Chiller Carrier 30XA-400

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26
At a glance
Powered by AI
The document discusses the features and benefits of AquaForce chillers, including their high efficiency, quiet operation, built-in reliability, and environmentally friendly refrigerants.

The AquaForce chillers provide best-in-class efficiency, quiet operation, virtually maintenance-free compressors, and operate reliably from -20°F to 125°F. They offer high EER and IPLV ratings with efficient rotary screw compressors and Novation heat exchanger technology.

The chillers deliver high part-load efficiency through variable slide valves and independent refrigerant circuits. They also have robust chilled water circuits, optional integrated hydronics packages, electronic expansion valves for precise control, and protective controls for compressors.

Product AquaForce

30XA080-501
Data Fixed Speed Air-Cooled
Liquid Chillers
80 to 500 Nominal Tons
(265 to 1740 Nominal kW)

AquaForce chillers were designed


from the ground up to meet the effi-
ciency demands of today and the
future by providing premium air-
cooled chiller packages for contrac-
tors, consulting engineers and
building owners.
Rotary screw compression
R-134a HFC refrigerant
Quiet AeroAcoustic fan system
Novation heat exchanger
technology with microchannel coil
Easy to use ComfortLink controls
Optional integrated hydronic pump
package, available with variable
frequency drive (VFD)

Features/Benefits
AquaForce 30XA chillers
provide best full load and
part load performance in a
single chassis from 80 to
500 tons
Premium performance
Aqua series chillers are Carriers most
efficient air-cooled models. The Aqua-
a30-4024 Force chiller is one of the most afford-
able air-cooled chillers to operate and
maintain. The AquaForce chiller offers
full load EER (Energy Efficiency Ratio)
up to 10.9 and IPLV (Integrated Part
Load Value) up to 15.5 with Novation
heat exchanger technology. High-
efficiency rotary screw compressors
with infinitely variable slide valves allow
the chillers to exactly match actual load
conditions, delivering exceptional part
load performance. The AquaForce
chillers deliver superior efficiency
Well exceeds ASHRAE 90.1 Standards. through the entire operating range to
keep costs and demand charges down.
This exceptional performance has a

SEISMICOMPLIANT*
significant impact on energy savings
and cost of ownership.
* Meets IBC 2006, ASCE-7-05, CBC 2007, and OSHPD seismic requirements.

Carrier Corporation 2015 Form 30XA-16PD


Features/Benefits (cont)
AquaForce chillers quiet Electronic thermal-dispersion zinc-dipped galvanized frame (with
operation make them flow switch is included with the cool- Magni-coated screws) provides the best
ideal for sound sensitive er. The switch is factory installed and protection on the market for corrosion
applications tested and contains no moving parts resistance. With such a structurally
for high reliability. sound base, no perimeter base rail is
Great performance is delivered in a low
Optional integrated hydronics needed.
sound unit that will be quiet enough for
any application including hospitals, package is more than just a pump, it ComfortLink controls for ease
schools and other sites located in is an entire chilled water system, of use
residential neighborhoods. The Aqua- including: The ComfortLink controls communi-
Force chillers AeroAcoustic fan is Single/dual pumps up to 15 hp and cate in easy to understand English,
almost twice as quiet per cfm as the 140 ft head making it as easy as possible to moni-
competition. In part load operation, Available in constant speed or VFD tor and control each AquaForce chiller
such as cooler weather or night time configuration while accurately maintaining fluid
duty, fewer fans operate. This results in temperatures. ComfortLink controls
Strainer
even quieter operation. are available with French, Portuguese
Start-up strainer (to be removed
Built in reliability within 24 hours after chiller start-up) and Spanish as a standard configura-
Flow regulator tion option. Carriers 30 Series
AquaForce chillers were developed chillers ComfortLink controls provide
under one of the most exacting Freeze protection to 20 F (29 C)
(with freeze protection option) features such as chilled water tempera-
qualification programs ever used ture reset, demand limiting, compres-
for commercial chiller products. Heaters
sor wear minimization and protection,
The compressors are virtually Required piping
temperature and pressure displays and
maintenance-free and protected by Pressure/temperature taps diagnostic functions. These controls
an auto-adaptive control that minimiz- Isolation check valves for dual pump result in higher chiller reliability, simpli-
es compressor wear. Operate Aqua- systems fied training and more productive ser-
Force chillers year-round from The factory-installed and tested hy- vice calls with correspondingly lower
20 F (29 C) to 125 F (52 C), with a operational and maintenance costs.
dronics package provides faster, sim-
combination of options and control
methods. The following features are pler and less expensive installation. Two user interface options are
also provided to help ensure reliable available, the Touch Pilot display and
Environmentally balanced the Navigator module. The Touch
performance:
Refrigerant R-134a enables the user to Pilot display is an easy to use touch
Multiple independent circuits make a responsible choice in helping screen display that provides simple
provide redundancy and greater to preserve the environment. Refriger- navigation for configuration and con-
reliability. ant R-134a is an HFC refrigerant that trol of AquaForce units.
Electronic expansion valve (EXV) does not contain ozone-layer damag-
Carrier's exclusive handheld Naviga-
allows for precise control through all ing chlorine. This refrigerant is
tor display provides convenience and
operating ranges. unaffected by the Montreal Protocol. It
powerful information in the palm of
is a safe, non-toxic*, efficient and envi-
Highly efficient, reliable your hand. The Navigator display helps
ronmentally balanced refrigerant.
chilled water circuit technicians to quickly diagnose prob-
Easy installation lems and even prevent them from
AquaForce chillers provide a compre-
A single chassis design (with the excep- occurring. All AquaForce units are
hensive chilled water circuit utilizing a
tion of the 30XA-501) provides a ready to be used with Carrier Comfort
high-efficiency shell-in-tube flooded
one-piece unit from 80 to 500 tons. Network (CCN) devices.
cooler or an optional shell-in-tube DX
(direct expansion) cooler. Units are The base rail is industrial-quality 7 ga A BACnet communication option
equipped with a drainable cooler. for maximum structural integrity. The is also available for the i-Vu Open
control system or a third-party BACnet
building automation system.
Table of contents Page
Seismic certification
A seismic kit is available which will re-
Features/Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 sult in a unit SDS (seismic design accel-
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5 eration parameter) level of 2.4.
AHRI Capacity Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25
Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-28
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-109
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110,111
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112-121
Typical Piping and Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122-127
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128-145
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145-147
Control and Power Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . 148-151 *Under ASHRAE Standard 34-1992, R-134a is
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152-160 classified as an A1 refrigerant.
Sponsored by ASHRAE (American Society of
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161-167 Heating, Refrigerating, and Air-Conditioning
Engineers).
2
Novation heat exchanger determine whether corrosion protec- clean without causing damage to the
technology tion is recommended for particular ap- coil.
The Novation heat exchanger design plications in coastal/marine Due to the compact all aluminum
with microchannel (MCHX) condenser environments. Following the input of design, microchannel coils will reduce
coil is a robust, cost effective alterna- the requested data, the E-CAT pro- overall unit operating weight by 6 to
tive to traditional coil design. These gram output will advise the appropriate 7%. The streamlined MCHX coil de-
coils are offered coated or uncoated to coil to be used. Other factors described sign reduces refrigerant charge by up
match coil protection to site condi- in "Selection Guide: Environmental to 30%.
tions. The e-coated version of this coil Corrosion Protection catalog number
04-581061-01 must also be consid- The coil is designed with rubber iso-
can withstand an 8000-hour salt spray lation around the powder painted coil
test in accordance with ASTM (Ameri- ered to determine if corrosion protec-
tion is required. frame to eliminate galvanic couples,
can Society for Testing and Materials) which can cause corrosion due to dis-
B-117 standard. The Carrier Electron- Microchannel coils are sturdier than similar metals.
ic Catalog (E-CAT) can be used to other coil types, making them easier to

a30-4456
TOUCH PILOT DISPLAY

TUBES

FINS
a30-4458

OPTIONAL PUMP PACKAGE


(FLOODED COOLER SHOWN)

MANIFOLD

MICROCHANNELS

NOVATION HEAT EXCHANGER TECHNOLOGY


WITH MICROCHANNEL CONDENSER COILS

a30-3926

LOW-NOISE AEROACOUSTIC FAN

3
Model number nomenclature
3

30XA AquaForce Air-Cooled Chiller

Design Series
SEE NEXT PAGE
Unit Sizes*
080 102 140 182 240 282 350 451 FOR REMAINDER
082 110 142 200 242 300 352 476
090 112
092 120
160
162
202
220
260
262
302
325
400
401
500
501
OF MODEL NUMBER
100 122 180 222 280 327 450 NOMENCLATURE
Voltage
1 575-3-60 6 460-3-60
2 380-3-60 7 200-3-60
4 230-3-60 Cooler Options
- Cooler without Heater
0 Cooler with Heater
Condenser Coil/Ambient/Low Sound Options 1 DX Cooler with Heater, Hydronic Package
- Aluminum Fin/Copper Tube, High Ambient Temperature 3 Flooded Cooler with Heater, Minus One Pass
0 Copper Fin/Copper Tube, High Ambient Temperature 5 Flooded Cooler with Heater, Plus One Pass
1 Aluminum Pre-Coat Fin/Copper Tube, High Ambient Temperature 6 DX Cooler without Heater, Hydronic Package
2 Aluminum E-Coat Fin/Copper Tube, High Ambient Temperature 7 Cooler with Heater, Full End Screen, Coil Trim Panels, Grilles
3 Copper E-Coat Fin/Copper Tube, High Ambient Temperature 8 DX Cooler with Heater, Hydronic Package, Full End Screen,
4 Novation Heat Exchanger (MCHX), High Ambient Coil Trim Panels, Grilles
Temperature F DX Cooler without Heater, Hydronic Package, Full End Screen,
5 MCHX E-Coat, High Ambient Temperature Coil Trim Panels, Grilles
6 Aluminum Fin/Copper Tube, High Ambient Temperature, G DX Cooler without Heater, Full End Screen, Coil Trim Panels, Grilles
Low Sound K Flooded Cooler with Heater, Minus One Pass, Full End Screen,
7 Copper Fin/Copper Tube, High Ambient Temperature, Low Sound Coil Trim Panels, Grilles
8 Aluminum Pre-Coat Fin/Copper Tube, High Ambient Temperature, M Flooded Cooler with Heater, Plus One Pass, Full End Screen,
Low Sound Coil Trim Panels, Grilles
9 Aluminum E-Coat Fin/Copper Tube, High Ambient Temperature,
Low Sound
B Copper E-Coat Fin/Copper Tube, High Ambient Temperature,
Low Sound Hydronic Pump Package Options
C MCHX, High Ambient Temperature, Low Sound - None G Single Pump, 5 HP with VFD
D MCHX E-Coat, High Ambient Temperature, Low Sound 1 Single Pump, 5 HP H Single Pump, 7.5 HP with VFD
F Aluminum Fin/Copper Tube, Standard Ambient Temperature, 2 Single Pump, 7.5 HP J Single Pump, 10 HP with VFD
Low Sound 3 Single Pump, 10 HP K Single Pump, 15 HP with VFD
G Copper Fin/Copper Tube, Standard Ambient Temperature, 4 Single Pump, 15 HP N Dual Pump, 5 HP with VFD
Low Sound 7 Dual Pump, 5 HP P Dual Pump, 7.5 HP with VFD
H Aluminum Pre-Coat Fin/Copper Tube, Standard Ambient 8 Dual Pump, 7.5 HP Q Dual Pump, 10 HP with VFD
Temperature, Low Sound B Dual Pump, 10 HP R Dual Pump, 15 HP with VFD
J Aluminum E-Coated Fin/Copper Tube, Standard Ambient C Dual Pump, 15 HP
Temperature, Low Sound
K Copper E-Coat Fin/Copper Tube, Standard Ambient Temperature,
Low Sound
L MCHX, Standard Ambient Temperature, Low Sound
M MCHX E-Coat, Standard Ambient Temperature, Low Sound
N Aluminum Fin/Copper Tube, Standard Ambient Temperature
P Copper Fin/Copper Tube, Standard Ambient Temperature
Q Aluminum Pre-Coat Fin/Copper Tube, Standard Ambient
Temperature
R Aluminum E-Coat Fin/Copper Tube, Standard Ambient
Temperature
S Copper E-Coat Fin/Copper Tube, Standard Ambient Temperature
T MCHX, Standard Ambient Temperature
V MCHX E-Coat, Standard Ambient Temperature

a30-5589

LEGEND
CFSP Coil Face Shipping Protection
DX Direct Expansion
EMM Energy Management Module
LON Local Operating Network
SCCR Short Circuit Current Rating
VFD Variable Frequency Drive
XL Across-the-Line Starter
*xx0, xx1, xx5, and xx6 size units contain flooded style evaporators.
xx2 and xx7 size units contain direct expansion (DX) style evaporators. Quality Assurance
Both flooded and DX cooler.
**Available in Middle East only. Certified to ISO 9001

4
3

Packaging/Security/High SCCR Options


0 Coil Face Shipping Protection (CFSP), Skid
1 CFSP, Skid, Top Crate, Bag
3 CFSP, Coil Trim Panels
4 CFSP, Skid, Coil Trim Panels
SEE PREVIOUS PAGE 5 CFSP, Skid, Top Crate, Bag, Coil Trim Panels
7 CFSP, Coil Trim Panels, Upper and Lower Grilles
FOR REMAINDER 8 CFSP, Skid, Coil Trim Panels, Upper and Lower Grilles
9 CFSP, Skid, Top Crate, Bag, Coil Trim Panels, Upper and Lower Grilles
OF MODEL NUMBER C CFSP, Coil Trim Panels, Upper and Lower Grilles, Upper Hail Guards
D CFSP, Skid, Coil Trim Panels, Upper and Lower Grilles, Upper Hail Guards
F CFSP, Skid, Top Crate, Bag, Coil Trim Panels, Upper and Lower Grilles,
NOMENCLATURE Upper Hail Guards
H CFSP, Skid, High SCCR
J CFSP, Skid, Top Crate, Bag, High SCCR
K CFSP, High SCCR
L CFSP
Refrigeration Circuit Options
M CFSP, Coil Trim Panels, High SCCR
- None
N CFSP, Skid, Coil Trim Panels, High SCCR
0 Suction Line Insulation
P CFSP, Skid, Top Crate, Bag, Coil Trim Panels, High SCCR
1 Isolation Valves
R CFSP, Coil Trim Panels, Upper and Lower Grilles, High SCCR
2 Low Ambient Head Pressure Control
S CFSP, Skid, Coil Trim Panels, Upper and Lower Grilles, High SCCR
3 Suction Line Insulation, Isolation Valves
T CFSP, Skid, Top Crate, Bag, Coil Trim Panels, Upper and Lower Grilles,
4 Suction Line Insulation, Low Ambient Head Pressure Control
High SCCR
5 Isolation Valves, Low Ambient Head Pressure Control
W CFSP, Coil Trim Panels, Upper and Lower Grilles, Upper Hail Guards, High SCCR
6 Suction Line Insulation, Isolation Valves, Head Pressure Control
X CFSP, Skid, Coil Trim Panels, Upper and Lower Grilles, Upper Hail Guards,
7 Minimum Load Control
High SCCR
8 Suction Line Insulation, Minimum Load Control
Y CFSP, Skid, Top Crate, Bag, Coil Trim Panels, Upper and Lower Grilles, Upper
9 Isolation Valves, Minimum Load Control
Hail Guards, High SCCR
B Low Ambient Head Pressure Control Operation, Minimum Load Control
C Suction Line Insulation, Isolation Valves, Minimum Load Control
D Suction Line Insulation, Head Pressure Control, Minimum Load Control Controls/Communication Options
F Isolation Valves, Head Pressure Control, Minimum Load Control - Navigator Display
G Suction Line Insulation, Isolation Valves, Head Pressure Control, 0 Navigator Display, EMM
Minimum Load Control 1 Navigator Display, Service Option
H None (High Ambient)** 2 Navigator Display, EMM, Service Option
J Suction Line Insulation (High Ambient)** 3 Touch Pilot Display
K Isolation Valve (High Ambient)** 4 Touch Pilot Display, EMM
M Suction Line Insulation (High Ambient), Isolation Valve (High Ambient)** 5 Touch Pilot Display, Service Option
R Minimum Load Control (High Ambient)** 6 Touch Pilot Display, EMM, Service Option
S Suction Line Insulation (High Ambient), Minimum Load Control (High Ambient)** 7 Navigator Display, BACnet/Modbus Translator
T Isolation Valve (High Ambient), Minimum Load Control (High Ambient)** 8 Navigator Display, BACnet/Modbus Translator, EMM
W Suction Line Insulation (High Ambient), Minimum Load Control (High Ambient), 9 Navigator Display, BACnet/Modbus Translator, Service Option
Isolation Valve (High Ambient)** B Navigator Display, BACnet/Modbus Translator, EMM, Service Option
C Touch Pilot Display, BACnet/Modbus Translator
D Touch Pilot Display, BACnet/Modbus Translator, EMM
F Touch Pilot Display, BACnet/Modbus Translator, Service Option
Electrical Options
G Touch Pilot Display, BACnet/Modbus Translator, EMM, Service Option
- Single Point Power, XL, Terminal Block, No Control Transformer
H Navigator Display, LON Translator
0 Single Point Power, Wye-Delta, Terminal Block, No Control Transformer
J Navigator Display, LON Translator, EMM
3 Dual Point Power, XL, Terminal Block, No Control Transformer
K Navigator Display, LON Translator, Service Option
4 Dual Point Power, Wye-Delta, Terminal Block, No Control Transformer
L Navigator Display, LON Translator, EMM, Service Option
7 Single Point Power, XL, Disconnect, No Control Transformer
M Touch Pilot Display, LON Translator
8 Single Point Power, Wye-Delta, Disconnect, No Control Transformer
N Touch Pilot Display, LON Translator, EMM
C Dual Point Power, XL, Disconnect, No Control Transformer
P Touch Pilot Display, LON Translator, Service Option
D Dual Point Power, Wye-Delta, Disconnect, No Control Transformer
Q Touch Pilot Display, LON Translator, EMM, Service Option
H Single Point Power, XL, Terminal Block, Control Transformer
R Navigator Display, BACnet Communication
J Single Point Power, Wye-Delta, Terminal Block, Control Transformer
S Navigator Display, BACnet Communication, EMM
M Dual Point Power, XL, Terminal Block, Control Transformer
T Navigator Display, BACnet Communication, Service Option
N Dual Point Power, Wye-Delta, Terminal Block, Control Transformer
V Navigator Display, BACnet Communication, EMM, Service Option
R Single Point Power, XL, Disconnect, Control Transformer
W Touch Pilot Display, BACnet Communication
S Single Point Power, Wye-Delta, Disconnect, Control Transformer
X Touch Pilot Display, BACnet Communication, EMM
W Dual Point Power, XL, Disconnect, Control Transformer
Y Touch Pilot Display, BACnet Communication, Service Option
X Dual Point Power, Wye-Delta, Disconnect, Control Transformer
Z Touch Pilot Display, BACnet Communication, EMM, Service Option

5
AHRI* capacity ratings (English and SI)
UNITS WITH AL/CU CONDENSER COILS
30XA CAPACITY TOTAL FULL LOAD IPLV COOLER FLOW RATE COOLER PRESSURE DROP
UNIT POWER
SIZE Tons kW (kW) EER COP EER COP GPM L/s ft wg kPa
080 75.6 265.9 91.6 9.9 2.9 14.2 4.2 181.3 11.4 11.7 34.9
090 84.8 298.2 95.1 10.7 3.1 14.6 4.3 203.4 12.8 11.4 34.0
100 93.9 330.2 107.8 10.5 3.1 15.0 4.4 225.4 14.2 13.7 40.9
110 102.4 360.1 118.6 10.4 3.0 15.2 4.4 245.8 15.5 13.9 41.5
120 110.7 389.3 129.5 10.3 3.0 15.2 4.4 265.7 16.8 11.9 35.5
140 132.8 467.0 148.7 10.7 3.1 14.4 4.2 318.8 20.1 13.3 39.7
160 152.3 535.6 173.0 10.6 3.1 14.8 4.3 365.5 23.1 13.1 39.1
180 171.3 602.4 192.1 10.7 3.1 14.3 4.2 411.1 25.9 15.5 46.2
200 194.0 682.3 217.2 10.7 3.1 14.8 4.3 465.6 29.4 13.2 39.4
220 211.7 744.5 239.6 10.6 3.1 14.5 4.2 508.0 32.0 15.5 46.2
240 228.1 802.2 264.1 10.4 3.0 14.8 4.3 547.5 34.5 17.8 53.1
260 250.9 882.4 281.7 10.7 3.1 14.3 4.2 602.2 38.0 10.3 30.7
280 268.5 944.3 301.2 10.7 3.1 14.3 4.2 644.3 40.6 11.6 34.6
300 287.5 1011.1 326.3 10.6 3.1 14.9 4.4 690.0 43.5 13.1 39.1
325 306.6 1078.3 347.1 10.6 3.1 14.3 4.2 735.9 46.4 13.5 40.3
350 324.1 1139.8 374.8 10.4 3.0 14.4 4.2 777.7 49.1 14.9 44.4
400 383.6 1349.1 449.4 10.2 3.0 14.8 4.3 920.7 58.1 10.4 31.0
401 396.3 1393.9 464.0 10.2 3.0 13.4 3.9 951.2 59.8 20.8 61.6
450 426.7 1500.6 509.2 10.1 2.9 14.1 4.1 1024.1 64.6 10.1 30.1
451 435.6 1532.2 503.9 10.4 3.0 13.6 4.0 1045.5 65.7 25.3 75.1
476 459.2 1615.0 554.3 9.9 2.9 14.0 4.1 1102.0 69.3 22.6 67.1
500 458.0 1610.7 549.1 10.0 2.9 14.3 4.2 1099.2 69.3 12.1 36.1
501 494.1 1737.8 580.0 10.2 3.0 13.8 4.1 1185.8 74.6 26.1 77.6

UNITS WITH MCHX CONDENSER COILS


MCHX CAPACITY FULL LOAD IPLV COOLER FLOW RATE COOLER PRESSURE DROP
COILS TOTAL
30XA POWER
UNIT Tons kW (kW) EER COP EER COP GPM L/s ft wg kPa
SIZE
080 75.8 266.6 90.1 10.1 3.0 14.5 4.2 182.0 11.5 11.8 35.2
090 85.2 299.6 93.4 10.9 3.2 14.8 4.3 204.5 12.9 11.5 34.3
100 94.4 332.0 105.7 10.7 3.1 15.3 4.5 226.7 14.3 13.9 41.5
110 103.0 362.2 116.4 10.6 3.1 15.4 4.5 247.2 15.6 14.1 42.1
120 111.4 391.8 127.2 10.5 3.1 15.5 4.5 267.4 16.9 12.0 35.8
140 133.4 469.1 146.4 10.9 3.2 14.7 4.3 320.1 20.2 13.4 40.0
160 153.1 538.4 170.1 10.8 3.2 15.0 4.4 367.3 23.2 13.2 39.4
180 172.0 604.9 189.2 10.9 3.2 14.5 4.2 412.8 26.0 15.6 46.5
200 194.9 685.4 213.7 10.9 3.2 15.1 4.4 467.8 29.5 13.3 39.7
220 212.7 748.0 235.7 10.8 3.2 14.7 4.3 510.4 32.2 15.7 46.8
240 229.2 806.1 260.1 10.6 3.1 15.0 4.4 550.1 34.7 18.0 53.7
260 251.7 885.2 278.8 10.8 3.2 14.4 4.2 604.0 38.1 10.3 30.7
280 269.3 947.1 298.0 10.8 3.2 14.5 4.2 646.3 40.8 11.6 34.6
300 288.3 1013.9 323.3 10.7 3.1 15.0 4.4 691.8 43.6 13.2 39.4
325 307.1 1080.0 344.8 10.7 3.1 14.4 4.2 737.1 46.5 13.6 40.6
350 324.5 1141.2 372.7 10.5 3.1 14.5 4.3 778.8 49.1 15.0 44.7
400 385.0 1354.0 444.1 10.4 3.0 14.9 4.4 924.0 58.3 10.5 31.3
401 396.8 1395.7 462.0 10.3 3.0 13.5 4.0 952.4 59.9 20.8 61.8
450 427.6 1503.8 505.5 10.2 3.0 14.2 4.2 1026.3 64.7 10.1 30.1
451 436.2 1534.1 501.7 10.4 3.1 13.8 4.0 1046.8 65.8 25.4 75.3
476 459.8 1617.0 552.0 10.0 2.9 14.1 4.1 1103.4 69.4 22.7 67.2
500 459.1 1614.6 544.8 10.1 3.0 14.4 4.2 1101.8 69.5 12.2 36.4
501 494.7 1740.0 577.3 10.3 3.0 14.0 4.1 1187.4 74.7 26.2 77.8
LEGEND 3. All data in the above table was generated in Packaged Chiller
AL Aluminum Builder version 3.49h. Refer to the most current version of the
COP Coefficient of Performance Packaged Chiller Builder for the most up-to-date data.
CU Copper
EER Energy Efficiency Ratio
IPLV Integrated Part Load Value
MCHX Microchannel Heat Exchanger
*Air Conditioning, Heating, and Refrigeration Institute (U.S.A.).

NOTES:
1. Rated in accordance with AHRI Standard 550/590 at standard rat-
ing conditions.
2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving water temperature: 44 F (6.7 C)
Flow rate: 2.4 gpm/ton (0.043 l/s per kW)
Fouling Factor:
0.00010 hr x sq ft F/Btu (0.000018 m2 x C/W)
Condenser Conditions:
Entering air temperature: 95 F (35 C)

6
Physical data (cont)
30XA222-302 ENGLISH
UNIT 30XA 222 240 242 260 262 280 282 300 302
OPERATING WEIGHT (lb)*
Al-Cu Condenser Coils 15,071 14,887 15,231 16,853 17,055 17,022 17,224 17,362 17,834
Cu-Cu Condenser Coils 16,639 16,455 16,799 18,662 18,864 18,831 19,033 19,292 19,764
MCHX Condenser Coils 14,092 13,897 14,241 15,720 15,922 15,878 16,080 16,141 16,613
REFRIGERANT TYPE R-134a, EXV Controlled System
Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C 246/198/ 270/270/ 246/246/ 375/220/ 330/206/ 375/270/ 330/256/ 415/270/ 386/261/
Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C (MCHX) 135/125/ 159.5/159/ 135/135/ 233.5/156/ 188/142/ 226.5/159.5/ 181/145/ 230/161/ 201/152/
COMPRESSORS Semi-Hermetic Twin Rotary Screws
Quantity 2 2 2 2 2 2 2 2 2
Speed (rpm) 3500
(Qty) Compressor Model Number Ckt A (1) 06TT-356 (1) 06TT-356 (1) 06TT-356 (1) 06TU-483 (1) 06TU-483 (1) 06TU-483 (1) 06TU-483 (1) 06TU-554 (1) 06TU-554
(Qty) Compressor Model Number Ckt B (1) 06TT-301 (1) 06TT-356 (1) 06TT-356 (1) 06TT-301 (1) 06TT-301 (1) 06TT-356 (1) 06TT-356 (1) 06TT-356 (1) 06TT-356
(Qty) Compressor Model Number Ckt C N/A N/A N/A N/A N/A N/A N/A N/A N/A
Oil Charge (gal), Ckt A/Ckt B/Ckt C 6.75/6.25/ 6.75/6.75/ 6.75/6.75/ 7.5/6.75/ 7.5/6.75/ 7.5/6.75/ 7.5/6.75/ 7.5/6.75/ 7.5/6.75/
Minimum Capacity Step (%)
Standard 14 15 15 11 11 13 13 12 12
Optional 10 10 10 8 8 9 9 7 7
Direct Expan- Flooded, Shell Direct Expan- Flooded, Shell Direct Expan- Flooded, Shell Direct Expan- Flooded, Shell Direct Expan-
COOLER
sion Cooler and Tube Type sion Cooler and Tube Type sion Cooler and Tube Type sion Cooler and Tube Type sion Cooler
Net Fluid Volume (gal.) 71.0 39.0 71.0 42.0 82.8 44.0 82.8 48.5 108.0
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220 220 220
Maximum Water-Side Pressure without Pumps (psig) 300 300 300 300 300 300 300 300 300
Maximum Water-Side Pressure with Pumps (psig)
WATER CONNECTIONS
Drain (NPT, in.) 3/ 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4
4
Standard, Inlet and Outlet, Victaulic (in.) 6 6 6 8 6 8 6 8 6
Number of Passes 2 2 2 2
Minus 1 Pass, Inlet and Outlet, Victaulic (in.) 8 8 8 8
Number of Passes 1 1 1 1
Plus 1 Pass, Inlet and Outlet, Victaulic (in.) 6 8 8 8
Number of Passes 3 3 3 3
CONDENSER FANS Shrouded Axial Type, Vertical Discharge
Fan Speed (rpm) Standard/High Ambient** 850/1140 850/1140 850/1140 850/1140 850/1140 850/1140 850/1140 850/1140 850/1140
No. Blades...Diameter (in.) 9...30 9...30 9...30 9...30 9...30 9...30 9...30 9...30 9...30
No. Fans (Ckt A/Ckt B/Ckt C) 7/6/ 7/6/ 7/6/ 9/6/ 9/6/ 9/7/ 9/7/ 10/6/ 10/6/
Total Airflow (cfm) 850 rpm 120,900 120,900 120,900 139,500 139,500 148,800 148,800 148,800 148,800
Total Airflow (cfm) 1140 rpm 161,200 161,200 161,200 186,000 186,000 198,400 198,400 198,400 198,400
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C) 7/6/ 7/6/ 7/6/ 9/6/ 9/6/ 9/7/ 9/7/ 10/6/ 10/6/
Total Face Area (sq ft) 305 305 305 352 352 375 375 375 375
HYDRONIC MODULE (Optional)
N/A
Pump
CHASSIS DIMENSIONS (ft-in.)
Length 27-6 31-5
Width 7-43/4
Height 7-67/16

30XA325-501 ENGLISH
UNIT 30XA 325 327 350 352 400 401 450 451 476 500 501
OPERATING WEIGHT (lb)*
Al-Cu Condenser Coils 18,834 19,306 19,040 19,512 24,578 22,690 26,600 23,421 25,555 26,894 27,918
Cu-Cu Condenser Coils 21,005 21,477 21,211 21,683 26,990 25,102 29,254 26,075 28,209 29,547 31,054
MCHX Condenser Coils 17,467 17,939 17,659 18,131 23,038 20,782 24,901 21,324 23,457 25,167 25,438
REFRIGERANT TYPE R-134a, EXV Controlled System
Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C 375/375/ 344/344/ 415/375/ 384/344/ 270/270/375 490/415 415/205/415 560/415 505/495 415/270/415 590/525
226.5/226.5/ 231.5/226.5/
Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C (MCHX) 195/195/ 200/195/ 161/161/203 285/235 224/161/215 300/325 295/290 231/168/215 310/300

COMPRESSORS Semi-Hermetic Twin Rotary Screws


Quantity 2 2 2 2 3 2 3 2 2 3 2
Speed (rpm) 3500
(1) 06TU- (1) 06TU- (1) 06TU- (1) 06TU- (1) 06TT- (1) 06TV- (1) 06TU- (1) 06TV- (1) 06TV- (1) 06TU- (1) 06TV-
(Qty) Compressor Model Number Ckt A
483 483 554 554 356 680 554 819 753 554 819
(1) 06TU- (1) 06TU- (1) 06TU- (1) 06TU- (1) 06TT- (1) 06TU- (1) 06TT- (1) 06TU- (1) 06TV- (1) 06TT- (1) 06TV-
(Qty) Compressor Model Number Ckt B
483 483 483 483 356 554 266 554 680 356 753
(1) 06TU- (1) 06TU- (1) 06TU-
(Qty) Compressor Model Number Ckt C N/A N/A N/A N/A 483 N/A 554 N/A N/A 554 N/A
6.75/6.75/
Oil Charge (gal), Ckt A/Ckt B/Ckt C 7.5/7.5/ 7.5/7.5/ 7.5/7.5/ 7.5/7.5/ 7.5/7.5/ 7.5/6.25/7.5 7.5/7.5/ 7.5/7.5/ 7.5/6.75/7.5 7.5/7.5/
7.5
Minimum Capacity Step (%)
Standard 15 15 15 15 9 15 6 12 15 7 15
Optional 10 10 10 10 6 11 4 8 11 5 11
Flooded, Direct Flooded, Direct
COOLER Shell and Expansion Shell and Expansion Flooded, Shell and Tube Type
Tube Type Cooler Tube Type Cooler
Net Fluid Volume (gal.) 50.5 108.0 53.4 108.0 68.0 64.5 75.0 64.5 81.8 83.0 81.8
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220 220 220 220 220
Maximum Water-Side Pressure without Pumps (psig) 300 300 300 300 300 300 300 300 300 300 300
Maximum Water-Side Pressure with Pumps (psig)
WATER CONNECTIONS
Drain (NPT, in.) 3/ 3/4 3/8 3/4 3/8 3/8 3/8 3/8 3/8 3/8 3/8
8
Standard, Inlet and Outlet, Victaulic (in.) 8 6 8 6 8 8 8 8 8 8 8
Number of Passes 2 2 1 2 1 2 2 1 2
Minus 1 Pass, Inlet and Outlet, Victaulic (in.) 8 8 8 8 8 8
Number of Passes 1 1 1 1 1 1
Plus 1 Pass, Inlet and Outlet, Victaulic (in.) 8 8
Number of Passes 3 3
CONDENSER FANS Shrouded Axial Type, Vertical Discharge
Fan Speed (rpm) Standard/High Ambient** 850/1140 850/1140 850/1140 850/1140 850/1140 /1140 850/1140 /1140 /1140 850/1140 /1140
No. Blades...Diameter (in.) 9...30 9...30 9...30 9...30 9...30 9...30 9...30 9...30 9...30 9...30 9...30
No. Fans (Ckt A/Ckt B/Ckt C) 9/9/ 9/9/ 9/9/ 9/9/ 6/6/8 11/9/ 8/6/8 13/9/ 11/11/ 8/6/8 14/12/
Total Airflow (cfm) 850 rpm 167,400 167,400 167,400 167,400 186,000 204,600 204,600
Total Airflow (cfm) 1140 rpm 223,200 223,200 223,200 223,200 248,000 248,000 272,800 272,800 272,800 272,800 322,400
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C) 9/9/ 9/9/ 9/9/ 9/9/ 6/6/8 11/9/ 8/6/8 13/9/ 11/11/ 8/6/8 14/12/
Total Face Area (sq ft) 422 422 422 422 469 469 516 516 516 516 608
HYDRONIC MODULE (Optional) N/A
Pump
CHASSIS DIMENSIONS (ft-in.)
Length 35-4 39-3 43-2 51-3
Width 7-43/4
Height 7-67/16

LEGEND *Operating weight includes 2 pumps on models 30XA090-162. No pumps are available on 30XA080,
Cu Copper
30XA082, or 30XA180-501. All weights include coil trim panels. See pages 11-25 for mounting weights
Al Aluminum for units without pumps and units with single pump packages.
EXV Electronic Expansion Valve 30XA080,082 units do not have an economizer.
MCHX Microchannel Heat Exchanger **The standard ambient temperature option is not available on 30XA401, 451, 476, and 501 units. The
N/A Not Applicable high ambient temperature option is not available on 30XA080-122 units.

8
Physical data (cont)
30XA222-302 SI
UNIT 30XA 222 240 242 260 262 280 282 300 302
OPERATING WEIGHT (kg)*
Al-Cu Condenser Coils 6 836 6 753 6 909 7 644 7 736 7 721 7 813 7 876 8 089
Cu-Cu Condenser Coils 7 547 7 464 7 620 8 465 8 556 8 542 8 633 8 751 8 965
MCHX Condenser Coils 6 392 6 304 6 459 7 130 7 222 7 202 7 294 7 322 7 535
REFRIGERANT TYPE R-134a, EXV Controlled System
Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C 112/90/ 122.5/122.5/ 112/112/ 170.1/99.8/ 150/93/ 170.1/122.5/ 150/116/ 188.3/122.5/ 175/118/
Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C (MCHX) 61/57/ 72.3/72.1/ 61/61/ 105.9/70.8/ 85/64/ 102.7/72.3/ 82/66/ 104.3/73.0/ 91/69/
COMPRESSORS Semi-Hermetic Twin Rotary Screws
Quantity 2 2 2 2 2 2 2 2 2
Speed (r/s) 3500
(Qty) Compressor Model Number Ckt A (1) 06TT-356 (1) 06TT-356 (1) 06TT-356 (1) 06TU-483 (1) 06TU-483 (1) 06TU-483 (1) 06TU-483 (1) 06TU-554 (1) 06TU-554
(Qty) Compressor Model Number Ckt B (1) 06TT-301 (1) 06TT-356 (1) 06TT-356 (1) 06TT-301 (1) 06TT-301 (1) 06TT-356 (1) 06TT-356 (1) 06TT-356 (1) 06TT-356
(Qty) Compressor Model Number Ckt C N/A N/A N/A N/A N/A N/A N/A N/A N/A
Oil Charge (liter), Ckt A/Ckt B/Ckt C 25.6/23.7/ 25.6/25.6/ 25.6/25.6/ 28.4/25.6/ 28.4/25.6/ 28.4/25.6/ 28.4/25.6/ 28.4/25.6/ 28.4/25.6/
Minimum Capacity Step (%)
Standard 14 15 15 10 11 13 13 12 12
Optional 10 10 10 8 8 9 9 7 7
Direct Expan- Flooded, Shell Direct Expan- Flooded, Shell Direct Expan- Flooded, Shell Direct Expan- Flooded, Shell Direct Expansion
COOLER sion Cooler and Tube Type sion Cooler and Tube Type sion Cooler and Tube Type sion Cooler and Tube Type Cooler
Net Fluid Volume (liters) 269.0 147.6 269.0 159.0 313.0 166.6 313.0 183.6 409.0
Maximum Refrigerant Pressure (kPa) 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8
Maximum Water-Side Pressure without
2 068 2 068 2 068 2 068 2 068 2 068 2 068 2 068 2 068
Pumps (kPa)
Maximum Water-Side Pressure with Pumps (kPa)
WATER CONNECTIONS
Drain (NPT, in.) 3/ 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4
4
Standard, Inlet and Outlet, Victaulic (in.) 6 6 6 8 6 8 6 8 6
Number of Passes 2 2 2 2
Minus 1 Pass, Inlet and Outlet, Victaulic (in.) 8 8 8 8
Number of Passes 1 1 1 1
Plus 1 Pass, Inlet and Outlet, Victaulic (in.) 6 8 8 8
Number of Passes 3 3 3 3
CONDENSER FANS Shrouded Axial Type, Vertical Discharge
Fan Speed (r/s) Standard/High Ambient** 14.2/19.0 14.2/19.0 14.2/19.0 14.2/19.0 14.2/19.0 14.2/19.0 14.2/19.0 14.2/19.0 14.2/19.0
No. Blades...Diameter (mm) 9...762 9...762 9...762 9...762 9...762 9...762 9...762 9...762 9...762
No. Fans (Ckt A/Ckt B/Ckt C) 7/6/ 7/6/ 7/6/ 9/6/ 9/6/ 9/7/ 9/7/ 10/6/ 10/6/
Total Airflow (L/s) 14.2 r/s 57 059 57 059 57 059 65 837 65 837 70 226 70 226 70 226 70 226
Total Airflow (L/s) 19.0 r/s 76 078 76 078 76 078 87 782 87 782 93 634 93 634 93 634 93 634
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C) 7/6/ 7/6/ 7/6/ 9/6/ 9/6/ 9/7/ 9/7/ 10/6/ 10/6/
Total Face Area (sq m) 28 28 28 33 33 35 35 35 35
HYDRONIC MODULE (Optional)
N/A
Pump
CHASSIS DIMENSIONS (mm)
Length 8 382 9 576
Width 2 255
Height 2 300

30XA325-501 SI
UNIT 30XA 325 327 350 352 400 401 450 451 476 500 501
OPERATING WEIGHT (kg)*
Al-Cu Condenser Coils 8 543 8 757 8 636 8 850 11 149 10 292 12 066 10 624 11 592 12 199 12 663
Cu-Cu Condenser Coils 9 528 9 742 9 621 9 835 12 243 11 386 13 269 11 828 12 795 13 402 14 086
MCHX Condenser Coils 7 923 8 137 8 010 8 224 10 450 9 427 11 295 9 672 10 640 11 416 11 539
REFRIGERANT TYPE R-134a, EXV Controlled System
Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C 170.1/170.1/ 188.3/170.1/ 122.5/122.5/ 188.3/102/ 188.3/188.3/
156/156/ 174/156/ 222/188/ 254/188/ 229/225/ 268/238/
170.1 188.3 122.5
Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C (MCHX) 102.7/102.7/ 88/88/ 105.0/102.7/ 91/88/ 73.0/73.0/92.1 129/107/ 101.6/73.0/ 136/107/ 134/132/ 104.8/76.2/ 141/136/
97.5 97.5
COMPRESSORS Semi-Hermetic Twin Rotary Screws
Quantity 2 2 2 2 3 2 3 2 2 3 2
Speed (r/s) 58.3
(1) 06TU- (1) 06TU- (1) 06TU-
(Qty) Compressor Model Number Ckt A (1) 06TU-554 (1) 06TT-356 (1) 06TV-680 (1) 06TU-554 (1) 06TV-819 (1) 06TV-753 (1) 06TU-554 1) 06TV-819
483 483 554
(1) 06TU- (1) 06TU- (1) 06TU-
(Qty) Compressor Model Number Ckt B (1) 06TU-483 (1) 06TT-356 (1) 06TU-554 (1) 06TT-266 (1) 06TU-554 (1) 06TV-680 (1) 06TT-356 (1) 06TV-753
483 483 483
(Qty) Compressor Model Number Ckt C N/A N/A N/A N/A (1) 06TU-483 N/A (1) 06TU-554 (1) 06TU-554 N/A (1) 06TU-554 N/A
28.4/23.7/
Oil Charge (liter), Ckt A/Ckt B/Ckt C 28.4/28.4/ 28.4/28.4/ 28.4/28.4/ 28.4/28.4/ 25.6/25.6/28.4 28.4/28.4/ 28.4/28.4/ 28.4/28.4/ 28.4/25.6/28.4 28.4/28.4/
28.4
Minimum Capacity Step (%)
Standard 15 15 14 14 9 15 6 12 15 7 15
Optional 10 10 10 10 6 11 4 8 11 5 11
Flooded, Direct Flooded, Direct
COOLER Shell and Expansion Shell and Expansion Flooded, Shell and Tube Type
Tube Type Cooler Tube Type Cooler
Net Fluid Volume (liters) 191.2 409.0 202.1 409.0 257.4 244.2 283.9 244.2 309.6 314.2 309.6
Maximum Refrigerant Pressure (kPa) 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8 1516.8
Maximum Water-Side Pressure without
2 068 2 068 2 068 2 068 2 068 2 068 2 068 2 068 2 068 2 068 2 068
Pumps (kPa)
Maximum Water-Side Pressure with Pumps (kPa)
WATER CONNECTIONS
Drain (NPT, in.) 3/ 3/ 3/ 3/ 3/ 3/ 3/ 3/ 3/ 3/ 3/
8 4 8 4 8 8 8 8 8 8 8
Standard, Inlet and Outlet, Victaulic (in.) 8 6 8 6 8 8 8 8 8 8 8
Number of Passes 2 2 1 2 1 2 2 1 2
Minus 1 Pass, Inlet and Outlet, Victaulic (in.) 8 8 8 8 8 8
Number of Passes 1 1 1 1 1 1
Plus 1 Pass, Inlet and Outlet, Victaulic (in.) 8 8
Number of Passes 3 3
CONDENSER FANS Shrouded Axial Type, Vertical Discharge
Fan Speed (r/s) Standard/High Ambient** 14.2/19.0 14.2/19.0 14.2/19.0 14.2/19.0 14.2/19.0 /19.0 14.2/19.0 /19.0 /19.0 14.2/19.0 /19.0
No. Blades...Diameter (mm) 9...762 9...762 9...762 9...762 9...762 9...762 9...762 9...762 9...762 9...762 9...762
No. Fans (Ckt A/Ckt B/Ckt C) 9/9/ 9/9/ 9/9/ 9/9/ 6/6/8 11/9/ 8/6/8 13/9/ 11/11/ 8/6/8 14/12/
Total Airflow (L/s) 14.2 r/s 79 004 79 004 79 004 79 004 87 782 96 561 96 561
Total Airflow (L/s) 19.0 r/s 93 634 93 634 105 339 105 339 117 043 117 044 128 747 128 748 128 748 128 747 152 157
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C) 9/9/ 9/9/ 9/9/ 9/9/ 6/6/8 11/9/ 8/6/8 13/9/ 11/11/ 8/6/8 14/12/
Total Face Area (sq m) 39 39 39 39 44 44 48 48 48 48 57
HYDRONIC MODULE (Optional)
N/A
Pump
CHASSIS DIMENSIONS (mm)
Length 10 770 11 964 11 945 13 158 13 139 13 158 15 532
Width 2 255
Height 2 300

LEGEND *Operating weight includes 2 pumps on models 30XA090-160. No pumps are available on 30XA080,
Cu Copper
30XA082 or 30XA180-501. All weights include coil trim panels. See pages 11-25 for mounting weights
Al Aluminum for units without pumps and units with single pump packages.
EXV Electronic Expansion Valve 30XA080,082 units do not have an economizer.
MCHX Microchannel Heat Exchanger **The standard ambient temperature option is not available on 30XA401, 451, 476, and 501 units. The
N/A Not Applicable high ambient temperature option is not available on 30XA080-122 units.

10
UNIT MOUNTING WEIGHTS
UNITS WITHOUT PUMPS AND WITH MCHX CONDENSER COILS ENGLISH
MOUNTING WEIGHT (lb)
30XA MCHX CONDENSER COILS
UNIT SIZE
A B C D Total
080 1947 1673 1670 1943 7234
082 1989 1709 1706 1985 7391
30XA MOUNTING WEIGHT (lb) MCHX CONDENSER COILS
UNIT SIZE A B C D E F Total
090 1201 2043 750 951 1983 1199 8127
092 1219 2074 761 965 2013 1217 8251
100 1226 2098 780 981 2038 1224 8348
102 1244 2129 792 996 2068 1242 8472
110 1239 2136 798 1006 2075 1229 8483
112 1274 2196 820 1034 2133 1263 8720
120 1272 2174 800 1007 2106 1263 8622
122 1303 2227 819 1032 2157 1294 8832
30XA MOUNTING WEIGHT (lb) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H Total
140 1897 1444 864 1181 1217 883 1584 1699 10,768
142 1977 1505 901 1231 1269 920 1651 1771 11,225
160 1949 1469 878 1206 1246 899 1603 1750 11,000
162 2024 1526 912 1253 1294 934 1665 1818 11,426
30XA MOUNTING WEIGHT (lb) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H I J Total
180 905 1484 1164 1849 1187 1224 1868 840 1289 888 12,699
182 930 1524 1196 1899 1219 1257 1919 863 1324 912 13,044
200 909 1499 1188 1870 1192 1232 1879 848 1299 893 12,810
202 930 1534 1216 1914 1220 1261 1923 868 1330 914 13,112
30XA MOUNTING WEIGHT (lb) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H I J K L Total
220 813 1196 1592 1498 828 1216 1259 848 1363 1064 1237 832 13,748
222 833 1226 1632 1535 849 1246 1290 869 1397 1091 1268 853 14,092
240 829 1218 1617 1520 830 1218 1261 850 1371 1073 1260 849 13,897
242 849 1248 1657 1558 851 1248 1292 871 1405 1100 1291 870 14,241
260 495 1431 1630 763 2465 1013 1528 2380 800 1333 1386 495 15,720
262 501 1449 1651 773 2497 1026 1548 2411 810 1350 1404 501 15,922
280 497 1451 1663 771 2497 1015 1530 2390 803 1358 1406 497 15,878
282 503 1469 1684 781 2529 1028 1549 2420 813 1375 1424 503 16,080
300 502 1465 1686 786 2568 1027 1557 2454 811 1367 1417 502 16,141
302 517 1508 1735 809 2643 1057 1602 2526 835 1407 1458 517 16,613
30XA MOUNTING WEIGHT (lb) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H I J K L M N Total
325 742 742 978 1531 783 2546 1067 1563 2334 804 1646 1247 742 742 17,467
327 762 762 1004 1572 804 2615 1096 1605 2397 826 1690 1281 762 762 17,939
350 745 745 982 1546 792 2598 1077 1589 2386 808 1651 1249 745 745 17,659
352 765 765 1008 1587 813 2667 1106 1631 2450 830 1695 1282 765 765 18,131
30XA MOUNTING WEIGHT (lb) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H I J K L M N O P Total
400 847 1234 1511 2965 1255 789 2214 1071 1566 2286 747 1265 2152 991 1277 868 23,038
401 1471 1827 1921 2057 2134 1154 579 579 579 579 1950 1902 971 971 1147 964 20,782
450 856 1179 2160 2282 905 1057 2030 2053 2711 1934 1551 1266 1440 1385 1216 876 24,901
451 524 683 3121 3060 2130 858 978 1085 1705 1974 762 1017 1193 1281 842 524 21,324
476 725 923 3281 3724 2423 842 921 1020 1587 1834 723 1040 1236 1334 1120 725 23,458
500 843 1236 2207 2334 909 1060 2037 2060 2718 1941 1555 1269 1457 1401 1279 863 25,167
501A 1507 1949 2405 2601 2405 1137 760 561 561 561 722 1903 2151 1035 1331 841 22,430
501B 631 812 932 631 3,006

LEGEND
MCHX Microchannel Heat Exchanger
NOTE: Size 501 ships as two modules. The 501A and 501B
modules are installed as one chiller.

11
Physical data (cont)
UNIT MOUNTING WEIGHTS (cont)
UNITS WITHOUT PUMPS AND WITH MCHX CONDENSER COILS SI
MOUNTING WEIGHT (kg)
30XA MCHX CONDENSER COILS
UNIT SIZE
A B C D Total
080 883 759 758 882 3281
082 902 775 774 900 3353
30XA MOUNTING WEIGHT (kg) MCHX CONDENSER COILS
UNIT SIZE A B C D E F Total
090 545 927 340 431 899 544 3686
092 553 941 345 438 913 552 3742
100 556 952 354 445 924 555 3786
102 564 966 359 452 938 563 3843
110 562 969 362 456 941 558 3848
112 578 996 372 469 968 573 3955
120 577 986 363 457 955 573 3911
122 591 1010 372 468 979 587 4006
30XA MOUNTING WEIGHT (kg) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H Total
140 860 655 392 536 552 401 719 771 4884
142 897 683 409 558 575 418 749 803 5091
160 884 666 398 547 565 408 727 794 4990
162 918 692 414 568 587 424 755 825 5183
30XA MOUNTING WEIGHT (kg) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H I J Total
180 410 673 528 839 538 555 847 381 584 403 5760
182 422 691 542 861 553 570 870 391 601 414 5917
200 412 680 539 848 541 559 852 385 589 405 5811
202 422 696 552 868 553 572 872 394 603 415 5948
30XA MOUNTING WEIGHT (kg) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H I J K L Total
220 369 542 722 680 376 552 571 385 618 483 561 378 6236
222 378 556 740 696 385 565 585 394 634 495 575 387 6392
240 376 552 734 690 377 553 572 386 622 487 572 385 6304
242 385 566 752 707 386 566 586 395 637 499 586 395 6460
260 225 649 740 346 1118 460 693 1079 363 605 629 225 7130
262 227 657 749 351 1132 465 702 1093 368 612 637 227 7222
280 225 658 754 350 1133 461 694 1084 364 616 638 225 7202
282 228 667 764 354 1147 466 703 1098 369 624 646 228 7294
300 228 664 765 357 1165 466 706 1113 368 620 643 228 7322
302 234 684 787 367 1199 479 727 1146 379 638 662 234 7535
30XA MOUNTING WEIGHT (kg) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H I J K L M N Total
325 337 337 444 695 355 1155 484 709 1058 365 746 565 337 337 7923
327 346 346 456 713 365 1186 497 728 1087 375 767 581 346 346 8137
350 338 338 446 701 359 1179 488 721 1082 367 749 567 338 338 8010
352 347 347 457 720 369 1210 502 740 1111 376 769 582 347 347 8224
30XA MOUNTING WEIGHT (kg) MCHX CONDENSER COILS
UNIT SIZE A B C D E F G H I J K L M N O P Total
400 384 560 685 1345 569 358 1004 486 710 1037 339 574 976 450 579 394 10 450
401 667 829 871 933 968 523 262 262 262 262 885 863 440 440 520 437 9 427
450 388 535 980 1035 411 479 921 931 1230 877 704 574 653 628 551 397 11 295
451 238 310 1416 1388 966 389 443 492 773 895 346 461 541 581 382 238 9 672
476 329 418 1488 1689 1099 382 418 463 720 832 328 472 561 605 508 329 10 640
500 382 561 1001 1059 412 481 924 934 1233 880 705 576 661 635 580 391 11 416
501A 683 884 1091 1180 1091 516 345 255 255 255 328 863 976 470 604 381 10 175
501B 286 368 423 286 1 364

LEGEND
MCHX Microchannel Heat Exchanger

NOTE: Size 501 ships as two modules. The 501A and 501B
modules are installed as one chiller.

12
UNIT MOUNTING WEIGHTS (cont)
UNITS WITHOUT PUMPS AND WITH MCHX CONDENSER COILS

30XA080, 082 30XA220-302


COOLER SIDE COOLER SIDE
B A F E D C B A

a30-4419 a30-4423

C D G H I J K L
COMPRESSOR SIDE COMPRESSOR SIDE

30XA090-122 30XA325-352
COOLER SIDE COOLER SIDE
C B A G F E D C B A

a30-4424
a30-4420

D E F H I J K L M N
COMPRESSOR SIDE COMPRESSOR SIDE

30XA140-162 30XA400-501A
COOLER SIDE COOLER SIDE
D C B A H G F E D C B A

a30-4425

a30-4421

E F G H I J K L M N O P
COMPRESSOR SIDE COMPRESSOR SIDE

30XA180-202 30XA501B
COOLER SIDE COOLER SIDE
E D C B A B A

a30-4422
a30-4419

F G H I J C D
COMPRESSOR SIDE COMPRESSOR SIDE

LEGEND

MCHX Microchannel Heat Exchanger

NOTE: Size 501 ships as two modules. The 501A and 501B modules
are installed as one chiller.

13
Physical data (cont)
UNIT MOUNTING WEIGHTS (cont)
UNITS WITHOUT PUMPS AND WITH Al/Cu CONDENSER COILS ENGLISH
30XA MOUNTING WEIGHT (lb) Al/Cu*
UNIT SIZE A B C D Total
080 2059 1785 1778 2051 7674
082 2101 1822 1814 2093 7831
30XA MOUNTING WEIGHT (lb) Al/Cu*
UNIT SIZE A B C D E F Total
090 1273 2188 822 1023 2127 1271 8704
092 1291 2219 834 1038 2157 1289 8828
100 1299 2244 853 1054 2184 1297 8931
102 1317 2275 865 1069 2214 1315 9055
110 1312 2284 872 1079 2222 1303 9071
112 1346 2344 895 1107 2280 1337 9308
120 1346 2322 874 1082 2255 1337 9216
122 1377 2375 894 1107 2306 1367 9426
30XA MOUNTING WEIGHT (lb) Al/Cu*
UNIT SIZE A B C D E F G H Total
140 2007 1554 938 1254 1291 957 1695 1809 11,505
142 2087 1616 975 1304 1342 995 1762 1881 11,962
160 2061 1581 953 1281 1321 974 1715 1862 11,748
162 2136 1638 988 1327 1369 1009 1777 1930 12,174
30XA MOUNTING WEIGHT (lb) Al/Cu*
UNIT SIZE A B C D E F G H I J Total
180 979 1558 1239 1998 1261 1298 2016 915 1363 962 13,590
182 1004 1598 1270 2049 1293 1331 2067 938 1398 986 13,935
200 984 1574 1263 2020 1267 1308 2029 923 1375 968 13,712
202 106 1609 1291 2065 1295 1337 2074 943 1405 989 14,014
30XA MOUNTING WEIGHT (lb) Al/Cu*
UNIT SIZE A B C D E F G H I J K L Total
220 883 1266 1697 1603 898 1286 1329 918 1468 1169 1307 902 14,727
222 904 1296 1737 1640 919 1316 1360 939 1502 1196 1337 923 15,071
240 900 1288 1723 1626 901 1289 1331 921 1477 1179 1331 920 14,887
242 921 1318 1763 1664 922 1319 1362 942 1511 1206 1362 941 15,231
260 566 1572 1701 834 2607 1084 1599 2521 871 1404 1528 566 16,853
262 573 1591 1721 844 2638 1097 1618 2551 881 1421 1546 573 17,055
280 569 1594 1734 843 2640 1087 1601 2533 875 1429 1549 569 17,022
282 576 1613 1755 853 2671 1100 1620 2563 885 1446 1567 576 17,224
300 578 1617 1762 862 2720 1103 1633 2607 887 1444 1570 578 17,362
302 594 1661 1810 885 2794 1133 1677 2678 911 1483 1613 594 17,834
30XA MOUNTING WEIGHT (lb) Al/Cu*
UNIT SIZE A B C D E F G H I J K L M N Total
325 856 856 1054 1607 859 2697 1143 1639 2485 880 1722 1322 856 856 18,834
327 877 877 1080 1647 881 2765 1172 1680 2547 902 1765 1355 877 877 19,306
350 860 860 1059 1623 869 2752 1153 1666 2539 885 1727 1326 860 860 19,040
352 881 881 1085 1663 891 2820 1182 1707 2602 907 1770 1359 881 881 19,512
30XA MOUNTING WEIGHT (lb) Al/Cu*
UNIT SIZE A B C D E F G H I J K L M N O P Total
400 924 1311 1588 3119 1332 866 2368 1148 1643 2440 824 1342 2306 1069 1354 945 24,578
401 1599 1960 2056 2194 2272 1278 667 667 667 667 2085 2036 1092 1092 1271 1085 22,690
450 933 1256 2276 2398 982 1134 2184 2207 2866 2089 1629 1343 1556 1501 1293 953 26,600
451 597 758 3260 3198 2254 962 1084 1193 1822 2095 865 1124 1303 1392 919 597 23,421
476 851 1052 3444 3895 2570 958 1038 1139 1718 1970 837 1159 1359 1459 1254 851 25,555
500 921 1314 2325 2452 987 1139 2194 2217 2875 2098 1633 1348 1575 1519 1357 941 26,894
501A 1635 2086 2552 2751 2552 1259 849 647 647 647 835 2040 2293 1155 1456 957 24,359
501B 747 961 1103 747 3,558

*Condenser Coil: Aluminum Fins/Copper Tubing.


NOTE: Size 501 ships as two modules. The 501A and 501B
modules are installed as one chiller.

16
UNIT MOUNTING WEIGHTS (cont)
UNITS WITHOUT PUMPS AND WITH Al/Cu CONDENSER COILS SI
30XA MOUNTING WEIGHT (kg) Al/Cu*
UNIT SIZE A B C D Total
080 934 810 807 930 3481
082 953 826 823 949 3552
30XA MOUNTING WEIGHT (kg) Al/Cu*
UNIT SIZE A B C D E F Total
090 578 992 373 464 965 576 3948
092 586 1007 378 471 979 585 4004
100 589 1018 387 478 991 588 4051
102 597 1032 392 485 1004 596 4107
110 595 1036 396 489 1008 591 4115
112 611 1063 406 502 1034 606 4222
120 611 1053 397 491 1023 607 4181
122 624 1077 405 502 1046 620 4276
30XA MOUNTING WEIGHT (kg) Al/Cu*
UNIT SIZE A B C D E F G H Total
140 910 705 425 569 585 434 769 821 5219
142 946 733 442 591 609 451 799 853 5426
160 935 717 432 581 599 442 778 845 5329
162 969 743 448 602 621 458 806 875 5522
30XA MOUNTING WEIGHT (kg) Al/Cu*
UNIT SIZE A B C D E F G H I J Total
180 444 707 562 906 572 589 915 415 618 436 6164
182 455 725 576 929 586 604 938 426 634 447 6321
200 446 714 573 916 575 593 920 419 624 439 6220
202 456 730 586 936 587 606 941 428 637 449 6357
30XA MOUNTING WEIGHT (kg) Al/Cu*
UNIT SIZE A B C D E F G H I J K L Total
220 401 574 770 727 407 583 603 416 666 530 593 409 6680
222 410 588 788 744 417 597 617 426 681 543 607 419 6836
240 408 584 782 738 409 585 604 418 670 535 604 417 6753
242 418 598 800 755 418 598 618 427 685 547 618 427 6909
260 257 713 772 378 1182 492 725 1144 395 637 693 257 7644
262 260 722 781 383 1197 498 734 1157 400 644 701 260 7736
280 258 723 787 382 1197 493 726 1149 397 648 703 258 7721
282 261 732 796 387 1212 499 735 1163 402 656 711 261 7813
300 262 734 799 391 1234 501 741 1182 402 655 712 262 7876
302 269 753 821 402 1267 514 761 1215 413 673 731 269 8089
30XA MOUNTING WEIGHT (kg) Al/Cu*
UNIT SIZE A B C D E F G H I J K L M N Total
325 388 388 478 729 390 1224 518 744 1127 399 781 600 388 388 8543
327 398 398 490 747 399 1254 531 762 1155 409 801 615 398 398 8757
350 390 390 480 736 394 1248 523 756 1152 401 784 601 390 390 8636
352 400 400 492 754 404 1279 536 774 1180 411 803 616 400 400 8850
30XA MOUNTING WEIGHT (kg) Al/Cu*
UNIT SIZE A B C D E F G H I J K L M N O P Total
400 419 595 720 1415 604 393 1074 521 745 1107 374 609 1046 485 614 428 11 149
401 725 889 933 995 1030 580 303 303 303 303 946 924 495 495 576 492 10 292
450 423 570 1032 1088 446 514 991 1001 1300 948 739 609 706 681 586 432 12 066
451 271 344 1479 1450 1022 436 492 541 826 950 393 510 591 631 417 271 10 624
476 386 477 1562 1767 1166 435 471 517 779 893 380 526 617 662 569 386 11 592
500 418 596 1055 1112 448 516 995 1005 1304 952 741 611 714 689 616 427 12 199
501A 742 946 1157 1248 1157 571 385 293 293 293 379 925 1040 524 661 434 11 049
501B 339 436 500 339 1 614

*Condenser Coil: Aluminum Fins/Copper Tubing.


NOTE: Size 501 ships as two modules. The 501A and
501B modules are installed as one chiller.

17
Physical data (cont)

UNIT MOUNTING WEIGHTS (cont)


UNITS WITHOUT PUMPS AND WITH Al/Cu CONDENSER COILS

30XA080, 082 30XA220-302


COOLER SIDE COOLER SIDE
B A F E D C B A

a30-4419 a30-4423

C D G H I J K L
COMPRESSOR SIDE COMPRESSOR SIDE

30XA090-122 30XA325-352
COOLER SIDE COOLER SIDE
C B A G F E D C B A

a30-4424
a30-4420

D E F H I J K L M N
COMPRESSOR SIDE COMPRESSOR SIDE

30XA140-162 30XA400-501A
COOLER SIDE COOLER SIDE
D C B A H G F E D C B A

a30-4425

a30-4421

E F G H I J K L M N O P
COMPRESSOR SIDE COMPRESSOR SIDE

30XA180-202 30XA501B
COOLER SIDE COOLER SIDE
E D C B A B A

a30-4422
a30-4419

F G H I J C D
COMPRESSOR SIDE COMPRESSOR SIDE

NOTE: Size 501 ships as two modules. The


501A and 501B modules are installed as one
chiller.

18
82
30XA400 SINGLE POINT (SEE NOTE 4)

NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft (1.8 m) from solid surface.
2. Temperature relief devices are located on liquid line and economizer assem-
blies and have 1/4-in. flare connection.
3. 3/8-in. NPT vents and drains located in each cooler head at each end of
cooler.
4. Drawing depicts unit with single point power and standard one-pass cooler.
Refer to the Packaged Chiller Builder program for other configurations.
5. Actual cooler consists of two separate coolers piped in series at the factory.
Piping may be split for rigging.
6. Dimensions are shown in inches. Dimensions in [ ] are in millimeters.
Dimensions (cont)

[8328]
[3749] [2438]
[3150]
[3013] [162]
[114]

[317] [162]
[1163]
[1779] [1577] [1831]
[508] [2236]
[810]
[508]

[256]
[1354] [711]
[1609]

[3024] [6114]
[9625]
[11944]

TOP VIEW

a30-51222
30XA400 SINGLE POINT (cont)

[114]

[2300]

[1003]

[722]
[455]
[208]

[162]
[317]
[1779]
[2236]

LEFT END VIEW

a30-5221

83
84
30XA400 SINGLE POINT (cont)

[114]
Dimensions (cont)

[2300]

[1003]
[722]
[455]
[208]

[162]
[317]
[1831]
[2236]

RIGHT END VIEW

a30-4181
30XA400 SINGLE POINT (cont)

1.50 DIA. [38.1]


RIGGING HOLE

1.75
[44]
DETAIL "A"
MOUNTING PLATE
CONTACT SURFACE
0.875 DIA.[22.2] TYPICAL 4 PLACES
MOUNTING HOLE
1.31
[33]
MOUNTING
PLATE

5.0

a30-4182
[127]

Cooler Vent 3/8 NPT


located in cooler heads
3.93
[100]

7.88
[200]
Cooler Drain 3/8 NPT
3/4 NPT Relief Conn. Female located in cooler heads

8" Victaulic Leaving Water 8" Victaulic Entering Water

90.55
[2300]

17.92 17.92
[455] [455]

Mounting Holes 16.1 78.02 [1982] 78.02 [1982] 31.96 78.02 [1982] 78.02 [1982] 33.93 58.08 [1475]
Rigging Holes [409] [812] [862]
(See Detail A) 53.29 [1354]
378.95 [9625]
470.22 [11944]

FRONT VIEW

85
86
30XA400 SINGLE POINT (cont)
Dimensions (cont)

[3150]

[2300]
[1003]

[424] [208] [132] [132] [208] [532] [614] [722]

[1500]
[3013]
[1900]
[3749]
[3763]
[4186]
[7789]
[8328]
[8653]
[11944]

BACK VIEW

a30-5224
Typical piping and wiring (flooded cooler)
30XA UNITS WITHOUT HYDRONIC PACKAGE
FIELD-SUPPLIED
FUSED DISCONNECT
UNIT POWER
FIELD-SUPPLIED
FUSED DISCONNECT
CONTROL POWER

BALANCING VALVE/
SHUT OFF*

VIBRATION STRAINER*
ELIMINATORS*
GATE VALVE*
DRAIN PRESSURE/
SHUTOFF TEMPERATURE TAPS*
PUMP VALVE

HEAT TAPE AND INSULATION ARE RECOMMENDED ON ALL EXPOSED PIPING IF AMBIENT
TEMPERATURE <32 F (0 C) AND NO ANTIFREEZE SOLUTION IS IN SYSTEM
NOTES:
LEGEND 1. Chiller must be installed level to maintain proper compressor oil return.
2. Piping shown are general points-of-connection guides only and are not
Airflow Through Condenser intended for a specific installation. Wiring and piping shown are for a quick
overview of system and are not in accordance with recognized standards.
Power Wiring 3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System
Chilled Water Piping Design Manual or appropriate ASHRAE (American Society of Heating,
*Field-installed. Refrigerating, and Air-Conditioning Engineers) handbook for details.
See note 5. 5. A 20-mesh strainer must be field-supplied and installed within 10 feet
(3 meters) of the cooler inlet.

30XA UNITS WITH HYDRONIC PACKAGE


AIRFLOW
FIELD-SUPPLIED
FUSED DISCONNECT
FIELD-SUPPLIED UNIT POWER
FUSED DISCONNECT
CONTROL POWER

NOTES:
1. Chiller must be installed level to maintain proper
compressor oil return and hydraulics. BALANCING VALVE/
PRESSURE/
2. Wiring and piping shown are general points-of-con- SHUTOFF*
TEMPERATURE
TAPS*
nection guides only and are not intended for a spe-
cific installation. Wiring and piping shown are for a VIBRATION DRAIN SHUTOFF VALVE
quick overview of system and are not in accordance ELIMINATORS*
with recognized standards.
3. All wiring must comply with applicable local and
national codes.
4. All piping must follow standard piping techniques.
Refer to Carrier System Design Manual or appropri- STRAINER*
ate ASHRAE (American Society of Heating, Refrig-
erating, and Air-Conditioning Engineers) handbook LEGEND
GATE VALVE*
for details.
5. Air separator required as close to chiller as possible Airflow Through Condenser
(except primary/secondary systems).
6. Additional 20 mesh strainer required for open loop
PUMP Power Wiring
systems. Chilled Water Piping
HEAT TAPE AND INSULATION ARE RECOMMENDED ON ALL EXPOSED PIPING IF AMBIENT *Field-installed.
TEMPERATURE <32 F (0 C) AND NO ANTIFREEZE SOLUTION IS IN SYSTEM See note 6.

122
Electrical data
SINGLE POINT (STANDARD CONDENSER FAN MOTORS)
UNIT VOLTAGE NUMBER NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM 7.5 HP PUMP, 3450 RPM CONTROL CIRCUIT
UNIT Supplied OF ICF Rec ICF Rec ICF Rec Voltage MCA
30XA V-Hz COND MCA MOCP Fuse MCA MOCP Fuse MCA MOCP Fuse 1 PH, and
(3 Ph) Min Max FANS WD XL WD XL WD XL
Size Size Size 60 Hz MOCP
230-60 207 253 6 315.5 400 484.2 1170.2 350 115 40
200-60 187 220 6 347.6 450 549.6 1338.6 400 115 40
080, 460-60 414 506 6 157.7 200 242.1 585.1 175 115 40
082 575-60 518 633 6 121.2 150 191.9 465.9 150 115 40
380-60 342 418 6 183.5 250 289.7 704.7 225 115 40
230-60 207 253 8 334.0 450 499.1 1185.1 400 350.0 450 515.1 1201.1 400 357.2 450 522.3 1208.3 400 115 40
200-60 187 220 8 368.0 500 566.0 1355.0 450 385.7 500 583.7 1372.7 450 393.6 500 591.7 1380.7 450 115 40
090, 460-60 414 506 8 167.0 225 249.6 592.6 200 175.0 225 257.6 600.6 200 178.6 225 261.2 604.2 200 115 40
092 575-60 518 633 8 128.5 175 197.8 471.8 150 134.9 175 204.2 478.2 150 137.7 175 207.0 481.0 150 115 40
380-60 342 418 8 194.5 250 298.6 713.6 225 204.2 250 308.3 723.3 225 208.6 250 312.6 727.6 250 115 40
230-60 207 253 8 364.6 500 536.7 1278.7 400 380.6 500 552.7 1294.7 450 387.8 500 559.9 1301.9 450 115 40
200-60 187 220 8 401.3 500 607.8 1461.8 450 419.0 500 625.5 1479.5 500 427.0 500 633.5 1487.5 500 115 40
100, 460-60 414 506 8 182.3 250 268.4 639.4 200 190.3 250 276.4 647.4 225 193.9 250 280.0 651.0 225 115 40
102 575-60 518 633 8 139.5 175 211.7 508.7 175 145.9 175 218.1 515.1 175 148.8 200 220.9 517.9 175 115 40
380-60 342 418 8 212.7 250 321.7 770.7 250 222.4 300 331.3 780.3 250 226.7 300 335.7 784.7 250 115 40
230-60 207 253 8 405.7 500 536.7 450 421.7 500 552.7 500 428.9 600 559.9 500 115 40
200-60 187 220 8 446.2 600 607.8 500 463.9 600 625.5 600 471.9 600 633.5 600 115 40
110, 460-60 414 506 8 202.4 250 268.4 639.4 225 210.4 250 276.4 647.4 250 214.0 300 280.0 651.0 250 115 40
112 575-60 518 633 8 155.5 200 211.7 508.7 175 161.9 225 218.1 515.1 200 164.8 225 220.9 517.9 200 115 40
380-60 342 418 8 236.4 300 321.7 770.7 300 246.1 300 331.3 780.3 300 250.4 350 335.7 784.7 300 115 40
230-60 207 253 8 438.6 600 569.6 500 454.6 600 585.6 500 461.8 600 592.8 600 115 40
200-60 187 220 8 482.2 600 643.8 600 499.9 600 661.5 600 507.8 600 669.4 600 115 40
120, 460-60 414 506 8 218.4 300 284.4 655.4 250 226.4 300 292.4 663.4 250 230.0 300 296.0 667.0 300 115 40
122 575-60 518 633 8 168.4 225 224.5 521.5 200 174.8 225 230.9 527.9 200 177.7 225 233.8 530.8 200 115 40
380-60 342 418 8 255.3 350 340.6 789.6 300 265.0 350 350.3 799.3 300 269.4 350 354.7 803.7 300 115 40
230-60 207 253 10 534.7 800 796.7 700 550.7 800 812.7 700 557.9 800 819.9 700 115 40
200-60 187 220 10 588.5 800 906.1 700 606.2 800 923.8 700 614.1 800 931.8 700 115 40
140, 460-60 414 506 10 267.3 400 398.4 1030.4 350 275.3 400 406.4 1038.4 350 278.9 400 410.0 1042.0 350 115 40
142 575-60 518 633 10 205.0 300 315.5 821.5 250 211.4 300 321.9 827.9 250 214.3 300 324.7 830.7 250 115 40
380-60 342 418 10 311.2 450 478.9 1243.9 350 320.9 450 488.6 1253.6 400 325.3 450 493.0 1258.0 400 115 40
230-60 207 253 10 621.1 800 997.6 700 637.1 800 1013.6 800 644.3 800 1020.8 800 115 40
200-60 187 220 10 682.8 1000 1136.1 800 700.5 1000 1153.8 800 708.5 1000 1161.7 800 115 40
160, 460-60 414 506 10 309.7 450 498.4 1306.4 350 317.7 450 506.4 1314.4 400 321.3 450 510.0 1318.0 400 115 40
162 575-60 518 633 10 238.1 350 396.3 1042.3 300 244.5 350 402.7 1048.7 300 247.4 350 405.6 1051.6 300 115 40
380-60 342 418 10 361.1 500 598.9 1577.9 450 370.8 500 608.6 1587.6 450 375.2 500 612.9 1591.9 450 115 40
230-60 207 253 12 673.2 800 935.2 800 115 60
200-60 187 220 12 740.9 1000 1058.5 1000 115 60
180, 460-60 414 506 12 336.6 450 467.6 1099.6 400 115 60
182 575-60 518 633 12 258.3 350 368.8 874.8 300 115 60
380-60 342 418 12 391.5 500 559.2 1324.2 450 115 60
230-60 207 253 12 769.6 1000 1146.0 1000 115 60
200-60 187 220 12 846.0 1000 1299.2 1000 115 60
200, 460-60 414 506 12 383.9 500 572.6 1380.6 450 115 60
202 575-60 518 633 12 294.8 400 453.0 1099.0 350 115 60
380-60 342 418 12 447.2 600 685.0 1664.0 500 115 60
230-60 207 253 13 850.2 1200 1152.0 1000 115 60
200-60 187 220 13 935.1 1200 1305.9 1200 115 60
220, 460-60 414 506 13 424.7 600 575.6 1383.6 500 115 60
222 575-60 518 633 13 326.3 450 455.4 1101.4 400 115 60
380-60 342 418 13 494.5 700 688.6 1667.6 600 115 60
230-60 207 253 13 910.0 1200 1211.8 1200 115 60
200-60 187 220 13 1001.1 1200 1371.8 1200 115 60
240, 460-60 414 506 13 455.0 600 605.9 1413.9 600 115 60
242 575-60 518 633 13 349.6 450 478.7 1124.7 400 115 60
380-60 342 418 13 529.5 700 723.5 1702.5 600 115 60
460-60 414 506 15 516.5 700 777.6 1999.6 600 115 60
260, 575-60 518 633 15 396.4 500 616.2 1594.2 450 115 60
262 380-60 342 418 15 600.2 800 933.9 2412.9 700 115 60
460-60 414 506 16 549.7 800 810.9 2032.9 700 115 60
280, 575-60 518 633 16 422.1 600 641.9 1619.9 500 115 60
282 380-60 342 418 16 638.7 800 972.4 2451.4 800 115 60
460-60 414 506 16 610.9 800 810.9 2032.9 700 115 60
300, 575-60 518 633 16 468.7 600 641.9 1619.9 600 115 60
302 380-60 342 418 16 710.3 1000 972.4 2451.4 800 115 60
460-60 414 506 18 624.3 800 885.5 2107.5 700 115 60
325, 575-60 518 633 18 479.1 600 698.9 1676.9 600 115 60
327 380-60 342 418 18 724.7 1000 1058.4 2537.4 800 115 60
460-60 414 506 18 685.5 800 885.5 2107.5 800 115 60
350, 575-60 518 633 18 525.7 700 698.9 1676.9 600 115 60
352 380-60 342 418 18 796.3 1000 1058.4 2537.4 1000 115 60

LEGEND 4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
ICF Instantaneous Current Flow 500 kcmil.
MCA Minimum Circuit Amps b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
MOCP Maximum Overcurrent Protection 500 kcmil.
WD Wye-Delta c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
XL Across-the-Line 1/0 to 500 kcmil.
NOTES: d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcmil.
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 5. Data provided as circuit 1/circuit 2 where there are two circuits.
is not below or above the listed minimum and maximum limits. Maximum allowable phase 6. Standard condenser fan motors are not used with sizes 30XA401, 451, 476, and 501.
imbalance is: voltage, 2%; amps 10%. These sizes use high ambient temperature condenser fans.
2. Cooler heater (where applicable) is wired into the control circuit so it is always operable as
long as the control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.

128
SINGLE POINT (STANDARD CONDENSER FAN MOTORS) (cont)
UNIT VOLTAGE NUMBER NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM 7.5 HP PUMP, 3450 RPM CONTROL CIRCUIT
UNIT Supplied OF ICF Rec ICF Rec ICF Rec Voltage MCA
30XA V-Hz COND MCA MOCP Fuse MCA MOCP Fuse MCA MOCP Fuse 1 PH, and
(3 Ph) Min Max FANS WD XL WD XL WD XL
Size Size Size 60 Hz MOCP
460-60 414 506 20 746.6 1000 1007.8 2229.8 1000 115 60
400 575-60 518 633 20 573.2 700 793.1 1771.1 700 115 60
380-60 342 418 20 867.6 1000 1201.3 2680.3 1000 115 60
460-60 414 506 22 880.0 1000 1080.0 2302.0 1000 115 60
450 575-60 518 633 22 674.6 800 847.8 1825.8 800 115 60
380-60 342 418 22 1022.7 1200 1284.8 2763.8 1200 115 60
460-60 414 506 22 931.3 1200 1131.3 2353.3 1200 115 60
500 575-60 518 633 22 714.1 800 887.3 1865.3 800 115 60
380-60 342 418 22 1082.4 1200 1344.5 2823.5 1200 115 60

LEGEND 4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
ICF Instantaneous Current Flow 500 kcmil.
MCA Minimum Circuit Amps b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
MOCP Maximum Overcurrent Protection 500 kcmil.
WD Wye-Delta c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
XL Across-the-Line 1/0 to 500 kcmil.
NOTES: d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcmil.
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 5. Data provided as circuit 1/circuit 2 where there are two circuits.
is not below or above the listed minimum and maximum limits. Maximum allowable phase 6. Standard condenser fan motors are not used with sizes 30XA401, 451, 476, and 501.
imbalance is: voltage, 2%; amps 10%. These sizes use high ambient temperature condenser fans.
2. Cooler heater (where applicable) is wired into the control circuit so it is always operable as
long as the control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.

129
Electrical data (cont)
SINGLE POINT (STANDARD CONDENSER FAN MOTORS) (cont)
UNIT VOLTAGE NUMBER 10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM CONTROL CIRCUIT
UNIT Supplied OF ICF Rec ICF Rec Voltage MCA
30XA V-Hz COND MCA MOCP Fuse MCA MOCP Fuse 1 PH, and
(3 Ph) Min Max FANS WD XL WD XL
Size Size 60 Hz MOCP
230-60 207 253 6 115 40
200-60 187 220 6 115 40
080, 460-60 414 506 6 115 40
082 575-60 518 633 6 115 40
380-60 342 418 6 115 40
230-60 207 253 8 364.4 450 529.5 1215.5 400 379.0 500 544.1 1230.1 450 115 40
200-60 187 220 8 401.6 500 599.6 1388.6 450 417.7 500 615.8 1404.8 500 115 40
090, 460-60 414 506 8 182.2 225 264.8 607.8 200 189.5 250 272.1 615.1 225 115 40
092 575-60 518 633 8 140.6 175 209.9 483.9 175 146.5 175 215.8 489.8 175 115 40
380-60 342 418 8 212.9 250 317.0 732.0 250 221.8 250 325.8 740.8 250 115 40
230-60 207 253 8 395.0 500 567.1 1309.1 450 409.6 500 581.7 1323.7 450 115 40
200-60 187 220 8 434.9 500 641.5 1495.5 500 451.1 600 657.6 1511.6 500 115 40
100, 460-60 414 506 8 197.5 250 283.6 654.6 225 204.8 250 290.9 661.9 225 115 40
102 575-60 518 633 8 151.7 200 223.8 520.8 175 157.5 200 229.7 526.7 175 115 40
380-60 342 418 8 231.1 300 340.1 789.1 300 239.9 300 348.9 797.9 300 115 40
230-60 207 253 8 436.1 600 567.1 500 450.7 600 581.7 500 115 40
200-60 187 220 8 479.9 600 641.5 600 496.0 600 657.6 600 115 40
110, 460-60 414 506 8 217.6 300 283.6 654.6 250 224.9 300 290.9 661.9 250 115 40
112 575-60 518 633 8 167.7 225 223.8 520.8 200 173.5 225 229.7 526.7 200 115 40
380-60 342 418 8 254.8 350 340.1 789.1 300 263.6 350 348.9 797.9 300 115 40
230-60 207 253 8 469.0 600 600.0 600 483.6 600 614.6 600 115 40
200-60 187 220 8 515.8 700 677.4 600 531.9 700 693.5 600 115 40
120, 460-60 414 506 8 233.6 300 299.6 670.6 300 240.9 300 306.9 677.9 300 115 40
122 575-60 518 633 8 180.5 225 236.7 533.7 200 186.4 250 242.5 539.5 225 115 40
380-60 342 418 8 273.7 350 359.0 808.0 300 282.6 350 367.9 816.9 350 115 40
230-60 207 253 10 565.1 800 827.1 700 579.7 800 841.7 700 115 40
200-60 187 220 10 622.1 800 939.7 700 638.2 800 955.9 800 115 40
140, 460-60 414 506 10 282.5 400 413.6 1045.6 350 289.8 400 420.9 1052.9 350 115 40
142 575-60 518 633 10 217.1 300 327.6 833.6 250 223.0 300 333.5 839.5 250 115 40
380-60 342 418 10 329.6 450 497.3 1262.3 400 338.5 450 506.2 1271.2 400 115 40
230-60 207 253 10 651.5 800 1028.0 800 666.1 800 1042.6 800 115 40
200-60 187 220 10 716.4 1000 1169.7 1000 732.6 1000 1185.8 1000 115 40
160, 460-60 414 506 10 324.9 450 513.6 1321.6 400 332.2 450 520.9 1328.9 400 115 40
162 575-60 518 633 10 250.2 350 408.5 1054.5 300 256.1 350 414.3 1060.3 300 115 40
380-60 342 418 10 379.5 500 617.3 1596.3 450 388.4 500 626.1 1605.1 450 115 40
230-60 207 253 12 115 60
200-60 187 220 12 115 60
180, 460-60 414 506 12 115 60
182 575-60 518 633 12 115 60
380-60 342 418 12 115 60
230-60 207 253 12 115 60
200-60 187 220 12 115 60
200, 460-60 414 506 12 115 60
202 575-60 518 633 12 115 60
380-60 342 418 12 115 60
230-60 207 253 13 115 60
200-60 187 220 13 115 60
220, 460-60 414 506 13 115 60
222 575-60 518 633 13 115 60
380-60 342 418 13 115 60
230-60 207 253 13 115 60
200-60 187 220 13 115 60
240, 460-60 414 506 13 115 60
242 575-60 518 633 13 115 60
380-60 342 418 13 115 60
460-60 414 506 15 115 60
260, 575-60 518 633 15 115 60
262 380-60 342 418 15 115 60
460-60 414 506 16 115 60
280, 575-60 518 633 16 115 60
282 380-60 342 418 16 115 60
460-60 414 506 16 115 60
300, 575-60 518 633 16 115 60
302 380-60 342 418 16 115 60
460-60 414 506 18 115 60
325, 575-60 518 633 18 115 60
327 380-60 342 418 18 115 60
460-60 414 506 18 115 60
350, 575-60 518 633 18 115 60
352 380-60 342 418 18 115 60

LEGEND 4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
ICF Instantaneous Current Flow 500 kcmil.
MCA Minimum Circuit Amps b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
MOCP Maximum Overcurrent Protection 500 kcmil.
WD Wye-Delta c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
XL Across-the-Line 1/0 to 500 kcmil.
NOTES: d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcmil.
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 5. Data provided as circuit 1/circuit 2 where there are two circuits.
is not below or above the listed minimum and maximum limits. Maximum allowable phase 6. Standard condenser fan motors are not used with sizes 30XA401, 451, 476, and 501.
imbalance is: voltage, 2%; amps 10%. These sizes use high ambient temperature condenser fans.
2. Cooler heater (where applicable) is wired into the control circuit so it is always operable as
long as the control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.

130
SINGLE POINT (STANDARD CONDENSER FAN MOTORS) (cont)
UNIT VOLTAGE NUMBER 10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM CONTROL CIRCUIT
UNIT Supplied OF ICF Rec ICF Rec Voltage MCA
30XA V-Hz COND MCA MOCP Fuse MCA MOCP Fuse 1 PH, and
(3 Ph) Min Max FANS WD XL WD XL
Size Size 60 Hz MOCP
460-60 414 506 20 115 60
400 575-60 518 633 20 115 60
380-60 342 418 20 115 60
460-60 414 506 22 115 60
450 575-60 518 633 22 115 60
380-60 342 418 22 115 60
460-60 414 506 22 115 60
500 575-60 518 633 22 115 60
380-60 342 418 22 115 60

LEGEND 4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
ICF Instantaneous Current Flow 500 kcmil.
MCA Minimum Circuit Amps b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
MOCP Maximum Overcurrent Protection 500 kcmil.
WD Wye-Delta c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is
XL Across-the-Line 1/0 to 500 kcmil.
NOTES: d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcmil.
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals 5. Data provided as circuit 1/circuit 2 where there are two circuits.
is not below or above the listed minimum and maximum limits. Maximum allowable phase 6. Standard condenser fan motors are not used with sizes 30XA401, 451, 476, and 501.
imbalance is: voltage, 2%; amps 10%. These sizes use high ambient temperature condenser fans.
2. Cooler heater (where applicable) is wired into the control circuit so it is always operable as
long as the control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.

131
COMPRESSOR AND FAN ELECTRICAL DATA
CONDENSER COMPRESSOR
FANS A B C
UNIT FLA
30XA VOLTAGE NUMBER LRA (All Units) RLA LRA (All Units) RLA LRA (All Units) RLA
UNIT V-Hz OF COND High High High High
SIZE (3 Ph, FANS* Ambient Standard Ambient Standard Ambient Standard Ambient Standard
60 Hz) Temp Cond. Fans XL WD Temp Cond. Fans XL WD Temp Cond. Fans XL WD Temp Cond. Fans
Cond. Fans (850 rpm) Cond. Fans (850 rpm) Cond. Fans (850 rpm) Cond. Fans (850 rpm)
(1140 rpm) (1140 rpm) (1140 rpm) (1140 rpm)
200 3/3 6.6 1162 373 136.8 1162 373 136.8
230 3/3 6.0 1010 324 124.2 1010 324 124.2
080,
380 3/3 3.6 611 196 71.9 611 196 71.9
082
460 3/3 3.0 505 162 62.1 505 162 62.1
575 3/3 2.4 404 130 47.5 404 130 47.5
200 4/4 6.6 1162 373 140.0 1162 373 140.0
230 4/4 6.0 1010 324 127.1 1010 324 127.1
090,
092 380 4/4 3.6 611 196 73.5 611 196 73.5
460 4/4 3.0 505 162 63.6 505 162 63.6
575 4/4 2.4 404 130 48.6 404 130 48.6
200 4/4 6.6 1254 400 154.8 1254 400 154.8
230 4/4 6.0 1090 348 140.7 1090 348 140.7
100, 380 4/4 3.6 660 211 81.6 660 211 81.6
102
460 4/4 3.0 545 174 70.4 545 174 70.4
575 4/4 2.4 436 139 53.5 436 139 53.5
200 4/4 6.6 1254 400 190.7 1254 400 154.8
230 4/4 6.0 1090 348 173.6 1090 348 140.7
110,
380 4/4 3.6 660 211 100.6 660 211 81.6
112
460 4/4 3.0 545 174 86.4 545 174 70.4
575 4/4 2.4 436 139 66.3 436 139 53.5
200 4/4 6.6 1254 400 190.7 1254 400 190.7
230 4/4 6.0 1090 348 173.6 1090 348 173.6
120,
380 4/4 3.6 660 211 100.6 660 211 100.6
122
460 4/4 3.0 545 174 86.4 545 174 86.4
575 4/4 2.4 436 139 66.3 436 139 66.3
200 6/4 11.9 6.6 2139 685 280.8 293.9 1254 400 148.4 154.8
230 6/4 10.8 6.0 1860 596 255.2 267.2 1090 348 134.9 140.7
140,
380 6/4 6.5 3.6 1126 361 147.7 154.6 660 211 78.3 81.6
142
460 6/4 5.4 3.0 930 298 127.6 133.6 545 174 67.5 70.4
575 6/4 4.3 2.4 744 238 97.5 102.0 436 139 51.3 53.5
200 6/4 11.9 6.6 2737 879 325.2 340.6 1254 400 180.9 190.7
230 6/4 10.8 6.0 2380 764 296.0 310.0 1090 348 164.7 173.6
160,
380 6/4 6.5 3.6 1441 462 171.3 179.4 660 211 95.4 100.6
162
460 6/4 5.4 3.0 1190 382 147.6 154.6 545 174 82.0 86.4
575 6/4 4.3 2.4 952 306 112.9 118.2 436 139 62.9 66.3
200 6/6 11.9 6.6 2139 685 280.8 293.9 2139 685 280.8 293.9
230 6/6 10.8 6.0 1860 596 255.2 267.2 1860 596 255.2 267.2
180,
380 6/6 6.5 3.6 1126 361 147.7 154.6 1126 361 147.7 154.6
182
460 6/6 5.4 3.0 930 298 127.6 133.6 930 298 127.6 133.6
575 6/6 4.3 2.4 744 238 97.5 102.0 744 238 97.5 102.0
200 6/6 11.9 6.6 2737 879 325.2 340.6 2737 879 325.2 340.6
230 6/6 10.8 6.0 2380 764 296.0 310.0 2380 764 296.0 310.0
200,
202 380 6/6 6.5 3.6 1441 462 171.3 179.4 1441 462 171.3 179.4
460 6/6 5.4 3.0 1190 382 147.6 154.6 1190 382 147.6 154.6
575 6/6 4.3 2.4 952 306 112.9 118.2 952 306 112.9 118.2
200 7/6 11.9 6.6 2737 879 387.3 406.6 2737 879 325.2 340.6
230 7/6 10.8 6.0 2380 764 352.3 369.8 2380 764 296.0 310.0
220, 380 7/6 6.5 3.6 1441 462 204.2 214.3 1441 462 171.3 179.4
222
460 7/6 5.4 3.0 1190 382 176.1 184.9 1190 382 147.6 154.6
575 7/6 4.3 2.4 952 306 134.8 141.5 952 306 112.9 118.2
200 7/6 11.9 6.6 2737 879 387.3 406.6 2737 879 387.3 406.6
230 7/6 10.8 6.0 2380 764 352.3 369.8 2380 764 352.3 369.8
240,
380 7/6 6.5 3.6 1441 462 204.2 214.3 1441 462 204.2 214.3
242
460 7/6 5.4 3.0 1190 382 176.1 184.9 1190 382 176.1 184.9
575 7/6 4.3 2.4 952 306 134.8 141.5 952 306 134.8 141.5
380 9/6 6.5 3.6 2179 700 277.9 293.0 1441 462 171.3 179.4
260,
460 9/6 5.4 3.0 1800 578 240.4 253.5 1190 382 147.6 154.6
262
575 9/6 4.3 2.4 1440 462 183.7 193.7 952 306 112.9 118.2
380 9/7 6.5 3.6 2179 700 277.9 293.0 1441 462 204.2 214.3
280, 460 9/7 5.4 3.0 1800 578 240.4 253.5 1190 382 176.1 184.9
282
575 9/7 4.3 2.4 1440 462 183.7 193.7 952 306 134.8 141.5
380 10/6 6.5 3.6 2179 700 330.8 350.3 1441 462 204.2 214.3
300,
460 10/6 5.4 3.0 1800 578 285.6 302.4 1190 382 176.1 184.9
302
575 10/6 4.3 2.4 1440 462 218.2 231.0 952 306 134.8 141.5
380 9/9 6.5 3.6 2179 700 277.9 293.0 2179 700 277.9 293.0
325, 460 9/9 5.4 3.0 1800 578 240.4 253.5 1800 578 240.4 253.5
327
575 9/9 4.3 2.4 1440 462 183.7 193.7 1440 462 183.7 193.7
380 9/9 6.5 3.6 2179 700 330.8 350.3 2179 700 277.9 293.0
350,
460 9/9 5.4 3.0 1800 578 285.6 302.4 1800 578 240.4 253.5
352
575 9/9 4.3 2.4 1440 462 218.2 231.0 1440 462 183.7 193.7

LEGEND NOTES:
1. For 30XA080-352, 401, 451, 476, and 501 units with dual power supply, main power supply 1 uses
FLA Full Load Amps WD Wye Delta refrigerant circuit A components to calculate MCA and MOCP. Main power supply 2 uses refrigerant
LRA Locked Rotor Amps XL Across-the-Line circuit B components to calculate MCA and MOCP.
RLA Rated Load Amps 2. 30XA400,450,500 units have dual power supply. Main power supply 1 uses refrigerant circuit C
components to calculate MCA and MOCP. Main power supply 2 uses refrigerant circuit A and B
components to calculate MCA and MOCP.
*Quantity of fan motors for incoming power supply Circuit 1/Circuit 2.

143
Electrical data (cont)
COMPRESSOR AND FAN ELECTRICAL DATA (cont)
CONDENSER COMPRESSOR
FANS A B C
UNIT FLA
30XA VOLTAGE NUMBER LRA (All Units) RLA LRA (All Units) RLA LRA (All Units) RLA
UNIT V-Hz OF COND High High High High
SIZE (3 Ph, FANS* Ambient Standard Ambient Standard Ambient Standard Ambient Standard
60 Hz) Temp Cond. Fans XL WD Temp Cond. Fans XL WD Temp Cond. Fans XL WD Temp Cond. Fans
Cond. Fans (850 rpm) Cond. Fans (850 rpm) Cond. Fans (850 rpm) Cond. Fans (850 rpm)
(1140 rpm) (1140 rpm) (1140 rpm) (1140 rpm)
380 8/12 6.5 3.6 1441 462 204.2 214.3 1441 462 204.2 214.3 2179 700 277.9 293.0
400 460 8/12 5.4 3.0 1190 382 176.1 184.9 1190 382 176.1 184.9 1800 578 240.4 253.5
575 8/12 4.3 2.4 952 306 134.8 141.5 952 306 134.8 141.5 1440 462 183.7 193.7
380 11/9 6.5 2312 758 449.8 2179 700 418.9
401 460 11/9 5.4 1906 625 371.0 1800 578 346.3
575 11/9 4.3 1521 498 294.8 1440 462 275.0
380 8/14 6.5 3.6 2179 700 330.8 350.3 1126 361 147.7 154.6 2179 700 330.8 350.3
450 460 8/14 5.4 3.0 1800 578 285.6 302.4 930 298 127.6 133.6 1800 578 285.6 302.4
575 8/14 4.3 2.4 1440 462 218.2 231.0 744 238 97.5 102.0 1440 462 218.2 231.0
380 13/9 6.5 2312 758 529.4 2179 700 403.9
451 460 13/9 5.4 1906 625 438.2 1800 578 346.3
575 13/9 4.3 1521 498 349.5 1440 462 266.4
380 11/11 6.5 2312 756 490.8 2312 758 449.8
476 460 11/11 5.4 1906 625 404.3 1906 625 371.0
575 11/11 4.3 1521 498 323.0 1521 498 294.8
380 8/14 6.5 3.6 2179 700 330.8 350.3 1441 462 204.2 214.3 2179 700 330.8 350.3
500 460 8/14 5.4 3.0 1800 578 285.6 302.4 1190 382 176.1 184.9 1800 578 285.6 302.4
575 8/14 4.3 2.4 1440 462 218.2 231.0 952 306 134.8 141.5 1440 462 218.2 231.0
380 14/12 6.5 2312 758 535.9 2312 758 497.3
501 460 14/12 5.4 1906 625 443.6 1906 625 409.7
575 14/12 4.3 1521 498 353.8 1521 498 327.3

LEGEND NOTES:
1. For 30XA080-352, 401, 451, 476, and 501units with dual power supply, main power supply 1 uses
FLA Full Load Amps WD Wye Delta refrigerant circuit A components to calculate MCA and MOCP. Main power supply 2 uses refrigerant
LRA Locked Rotor Amps XL Across-the-Line circuit B components to calculate MCA and MOCP.
RLA Rated Load Amps 2. 30XA400,450,500 units have dual power supply. Main power supply 1 uses refrigerant circuit C
components to calculate MCA and MOCP. Main power supply 2 uses refrigerant circuit A and B
components to calculate MCA and MOCP.
*Quantity of fan motors for incoming power supply Circuit 1/Circuit 2.

144

You might also like