: DO NOT adjust test leads when footswitch is being
operated. Leads will have live voltage and severe electric shock may result.
4) Make sure the tester leads are disconnected before the motor is energized or
powered up.
5) Do not remove the product covers or panels or operate the tester without the
covers and panels properly installed. Components on inside of tester carry voltage
for operation and if touched can render a shock.
7) Repair Parts Warning : Defective, damaged, or broken test leads must be replaced
with factory-authorized parts to ensure safe operation and maintain performance
specifications.
8) Ground the product : This product is grounded through the grounding conductor
of the power cord. To avoid electrical shock, plug the power cord into a properly
wired/grounded receptacle before connecting the product test leads.
Danger from loss of ground Upon loss of the protective ground connection,
all accessible conductive parts, including knobs and controls that may appear
to be insulated, can cause an electric shock!
12/2/2009 | 71-002-V5 EN 21
ST103A, ST106A, ST112A
DC HiPot Testing
10) The unit is for indoor use. If used outdoors, the unit must be protected from rain,
snow and other contaminants.
1) Turn the Function switch to one of the HiPot Micro-Amps/Div settings. The highest
scale setting is suggested. This setting defines the number of micro-amps of current
measured per one graticule division on the CRT display.
NOTE: Test standards recommend starting at the 100 microamp/division setting. In the
event of a dead short, the fault will be readily detectable. The lowest setting gives the
operator the greatest sense of understanding and control of what is occurring as the winding
is being charged during the test. However, the desired test voltage can be reached faster by
initially using the highest setting. The 100 setting decreases sensitivity and prevents
overcurrent tripping due to charging currents.
2) Rotate the vertical control to position the trace on the CRT display to near the bottom of
the screen, behind one of the graticule lines. This graticule will serve as the zero
reference line.
3) Switch the Test Lead Select (TLS) to the HiPot Setting. This selects the red test lead
#1 as Hot. The black lead is the Ground. Lead #2, and #3 are open.
5) Check the circuits to ensure that capacitors or other devices are not connected. Not only
could this be hazardous to the person performing the test, but it will also provide
inaccurate results.
7) Connect the black Ground lead to a clean ground on the frame or core of the equipment
under test.
12/2/2009 | 71-002-V5 EN 22
ST103A, ST106A, ST112A
DC HiPot Testing
Note: It is not recommended to use the motor junction box for grounding.
To test, depress and hold the Test button and slowly raise the voltage with the Output
Control.
Note: The rate at which the Output Control is increased affects the amount of current
necessary to charge the winding. Slowly raising the output (voltage) will keep charging current
at low levels. Monitor the current indication on the right half of the display to observe the
charging current levels.
CAUTION
This test should be stopped immediately, if at any time a fast sharp rise in the current
is seen.
Danger
Use extreme caution.
Completely discharge the equipment under test
By moving the TLS position to LEADS GROUND
For a time equal to the duration of the test just completed.
As the voltage is applied to the motor, two horizontal lines appear on the display. The applied
voltage is seen on the left half of the display as a steadily rising horizontal line. The current,
also a horizontal line, will rise and fall on the right half of the display, showing the current
necessary to charge the windings. Once the winding is charged the current falls. The steady
state current is the leakage current level.
Once the test voltage has been reached, turn the Micro-Amps/Div switch to the lowest
setting that will still display a current bar on the screen.
12/2/2009 | 71-002-V5 EN 23
ST103A, ST106A, ST112A
DC HiPot Testing
Fig 4.3 Good insulation with Fig 4.4 Poor insulation with low voltage
high voltage and low leakage 8)andMaintain the current.
high leakage test potential for one (
9)
10) 1) minute. If instability or a sharp rise in the current (right half of display) is noted,
discontinue the test immediately.
11) Measure the leakage current by multiplying the number of major graticules or divisions
of deflection of the trace from the zero reference line by the Micro-Amps/Div setting.
12) When the test is complete, release the Test button and return the Output Control to
minimum. The voltage bar will gradually return to the baseline as the winding
capacitance is discharged through the internal resistance of the tester.
Note: The current trace will temporarily go negative as the winding discharges. Allow a
sufficient time for the test winding to discharge completely. Recommended practice is to
ground the leads of the test winding for a time equal to the time the test potential was
applied. Baker recommends using the TLS Leads Ground position. (When the current trace
returns to zero from its negative position, the windings are discharged.)
Windings that are grounded will cause the current trace to quickly go off screen and the HiPot
over-current trip to activate.
Note: Before beginning the DC HiPot test, the HiPot over-current safety trip may be used to
verify that a good ground has been made with the black ground lead. After making the
connection to the frame (ground) with the ground lead, connect red lead #1 to another point
on the frame. Keep the Output Control at minimum and press the Test button. A good
ground connection will activate the overcurrent trip at the slightest increase of output (trip
sensitivity is affected by current setting). If the trip does not operate, reconnect the ground
and repeat this test. Ensure the continuity of the ground lead. Often the paint on the device is
preventing a good ground and may need to be scraped off.
12/2/2009 | 71-002-V5 EN 24
ST103A, ST106A, ST112A
DC HiPot Testing
The DC HiPot test component of the tester can test the insulation between any two
conductors. For example, it may be used to test the insulation between feeder cables and
the ground lead on the others. Follow the same procedures outlined for HiPot Testing.
Change these connections to test all cables.
The Rule of Thumb for determining the effect of temperature on resistance measurements is
that resistance halves for each 10oC (Celsius) rise in winding temperature. Usually, the
baseline temperature is 40oC for windings. This rating is usually found on the motors data
plate. The following two examples illustrate this relationship.
12/2/2009 | 71-002-V5 EN 25
ST103A, ST106A, ST112A
DC HiPot Testing
12/2/2009 | 71-002-V5 EN 26
ST103A, ST106A, ST112A
5
Surge testing
Principles of Surge testing
Prior to the introduction of surge testing, the most common electrical test for motors was a
low-potential test of the winding insulation to ground (or frame). This popular test is the
Insulation Resistance or Meg-Ohm test. This test is adequate for testing winding insulation to
ground, but it does not detect failures between turns or phases.
A more thorough test is the Surge Test. A typical motor coil consists of copper wire turns or
windings. Motor winding insulation failure often starts as a turn-to-turn, copper-to-copper,
or winding-to-winging fault. Surge Tests can detect the early stages of insulation failures in
the winding such as a coil-to-coil failures, short circuits, grounds, misconnections, and wrong
turn counts without permanently damaging the winding.
Brief voltage surges (or pulses) are applied to the coil during a Surge Test to create a voltage
gradient (or potential) across the length of the wire in the winding. This gradient produces a
momentary voltage stress between turns.
The coil will respond, in the time periods between pulses, with a ringing or damped sinusoidal
waveform pattern. Each coil has its own unique signature ringing or wave pattern which can
be displayed on a CRT display screen.
The wave pattern observed during a Surge Test is directly related to the coils inductance.
(There are other factors influencing the wave pattern but inductance is the primary one.) The
coil becomes one of two elements in what is known as a tank circuit a LC-type circuit made
up of the coils inductance (L) and the surge testers internal capacitance (C).
Inductance (L) of a coil is basically set by the number of turns in a winding and the type of
iron core it rests in. The frequency of the wave pattern is determined by the formula:
1
Frequency =
2 LC
This formula implies that when the inductance decreases, the frequency will increase.
A surge test can detect a fault between turns that is due to weak insulation. If the voltage is
greater than the dielectric strength of the turn insulation, one or more turns may be shorted
out of the circuit. In effect, the number of turns in the coil is reduced. Fewer working turns
reduces the inductance of the coil and increased the frequency of the ringing pattern from the
surge.
12/2/2009 | 71-002-V5 EN 27
ST103A, ST106A, ST112A
Surge Testing
The voltage or amplitude of the surge wave pattern is also reduced due to the decrease in
inductance of a coil with a fault between turns. It is determined by the formula:
di
Voltage = L
dt
Where the current (i) varies according to pulse time (t)
When the insulation between turns is weak, the result is a low energy arc-over and a change
in inductance. When this happens the wave pattern becomes unstable it may shift rapidly to
the left and right, and back to the original position.
The Surge Test is most often used to test turn-to-turn insulation of coils or single windings.
Form coils, start and run windings, and multi-tapped windings are a few examples. Surge
Tests are also used to compare new windings to a standard winding to assure they conform.
Danger
High Voltage
To prevent serious injury or death:
- Do not use in explosive atmospheres.
- Do not contact test leads or device being testing
while test is in progress or during discharge period.
- Do not connect test leads to live circuits.
Read and follow safety precautions and safe operating
practices in operator manual. Do not exceed maximum
operating capabilities of this instrument.
11) Never attempt a two-party operation. Always know what test is being performed
and when. FOR EXAMPLE: DO NOT adjust test leads when footswitch is being
operated. Leads will have live voltage and severe electric shock may result.
13) Upon completion of a DC High Potential, Megohm, Polarization Index, Step Voltage,
Dielectric absorption, or Continuous Ramp test, before disconnecting the test leads,
short the winding, motor, etc., to ground and allow time for discharge. If this is not
done, voltage may still be active on leads and tested components.
12/2/2009 | 71-002-V5 EN 28
ST103A, ST106A, ST112A
Surge Testing
14) Make sure the tester leads are disconnected before the motor is energized or
powered up.
15) Do not remove the product covers or panels or operate the tester without the
covers and panels properly installed. Components on inside of tester carry voltage
for operation and if touched can render a shock.
16) Use appropriate safety equipment required by your organization, including high
voltage globes and eye protection.
17) Repair Parts Warning : Defective, damaged, or broken test leads must be replaced
with factory-authorized parts to ensure safe operation and maintain performance
specifications.
18) Ground the product : This product is grounded through the grounding conductor
of the power cord. To avoid electrical shock, plug the power cord into a properly
wired/grounded receptacle before connecting the product test leads.
Danger from loss of ground Upon loss of the protective ground connection,
all accessible conductive parts, including knobs and controls that may appear
to be insulated, can cause an electric shock!
20) The unit is for indoor use. If used outdoors, the unit must be protected from rain,
snow and other contaminants.
Because the wave pattern of a Surge Test is unique to the coil being tested (due to its unique
number of turns, type of wire and insulation, orientation, etc) wave patterns of supposedly
identical coils should also be identical. Any difference in the coil (more or less turns, insulation
break-down, orientation, etc.) would result in a different wave pattern during the Surge Test.
These differences are most often due to a fault in the winding.
The A Series Tester provides a means for observing very small differences in Surge Tests,
making it very sensitive to any faults in the windings. The tester does this by simultaneously
superimposing the wave patterns of two Surge Tests.
When the wave pattern of two equal voltage Surge Tests are displayed simultaneously, if
a single wave pattern is seen, the phases being tested are equal in their inductance. In
other words the phased or windings have the same number of turns, insulation,
orientation, etc. and are considered to be good.
When the wave patterns of two equal voltage Surge Tests are displayed simultaneously,
if two distinct wave patterns are seen, the phases being tested are not equal in their
inductance. There probably is a fault in one of the windings or there is some other cause
for the differing inductance. For example, the faulted winding may have shorted turns
compared to the complete phase, reducing the inductance, and thus altering the wave
pattern. (An exception would occur as in the case for Rotor Loading as described later.)
12/2/2009 | 71-002-V5 EN 29
ST103A, ST106A, ST112A
Surge Testing
Fig 5-2: Good Comparison Pattern. Only one wave appears on the surge tester screen
when two tests are displayed simultaneously. (The wave patterns being compared are
superimposed exactly.)
When one of the phases has a fault, one of two things will be seen on the tester. (See Fig 5-
3.)
The wave pattern may become erratic during the test, indicating intermittent shorting in
the winding and arc-over (left example in Fig 5-3).
The wave pattern for the faulted phase may appear stable, but when it is compared to
the wave pattern of another good phase, it will be slightly different in comparison (right
example in Fig 5-3). This is indicative of a fault in the phase associated with the differing
wave pattern. Usually, this wave pattern is decreased in amplitude and has a lower
frequency which shifts it toward the left.
Fig 5-3: Faulty Surge Patterns: Waveforms are erratic during the test (left) or
separated throughout the entire trace (right).
12/2/2009 | 71-002-V5 EN 30
ST103A, ST106A, ST112A
Surge Testing
The surge tester will simultaneously display the surge wave patterns of both coils or windings
on the display. If they are the same, the patterns will superimpose and appear to be one wave
pattern. If the test coil or winding is not the same as the standard, due to a fault or arcing in
the coil, two wave patterns will appear on the screen.
1) With the Test Lead Select (TLS) switch in the Leads Ground position, make the following
connections.
a) Connect the red #1 and #2 leads on one side of the coil or winding.
b) Connect test lead #3 to the opposite side of the two terminal device. Connect the
ground lead to the frame or metal core material. (Refer to Single Coil Surge Test
and Set-Up on page 49 for detailed instruction.)
2) Turn the Function switch to the Surge position. The surge display should be blank with a
horizontal line centered in it. This line is the reference zero or base line.
4) Set the Volts/Div switch at the lowest setting that will allow the maximum pattern to be
viewed entirely on the screen.
Example: For a test voltage of 2000 V, a Volts/Div setting of 500 will give a wave pattern
with 4 divisions of amplitude that does not go off the screen. For a test voltage of 4000 V, a
12/2/2009 | 71-002-V5 EN 31
ST103A, ST106A, ST112A
Surge Testing
setting of 500 Volts/Div would result in a wave pattern with 8 divisions amplitude which
would go off the screen.
b) Depress and hold the Test button (or Footswitch). The Leads Energized light
will come on, indicating that the test leads are hot.
c) Slowly raise the Output, applying voltage to the test windings. Carefully
monitor the trace on the display and adjust the Volts/Div and Sweep controls to
get the best waveform possible.
d) Adjust the Output and Volts/Div controls to the desired voltage level while
maintaining a fully visible wave pattern on the display. The voltage is measured
from the zero line to the first positive peak (at the far left) of the trace
multiplied by the displayed Volts/Div setting.
First
Zero
Line
e) When the test for the lead is complete, the Test button may be released. Return the
Output to minimum. The Lead Energized light will turn off.
If the surge wave pattern appears steady and stable, the winding insulation is
sufficient to withstand the applied voltage and the test is successful.
Note: If the wave pattern begins to flicker or rapidly shift left and right and/or up
and down as the Output is increased, there is weakness in the winding insulation
and intermittent arcing between the windings or phases. The winding or phase
contains a fault when the wave pattern shift to the left and the amplitude drops.
The more severe the shift and amplitude drop, the more severe the fault. Faults are
often accompanied by an audible arcing sound. When an obvious fault is present,
the motor is bad. End the test by releasing the Test button and disconnecting the
motor from the tester.
6) Reverse the test leads on the coil. In other words, connect test leads #1 and #2 to the
other side of the coil and test lead #3 and ground to the opposite side. This is done to
shoot the coil in the opposite direction.
7) Repeat Step 5, bringing the peak voltage to the same value used in the first test.
In summary, for each direction the coil is tested, you will check the display for the wave
pattern produced in each test. If you see stable patterns, the winding is good. If you see
anything other than good patterns there is a possible fault. Refer to Determination of a Fault
for explanations of wave patterns indicating good or faulty windings. Refer to Surge Test
Applications for descriptions of wave patterns for a variety of devices. Keep in mind, fault
determination is often a result of experience.
12/2/2009 | 71-002-V5 EN 32
ST103A, ST106A, ST112A
Surge Testing
The motor can be tested remotely through feeder cables (or a motor control center), however;
it must be a direct path. No other electrical elements can be in the path such as surge
arrestors or power factor capacitors.
1) With the Test Lead Select (TLS) switch in the Leads Ground position, make the
appropriate connection as follows:
a) Connect all three red test leads to the motor input leads. Any order is fine but Baker
Instrument Company, an SKF Group Company recommends test lead #1 to motor
output lead #1, #2 to #2, and #3 to #3. Refer to the chart Test Lead Connections
(page 25) to know which leads will be tested for any given TLS switch position.
b) Connect the black Ground lead to the frame or housing of the motor.
Fig 5-5: Examples of how to connect test leads for three phase motor surge
testing.
2) Turn the Function switch to the Surge position. The surge display should be blank with a
horizontal line centered in it. This line is the reference zero or base line.
3) Set the Volts/Div switch at the lowest setting that will allow the maximum pattern to be
viewed entirely on the display.
Example: For a test voltage of 2000 V, a Volts/Div setting of 500 will give a wave pattern with 4
divisions of amplitude that does not go off the screen. For a test voltage of 4000 V, a setting of
500 Volts/Div would result in a wave pattern with 8 divisions amplitude which would go off the
screen.
4) Select TLS position 1-2. These leads will be Hot. Refer to the chart Test Lead
Connections (page 25).
12/2/2009 | 71-002-V5 EN 33
ST103A, ST106A, ST112A
Surge Testing
d) Adjust the Output and Volts/Div controls to the desired voltage level while
maintaining a fully visible wave pattern on the display. The voltage is measured
from the zero line to the first possible peak (at the far left) of the trace multiplied by
the display Volts/Div setting.
e) When the test for the lead is complete, the Test button may be released. Return the
Output Control to minimum (full CCW). The Leads Energized light will turn off.
If the surge wave pattern(s) appears steady and stable, the winding insulation is
sufficient to withstand the applied voltage and the test is successful.
Note: If the wave pattern begins to flicker or rapidly shift left and right and/or up
and down as the Output is increased, there is weakness in the winding insulation
and intermittent arcing between the windings or phases. The winding or phase
contains a fault when the wave pattern shifts to the left and the amplitude drops.
The more severe the shift and amplitude drop, the more severe the fault. Faults are
often accompanied by an audible arcing sound.
When an obvious fault is present, the motor is bad. End the test by releasing the
Test button and disconnecting the motor from the tester.
f) Repeat Step 5 for each position of the TLS (position 2-3 and then position 3-1),
bringing the peak voltage to the same value used in the first test.
For the Surge Comparison Test, determine if there is an individual coil or phase with
winding faults. The basic method here is to compare all of the wave patterns for
each winding or coil in pairs. For identical windings, all three wave patterns should
be identical. If one or two windings are different in any way, the wave patterns will
show differences when compared.
In general, for each phase or coil of the motor that is tested, you will check the
display for a wave pattern and compare it to another wave pattern for that motor. If
you see three good, stable patterns or separations in the patterns when compared
there is a possible fault. Refer to Determination of a Fault and Surge Test
Applications for more information. Keep in mind, fault determination is often a
result of experience.
12/2/2009 | 71-002-V5 EN 34
ST103A, ST106A, ST112A
Surge Testing
For example, on a large high voltage motor a 6000 V tester may only be capable of
producing 4000 V. The load is too great for the testers power supply. The test is valid up
to this load.
If this condition is encountered, call Baker Instrument Company, an SKF Group Company
for assistance. Some test tips may be available to overcome this limitation. Also see
Factors affecting the Surge testers output.
The test should be considered successful if the desired voltage level can be reached.
For the example above, if the motor is 3000 horsepower and operated at 2300V, a
recommended test voltage would be 2 x 2300 V + 1000 V = 5600 V. The size of the
motor limits the testers output below its rating, but an appropriate test voltage (above
5600 volts) can be reached.
Adjacent windings such as a start winding, part winding, high or low-voltage winding
should be jumpered together and grounded during testing. This procedure eliminates
incorrect test results caused by inductive coupling.
Several factors may individually, or in combination, reduce the ability of a surge tester to
generate the recommended test voltage. It should be noted that in some cases, with adapted
test procedures, motors larger than the recommended maximum size to tested have been
successfully tested to the recommended test voltage levels. In many cases, a larger, higher
12/2/2009 | 71-002-V5 EN 35
ST103A, ST106A, ST112A
Surge Testing
output voltage surge tester that is overrated for particular motor sizes may be needed if
factors exist which will load the testers output.
The following table of information shows various factors which will reduce the output voltage
of a Baker Instrument Company, an SKF Group Company Surge Tester below its maximum
rating. The table is based on general information and does not comprehensively cover every
motor and/or design or configuration that exists.
NOTICE
Factor Effect
Motor is larger than Capacitance and inductance of motor windings can load the tester
the recommended output down. Output voltage is reduced below maximum. Damage to
maximum size to test. the tester can occur if testing occurs for an extended period of time.
Note: The test is considered successful if the test voltage 2E +1000V is
achieved, although that voltage may be below the rated output of the
tester.
Motor RPM is slow. For each reduction of the motors RPM (ie 3600>1800) the effective
horsepower of the motor that the surge tester senses is doubled.
Example: A 500 hp/3600 RPM motor = 500 hp A 500 hp/1800 RPM
motor = 1000 hp. A 500 hp /900 RPM motor = 2000 hp, etc.
Motor has high Same condition as above comments on motor RPM
number of poles
Feeder cable length Distributed capacitance of the feeder cable loads down the test
according to the approximate formula:
C Tester
V max capable = V Tester X
C tester + C cable
Feeder cable shielded The above condition becomes extreme. Shielded feeder cables lengths
of less than 50 feet are recommended if attempting to test from the
Motor Control Center (MCC).
High horsepower The low winding impedance of these motors require high tester output
motors at low energy to surge test windings. Select a tester based on the maximum
operating voltage recommended AC motor to test which will cover the horsepower rating
of the motor, then go up one model in maximum test output voltage.
Testing is generally required at the motor, or if from the Motor Control
Center, very short feeder cable length. The Power Pack option may be
necessary.
Motor assembled with The presence of the rotor will load the tester by drawing energy from
rotor in place the tester like the secondary of a transformer. Refer to Rotor Loading
(Coupling) when Testing Assembled Motors.
12/2/2009 | 71-002-V5 EN 36
ST103A, ST106A, ST112A
Surge Testing
Determination of a fault
There are only five main wave patterns to remember which are obvious from an
understanding of the test. These are:
Open circuit.
Ground winding.
Note: If all three wave pattern comparisons in surge testing show considerable separation
when testing three phase windings, the motor has a phase-to-phase short.
Instability
If the wave pattern begins to flicker or rapidly shift left and right and/or up and down as the
Output is increased, there is a weakness in the winding insulation and intermittent arcing
between the winding or phases. The winding or phase contains a fault when the wave pattern
shifts to the left and the amplitude drops. The more severe the shift and amplitude drop,
the more severe the fault. These faults are often accompanied by an audible arcing sound.
12/2/2009 | 71-002-V5 EN 37
ST103A, ST106A, ST112A
Surge Testing
Figure 5.9 exemplifies this. Wave comparison 1-2 and 2-3 show differing wave patterns,
while wave comparison 3-1 shows identical patterns for the two leads. The fault must be in
the phase connected to test lead 2. In other words, wave comparison 3-1 shows
superimposing wave patterns because the bad phase was not compared.
12/2/2009 | 71-002-V5 EN 38
ST103A, ST106A, ST112A
Surge Testing
12/2/2009 | 71-002-V5 EN 39
ST103A, ST106A, ST112A
Surge Testing
Open circuit
Open circuit indications are almost always the same for wye and delta-connected motors. For
each, an open circuit is indicated when one wave pattern is elevated over the other. These
patterns are also seen when nothing is connected to the surge test leads.
Note: If an open circuit is indicated, check the connection between all three test leads and
the device being tested and the clip ends. The test leads should be checked weekly to ensure
there is no breakage! Test leads are easily checked for breakage by firmly grasping the boot
and clip in one hand while pulling on the lead with the other. A broken lead will stretch a
good lead will not.
As with a fault in the winding, an open condition will result in two surge tests that will display
one normal surge wave pattern and one wave pattern that is elevated. A ski ramp pattern will
result when the open condition is in the ground return leg of the circuit. The open condition
will be located in the phase connected to the lead in common with the two surge tests that
produce the elevated pattern. Refer to Fault Location for Wye Connected Three Phase
Motors to interpret the results of a surge test that involves an open phase in a wye-
connected motor.
12/2/2009 | 71-002-V5 EN 40
ST103A, ST106A, ST112A
Surge Testing
Note: Wave patterns signatures are normally higher in frequency for delta-connected
windings as compared to wye-connected windings because windings are tested in parallel.
Refer to the illustrations and table used in Wave Pattern Separation for Delta-Connected
Motors to interpret the results of a surge test that involves an open phase in a delta-
connected motor.
Grounded winding
A hard short to ground can be detected when surge testing. Grounded windings in both wye-
and delta-connected motors will also be detected by the DC HiPot test (refer to Chapter 4:
DC HiPot Testing).
12/2/2009 | 71-002-V5 EN 41
ST103A, ST106A, ST112A
Surge Testing
Fig 5-13: Example of a surge test comparison where there is a hard short
to ground in lead #2.
Delta-connected motors
The phase of a partial short to ground in a delta-connected motor is determined in a manner
like that for locating a shorted turn fault in the winding. Refer to the illustration and table in
Wave Pattern Separation for Delta-Connected Motors (page 62).
Hard-shorted winding faults are rarely found in motors during maintenance testing. Solid
turn-to-turn winding faults happen when the insulation on adjacent copper wires has failed to
the point that adjacent wires are welded together. It is a rare condition in maintenance
testing. A transformer action occurs within the windings which induces very high current in a
hard turn-to-turn short. The high current causes heating and deterioration of the
surrounding insulation systems, typically within a few minutes. The single turn-to-turn short
rapidly compounds until the damage causes a failure in the ground wall insulation.
The high current will trip the circuit breaker and stop the motor. A solid turn-to-turn, or
hard-shorted winding fault is not the type of fault to expect to see during maintenance
testing. This condition is usually only found after the motor has failed.
During surge testing, steady separation in the wave pattern comparisons is most often the
result of the rotor coupling with the stator. (See Rotor Loading (Coupling) when Testing
Assembled Motors.) In this case a consistent double wave pattern will be seen at all voltage
levels. Separation due to rotor coupling should not be interpreted as a fault.
12/2/2009 | 71-002-V5 EN 42
ST103A, ST106A, ST112A
Surge Testing
The key to the surge testing for maintenance is to detect a fault at a voltage level above the
peak operating voltage but not above what the motor would withstand. For example, a 460V
motor that shows a good trace at 500 V but shows an unstable, flickering pattern (regardless
of rotor coupling) at 1500V definitely contains a fault. When the fault is detected above
operating voltage, time is available to schedule service for the motor before a hard short and
rapid failure occurs.
Consider a 460 volt AC motor. The operating voltage is the root mean square, a kind of
average, of the AC power supply. For this motor, multiply 460 volts by 1.4 to determine the
maximum voltage level that the coil undergoes during normal operation. It is approximately
650 volts. Suppose this motor has an insulation fault at 500 volts. This motor will probably
fail while in service well before it can be surge tested because the peak of the AC voltage will
continuously stress the fault under normal operating conditions.
The goal, therefore of the surge test is to detect weakness well above the operating voltage of
the motor, as much as twice the operating voltage plus 1000 volts. Refer to
Recommended Voltages for a thorough description of how to determine test voltages along
with IEEE references (page 31) that explain the reasons for these recommendations.
As shown below, a good winding will produce stable wave patterns from zero volts up to the
recommended test voltages. Faults will be detected during surge tests as unstable, flickering
wave patterns that appear as the voltage is increased.
Fig 5-14: Good wave pattern (left) and a representation of how a live wave
pattern may appear to move on the display for a winding that contains an
intermittent short or is arcing (right).
Application notes
If an open circuit condition is indicated, check the connections between all three test
leads and the device under test.
Check for open test leads at the clip end. With heavy use test leads should be checked weekly
to ensure there is no breakage. Test leads are easily checked by firmly grasping the boot and
clip in one hand while pulling on the lead with the other. A broken lead will stretch. A good
lead will not stretch.
12/2/2009 | 71-002-V5 EN 43
ST103A, ST106A, ST112A
Surge Testing
Determination of a fault
If a fault exists in a single phase motor or two terminal device, the wave pattern on the
display will collapse in amplitude and a distinct shift to the left will occur, signifying an
increase in frequency (a decrease in inductance). When inductance decreases, the frequency
of the wave pattern will increase according to the following formula where L is inductance and
C is capacitance.
1
Frequency =
2 LC
This is illustrated in the figure below. This type of fault is generally one that indicates a failure
of the turn-to-turn insulation.
If any wave pattern becomes erratic and/or flickers during testing, intermittent shorting or
arcing is probably occurring in the windings under the voltage stress. Arcing is often
accompanied by audible sounds.
Form coils
A form coils should be tested as a two terminal device (refer to Single Phase Motors and
Two Terminal Devices (page 69). This surge test is recommended for form coils testing
because it can generate the turn-to-turn voltage stress that is required in these low
impedance coils.
Determination of a fault
Refer to the previous section on Single Phase Motors and Two Terminal Devices to
determine if a fault is present.
1) Connect the three numbered red test leads to the three winding legs.
2) Connect the black ground lead to the frame or core of the winding.
3) Begin with the TLS in position 1-2. This indicates leads #1 and #2 will be hot while lead
#3 will provide a ground path.
4) Perform the test as described in Three Phase Motor Surge Test and Set-Up (page 52).
For each test, check the display for a wave pattern. If you see three good wave comparisons,
the motor is good. If you have seen anything other than good patterns, there is a possible
fault.
Determination of a fault
If any wave pattern becomes erratic and/or flickers during testing, intermittent shorting or
arcing is probably occurring in the windings. Arcing is often accompanied by audible sounds.
Separation in two of three wave pattern comparisons indicate incorrect turns count or
another type of fault. The fault will be in the phase connected to the test lead in common with
the two comparisons which show the separation for wye-connected windings.
In the Repair Shop: Separation of compared wave patterns on stators indicates a hard fault,
such as a solid turn-to-turn or group-to-group short, an incorrect turn count, or
misconnection.
In the Field: In assembled motors, separation of the wave pattern is often the effect or rotor
coupling, also know as rotor loading (see Rotor Loading (Coupling) when Testing
Assembled Motors).
Concentric or Basket Wound Motors: These windings, due to their unique structure,
inherently have phases or differing wire length and size and proximity to the iron housing.
Very slight separation of wave patterns should be acceptable. If the wave patterns are very
close in shape and remain Stable during the test, the motor is generally acceptable. The
operator should investigate where this condition is acceptable or not.
1) Connect test lead #1 to one side of the first coil and connect the ground test lead to the
other side.
2) Connect test lead #2 to the second coil and connect test lead #3 to the coils other side.
If the patterns are stable and superimpose on the display, the two windings are identical.
They have no faults and the insulation of both coils is good.
12/2/2009 | 71-002-V5 EN 45
ST103A, ST106A, ST112A
Surge Testing
Determination of a fault
If the wave pattern becomes erratic and/or flickers during testing, intermittent shorting or
arcing is occurring in the windings. Arcing is often accompanied by audible sounds.
Separation of the wave patterns when compared indicates the presence of a fault.
To verify which coil is shorted, connect leads #1 and #2 together to the first coil. Test it at
the voltage specified. Then connect leads #1 and #2 to the second coil. Test at the specified
voltage. The faulty coil will give an erratic waveform.
Slight variations in magnetics of the tested device can result in similar coils not
comparing identically. An example of this is synchronous pole pieces, one of which is
making better magnetic contact with the rotor than the comparing pole. For this reason
it is recommended that devices like pole pieces be evaluated individually and not
compared.
Paschens Law states that a voltage greater than 335 volts is required to initiate an arc
between two conductors in air. This suggests a minimum voltage for surge testing to be
greater than 335 volts. Because of the sometimes non-linear distribution of the surge
pulse, it is recommended that a minimum surge potential of 500 volts be used when
testing a two terminal device.
Shunt coils often have a small error in turn counts. Some mismatch or separation of
patterns should be acceptable. If the wave patterns are very close in shape and remain
stable during the test, the coils may allow for differences in turn count which causes a
slight, steady separation. The operator should investigate whether this condition is
acceptable or not.
A slight imbalance (separation) may be noticed if the windings are not correctly phased:
i.e. the winding configuration of one compared to another is clockwise versus
counterclockwise. Try reversing one set of test lead connections and repeating the test
before rejecting the winding.
Many two terminal devices have very high turn counts. The waveform displayed is similar
to that of an open circuit. In this case, the impedance of the coil is too high to be tested.
Double check for poor connections and test lead breakage to see if these conditions may
be causing the apparent open circuit.
2) Short together the slip rings with jumpers. The jumpers minimize the coupling effect
between rotor and stator.
12/2/2009 | 71-002-V5 EN 46
ST103A, ST106A, ST112A
Surge Testing
3) Surge test the stator as would be done on a three phase induction motor. See Three
Phase Motors (page 71) or follow the directions in Three Phase Motor Surge Test and
Set-Up (page 52).
NOTE: Since the rotor is shorted out there will be no chance for a high induced voltage
transformed from the stator to damage the rotor.
4) To surge test the rotor, disconnect the jumpers from the slip rings. Connect the tester
test leads to the rotor slip rings.
5) Short together the stator leads with jumpers, as done for the rotor.
Note: check the motor for rotor voltage to calculate the rotor test voltage level. Rotor voltage
is not the same as the stator voltage.
If the wave patterns are stable and superimpose on the display, the windings are identical.
They have no faults and the insulation of both coils is good.
Determination of a fault
If any wave pattern becomes erratic and/or flickers during testing, intermittent shorting or
arcing is occurring in the windings under the voltage stress. Arcing is often accompanied by
audible sounds.
Separation of the wave patterns when compared indicates incorrect turns count. Interpret the
separation as the three phase motors.
Synchronous motor/generator
The synchronous stator is tested as a three phase induction motor. The rotating fields should
be tested individually.
2) Surge Test the stator following the procedures and steps for Three Phase Motors.
3) Individual poles are surge tested as outlined in the procedures for testing Single Phase
Motors and Two Terminal Devices. The recommended test voltage is 600 volts per pole.
It is not necessary to disconnect the pole piece leads before testing.
4) The hot and ground leads are then reversed and the test repeated on each coil.
If the wave patterns are stable and superimpose on the display, the windings are identical.
They have no faults and the insulation of both coils is good.
Determination of a fault
Two types of faults may exist in synchronous motors and generators.
12/2/2009 | 71-002-V5 EN 47
ST103A, ST106A, ST112A
Surge Testing
increase in frequency (a decrease in inductance). This type of fault is usually failure of the
turn-to-turn insulation.
Surge test procedures for chiller motors follow those outline for Three Phase Motors.
Field coils
When testing field coils follow the procedures outlined for testing Single Phase Motors and
Two Terminal Devices and Synchronous Motor/Generator. The recommended surge test
voltage for DC fields is 600 volts.
If the impedance of the coils is very low (few turn counts, generally form coils with very low
resistance) the surge tester stand-alone may not adequately test the coils. A bar-to-bar, low
impedance test accessory from Baker Instrument Company, an SKF Group Company will be
necessary.
DC motor/generators
The series or shunt fields of the DC motor/generator are tested as a two terminal device (see
Single Phase Motors and Two Terminal Devices). The armature may be tested by two
different methods (see Armatures).
Armatures
There are two methods of Surge testing armatures: the Bar-to-Bar surge test and the span
surge test. The use of a Footswitch is highly recommended to ease the operation of these
tests.
To perform Bar-to-Bar surge testing, the Model AT101 Bar-to-Bar Accessory is necessary.
Bar-to-Bar testing instructions accompany the AT101 and can be found in Appendix E:
Model AT101 Bar-to-Bar Armature Test Accessory in this manual.
12/2/2009 | 71-002-V5 EN 48
ST103A, ST106A, ST112A
Surge Testing
Span testing
Fig 5-18 Span Test using the motors brushes
This method uses the brushes of the assembled DC motor to make the connection with the
commutator for testing of the armature. Any number of bars can be used in this test. Either
adjacent bars can be surge tested or a specific number, or span of bars, can be tested. The
number of bars tested in each span for an individual motor must be the same during the
entire test. In the repair shop, a fixture can be used in place of the motors brushes (refer to
Notes and Tips for Span Testing Armatures).
The wave pattern produced in this test represents the voltage oscillation between the tester
and the coils for the specific number of commutator bars spanned. For example, any 10 bars
spanned in series on the armature should give the same pattern as any other 10 bars
spanned. As the armature is rotated, all the commutator segments and therefore their
respective coils, pass into the test area between the Hot surge test lead and the Grd lead.
Note: It is important that the same number of bars (and therefore coils) always be in the test
area.
1) Remove all brush pig tail connections from the leads at the brush rigging for all sets of
brushes to isolate the armature from the power source.
2) With the TLS switch in the Leads Ground position, connect test leads #1 and #2 to one
of the brush assembly pigtails. Connect the black ground test lead to the shaft or other
good ground on the frame.
3) Select the adjacent set of brushes of the bar corresponding to the desired span. Connect
test lead #3 to the pigtail of that brush assembly.
4) Select the TLS position 1-2. Be sure the Function switch is set to Surge.
5) Begin the test by pressing the Test button or Footswitch and slowly raise the Output
Control to the desired test voltage level. Carefully observe the wave pattern for its
reference shape.
Note: The Zero Start Interlock is disabled only when the Function switch is set to AT101
and the AT101 accessory is in use (see Appendix E: Model AT101 Bar-to-Bar Armature
Test Accessory). Without the accessory, the Output must be turned back to zero or minimum
and then brought back up to the peak voltage value noted above in Step 5. The same test
voltage must be used for each span tested.
6) Rotate the armature slowly through 360 degrees so that all commutator segments are
tested while observing the wave pattern.
Note: It is recommended to release the Test button (or Footswitch) each time the armature
is turned, but it is not necessary. Doing so minimizes the chance of marking the commutator.
12/2/2009 | 71-002-V5 EN 49
ST103A, ST106A, ST112A
Surge Testing
If the test button or Footswitch is not released each time the armature is turned, the wave
pattern will show regular shifts and flickers as the brushes move across one commutator bar
to the next. This wave pattern movement should be ignored as long as the trace returns to
the reference wave pattern and remains stable when the brushes are again centered on top
of the bars.
Determination of a fault
If the insulation is weak or failing on a particular bar or coil of the armature, the test wave
pattern will become unstable and shift left when the section that contains the fault passes
through the test area.
Usually, as soon as the bad bar is placed under the hot brush, the wave pattern will show the
shift to the left as noted above. Thus the bar directly below the hot brush is the faulty bar. An
example of a fault found surge testing using the motors brushes is illustrated below.
Set the span between the fixtures brushes to the desired number of commutator
bars. Either the fixture can be moved around the commutator during testing, or the
armature can be rotated. Procedures for testing and fault determination are the
same.
Always HiPot the armature to ground first. This gives an upper limit for the voltage
to apply when surge testing.
Voltage stress is measured by the differential or drop between each bar. For
example, a 10 bar span with 1000 volts applied to it will result in a 100 volt stress
between bars. If the span is lowered to 5 bars, 1000 volts to the span will result in
200 volts between bars.
Consider, however, that a then bar span at 335 Volts between bars would require a
span test voltage of 3350 volts. This potential to ground at the first coil may be too
high. A lower span test voltage is recommended if, for instance, the HiPot test was
only 2200 volts.
It is advantageous to keep the span as low as possible to still get a reasonably good
ringing wave on the display. However, lowering the span reduces the resistance and
12/2/2009 | 71-002-V5 EN 50
ST103A, ST106A, ST112A
Surge Testing
inductance of the load under test. The low inductive load may cause difficulty
achieving the desired test voltage and a good ringing wave pattern on the screen.
Equalizer windings can separate the test wave pattern from the reference pattern
seen during span tests. Thus, a good armature winding can appear to be bad. For
example, a wave pattern for 7 bars spanned my sometimes match that for 11 bars
spanned. In addition, the patterns may show a rhythmic shift consistently
throughout the 360 degrees of rotation, (for instance, as the armature or fixture is
rotated, every third bar shifts left a little), which is not a fault. This is due to the
equalizers and does not indicate faulty windings.
Releasing the Test button or the Footswitch before moving to the next bar during
the test minimizes the chance of marking the commutator.
The figures below show wave pattern comparisons for a typical 4160V stator. The first wave
pattern is produced when the Sweep control has been turned clockwise too far, expanding
the display of the wave pattern. The sweep rate is set too fast. This wave pattern is actually
the first half cycle of the full wave. Distortion is caused by the non-symmetrical, distributed
capacitance of the winding.
To correct for this display condition turn the Sweep control counter-clockwise, slowing the
sweep rate. The correct surge wave pattern will always extend below the zero line. Observe
the natural ringing to the right of the point where the wave pattern crosses the zero line in a
positive (upward) direction.
Good practice is to start with the Sweep control turned to its counterclockwise limit to begin
when testing high voltage AC machines.
12/2/2009 | 71-002-V5 EN 51
ST103A, ST106A, ST112A
Surge Testing
1) Loss of wave pattern amplitude: The inductive loading of the rotor causes rapid
damping (little to no cycles of the ringing pattern) of the wave pattern.
2) Separated wave pattern comparison for good windings: Unbalance in the inductive
coupling between the rotor and stator winding causes the wave pattern of two good
phases to appear separated when they are compared. By turning the rotor, this coupling
affect can be balanced out so the wave patterns superimpose.
Not all motors exhibit this characteristic. It is most prevalent in smaller, high efficiency motors
with small air gaps. Separation of wave patterns that are due to rotor coupling can be
determined when the wave patterns separate from the first positive peak downward, cross
one another at the bottom (first most negative point) and separate again as they go upward
(positive).
Fig 5-22 Wave pattern comparisons for motor with rotor in place.
The recommended procedure for testing assembled motors when rotor coupling may occur is
as follows. Refer to Three Phase Motor Surge Test and Set-Up for detailed instructions for
surge testing.
If the rotor cannot be turned, carefully observe the wave pattern as the test voltage is slowly
raised. Watch for a sudden shift to the left, instability or flickering which would indicate a
winding fault. Many winding insulation failures will not be visible at low voltages but become
apparent at a higher voltage.
Note: Rotor coupling does not impede the surge impulse from stressing the turn-to-turn or
phase-to-phase insulation. It only causes the rapid damping of the wave pattern. The surge
test can still detect turn-to-turn or phase-to-phase shorts. Unstable, flickering wave patterns
clearly indicate a fault in assembled motors whether rotor coupling is present or not.
12/2/2009 | 71-002-V5 EN 52
ST103A, ST106A, ST112A
Surge Testing
Fig 5-23 Motor with rotor in place and with faulty windings. One trace shifts
significantly to the left.
Follow all the procedures for surge testing (refer to Surge Testing). Keep in mind that
different types and sizes of motors will give different traces, but the principle of testing
assembled motors is still the same. When interpreting the wave patterns for good or bad
windings, stability and symmetry are the most important factors.
Warning
The motor must be de-energized before testing!
Connect the test leads to only the load side of the open disconnect!
All of the limitations and guidelines covered for testing assembled motors apply here
(see Rotor Loading (Coupling) when Testing Assembled Motors).
Any power factor capacitors, surge suppression, etc., in the circuit must be
disconnected.
If power factor capacitors are present, no waveform will be observed when the
voltage is raised. This will also happen if the motor was not connected to the cable.
Only a rise in the trace on the far left will be noted.
The surge test circuit will be loaded by the feeder cable capacitance as well as the
motor. Significantly higher Output settings will be needed to reach the required test
voltage. If the surge tester is too small to handle both the cable and the motor load,
a trace will be observed but the proper test voltage will not be reached. A higher
output surge tester model will be required or the motor may have to be tested while
disconnected from the feeder cable.
There is no precise science to determine what size motor, with what size and length feeder
cable a particular surge tester can adequately test. In general, the closer the size of the motor
is to the recommended maximum motor size for a given model surge tester, the shorter the
12/2/2009 | 71-002-V5 EN 53
ST103A, ST106A, ST112A
Surge Testing
cables can be and still allow testing at the required voltage. Conversely, the small the motor
size, the longer the cable can be.
Transformers
Transformers contain similar insulation systems as motors: ground, turn-to-turn and phase
insulation. However, the spectrum of winding characteristics for transformers is much
broader than for motors.
The Surge Test is only one of many tests that should be performed to properly test a
transformer. If the transformer has thousands of turns, the surge tester may not be sensitive
enough to detect a single shorted winding. It may also sense the high inductance of a
transformer as an open.
The following testing procedures for single phase and three phase transformers provide the
basics necessary to surge test transformers. Please call Baker Instrument Company, an SKF
Group Company at 800-752-8272 or 970-282-1200 for further assistance or if difficulties
are encountered when testing transformers.
2) Select TLS 1-2. Follow the diagram below to connect test leads #1 and #2 to H1 and
test lead #3 to H2 of the transformer. The black ground lead connects to the frame.
3) Surge test the winding following the procedures outlined for Single Phase Motors and
Two Terminal Devices. The discussion of determining a fault applies.
Note: Secondary winding insulation problems are reflected into the primary winding, and will
be observed on the display.
4) After completing the test, reverse the test leads (connect the hot leads to H2 and the
ground (#3) lead to H1) and repeat the surge test. This is commonly referred to as
shooting it in the other direction.
12/2/2009 | 71-002-V5 EN 54
ST103A, ST106A, ST112A
Surge Testing
Note: A wye-wye transformer with the star point internally tied can be surge tested without
opening the tie point.
2) Connect the black ground test lead to the frame (ground) of the transformer.
3) Follow one of the charts below for connection for wye-wye or delta-wye transformers.
The transformer winding should be surge tested for all the configurations shown.
4) Test procedures follow identically as for Single Phase transformer testing (refer to
Single Phase Motors and Two Terminal Devices).
Determination of a fault
The determination of a fault when surge testing a transformer winding follows that of the
Two Terminal Device (refer to Single Phase Motors and Two Terminal Devices).
Wye-Wye transformers
Test Leads #1 & Test Lead #3 Jumper
#2
H1 H0 X0 to X1
H2 H0 X0 to X2
H3 H0 X0 to X3
Delta-Wye transformers
Test Lead #1 & #2 Test Lead #3 Jumper
H1 H2 X0 to X2
H1 H3 X0 to X1
H2 H1 X0 to X2
H2 H3 X0 to X3
H3 H2 X0 to X3
H3 H1 X0 to X1
12/2/2009 | 71-002-V5 EN 55
ST103A, ST106A, ST112A
Surge Testing
12/2/2009 | 71-002-V5 EN 56
ST103A, ST106A, ST112A
6
Additional Tests
The Baker Instrument Company, an SKF Group Company Surge/HiPot Tester is capable of
performing two tests in addition to DC HiPot and Surge Tests. These are the Polarization
Index (PI) and Step-Voltage Tests.
Danger
High Voltage
To prevent serious injury or death:
- Do not use in explosive atmospheres.
- Do not contact test leads or device being testing
while test is in progress or during discharge period.
- Do not connect test leads to live circuits.
Read and follow safety precautions and safe operating
practices in operator manual. Do not exceed maximum
operating capabilities of this instrument.
21) Never attempt a two-party operation. Always know what test is being performed
and when. FOR EXAMPLE: DO NOT adjust test leads when footswitch is being
operated. Leads will have live voltage and severe electric shock may result.
23) Upon completion of a DC High Potential, Megohm, Polarization Index, Step Voltage,
Dielectric absorption, or Continuous Ramp test, before disconnecting the test leads,
short the winding, motor, etc., to ground and allow time for discharge. If this is not
done, voltage may still be active on leads and tested components.
24) Make sure the tester leads are disconnected before the motor is energized or
powered up.
25) Do not remove the product covers or panels or operate the tester without the
covers and panels properly installed. Components on inside of tester carry voltage
for operation and if touched can render a shock.
26) Use appropriate safety equipment required by your organization, including high
voltage globes and eye protection.
12/2/2009 | 71-002-V5 EN 57
ST103A, ST106A, ST112A
Additional Tests
27) Repair Parts Warning : Defective, damaged, or broken test leads must be replaced
with factory-authorized parts to ensure safe operation and maintain performance
specifications.
28) Ground the product : This product is grounded through the grounding conductor
of the power cord. To avoid electrical shock, plug the power cord into a properly
wired/grounded receptacle before connecting the product test leads.
Danger from loss of ground Upon loss of the protective ground connection,
all accessible conductive parts, including knobs and controls that may appear
to be insulated, can cause an electric shock!
30) The unit is for indoor use. If used outdoors, the unit must be protected from rain,
snow and other contaminants.
There are a number of advantages in using the Polarization Index test over a possibly ever-
changing insulation resistance test.
The PI test can determine insulation faults in larger test pieces with much more
insulation than smaller test pieces.
Step-Voltage test
Another test that can be performed is the Step-Voltage test. This test, if used properly, can
indicate the condition of winding insulation. The best results can be gained if you maintain
historical records of multiple Step-Voltage tests, beginning with measurements made when
the winding is new.
Use the same voltage increments and time intervals for all subsequent Step-Voltage tests.
Baker Instrument Company, an SKF Group Company recommends that you plot out your
results on graph paper in order for you to make quick comparisons of different tests.
It is important for the insulation to be free of moisture and dirt when this test is performed.
12/2/2009 | 71-002-V5 EN 58
ST103A, ST106A, ST112A
Additional Tests
1) Determine the number of steps you wish to perform, at what voltages and time
increments that suit your needs. For example, if your maximum voltage is12,000 volts,
you may wish to use six steps of 2000 volts each. The time interval that you use will
depend upon the capacitance of the test piece and the type of insulation it uses. Choose
an interval that allows for a noticeable change in resistance readings at each step. One-
minute step intervals are fairly standard for many windings.
2) Take note of the resistance reading for each step. For example, with a 12kV test voltage,
using steps of 2000 volts and one minute intervals, note the stabilized resistance
readings at 2000 volts at one minute, 4000 volts at two minutes, 6000 volts at three
minutes, 8000 volts at four minutes, 10,000 volts at five minutes and 12,000 volts at six
minutes. Raise the output voltages on the tester in single motions to get the most
accurate rise from one test voltage to the next. When plotted on graph paper, the results
should resemble a set of ascending steps. Each step should be flat, indicating a steady
resistance value.
12/2/2009 | 71-002-V5 EN 59
ST103A, ST106A, ST112A
Additional Tests
12/2/2009 | 71-002-V5 EN 60
ST103A, ST106A, ST112A
Typical Winding Faults
Appendix A
Typical Winding Faults
For initial determination of winding faults, refer to the following figures. These wave patterns
are typically seen for three phase, wye-connected, lap-wound induction stators. They provide
a reference for associating a characteristic wave pattern with a fault-type.
Note: Variation from these wave patterns is to be expected. Do not consider these wave
patterns as absolute. Remember, that due to the variety of motor windings and connections
that exist, each motor winding will have its own signature wave pattern. Memorization of
exact matches to the following wave patterns is NOT necessary when testing.
12/2/2009 | 71-002-V5 EN 61
ST103A, ST106A, ST112A
Typical Winding Faults
Note: If all wave pattern comparisons during surge testing show considerable separation
when testing three phase windings, the motor has a phase-to-phase short. Because two
phases are faulty, a good wave pattern will not be achieved in any position of the TLS switch.
12/2/2009 | 71-002-V5 EN 62
ST103A, ST106A, ST112A
Appendix B
Troubleshooting
Please review this section before you call Baker Instrument
Company, an SKF Group Company or return the unit.
By performing these procedures and having the requested information available, Baker
Instrument Company, an SKF Group Companys Service or Applications Departments will be
able to better analyze your situation and provide the appropriate response. Either department
may be reached toll-free at 800-752-8272 or 970-282-1200 for assistance.
Note: All information above is located on the rear panel product label. If the tester has
special options installed that you are aware of, please note these. Any and all information you
know or can derive would be of help! A great tool would be a printout or sketch of the
waveforms displayed on the tester.
If you can Not say the problem is associated with any One type of motor/generator, or other
coil type, then Service would be involved. See Service: What to do first!
Examples: Hp rating
kW rating
RPM rating
Operating voltage & current
How the item being tested is wound and/or number
and type of coils
Application of motor/generator
12/2/2009 | 71-002-V5 EN 63
ST103A, ST106A, ST112A
Troubleshooting
In short, any and all information you know or can derive from the motor name plate
would be of help. A great tool is a printout or sketch of the waveforms displayed on the
tester. If you have a FAX available, send a draft to 970-282-1010, attn: Applications.
Common application problems
There are a few common application-related problems which many users encounter. Please
review the following cases.
The surge tester will not give the desired output test voltage for the apparatus
being tested.
This may happen when the test motor is too large for the surge tester, or if the impedance of
the windings is too low. Refer to Chapter 5 Surge Testing for specific test procedures and
results. There may also be a problem with the tester in this case. DO NOT continue testing
until you have contacted Baker Instrument Company, an SKF Group Company Applications
Department.
Separation of compared wave patterns is seen when surge testing on coils that
are assumed to be good, even on brand new motors or windings. Often
separation is seen in all three possible comparisons but to varying degrees.
There may not be separation throughout the whole wave pattern.
This situation can be seen in DC field or rotating poles. Be sure the coils being compared are
being tested in identical configurations; i.e. both coils are wound clockwise beginning to end.
On very large equipment, slight differences in capacitance may be the cause. At low voltage
levels, begin the test again with the black ground lead removed from the motor frame. If the
separation is now gone, capacitance was affecting the test.
If the above situation does not apply there is probably an unbalance of the impedance
windings that is inherent to the design. The most common case is found in basket or
concentric wound motors. The phases are not magnetically balanced due to different coil
lengths.
To verify that the tester is working properly, perform the following test. Parallel the test leads
by connecting both of the hot, red leads, indicated by the selected TLS position, from the
tester to one end of a coil and the remaining red grounded lead to the other end of the coil. In
this configuration, both hot leads are looking at the same coil. Therefore, there should not be
any separation of the wave patterns on the display.
If separation of the wave patterns is not seen (traces superimpose), the tester is operating
properly and there is probably a faulted winding or a factor in the winding design that is
causing the separation. If there is still separation in the wave patterns after paralleling the
test leads, there is a problem with the tester and it will need to be serviced.
There is no damped sinusoidal wave pattern on the display when testing a coil.
The wave pattern rises on the left and then slowly drops as it trails off to the
right. It may or may not cross the zero/base line. The pattern looks like that in
the figure on the next page.
The test coil probably has too high an impedance to get a good working pattern. The coil may
be very high in resistance and turns count. The inability to surge test this coil, or group of
coils in series, will remain unless they can be broken down to smaller units of lower
impedance.
12/2/2009 | 71-002-V5 EN 64
ST103A, ST106A, ST112A
Troubleshooting
You may also have a broken test lead or lead to the test winding. With heavy use, test leads
should be checked weekly to ensure there is no breakage. Test leads are easily checked for
breakage by firmly grasping the boot and clip in one hand while pulling on the lead with the
other. A broken lead will stretch. A good lead will not.
NEVER come in contact with the item being tested and the test leads or with
the tester and the item being tested!
Because history has shown that several simple solutions which do not require return of a unit
may arise, please perform the following checks.
If yes, the unit may have at least one broken test lead causing an Open condition. In most
cases, the test lead in common with the two TLS positions that produces these types of wave
patterns is the lead which is broken. Verify this by pulling on the book/clip assembly of the
lead. A broken test lead will stretch. If it does not repeat this procedure at one foot intervals
for the length of the lead. If the leads of the tester are good, check the connections and
continuity of the test winding.
Perform the following check. During a surge test of a coil or three phase motor, stop the test
and simply disconnect one hot lead from the winding (a hot lead is one of the numbers of the
selected TLS position). The display should look like one of the figures above, showing an open
condition. If not, call Baker Instrument Company, an SKF Group Company Service Department
for assistance.
Note: Perform this test at a very low voltage. Use extra caution during the check. The
disconnected test lead is still energized!
12/2/2009 | 71-002-V5 EN 65
ST103A, ST106A, ST112A
Troubleshooting
The item being tested is in fact faulty and has either low insulation resistance or
open connections.
The tester has a test lead problem as shown above for an Open Condition.
Disconnect the test leads from the motor and isolate the tester from any grounded surface.
Reduce the Output to minimum and attempt a HiPot test with an open lead condition. Your
display should indicate a rising voltage bar. The current bar may rise slightly but fall back to
zero when the output increase is stopped. Do not exceed 10% rotation of the Output
control! There is no need to perform this test at high voltage.
If the display still shows NO voltage bar call Baker Instrument Company, an SKF Group
Company Service Department. Use a meter to confirm the insulation resistance of the device
being tested.
Current bar operation can be tested by shorting test lead #1 and the ground lead together.
Under this condition, the voltage bar will NOT move off the zero line and the current bar
should rise very rapidly and activate the HiPot Overcurrent Trip warning light (HiPot Trip). If
the HiPot Trip light does not light, check for open test leads at either test lead #1 or the
ground lead (see Open Condition Display). If the problem persists, contact Baker Instrument
Company, an SKF Group Company Service Department.
Call the Service Department immediately for assistance. Please record information off the unit
and the specific problem prior to calling.
1) Have you recently moved the unit to a new location with possibly an ungrounded outlet?
2) Is the unit being operated in a field where the AC power source is unknown?
3) Is the unit being operated on a scope cart that has its own outlet or power source?
12/2/2009 | 71-002-V5 EN 66
ST103A, ST106A, ST112A
Troubleshooting
If you answer is yes to any of these questions, the unit is probably operational and indicating
you have an open AC line ground connection.
In the case of numbers 1 through 3 above, use an outlet tester to assure proper wiring
connections to the outlet. For number 4, replace the two-wire extension cord with a two-
wire/with ground extension cord. For number 5, or any of the conditions noted above, use a
grounding strap to a good earth ground.
In the case of number 6, call Baker Instrument Company, an SKF Group Company Service for
assistance. There is an override available but precautions should be taken.
Call the Service Department immediately for assistance on this or any other abnormal
condition noted. Please record basic information from the tester and the specific problem
prior to calling.
Warranty return
Please review the Warranty Notes and Shipment sections at the beginning of this manual
before sending your tester to Baker Instrument Company, an SKF Group Company for
Warranty repair.
The Warranty Return Form on the following page MUST BE FILLED OUT and RETURNED
with the tester to obtain warranty service. This form will help to ensure that Baker Instrument
Company, an SKF Group Company will identify the problem, quickly repair our unit, and
return it to you.
12/2/2009 | 71-002-V5 EN 67
ST103A, ST106A, ST112A
Troubleshooting
Note: Be sure to follow the guidelines for shipping when sending your tester to Baker
Instrument Company, an SKF Group Company.
Ship the Tester to: Baker Instrument Company, an SKF Group Company, 4812 McMurry
Avenue, Fort Collins, CO 80525, Attn: Service Manager
12/2/2009 | 71-002-V5 EN 68
ST103A, ST106A, ST112A
Appendix C
Model AT101 bar-to-bar armature test
accessory
To illustrate the difference between the bar-to-bar and span tests, consider this example. A
manufacturer of lap wound elevator motor armatures determines that, to thoroughly test the
turn-to-turn and coil-to-coil insulation, a test voltage of 400 volts across each coil is
required. However, the impedance of a single coil in the armature is so low that it appears as
a dead short to a conventional surge tester designed for testing AC stators. Even with the
current of a 12 kV surge tester, only a few hundred volts may be generated into such a load.
Most of this voltage is actually lost in the test leads of the surge tester. Consequently, the
span test was developed (see the figures below).
In the span test, the test contacts are placed several bars apart, so that the impedance of
several coils in series is large enough to be tested with the surge tester. For example, to
generate 400 volts across each coil of a 10 bar span, the test voltage must be increased to
4000 volts. However, 4000 volts at the high voltage contacts delivering the surge test will
over-stress the ground insulation at the first coil in series. Therefore, the maximum test
voltage must be decreased to the same level as the safe DC HiPot voltage for that motor, or
about 2000 volts. Now the coils are not adequately being tested, since the bar-to-bar is only
200 volts.
In a bar-to-bar surge test, 400 volts is applied directly to each coil without over-stressing the
ground insulation (see figure below). The AT101 Bar-to-Bar Testing Accessory provides a
specially designed low output impedance surge tester with low impedance test leads to make
this test possible.
12/2/2009 | 71-002-V5 EN 69
ST103A, ST106A, ST112A
AT101 Bar-to-Bar Armature Test Accessory
The AT101, when connected between a surge tester and an armature, converts the surge
tester output from high voltage to lower voltage with high current. This is necessary for bar-
to-bar armature testing of low impedance coil windings. The AT101 contains a high energy
pulse transformer which steps down the surge tester voltage by a factor of 10 and increases
the current by a factor of 10.
The basic procedure involves connecting the surge tester output leads to the input of the
AT101. The output of the AT101 travels through a low impedance cable assembly and
armature contactor. The bar-to-bar output voltage is monitored by a peak-hold voltmeter in
the AT101. The surge test wave pattern and test voltage are displayed concurrently on the
surge tester CRT screen. Test voltage is measured directly at the contactor, so there is no
measurement error from test lead losses.
When a faulty coil is detected, the output voltage on the peak voltmeter will drop dramatically.
A corresponding collapse in the amplitude and left shift of the surge test wave pattern will be
evident. This is easily simulated by shorting the two bars under test with a screwdriver. In
fact, the AT101 will detect shorted bars that are four or five bars away from the bars under
test.
Operation
Note: The AT101 will show on its rear panel that it has been set up and calibrated for the
specific tester you are using. It may say that it has been calibrated for an A Series Tester.
1) Ensure the AT101 line voltage selector is positioned for the line voltage to be used. 115
VAC must be showing through the window for 110 to 120 volts operation, and 230 VAC
must show for 220 to 240 Volt operation.
2) Plug in the AT101. There is no power switch. The voltmeter will show 000. (The AT101
draws only 5 watts of power for the peak voltmeter, which is about the same power as
an electric clock. The AT101 may be plugged in at all times, even when not testing.
Note: If only one electric outlet is available, the surge tester may be plugged into the Line
Out accessory plug provided on the AT101 front panel.
The interconnect cable between the AT101 surge tester has a BNC connector at
one end and an AMP connector at the other. Connect the BNC connector to the
front panel of the AT101. The AMP plug connects to the port on the surge tester
marked Auxiliary.
Connect the surge tester leads #1 and #2 to the recessed bar on the rear of the
AT101. Connect surge tester leads #3 to the un-insulated ground terminal on the
rear of the AT101.
The black surge tester ground lead must be connected to the armature shaft. If
testing single low impedance coils using ATP02 alligator clips, connect the surge
tester ground lead to the core material.
Note: When using alligator clips or test probes on armatures that have bars that are wired in
series, it is very important to ground at least two bars of the armature a few bars away from
those that are being surged. If this in not done, very high potential voltages to ground can
develop in the armature due to a transformer effect in the coils.
4) Set the surge tester Test Lead Select (TLS) switch to position 1-2.
12/2/2009 | 71-002-V5 EN 70
ST103A, ST106A, ST112A
AT101 Bar-to-Bar Armature Test Accessory
Note: The Volts/Div setting need to be divided by 10 for the bar-to-bar test when the tester
is in the Aux function position. For example, 500 volts/division becomes 50 volts/division on
the surge tester display.
7) Connect the armature test fixture to be used (the hand-held contactor, test probes, or
test alligator clips) to the blue braided harness. (Instructions that follow will be for the
hand held contactor.) The black cover may be removed to access the brushes and shape
them as necessary for best contact.
8) Place the AT101 contactor on the armature commutator, making sure the contact
brushes are on adjacent bars, not the same bar.
9) Press the surge tester Test (or depress the Footswitch) and raise the Output control
slowly. A wave pattern should be visible on the surge tester screen and a voltage should
be indicated on the AT101. Adjust the Output control until the desired bar-to-bar
voltage is reached.
Note: The Zero Start Interlock (ZSI) is disabled to conveniently perform this test. Positioning
the Function switch to Aux automatically disables the ZSI.
The true test peak voltage is correctly measured from the surge tester display as the
contactor head is moved around the commutator. Be sure to divide the voltage reading by 10
during these tests.
Determination of a fault
As the contactor approaches a shorted pair of bars, the waveform becomes increasingly
distorted, shifting left and with lower amplitude. The test brushes are over the faulty, shorted
bars when the waveform amplitude is lowest. Faulty bars are read through the equalizer but
the amplitude of the waveform will not be as low as when the test brushes are directly
contacting the shorted bars.
Note: A slight, regular rhythmic shift may be observed when moving the bar-to-bar fixture
around the commutator. This is generally due to the equalizer windings and can be ignored.
Hard shorted turns or insulation breakdown will be evident by an obvious change in the surge
test wave pattern.
When testing coils with ATP02 alligator clips, a fault should be interpreted in one of two ways:
1) A single coil should be tested by observing the wave pattern from zero volts up to the
desired test voltage level. A coil with good insulation will show the same wave pattern at
12/2/2009 | 71-002-V5 EN 71
ST103A, ST106A, ST112A
AT101 Bar-to-Bar Armature Test Accessory
increasing voltage levels. A fault will show by the drop in amplitude and a shift to the left
of the wave pattern.
2) A group of single coils may be tested by examining and recording a known good coil first.
Using the good coil, adjust the display controls to obtain the desired wave pattern on
the display to be used as the reference wave pattern.
Leave all surge tester controls unchanged or record these reference settings. Begin
testing on the other coils. The other coils surge test wave patterns should fit very
closely to that of the first coil if they are in good condition. A shorted coils pattern
will be collapsed and shifted left of the pattern of the reference coil. A piece of
solder can be used to short two bars. This will simulate a fault for demonstration
purposes.
Application recommendations
Most armatures requiring the use of an AT101 will be tested to at least 350 volts bar-to-bar.
Armatures which require bar-to-bar test voltages up to 600 volts should use Baker
Instrument Company, an SKF Group Company 12 kV model surge testers with the AT101.
Very large armatures, such as diesel locomotive traction motor armatures, require testing up
to 750 volts bar-to-bar. These necessitate at least a 15 kV Baker Instrument Company, an
SKF Group Company surge tester used in conjunction with the AT101. Alternatively, a
Multiple Tester from Baker Instrument Company, an SKF Group Company may be required.
Please contact us for information regarding stand alone high power armature surge and
HiPot testers for large AC and DC motor work, especially heavy rail traction motors.
A 24 kV test may be used with the AT101. Its output should be limited so that the peak
voltage measurement on the AT101 never exceeds 950 volts.
AT101 specifications
Surge Input Maximum Voltage: 15,000 volts peak
Testable Induction Range: 0.4 to 20 micro-henries (h)
Cable and Test Head Inductance: 1.0 micro-henries (h)
Transformer Turns Ratio: 10:1
Observed Voltage Step-Down: 10:1 for 5 microhenries (h) or greater test load 20:1 for 1
microhenries (h) load
Display: Fast Acquisition peak hold voltmeter
3-1/2 Digit Liquid Crystal
height
Maximum reading of 1999 volts
Line Input: 90-135 VAC or 180-270 VAC
50/60 hertz
5 VAC maximum
500 ma fuse
12/2/2009 | 71-002-V5 EN 72
ST103A, ST106A, ST112A
Appendix D
Technical Specifications
Technical specifications
This information conforms to the requirements of MIL-M-7298D.
ST103/203A ST106/206A ST112/212A
Surge Test Output 0-3000 Volts 0-6000 Volts 0-12000 Volts
Voltage
Max Output 200 amps 380 amps 800 amps
Current
Pulse Energy 0.18 joules 0.72 joules 2.88 joules
Sweep Range 10-100 10-100 10-100
seconds seconds seconds
Volts/Division 250/500/1000 250/500/1000 250/500/1000/
/2500 / 2500 2500
Repetition 60 Hz (ST103) 60 Hz (ST106) 60 Hz (ST112)
Rate 50 Hz (ST203) 50 Hz (ST206) 50 Hz (ST212)
Voltage
Measurement +/- 10% +/- 10% +/- 10%
& Accuracy
DC HiPot Output 0-3000 Volts 0-6000 Volts 0-12000 Volts
Voltage
Max Output 1000 amps 1000 amps 1000 amps
Current
Current 1/10/100 1/10/100 1/10/100 amps
Resolution amps division amps division division
Over-Current 10/100/1000 10/100/1000 10/100/1000
Trip Settings amps amps amps
Voltage &
Current +/- 5% +/- 5% +/- 5%
Measure-
ment &
Accuracy
Phys. Weight 50 lbs./22.2 Kg 50 lbs./22.2 Kg 58 lbs./25.0 Kg
Char.
Dimensions 21 x 9 x 19 Same Same
(WxHxD) 560 x 210 x
480 mm
Pwr. Required
ST103/06/12 120V/60Hz/ 120V/60Hz/ 120V/60Hz/
A 118W 118W 350W
ST203/06/12 230V/50Hz/ 230V/50Hz/ 230V/50Hz/
A 118W 118W 350W
12/2/2009 | 71-002-V5 EN 73
ST103A, ST106A, ST112A
Technical Specifications
12/2/2009 | 71-002-V5 EN 74
ST103A, ST106A, ST112A
Index
A O
Auxiliary port 14 Open circuit 37, 40
Operation 8, 70
Output Voltage 9, 73
C
Cathode ray tube 11 P
precautions 46, 67
D Pulse Energy 73
S
F
Surge 1, 12, 15, 16, 20, 27, 28, 29, 30, 31,
32, 33, 34, 35, 36, 37, 42, 44, 45, 47, 48,
Footswitch 14, 32, 33, 48, 49, 50, 51, 71
49, 52, 53, 54, 57, 63, 64, 67, 72, 73
Function selector 12
Sweep 11, 32, 33, 51, 73
Sweep Range 73
Synchronous 17, 47, 48
G
Ground 8, 12, 13, 14, 22, 24, 31, 33, 37, 49 T
Test lead connections 14
H Test leads 14, 40, 43, 65
HiPot 1, 11, 12, 13, 14, 15, 16, 19, 20, 22,
24, 25, 41, 50, 53, 57, 63, 66, 69, 72, 73 V
Horizontal position 11
Vertical position 11
Volts/div 12
I Volts/Division 73
Intensity 11, 16
W
Wye-connected 38, 39, 40, 42
12/2/2009 | 71-002-V5 EN 75
ST103A, ST106A, ST112A
Index
12/2/2009 | 71-002-V5 EN 76
ST103A, ST106A, ST112A