Multi V 3 PDF
Multi V 3 PDF
Multi V
1. Introduction
1.1 What is Multi V? """""""""""""""""""""""""". 04
1.2 External Appearance """""""""""""""""""""""""".. 05
1.3 System Layout """""""""""""""""""""""""".. 10
1.4 Nomenclature """""""""""""""""""""""""". 11
2. Line Up
.."""""""""""""""""""""""""" 13
2.1 Line Up
"""""""""""""""""""""""""".. 15
2.2 Specification
3. USP
3.1 Major USP ."""""""""""""""""""""""""". 16
3.2 Minor USP """""""""""""""""""""""""".. 42
3.3 Product Comparison """""""""""""""""""""""""".. 44
3.4 Benefits """"""""""""""""""".""""""". 52
4. General Information
4.1 Item Inside Product Box """""""""""""""""""""""""". 54
6. Installation
6.1 Installation Scene """""""""""""""""""""""""". 59
6.2 Installation of Outdoor Unit """""""""""""""""""""""""".. 60
6.3 Piping & Wiring: Outdoor Unit """""""""""""""""""""""""".. 69
6.4 System Set-up """""""""""""""""""""""""". 97
7. Start up
7.1 Start up """""""""""""""""""""""""". 103
7.2 Checking point """""""""""""""""""""""""".. 106
7.3 Special Functions """""""""""""""""""""""""".. 108
8. Trouble Shooting
8.1 Error Codes """""""""""""""""""""""""". 120
9. New Functions
9.1 Cool/ Heat selector """""""""""""""""""""""""". 121
9.2 New Dry contact """""""""""""""""""""""""".. 123
9.3 Independent power module """""""""""""""""""""""""".. 126
Multi V III is the latest technology, with Worlds Best Efficiency, Largest Capacity,
Compact Design and Green Energy Solution.
Multi V III
Energy Saving & Environment Friendly
3,380~415,50/60Hz
UX1 Chassis (620 x 1680 x 760) UX2 Chassis (920 x 1680 x 760)
3,380~415,50/60Hz
3,380~415,50/60Hz
3,380~415,50/60Hz
Max. 80 HP
Refrigerant Pipes
4Way Console
CST
3
Serial number
Electrical rating
8 : 3, 380 ~ 415V, 50Hz 9 : 3, 380V, 60Hz
A : 3, 220V, 50HZ B : 3, 220V, 60HZ
L : 3, 380 ~ 415V, 50Hz / 3, 380V, 60Hz
D : 3, 460V, 60Hz
System with
Outdoor Unit using R410A
Generation
Combinations of functions
A : Basic function
L : Neo Plasma (Wall Mounted)
C : Plasma Ceiling Cassette)
G : Low Static
U : Floor Standing without Case
ART COOL Type Panel Color
B : Blue R : Mirror V : Silver
Chassis Name
Electrical rating
1 : 1, 115V, 60Hz 2 : 1, 220V, 60Hz
6 : 1, 220 ~ 240V, 50HZ 7 : 1, 100V, 50/60HZ
3 : 1, 208/230V, 60Hz
Total cooling capacity in Btu/h
Ex) 5,000 Btu/h '05 ' 18,000 Btu/h ' 18'
Combination of Inverter Type and
Cooling Only or Heat Pump
N : AC Inverter and H/P V : AC Inverter and C/O
B : DC Inverter and H/P and C/O
System with
Indoor Unit using R410A
* LGETA : U Ex) URN
Capacity
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
(HP)
UX1
Capacity S Chassis
62 64 66 68 70 72 74 76 78 80
(HP)
H/P L+L+L+L
UX3
L Chassis
1Way (Art)
Ceiling
2Way
Cassette
4Way
Ceiling Suspended
High Static
Ceiling
Concealed Low Static
Duct
Built-in
Console
COP Comparison
Heat Pump model (14HP)
4.25
Cooling Capacity Heating Capacity
4.55
propeller fan Inverter Fan Motor
25% 9%
Cyclone
sub-cool circuit Wide Louver fin in
Heat Exchanger
Sine wave
3.31
4.16
BLDC
inverter compressor
Oil Guide
Oil skirt
B/Weight Shaft
Old New
Input Power
LP 100%
11% 88%
Motor
LSS Compressor HSS Compressor 11%
9%
Friction 5.5%
LSS Compressor HSS Compressor 15% Leakage 6%
Low temp. Low Press. Sump High Temp. High Press. Sump
Increase in Suction Gas Temp. no change in Suction Gas Temp.
65% Compressor 65%
Oil Viscosity decreases with Temp. no change in Oil Viscosity
(Stable Discharge Temp.) New
Old
3 24 25 26 27 28 29 30 31 32 33 34 35
)
Outdoor temp.(
Standard
5 Heating
4 Multi V III
25
20 5Hz
COP 3
Multi V Plus II Multi V III
Multi V Plus II
2
1 -15-
15 -12-
12-10 -7 -5 -3 0 3 5 7 9 11
)
Outdoor temp.(
Oil
Compressor Separator Oil
Compressor Separator
HiPOR TM
Loss due to the Bypass of Refrigerant. No Loss due to the Bypass of Refrigerant.
COP increased by 3%
5/36
Nd Magnet
Rotor
Steel Plates
Cyclone Sub-cooler
Non-uniform Uniform
Distribution Distribution
Multi V III
3.1.8 Eco-friendly
R410A Refrigerant Refrigerant Recovery and Reuse
Chiller+
Gas boiler
Multi V Single RAC
+Oil boiler
Multi V
New Shroud
Bell Mouth Shape Expansion
Low torque ripple design of motor, resonant Robust & S-shape Blade
frequency shift, optimal current angle control New Design
Pitch Angle Increased
(Max 6 8mmAq)
Wrong piping
Malfunction Back-up
Wrong wiring
Conventional
Multi V III
A hr B hr
50 Measuring Function
Temp. On Load(%)
0
50 Load SPL
Mode 1 A : 8.0 hr, B : 9.0 hr Step 1 : max A (db)
47
Mode 2 A : 6.5 hr, B : 10.5 hr Step 2 : max B
Crane Slot
Elevator
50%
3hrs
Setting LGMV PC 100% operation 1 Unit operation Report
60%
Time Auto
save Test Run
Repair!
Pump Out
When Outdoor unit is failed, all refrigerant in failed ODU can be pumped out to Indoor Units.
Refrigerant Flow
Refrigerant Flow
Failed
3.1.25 LGMV
Slave
Slave
Series 3 3 3
Unit Capacity
1 Unit Max
Max Combination
Plus
LG
Multi V
Daikin VRV
4.0 Plus II
3.0
Multi V III
Foot
m2
Plus II
2.0
Print Multi V III
SIZE Daikin
1.0
ME
0.0
62
64
66
68
70
72
74
76
78
80
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
6
8
5
24/36
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 44
3.3 Product Comparison 3. USP
Max. COP
4.27 / 4.58 4.29 / 4.50 3.62 / 4.02
(Cooling / Heating)
Longest Pipe
200 m 200 m 165 m
Length
Difference in height
110m 50 m(90 m) 50 m
(Indoor Outdoor)
Outdoor Max
Max 80Hp Max 54 Hp Max 50 Hp
Capacity
V-Scroll(DC Inverter) DC Inverter DC Inverter
Compressor
Hi-POR tech. Scroll type Scroll type
25/36
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 45
3.3 Product Comparison 3. USP
3.3.3 COP
4.55
4.16
4.13 3.9
3.31 3.5 3.7
8
3.2 7 2
3
26/36
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 46
3.3 Product Comparison 3. USP
5.5
5
29%
4.5
COP
27%
3.5
2.5
2
40 50 60 70 80 90 100 110
Multi V III
Multi VRV III DVM III Operating Rate [%]
27/36
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 47
3.3 Product Comparison 3. USP
4.50
4.00
3.50
COP
3.00
2.50
2.00
0 10 20 30 40 50 60 70 80 Capacity [Hp]
Multi V III_50Hz Multi V Plus II_50Hz Daikin VRV III ss_50Hz
ME City Multi_50Hz/60Hz Toshiba SMMS_50/60Hz Samsung (Compact Model (50Hz)
30
HVAC system Heating
- LG Multi V III, 26HP 2each
10
10 20 30 40 50 60 70
Temperature [F]
MV III Plus II VRV III
29/36
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 49
3.3 Product Comparison 3. USP
15,000
13,000
Energy Consumption [kWh]
143,510
11,000 134,391 14%
9,000 125,319
7,000
5,000
3,000
1,000
Jan. Feb. Mar. Apr. May Jun. Jul. Aug. Sep. Oct. Nov. Dec. VRV III Plus II MV III
Month
30/36
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 50
3.3 Product Comparison 3. USP
No. of ODU
Foot print area 66.2% 100% 98.3%
20 HP
Weight 82.0% 100% 93.7%
Max. Connecting IDU 32 32 43
No. of ODU
Foot print area 79.5% 100% 87.1%
40 HP
Weight 87.1% 100% 84.0%
Max. Connecting IDU 64 64 50
No. of ODU
Foot print area 99.3% 100% 97.7%
50 HP
Weight 91.3% 100% 76.2%
Max. Connecting IDU 64 64 50
No. of OD U
Foot print area 99.3% 100%
54 HP
Weight 98.8% 100%
Max. Connecting IDU 64 64
Over 54Hp, only LG provides
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 51
3.4 Benefits 3. USP
USB
ARUV60LT3
ARUV80LT3
Unit (mm)
(Pitch of Foundation
bolt holes)
4 oblong holes
CN29-
CN29- INV PCB
CN39-
CN39- ODU EEV- INJ CN38-
CN38- ODU EEV- Out Communication terminal
CN40-
CN40- SC EEV
CN04-
CN04- On boarding
terminal
CN44-
CN44- INV CN05-
CN05- Jig connection
comp HP S/ W terminal LGMV
CN43-
CN43- INV comp
SW02V-
SW02V- Auto
HP S/ W 1
addressing switch
CN26-
CN26- INV comp
HP S/ W 2 SW01S-
SW01S-
Reset button
CN18-
CN18- H/ Gas 2
CN41-
CN41- Central
CN17-
CN17- H/ Gas 1 Control terminal
CN16-
CN16- Oil Return CN36-
CN36- PFC- IPM
CN15-
CN15- Const comp CN 33
magnetic switch 2
SC-
SC- IN-
IN- SC circuit
CN14-
CN14- Const comp inlet temp.
magnetic switch 1 sensor
SC-
SC- OUT-
OUT- SC
CN13-
CN13- Hot gas circuit outlet
solenoid valve (main) temp. sensor
CN 34
CN12-
CN12- Const comp DIS(I)-
DIS(I) - Inv
hearer 2 comp dis temp.
CN11-
CN11- Const comp SUC-
SUC- Suc temp.
hearer 1 sensor
CN 28-
28 - Const comp
CN10-- INV comp hearer
CN10 current sensor 1
IPM CN 35
CN09-
CN09- 4 way CN 27-
27 - Const comp
reversing valve current sensor 2 HEX-
HEX- ODU hex temp.
CN08-
CN08- 220V power input terminal sensor
DIS(C)-
DIS(C) - Const comp
CN 31-
31 - CN 32-
32 - Low CN 30-
30 - High dis temp. sensor
JIG1,JIG2-
JIG1,JIG2- JIG power terminal : AC 220V Pressure Pressure sensor Pressure sensor
sensor (Mid)
Refrigerant Pipes
4Way Floor
CST standing
6.2.2 Foundation
A) Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
Use the H-beam support as a base support
B) Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part
depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more
than 200mm).
Install at places where it can endure the weight and vibration/noise of the outdoor unit.
The outdoor unit supports at the bottom shall have width of at least 100mm under the unit legs
before being fixed.
The outdoor unit supports should have minimum height of 200mm.
Anchor bolts must be inserted at least 75mm.
Select installation location considering following conditions to avoid bad condition when additionally
performing defrost operation.
1. Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the
product at a place with a high humidity in winter (near beach, coast, lake, etc).
(Ex) Rooftop where sunshine always shines.
A10 A50
B300 B100
C10 C50
D500 D 500
E20 E100
4 sides
are
walls
A10 A50
B300 B100
C10 C50
D500 D 500
E20 E100
F600 F 500
A10 A50
B300 B100
4 sides
C10 C50
are
D300 D 100
walls
E20 E100
F 500 F 500
Only
2 sides
are walls
A 200
B 300
E 400
The height of the wall on the front side must be 1500mm or less.
The height of the wall on the inlet side must be 500mm or less.
There is no limit to the wall on the side.
Limitations on If the height of the walls on the front and the side are higher
than the
the height of
limit, there must be additional space on the front and the side.
the wall
- Additional Space on the inlet side by 1/2 of h1.
- Additional Space on the front side by 1/2 of h2
- h1 = A (Actual height) - 1500
- h2 = B (Actual height) - 500
When connecting to high low pressure common pipe, connect pipes using connecting elbows.
ID rId3 .
2
Unit ARCNN21
ID rId4 .
ID rId3 .
ID rId7 .
3
Unit ARCNN31
ID rId5 .
ID rId6 .
ID rId8 .
4
Unit
ARCNN41
Piping length from outdoor branch to outdoor unit 10m, equivalent length : max 13m(for 22HP or more)
Conditional Application
To satisfy below condition to make 40m ~ 90m of pipe length after first branch.
Diameter of pipes between first branch and the last branch should be increased by one step,
except pipe diameter B,C,D is same as Diameter A
6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9
38.1
*: it is not necessary to size up.
2) While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice.
A+B2+C2+D2+a+b+c+d+e 1,000m
3) Length of pipe from outdoor unit to the farthest indoor unit 5(abcd) 40m
4) [Length of pipe from outdoor unit to the farthest indoor unit 5(A + B + C + D + e)
-[Length of pipe outdoor unit to the closest indoor unit 1 (A + a) 40m
*: Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
* : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
** : To apply Conditional Application
Y Branch selection
ARBLN01621
ID rId5 .
ID rId6 .
ARBLN03321
ID rId7 .
ID rId8 .
ARBLN07121
ARBLN14521
ID rId6 .
ID rId5 .
ARBLN23220
4 branch
ARBL054
ID rId5 . ID rId6 .
7branch
ARBL057
ID rId8 .
ID rId7 .
4 branch
ARBL104
7 branch
ARBL107
ID rId5 .
ID rId6 .
10 branch
ARBL1010
ID rId7 .
ID rId8 .
10 branch
ARBL2010
CF value of indoor
+ unit
CAUTION
Use only 2-series of indoor unit. Ex) ARNU***2
Main PCB
Magnet switch
Inverter PCB
Take care of the phase
sequences of 3-phase 4-wire
power system
- Connect transmission line between main and sub outdoor unit through the terminal block.
- Connect transmission lines between outdoor unit and indoor/HR units through the terminal block.
- When the central control system is connected to the outdoor unit, a dedicated PCB must be connected
between them.
- When connecting transmission line between outdoor unit and indoor/HR units with shielded wire,
connect the shield ground to the earth screw
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
Note : Always add an appropriate amount of refrigerant. (For the refrigerant additional charge)
Too much or too little refrigerant will cause trouble.
To use the Vacuum Mode
(If the Vacuum mode is set, all valves of Indoor units and Outdoor units will be opened.)
Note: Refer PDB for more details.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 95
6.3 Piping & Wiring: Outdoor Unit 6. Installation
This function is used for creating vacuum in the system after compressor replacement, ODU parts
replacement or IDU addition/replacement.
Caution: ODU operation stops during vacuum mode. Compressor can't operate.
(Auto
Address)
(Auto
Address)
Heat pump
If the Dip switch is set when power is on, the changed setting will not be applied immediately.
The changed setting will be enabled only when Power is reset or by pressing Reset button.
ID rId4 .
Function
ID rId3 .
Function
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 100
6.4 System Set-up 6. Installation
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 101
6.4 System Set-up 6. Installation
1. X mark means that the dip switch must be turned OFF. If not, the function may not work properly.
2. If the applicable dip switch is not set properly, the product may not work properly.
3. When executing the test operation, check the operating condition of the indoor unit and only execute the
operation when all indoor units are stopped.
4. Auto test operation function does not work for the product where only one indoor unit is connected for use.
5. Cooling Only model is not working on functions of Heat Pump model.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 102
7.1 Start up 7. Start up
1. Installation information
-. Supervisors must check if the real installers name plate and piping diagram is attached on the outdoor unit.
-. Installer should submit the report of installation completion to the building constructor.
The report should include the piping diagram, the cable construction, commissioning result, a test run, etc.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 103
7.1 Start up 7. Start up
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 104
7.1 Start up 7. Start up
<example>
The name plate can offer the detailed information for the installation and it can make service more quickly.
To make quick service, the position of breaker should be shown on the column.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 105
7.2 Checking point 7. Start up
CAUTION
While cutting main power of the Multi V,
Always apply main power of the outdoor unit during use of product (cooling season/heating season).
Always apply power 6 hours in advance to heat the crank case heater where performing test run after installation of
product. It may result in burning out of the compressor if not preheating the crank case with the electrical heater for more
than 6 hours. (In case of the outdoor temperature below 10C)
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 106
7.2 Checking point 7. Start up
When system fault occurs, the error code is displayed at indoor unit display or remote control display, the
trouble Shooting guide is in the service manual
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 107
7.3 Special Functions 7. Start up
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 108
7.3 Special Functions 7. Start up
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 109
7.3 Special Functions 7. Start up
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 110
7.3 Special Functions 7. Start up
Ex) IDU No.2 Pipe inlet temperature sensor error and Master
ODU suction temperature sensor, Master ODU high pressure sensor error
Caution
Up to 5 number of errors is displayed continuously and repeatedly. IN case 5 error occurs, again
perform sensor checking after solving errors.
IDU in which error occurred operates air circulation mode.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 112
7.3 Special Functions 7. Start up
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 113
7.3 Special Functions 7. Start up
Note
1. After installing the refrigerant charging device, as shown in figure, open the valve
2. In case air temperature is out of guaranteed temperature, it may end without performing Auto charging
3. Refrigerant charging Time may change according to the charging amount. (Abt. 1.5min/lb)
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 114
7.3 Special Functions 7. Start up
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 115
7.3 Special Functions 7. Start up
Note
1. In case air temperature is out of guaranteed temperature, refrigerant checking function may end without
performing refrigerant checking. Use guaranteed temperature range only.
2. During the process of judging refrigerant amount, if the cycle isn't stable, refrigerant checking function
may end without performing refrigerant checking.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 116
7.3 Special Functions 7. Start up
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at
night which has low cooling load.
Max. RPM setting method Note 1) Setting Method for Fan Max. RPM
Note 1)
Setting Complete
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 117
7.3 Special Functions 7. Start up
Caution:
1. Request installer to set the function during
installation.
2. In case the function is not used, set the dip S/W OFF
and reset the power.
3. If ODU RPM changes, cooling capacity may go down.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 118
7.3 Special Functions 7. Start up
High static pressure mode : Master ODU Main PCB SW02B NO.13 Dip S/W
Static pressure compensation mode setting Static pressure compensation mode setting
method method
Power Reset
Power Reset
Static pressure compensation mode is set Static pressure compensation mode is cancelled
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 119
8.1 Error Codes 8. Troubleshooting
Error Indicator
This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
Error mark is displayed on display window of indoor units and wired remote controller, and
7-segment LED of outdoor unit control board as shown in the table.
If more than two troubles occur simultaneously, lower number of error code is first displayed.
After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
011 051 : No.105 error of master unit
Note: Refer PDB or Service Manual for all the Error Codes.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 120
9.1 Cool/ Heat Selector 9. New Functions
Multi V III series provides all off function instead of Fan mode.
[Installation]
- Connect wires to the cool/heat selector as shown in below figure
- Insert the wire in terminal by pushing "push" button
- Set the DIP Switch of main PCB in master outdoor unit.
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 121
9.1 Cool/ Heat Selector 9. New Functions
[Setting]
- Set DIP S/W according to DIP S/W setting table.
- Push black button on SVC PCB
- Select number as follow at 7-segment
0 : Selector does not use
1 : Cooling/ Heating & Fan mode
2 : Cooling/ Heating & All OFF mode
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 122
9.2 New Dry Contact 9. New Functions
[Installation]
- Connect wires to the PI485 Gate-way on Main PCB as shown.
- New ODU dry contact is using DC 12V (Using 12V Adaptor)
- Choice control module; Simple switch or DDC module
ID rId4 .
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 123
9.2 New Dry Contact 9. New Functions
[Installation]
- Connect wires to the PI485 Gate-way on Main PCB as shown.
- New ODU dry contact is using DC 12V (Using 12V Adaptor)
- Choice control module; Simple switch or timer.
- Set DIP S/W as same as Night Silent Operation
ID rId4 .
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 124
9.2 New Dry Contact 9. New Functions
[Installation]
- Connect wires to the PI485 Gate-way on Main PCB as shown.
- New ODU dry contact is using DC 12V (Using 12V Adaptor)
- Choice control module; buzzer or warning lamp
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 125
9.3 Independent Power Module 9. New Functions
The main PCB controls the Indoor EEV, when the power is turn on.
The independent sub PCB controls the Indoor EEV, when the power is turn off.
ID rId4 .
Multi V Copyright 2010 @LG Electronics / AC Company All Rights Reserved 126
Multi V
Publisher : CAC Engineering Team
Air Conditioning Company