DATA SHEETS - GMCB
24kV/80kA - 12,000 amp
1. Voltage Rating
1.1 Normal System Voltage 24kV
1.2 Rated Maximum Voltage 25.8kV
1.3 Voltage Range Factor 1.0
2. Interrupting Current Rating
2.1 Symmetrical Short Circuit Capability 80KA
2.2 Three second short-time current 125KA
carrying capability
2.3 Close and Latching Capability 240KA
2.4 Percent interrupting capability after 100%
0-1 min-CO-3 min-CO duty cycle
3. Continuous Current Rating 12,000A
4. Operating Time (60 Hz basis)
4.1 Permissible Tripping Delay 0.25 sec.
4.2 Interrupting Time 5 cycles
4.3 Opening Time 3.8 cycles
4.4 Closing time 7 cycles
4.5 Minimum allowable reclosing time 1 Min
4.6 Reclosing range 1-3 Min
5. Temperature Range
5.1 Maximum Ambient 40C
5.2 Minimum Ambient -30C
5.3 Contact temperature rise (max.) 65C
6. Insulation Level
6.1 Power Frequency Withstand Voltage(kV)
To Ground And Across The Contacts 50kV
Across Isolator Contacts 60kV
6.2 Impulse Withstand Voltage
To Ground And Across The Contacts 125kV
Across Isolator Contacts 145kV
7. Dielectric Strength at Atmospheric Pressure 1.2 times
8. Breaks per Phase 1
9. Operating Mechanism
12.1 Type Pneumatic/Spring
12.2 Individual or common mechanism Common
10. Air System
10.1 Operating range of air pressure 178-213 psig
10.2 Low air pressure alarm 181 psig
10.3 Low air pressure lockout 178 psig
10.4 Overpressure relief valve open at 235 psig
10.5 Compressor
13.5.1 Manufacturer EMGLO
13.5.2 Horsepower 1.5
10.6 Number of close-open 2
operations stored in air receiver
10.7 Pump up from atmospheric to operating pressure .7 hrs.
10.8 Pump up from lockout to operating pressure 12 min.
10.9 Compressor motor
13.9.1 Manufacturer Dayton
13.9.2 Voltage 230/115AC
single phase
13.9.3 Speed 1725 rpm
13.9.4 Class of insulation B
10.10 Air storage volume
Primary:30kg/cm2G(436 psiG) 35 liters
Secondary: 15kg/cm2G (213 psiG) 200 liters
Page - 2
11. SF6 System
11.1 Normal operating pressure at 20C 75 psig
11.2 Minimum operating pressure with full rating 64 psig
11.3 Temperature compensated gas density alarm 69 psig
11.4 Temperature compensated gas density lockout 64 psig
11.5 Overpressure relief valve 105 psig
11.6 Weight of SF6 gas 120 lbs.
12. Trip Coil
12.1 Voltage 125V DC
12.2 Allowable Voltage Range 70-140V DC
12.3 Current 10.4A
12.4 Number of trip coils 2
13. Close Coil
13.1 Voltage 125V DC
13.2 Voltage Range 90-140V DC
13.3 Current 3.3A
13.4 Number of close coils 1
14. Control Cabinet Heaters
14.1 Number & Wattage of heaters (4) - 160 Watt
14.2 Location 1-mechanism
2-compressor motor
1-control cabinet
14.3 Voltage 120/240V AC
Page - 3
15. Breaker Dimensions
15.1 Height of breaker 8-6"
15.2 Total length 10' 6"
15.3 Width 12' 8"
15.4 Weight 16,500 lbs.
15.5 Impact loading for foundation design None
15.6 Phase spacing 4'-5.15
16. CT Standard Ratings
16.1 Max. number available per phase 2
16.2 Number proposed per bushing per spec
16.2 Relaying or metering accuracy per spec
16.3 Accuracy (relaying) C400
16.4 Ratio per spec
16.5 Thermal Rating Factor 1.5
17. Maintenance Requirements
17.1 Arcing contact material Copper-Tungsten
17.2 Number of short circuits before 10
internal maintenance check
17.3 Number of rated continuous current interruptions 2000
before internal maintenance check recommended
18. Applicable Standards
18.1 ANSI C37
18.2 IEC 56