The National Academies Press: Design Guidelines For Durability of Bonded CFRP Repair/Strengthening of Concrete Beams
The National Academies Press: Design Guidelines For Durability of Bonded CFRP Repair/Strengthening of Concrete Beams
DETAILS
AUTHORS
BUY THIS BOOK
Visit the National Academies Press at NAP.edu and login or register to get:
Distribution, posting, or copying of this PDF is strictly prohibited without written permission of the National Academies Press.
(Request Permission) Unless otherwise indicated, all materials in this PDF are copyrighted by the National Academy of Sciences.
ACKNOWLEDGMENT
COPYRIGHT INFORMATION
Authors herein are responsible for the authenticity of their materials and
for obtaining written permissions from publishers or persons who own
the copyright to any previously published or copyrighted material used
herein.
DISCLAIMER
The information contained in this document was taken directly from the
submission of the author(s). This material has not been edited by TRB.
Table of Contents
List of Figures and Tables.................................................................................................. iii
AUTHOR ACKNOWLEDGMENTS ................................................................................ iv
ABSTRACT.........................................................................................................................v
EXECUTIVE SUMMARY ............................................................................................... vi
1. Introduction and Research Approach...............................................................................1
Introduction...................................................................................................................1
Research Objective .......................................................................................................1
Research Approach .......................................................................................................2
2. Environmental Factors Affecting Durability ...................................................................3
Moisture and Temperature ............................................................................................3
Chemical Solutions .......................................................................................................4
UV Radiation ................................................................................................................4
Fatigue ..........................................................................................................................4
Time Frame for CFRP Accelerating Aging ..................................................................5
Findings from Literature Review..................................................................................5
3. Evaluation Approach and Exposure Conditions ..............................................................6
Specimen Exposure Conditions ....................................................................................6
Definition and Fabrication of Test Specimen ...............................................................8
CFRP Systems ............................................................................................................10
4. Laboratory Test Program and Results............................................................................12
Failure Modes .............................................................................................................12
Summary of Test Results ............................................................................................13
General ........................................................................................................................13
Water Immersion ........................................................................................................16
System A .................................................................................................................16
System B .................................................................................................................17
System C .................................................................................................................18
System D .................................................................................................................20
System E .................................................................................................................20
Other Tests ..................................................................................................................21
Different Levels of RH Exposure ...........................................................................21
Wet-Dry Specimens ................................................................................................22
Sustained Load ........................................................................................................23
Ultraviolet Radiation, Alkali Exposure and Chloride Exposure .............................24
Fatigue .....................................................................................................................26
Pressurized Hygrothermal (Pressure Vessel) Accelerated Tests ............................27
Solar Exposure ........................................................................................................29
Tidal Exposure ........................................................................................................30
ii
iii
AUTHOR ACKNOWLEDGMENTS
The research reported herein was performed under NCHRP Project 12-73 by the
Department of Civil and Architectural Engineering at the University of Wyoming (UW) and the
Department of Civil and Coastal Engineering and Department of Materials Science and
Engineering at the University of Florida (UF). The University of Wyoming was the contractor
for the study.
Dr. Charles W. Dolan, PE, H. T. Person Professor of Engineering at UW was the
Principal Investigator. The other authors of the report are Dr. H. R. Hamilton II Associate
Professor at UF and co-PI, Dr. Jennifer E. Tanner, Assistant Professor at UW and co-PI, Dr.
Elliot Douglas at UF and Dr. David Mukai at UW, Jiangang Deng, Kyle Eyre, Research
Assistants at UW and Amber Gartner, Nathan Van Etten and Sungwon Choi, Research
Assistants at UF. The work was done under the general supervision of Professor Dolan at UW
and Dr. Hamilton at UF.
iv
ABSTRACT
This research provides a methodology for evaluation of durability related strength loss of
bonded carbon fiber reinforced polymer (CFRP) systems applied to concrete beams. The report
addresses test methods to establish a durability strength reduction factor, identification of
corresponding field exposure conditions affecting durability, and suggestions for the application
of the durability strength reduction factor for design of field applications. The durability strength
reduction factor is a measure of the loss in strength over time due to environmental exposure. It
is defined as the ratio of the flexural strength of a 4 in. x 4 in. x 14 in. concrete beam reinforced
with CFRP exposed at 140°F and submerged in water or 100% relative humidity for 60 days to
the flexural strength of a control specimen. The resulting durability strength reduction factor
may be used to evaluate CFRP system performance.
Two field environments are suggested: Wet and Air. In a Wet environment water
accumulates at the bond surface. This is the default condition and corresponds to test results in
submerged water at 140°F for 60 days. An Air environment allows drying between wetting
episodes so water cannot accumulate on the bond surface. This condition corresponds to test
results in 100% relative humidity at 140°F for 60 days.
EXECUTIVE SUMMARY
This research provides a methodology to evaluate durability of bonded Carbon Fiber
Reinforced Polymer (CFRP) repair and strengthening of concrete beams. The methodology is
based on use of a durability strength reduction factor, φd , to describe durability related strength
loss of CFRP systems. The report presents suggested test procedures, including test specimens
and exposure protocols, to establish the durability strength reduction factor. The test method
evaluation program led to the definition of field exposure environment. Definition of a field
environment allows the durability strength reduction factor to be used in conjunction with
existing load and resistance factors to evaluate the effects of durability strength loss in field
applications.
The strength of CFRP composites bonded to concrete deteriorates when exposed to
hygrothermal conditions. The deterioration occurs principally on the bond plane, which is the
interface between the epoxy adhesive and the concrete. The exact mechanism of the
deterioration is not well known; however deterioration is accelerated under elevated temperature,
immersion in water or sustained loads. Tests on a several CFRP systems indicated that the
procedures in this report were capable of differentiating a wide range of responses of
deterioration of CFRP systems subjected to the test procedures. Environmental exposure
conditions and test procedures assure uniform reporting and evaluation of durability strength
reduction factors to field application environments. The methodology presented in this report
allows engineers to obtain standardized comparisons of alternative CFRP systems, apply the
strength reduction factors to field applications, and to make decisions on the applicability of a
CFRP system for a given environment.
Two exposure environments: Wet and Air are recommended for design. The Wet
environment is characterized by the extensive exposure to and accumulation of moisture at the
epoxy-concrete interface and is the default environment for selection of durability strength
reduction factor for use in design. The Air environment is characterized by an ambient
environment in which water does not accumulate at the bond surface. Selection of the Air
environmental exposure condition requires confirmation to assure that water does not accumulate
on the bond surface and the report recommends comparison of the Wet and Air tests to further
assess the selection of a field exposure environment.
vi
The durability strength reduction factor is defined as the ratio of the flexural strength of
exposed test specimens to the flexural strength of control specimens. The durability strength
reduction factor may be established experimentally for any CFRP composite system and concrete
strength. The durability strength reduction factor may be used a) in conjunction with the
AASHTO resistance factor to provide design values for the reduced CFRP strength due to
environmental exposure, b) to qualify a specific CFRP system, c) to compare durability strength
reduction factors to those provided by system suppliers, or d) to confirm compliance with project
specifications. These recommendations are for strength deterioration of the bonded CFRP
system applied to concrete beams and do not address strength loss due to deterioration of the
underlying concrete or corrosion of steel reinforcement.
The test exposure for a Wet environment submerges the test specimen in 140°F water for
60 days. Test exposure for an Air environment is 60 days at 100% relative humidity at 140°F.
In lieu of other considerations, the Wet environment is recommended as the default condition. If
an Air environment is selected, the Wet environment tests are recommended to provide the
engineer with a basis to evaluate the exposure selection. The research recognizes that 140°F is a
high exposure temperature; however, the 60-day exposure at this temperature correlates with the
long-term lower bound response of specimens exposed to lower temperature conditions.
The test specimen is a 4 in. x 4 in. x 14 in. beam, tested in three-point bending (flexure)
on a 12 in. span length. The specimen is prepared by providing a full-width half-depth saw cut
approximately 0.1 in. wide at mid-span. Application of a CFRP system and surface preparation is
in accordance with NCHRP reports 514 and 609.
vii
Bonded Carbon Fiber Reinforced Polymer (CFRP) composite systems are widely used to
repair or strengthen bridge structures. Their light weight and ease of field application make them
an attractive alternative to traditional strengthening or replacement of bridge beams. Short-term
laboratory test results of CFRP application demonstrate that improvement in flexural or shear
strength is possible with these materials. (ACI 440) Concurrently, there is little comprehensive
information on the deterioration of CFRP strengthening systems in field environments nor is
there information allowing the estimation of the service life of these materials. A summary of
relevant research on durability of CFRP systems is given in Chapter 2.
Research Objective
The objective of this NCHRP 12-73 Project was to develop test methods to evaluate the
durability of CFRP used for repair or strengthening of concrete beams. A CFRP system consists
of the carbon fiber fabric or pre-cured CFRP laminate, the epoxy adhesive and associated
primers and sealers. The CFRP system is typically supplied as a system, that is, the carbon
material and adhesives. Application of bonded CFRP systems is addressed in NCHRP Report
514 and the manufacturers’ literature.
The research objective was met by defining a durability strength reduction factor, φd ,
which is applied to the strength calculations of CFRP systems used to strengthen or repair
concrete beams. Definition of moisture conditions for design environments and draft
specifications defining procedures for establishing the durability strength reduction factor are
provided. These recommendations result from an extensive testing program. The procedures
may be applied to any bonded CFRP system to establish durability strength reduction factors for
design or for manufactures to improve CFRP systems. The durability strength reduction factor
applies only to the CFRP component and is not applicable other mechanisms such as corrosion
of steel of reinforcement or concrete deterioration.
A second portion of this research examined procedures for estimating service life
associated with the strength loss of the bonded CFRP. In both the literature review and in the
experimental work conducted in this project, the degradation of the CFRP specimens submerged
in water occurred in days or weeks depending on the temperature. Service life is expected to be
in years or decades. Therefore, in lieu of prediction of service life, the research recommended
two exposure conditions that are dependent on the water content in the environment that affects
CFRP in service conditions. The strength reduction factors derived from the test procedures
recommended in this report represent lower bound values and are suitable for the life of the
structure.
Research Approach
The research approach included a review of relevant literature and factors affecting
durability, defined a test procedure for establishing a durability strength reduction factor,
conducted exposure tests, and assessed the test results. Attachments A and B contain test
specifications to determine the durability strength reduction factor, φd , for any given CFRP
system and specifications for mixing epoxies for the test specimens.
Moisture and temperature have been regarded the most important factor affecting CFRP
durability. Lefebvre et al. (1991) and Au et al. (2006) reported that a critical relative humidity
(RH) value in epoxy resins or CFRP composites existed beyond which durability degradation
occurs. Quantifiable identification of critical parameters affecting durability was not provided.
Wolff (1993) reported combinations of time, temperature, stress, chemicals, cyclic loads or
moisture cause increasing problems with durability of FRP composites. Karbhari et al. (1997)
reported that interfacial fracture energy decreased with exposure to water in CFRP composite
bonded concrete beams. Toutanji and Gomez (1997) observed a pronounced bond strength
reduction in CFRP composite systems subjected to wet/dry cycling. Tu and Kruger (1996) and
Aiello et al. (2002) concluded that water immersion led to bond strength degradation for epoxy
bonded concrete. Malvar et al. (2003) conducted CFRP to concrete pull-off tests and found that
bond strength of CFRP composite systems decreased at high temperature and relative humidity
(RH). Grace and Singh (2005) reported that reinforced concrete beams with externally bonded
CFRP plates exhibited an average of 33% reduction of load capacity after 10,000 hours of 100%
humidity exposure. Chun and Karbhari (2005) attributed the degradation of pultruded E-glass
vinylester composites to plasticization, hydrolysis, fiber-matrix debonding and microcracking
mechanisms caused by water ingress and temperature aging. Abanilla and Karbhari (2006a,
2006b, and 2006c) concluded that moisture uptake and other environmental factors deteriorated
the strength characteristics at the matrix and interface levels for FRP systems. Wan et al. (2006)
demonstrated that water presence in CFRP composite systems resulted in an adhesive failure
along the primer-concrete interface. Au and Buyukozturk (2006) concluded that 100% relative
humidity exposure resulted in a 50-60% loss in fracture toughness at the epoxy-concrete bond
surface in CFRP composite systems.
CHEMICAL SOLUTIONS
Chajes et al. (1994) reported that exposure to chlorides in both wet/dry and freeze/thaw
environments reduces flexural specimen strength, and that the wet/dry condition was slightly
more severe. Chin et al. (1998) reported a 40% tensile strength reduction in dogbone specimens
of isophthalic polyester and vinyl ester resins after immersion in alkaline solution (pH 13.5). Sen
et al. (1999) observed a 0 to 55% strength loss and a 0 to 45% loss in bond strength for CFRP
wet-layup systems bonded to concrete and subjected to cyclic sea water exposure. Hawary et al.
(2000) reported a 25% decrease in bond strength due to tidal saltwater exposure over 6, 12, and
18 months for epoxy bonded concrete specimens. Toutanji and Gomez (1997) observed a 5-30%
loss in flexural strength after 75 days of wet/dry exposure in simulated saltwater of CFRP and
GFRP wet layup bonded concrete beams.
UV RADIATION
Several investigators (Liao et al. 1998; Wolf 1993) reported ultraviolet radiation
deterioration increased in conjunction with moisture. They attributed observed strength reduction
to increased creep strain of the FRP. Haeberle et al. (2002) reported that UV exposure caused
surface cracking of carbon fiber vinylester resin matrix coupons. Liau and Tsent (1998) reported
that the UV exposure caused crack initiation in CFRP specimens, eventually reducing the
strength due to stress concentrations. Hulatt et al. (2002) found that stress at failure increased
after exposure of CFRP pre-impregnated coupons to 2000 hours of UV radiation according to
ASTM G 53.
FATIGUE
and monotonic strength of RC beams strengthened with CFRP laminate and reported the ultimate
deflection and strain of CFRP was slightly decreased, but the ultimate load was not affected by
cyclic fatigue loading.
A goal of accelerated aging testing is to reduce the time required to characterize long-
term behavior. Au et al. (2006) conducted a 3D diffusion simulation study and peel testing. Au
observed that specimens with CFRP bonded to concrete and subjected to 8 weeks of continuous
moisture exposure at 122°F resulted in the fracture toughness degrading to a steady value, which
was validated by peel testing. Au further reported that previous studies found that accelerated
aging tests could be terminated in a 60-day timeframe because equilibrium states were reached.
The Arrhenius equation was suggested as a method to correlate real time and accelerated aging
(Zhou and Lucas 1998). The equation is a power curve and the deterioration in strength is
correlated through curve fitting test data. Zhou and Lucas reported that the equation was valid
for continuous behavior, e.g., moisture migration into a CFRP system.
Four findings from the literature review influenced the development of a design
methodology. They are: moisture critically affected the performance of bonded CFRP systems;
elevated temperature accelerated deterioration; strength losses of up to 60% could be expected;
and accelerated aging results within a 60-day time could be expected.
The literature review presented conflicting findings. This was attributed to the materials
used in the various test programs. An underlying assumption was that all epoxies behave in a
similar manner. The literature review suggested that this is a false premise and each CFRP
system must be assessed individually.
The exposures used to condition the beam specimens are summarized in Table 1. These
conditions provided controlled accelerated aging and real time tidal and solar exposures. Control
specimens were cured in ambient laboratory (dry) conditions and were tested at 28 days. A
small number of control specimens were kept in ambient laboratory conditions and tested at the
conclusion of the environmental exposure tests. These specimens had the same or higher
flexural strength than the original control specimens.
A major consideration during the development of the test specimen was to replicate the
stress condition in concrete beams subjected to flexure or shear loadings. The test procedure had
to be sufficiently convenient so that statistically significant number of specimens could be
constructed and tested in a reasonable time frame. Furthermore, the test result interpretation
should be robust enough to ensure acceptance by state departments of transportation and CFRP
suppliers. The following sections summarize the process used to select a test specimen and
evaluate the test methodology.
selected as the starting point for specimen definition. The saw cut simulated a crack and assured
that the CFRP was exposed to the environment at the location of maximum moment. Three-
point loading resulted in a higher moment than four-point loading for the same maximum shear.
This loading reduced the possibility of a flexure-shear failure in the concrete. The configuration
shown in Figure 1 was selected for the durability tests. A single layer of wet-layup or pre-cured
composite was centered on the saw-cut. Shear and bearing at the specimen end was a concern so
Group 1 specimens were constructed with a length of 15 in. and Group 2 specimens were
constructed with a length of 14 in. to have a 1 in. and 1 – ½ in. extension past the center line of
the supports respectively. A span length of 12 in. was used by both groups when conducting
testing. For the wet-layup systems the fabric was cut to a width of 1 in. For the pre-cured
laminate system Group 1 specimens had a 1-in. width and the Group 2 specimens had a 0.75-in.
width to evaluate whether the stiffer laminate would generate excessive flexure-shear failures in
the concrete.
14 in.
4 in.
0.1 in. sawcut
4 in.
2 in.
Group 1 Specimens
Rocky Mountain Prestress, in Denver, CO cast the first batch of approximately 500
beams with a concrete 28-day compressive strength of 9,700-psi. The high strength was
representative of precast prestressed bridge beams and was selected to limit flexure-shear failure
in the specimen. The concrete mixture had a water:cement ratio of 0.32, and cement:fine
aggregate:coarse aggregate ratio of 1:1.65:1.96 by weight.
An additional 315 specimens were cast in two separate batches of 105 and 210
specimens, respectively. The two batches of concrete were cast in wooden forms with same
design mix except that pea gravel was used in the first batch and 3/8-in. maximum in the second
batch. These mixtures were representative of cast-in-place concrete beams. Type Ι/II low alkali
cement was used and the cement: sand: coarse aggregate ratio was 1:2.09:2.41 by weight. The
specimens were cured in the fog room at nearly 100% relative humidity and temperature of 68°F.
The 28-day compressive strength was 6,700 psi for the first batch and 6,900 psi for the second
batch (Deng 2008).
Group 2 Specimens
Six batches of 75 beams constituted the 450 Group 2 beams. They were cast at the
Florida Department of Transportation State Materials Office (FDOT) in Gainesville, FL. The
concrete was designed to have a 28-day compressive strength of 10,000-psi. The mixture had a
water:cement ratio of 0.35 and a cement:fine aggregate:coarse aggregate ratio of 1:1.5:1.7 by
weight. The measured 28 day compressive strength varied between 9,250 to 10,500 psi and the
MOR varied between 990 psi to 1090 psi (Gartner 2007).
CFRP SYSTEMS
The test procedures were designed to differentiate the durability performance of CFRP
systems. To determine if the procedures could differentiate performance, four - unidirectional
wet-layup CFRP systems (A, B, D, and E) and one unidirectional carbon laminate system (C)
were selected to construct the specimens. Systems A, B, and C were commercially available
systems in which the fiber and epoxy are provided together. These systems were proprietary so
the chemical composition of the resins and primers was not known. System D and E epoxies
were formulated using of commercially available components for which the chemical
composition was known.
Composite A was a unidirectional carbon fiber fabric and a two-component epoxy resin.
The system also included a sealant to provide a protective coating. To assess the effectiveness of
10
the coating, Group 1 specimens did not apply the coating and Group 2 specimens used the
coating.
Composite B consisted of unidirectional carbon fiber fabric, epoxy primer, epoxy putty,
epoxy saturant, fiber weave, and protective top coat. The primer was a low viscosity, 100%
solids, polyamine cured epoxy. The putty was a 100% solids non-sag paste used to level small
surface defects and provided a smooth surface to apply the composite system. The saturant was
a 100% solids, low viscosity epoxy material used to encapsulate the fiber fabric. The top coat
protected against UV radiation and mild abrasion.
Composite C consisted of a pre-cured unidirectional carbon fiber polymer laminate and
epoxy putty. The putty was a 100% solids, structural epoxy paste adhesive that conformed to
AASHTO M-235 and ASTM C-881 specifications. Group 1 used a 1 in. wide strip and Group 2
used a ¾ in. wide strip to assess the effects on concrete flexure-shear failure of the concrete
specimen.
Composites D and E consisted of a Composite B CFRP fabric and a custom formulated,
two component, epoxy with known properties. Composites D and E consisted of the two
components of this generic system, but different mixing ratios. The thermal and mechanical
properties of several mixture proportions were tested to determine the mixture ratios for the
generic system. The glass transition temperature (T g ) of these two epoxy mixtures was
measured using differential scanning calorimetry (DSC) and the effect of cross-linking on the
glass transition temperature was analyzed. The effect of water immersion over short term
periods was evaluated using tension tests on epoxy coupons. Composite D epoxy used a ratio
that allowed for equal number of reaction sites for both saturant components and was assumed to
simulate commercial systems. Composite E used an alternate ratio of the two parts of the epoxy
resulting in a different number of reaction sites.
11
FAILURE MODES
ACI 440.2R Guide for the Design and Construction of Externally Bonded FRP Systems
for Strengthening Concrete Structures (ACI 440.2R 2002) Section 9.2.1 identifies five possible
failure modes for flexural strengthening with CFRP. Three modes deal with steel yield and
primary or secondary concrete compression failure. The other two conditions address substrate
failure (cover delamination) and debonding. The test procedure developed in this research
addresses only the last two items and φd applies only to the bond actions, e.g., Eq. 9-2 in ACI
440.2R-02 or similar bond related behavior. If the bond is sufficient, even with the reduced
capacity, to force other modes of failure, e.g., compression failure of the concrete, then the
design is not bond critical. In this case the φd is applied only to bond sensitive conditions.
Bonded CFRP failure modes are reported in the literature; however there was wide
variation in the reporting nomenclature. In consequence, the definitions and descriptions in
Table 2 were developed and used in this research. Substrate failure is the desirable failure mode
in practice. The test procedure was designed to develop substrate failure in the control specimens
and to ensure the capacity obtained from testing directly correlates to the loss of CFRP bond
strength. A system having substrate failure following exposure is assumed to have no durability
strength reduction. Mixed mode, adhesive and composite delamination failures were evidence of
durability deterioration. Any flexure-shear failure was considered an invalid test result and was
excluded from test results.
12
General
13
Figure 2 and summary graphs for Systems D and E give the control strength and the final
strength in terms of the load that caused flexural failure. This allows comparison of strength of
alternative adhesive systems. Individual system test reports provided data in the format of
strength ratio, that is, the strength of the exposed specimen divided by the strength of the control
specimen, to better display strength losses. The control strength of CFRP System A varied
between 4000 and 4500 lb. for Group 1 and was approximately 3500 lb. for Group 2. Control
strength of System B was about 5000 lb. for both groups. Differences in the amount of epoxy
applied to the specimen, concrete strength, and aggregate composition explained the differences
between Group 1 and 2 CFRP Systems A and B. The difference in initial strength observed
between Group 1 and Group 2 specimens CFRP System C was attributed to differences in the
width of the CFRP laminate. Initial concrete specimen strength and CFRP width affect the final
strength loss because a higher concrete strength or wider CFRP strip has a higher control value.
A wider strip results in a higher initial flexural strength and increases the opportunity for a
flexure-shear failure in the test specimen. The ¾ in. and 1 in. laminate strips were chosen to
assess the occurrence of a concrete flexure-shear failure. The occurrence of concrete flexure-
shear failures was low, so a 1 in. width was recommended in the test procedures. The test
procedure included a tolerance on the CFRP width.
The flexural beam strength of the plain concrete prisms with the saw cut and without
CFRP was approximately 20% of the control strength. In the flexural specimens, when the
bonded CFRP failed, the load transferred to the concrete and the concrete failed in a brittle
fashion. Consequently, once the strength of the CFRP composite specimen drops below the
residual strength of the concrete, the CFRP was assumed to have reached zero strength. This
was consistent with direct tension tests, where the direct tension test results indicated no
remaining strength.
14
1000
2000
3000
4000
5000
6000
7000
0
Water 30C
Water 40C
Water 50C
A
Water 60C
UV 50C
Alkaline 50C
Chloride 50C
Real Time Bridge
Water 30C
Water 40C
Water 50C
60 d
Water 60C
B
12 mo
Control
UV 50C
Alkaline 50C
Chloride 50C
Group 2
Slotted MOR
15
Water 50C
14 d
6 mo
Water 60C
18 mo
C
UV 50C
Alkaline 50C
Design Guidelines for Durability of Bonded CFRP Repair/Strengthening of Concrete Beams
Chloride 50C
Real Time Bridge
Water 30C
Water 40C
D
Water 50C
Water 60C
Water 30C
Water 40C
E
Water 50C
Water 60C
Water 20C
Water 30C
Water 40C
Water 50C
A Water 60C
75% RH 20C
100% RH 20C
100% RH 20C
Water Fog Room 20C
Wet Dry 40C
Wet Dry 60C
Pressure Vessel 60C
Real Time Roof
30°C=86°F; 40°C=104°F; 50°C=122°F; 60°C=140°F
Water 20C
75% RH 20C
Group 1
100% RH 20C
Wet Dry 40C
Wet Dry 60C
Pressure Vessel 60C
Real Time Roof
Water 20C
Water 30C
Water 40C
Water 50C
Water 60C
C
75% RH 20C
100% RH 20C
Wet Dry 40C
Wet Dry 60C
Pressure Vessel 60C
Real Time Roof
D
Water 60C
Design Guidelines for Durability of Bonded CFRP Repair/Strengthening of Concrete Beams
WATER IMMERSION
Test results are given for Systems A, B, C, D and E specimens immersed in water for up to
18 months at 86°F, 104°F, 122°F and 140°F. System C specimens were tested at 6 and 12
months; none were tested at 18 months because of the near complete strength loss after 12
months. Systems D and E were tested at 6, 12, and 18 months. Group 1 did confirmation tests
of System D at 9 months and Group 2 performed confirmation tests on Systems A and B. The
inter-laboratory validation process expanded the research to include effects of different cements,
aggregates, mixture designs and laboratory techniques.
System A
Flexure test results of System A in water immersion at 86°F, 104°F, 122°F and 140°F are
shown in Figure 3. The strength ratio is defined as the flexural strength of an exposed specimen
to that of the 28 day old control specimen.
Redry Redry
0.8 0.8
0.6 0.6
0.4 0.4
0.2 0.2
0 0
0 100 200 300 400 500 600 0 100 200 300 400 500 600
Exposure Time (days) Exposure Time (days)
16
five System A specimens were removed from the 140°F water bath tanks after 16 months, placed
in a dry environment for 2 months then tested. The open circle symbols in Figure 3 represent the
drying test results.
• The flexural strength decreases rapidly in the first 14 days and slowly afterwards.
System B
17
Redry
Strength Ratio
0.8 0.8
0.6 0.6
0.4 0.4 30C
40C
0.2 0.2 50C
60C
Redry
0 0
0 100 200 300 400 500 600 0 100 200 300 400 500 600
Exposure Time (days) Exposure Time (days)
System C
System C flexural test results for water immersion are shown in Figure 5. System C lost
all strength after 12 months and a visible CFRP material delamination and laminate expansion
occurred. Testing at 18 months was terminated.
18
1.2
1.2 30C
30C 40C
1 40C 1 50C
50C
Strength Ratio
60C
Strength Ratio
0.8 0.8
60C
0.6 0.6
0.4 0.4
0.2 0.2
0 0
0 100 200 300 400 0 100 200 300 400
Exposure Time (days) Exposure Time (days)
0.8 60C
0.6
0.4
0.2
0.0
0 100 200 300 400 500 600
Time (Days)
System C specimens exhibited substantial strength loss at 6 and 12 months for both
flexural and direct tension tests exposed to all temperatures. Specimens exposed to 122°F and
140°F provided no additional strength to the plain concrete and therefore were recorded as
having 100% strength loss. The Group 2 strength ratios were slightly higher than Group 1 at
86°F, 104°F and 122°F.
All specimens displayed nearly complete strength loss and composite delamination. One
test series was conducted for 60 days at 140°F with all edges of the CFRP laminate sealed with
epoxy to evaluate whether wicking of water along the carbon fibers contributed to the strength
loss. The results were the same as the unsealed specimens.
19
• The flexural strength loss rate increased with an increase in water temperature.
• Eighty to one hundred percent strength loss occurred after submersion in 140°F water for
28 days.
• Sealed specimens had strength loss comparable to unsealed specimens indicating that
wicking along the laminate was not a source of premature failure.
• Test results at 140°F for 60 days were representative of long-term test results at lower
temperatures.
System D
Test results for System D beam indicated flexural strength ratios above 0.80 for all
temperatures when submerged for 6, 12 and 18 months, Figure 6. The Group 1 comparison
specimens submerged in 140°F water have a strength ratio of 0.76 at 9 months. The failure
mode of System D specimens was consistently adhesive.
1.2 1.2
1.0 1.0
Strength Ratio
Strength Ratio
0.8 0.8
System E
Test results for System E exhibited strength ratios above 0.80 after submersion at
elevated temperature for up to 600 days, Figure 7. The strength ratio was greater than 1 after 12
months at 104°F and 140°F. Epoxy coupon testing indicated that the increase in strength of
epoxy resin at elevated temperature was due to reactivation of amine, the curing agent. After 18
20
months of exposure, the strength ratios were 1.05, 0.94, 0.95 and 0.96 at 86°F, 104°F, 122°F and
140°F, respectively.
The failure mode in System E specimens was consistently adhesive, with a few mixed
mode failures.
1.2
1.0
Strength Ratio
0.8
0.6 30C
40C
0.4 50C
60C
0.2
0.0
0 100 200 300 400 500 600
Exposure Time (days)
Tests were conducted at 75 and 100% RH, at room temperature water bath, and at 100%
RH at 140°F for Systems A, B and C, Figure 8. The maximum strength loss occurred in the 100%
21
RH specimens at 140°F. For room temperature exposure conditions, the maximum strength loss
was in the submerged specimens. The strength loss generally increased with time.
1.2 1.2
1.0 1.0
Strength Ratio
0.8
Strength Ratio
0.8
0.6 0.6 75% RH
75% RH
100% RH 100% RH
0.4 0.4
Water Bath Water Bath
0.2 Control 0.2 Control
60C/100%RH 60C/100RH
0.0 0.0
0 100 200 300 400 0 100 200 300 400
Exposure Time (days) Exposure Time (days)
1.2
1.0
0.8
Strength Ratio
0.6
75% RH
0.4 100% RH
Water Bath
0.2 Control
60C/100RH
0.0
0 100 200 300 400
Exposure Time (days)
(c) System C
30°C=86°F; 40°C=104°F; 50°C=122°F; 60°C=140°F
Wet-Dry specimens
System A, B and C tests were conducted for 11.5 months at intermittent wet/dry cycles,
30°C=86°F; 40°C=104°F; 50°C=122°F; 60°C=140°F
Figure 9. Each wet/dry cycle consisted of two days submersion and 5 days in 68°Fair.
The control specimens gained 5% strength over the exposure period, Figure 10. Systems A and
C exhibited strength reduction with increasing temperature and exposure time. Very little
22
strength reduction was observed for System B. For Systems A and B, the failure modes were
mixed mode. System C failure modes began as mixed mode failure and transitioned to adhesive
or delamination failure modes. System C experienced nearly complete strength loss under
wet/dry exposure. In general, intermittent wet/dry exposure was more moderate than full
immersion in elevated water conditions for CFRP systems.
1.2
1.2
1.0
1.0
Strength Ratio
Strength Ratio
0.8
0.8
0.6 0.6
0.4 0.4
40C
40C
0.2 0.2 60C
60C
Control
Control
0.0 0.0
0 100 200 300 400 0 100 200 300 400
Exposure Time (days) Exposure Time (days)
1.2
1.0
Strength Ratio
0.8
0.6
0.4
40C
0.2 60C
Control
0.0
0 100 200 300 400
Exposure Time (days)
(c) System C
30°C=86°F; 40°C=104°F; 50°C=122°F; 60°C=140°F
Sustained load
Systems A, B, and C were subjected to a continuous sustained flexural load of 50% of the
control strength and submerged in 122°F water. Within two weeks of initial submersion at least
23
one specimen in each frame had failed. All specimens had failed within 60 days. The failure
mode was the same as the 122°F water immersion test results for each system.
Systems A, B, and C were exposed to chloride solution (TC) at 122°F, alkali solution
(TA) at 122°F, and UV light cycled (UV) with water immersion in 122°F water over a 12-month
period. All specimens included UV coatings. After 12 months, Systems A, B, and C specimens
were removed from the tanks and tested.
The strength ratio for a 12-month test of System A in thermal chloride exposure (TC) at
122°F, thermal alkali exposure (TA) at 122°F, and UV light exposure cycled with water
immersion at 122°F temperature (UV) is shown in Figure 10. The flexural strength ratio ranged
from 0.84 to 0.81 after exposure to TC, TA, or UV. The flexural strength ratios were slightly
higher than the strength ratio after water exposure at 140°F over a 6 month period, which was
0.76. The failure mode in System A specimens was consistently adhesive, except for a few
specimens in thermal chloride exposure that had mixed mode failure.
1.2
1.0
Strength Ratio
0.8
0.6
0.4
0.2
0.0
1 TC
2 TA
3 UV
4 5
Immersion Condition
Figure 10. Strength ratios for System A after 12 months exposure to chlorides, alkali and
UV at 122°F
24
1.2
1.0
Strength Ratio
0.8
0.6
0.4
0.2
0.0
1 TC
2 TA
3 UV
4 5
Immersion Condition
Figure 11. Strength ratios for System B after 12 months exposure to chlorides, alkali and
UV at 122°F
System C test results had strength ratios of 0.29 for TC, 0.37 for TA, and 0.46 for UV
exposures, Figure 12.
1.2
1.0
Strength Ratio
0.8
0.6
0.4
0.2
0.0
1 TC
2 TA
3 UV
4 5
Immersion Condition
Figure 12. Strength ratios for System C after 12 months exposure to chlorides, alkali and
UV at 122°F
Test results of 12-month exposure to the chemical solution were compared to specimens
submerged in water at 122°Ffor 18 months are shown in Figure 13. The results indicated that the
chemical solutions were more severe than water only. Composites A and B appeared to be
affected more by the alkaline environment than that of the chloride solution. Conversely,
composite C was affected more by the chloride solution. There did not appear to be sufficient
difference in performance to warrant routine use of the chemical solution testing.
25
1.2
TA
1.0 TC
50C
Strength Ratio
0.8
0.6
0.4
0.2
0.0
A B C
Composite
Fatigue
Three sets of specimens were tested to evaluate the effects of fatigue and exposure:
System A, B and C specimens were conditioned by placing them in water baths for
sufficient time to obtain a 10 percent strength reduction. Unconditioned specimens were loaded
to 50% of the control strength for 2,000,000 cycles then tested for residual flexural strength.
System B and C conditioned specimens were loaded to 45% of the control strength for 2,000,000
cycles. The conditioned CFRP System A specimens were loaded to 380,000 cycles at which
time the displacement limits of the test machine were exceeded. Test results of CFRP Composite
A, B and C Systems are shown in Figure 14 and were in agreement with other investigators
referenced in Chapter 2.
26
7000
Control
6000 Unconditioned specimen
Conditioned specimen
5000
3000
2000
1000
0
CFRP System
1 A CFRP System
2 B CFRP3System C
27
1.2
Strength Ratio
0.8
0.6
0.4
CFRP System A
The test results from CFRP System A, B and C subjected to pressure vessel exposure
indicated the following:
• CFRP Composite System A experienced a flexural strength loss of 20% and specimens
exhibited a mixed mode failure after 7 days, a 26% flexural strength loss and mixed
mode failure after 10 days, and a 24% flexural strength loss and mixed mode failure
after 14 days of exposure.
• For CFRP Composite System B, the flexural strength loss was 10% and specimens had
mixed mode failure after 7 days. A 13% flexural strength loss and mixed mode failure
occurred after 10 days, and a 15% flexural strength loss and mixed mode failure after
14 days of exposure.
• For CFRP Composite System C, the flexural strength loss was 11% and specimens had
mixed mode failure after 7 days. A 27% flexural strength loss and mixed mode failure
occurred after 10 days, and a 39% flexural strength loss and mixed mode failure
occurred after 14 days.
The test results of CFRP System A, B and C specimens indicated that the hygrothermal
exposure at a pressure of 30 psi after 14 days shows promise of being able to differentiate the
performance of CFRP systems. The 14-day pressure vessel tests correlate well with all Group 2
exposure tests except CFRP System C. The 14-day test suggests further development is
warranted.
28
Solar exposure
Solar exposure is a real time environment that combines UV, moisture variation and
ambient freeze-thaw cycles present at 7200 ft. The flexural test results of CFRP Composite A, B
and C Systems after 18 months are shown in Figure 16.
1.2
1
Strength Ratio
0.8
0.6
0.4
CFRP System A
The test results from CFRP System A, B and C solar exposure indicated the following:
• System A flexural strength decreases sharply in the first 200 days. The specimens failed
by a mixed mode failure after 6 months and adhesive failure after 12 months.
• System B flexural strength decreased sharply in the 200 days. The flexural bond
strength degraded up to 28% and specimens failed by a mixed mode failure after 6
months. At 12 months and beyond, the flexural strength tended to stabilize.
• System C flexural test results showed linear strength reduction with time. The
specimens failed by mixed mode failure after 6 months. Adhesive failure mode
occurred after 12 months, and CFRP laminate slip was observed after 18 months.
System A, B and C solar exposure resulted in strength loss. The System A losses
compare to the 140°F, 60-day losses and were aggravated by the intentional omission of UV
coatings and further influenced by thermal cyclic loading due to differences in the coefficient of
thermal expansion (CTE) of the laminate, adhesive, and concrete. The diurnal temperature
changes and the CTE differences result in a residual stress between CFRP and the concrete that
may affect the bond strength.
29
Tidal exposure
1.0
0.8
0.6
0.4 System A
0.2 System B
System C
0.0
0 100 200 300 400 500 600
Exposure Time (days)
The strength ratio after 12 months of exposure of System A was 0.78. The initial drop in
strength at 12 months was followed by a slight increase in strength to 0.86 at 18 months. This
increase might be due to the buildup of barnacles and their associated marine adhesive, which
protected specimens from deterioration and acted as additional adhesive or sealant (El-Hawary
2000). The failure mode for System A was consistently adhesive.
The reduction of the flexural strength in System B was 12% after 12 months. This was
much less than the 58% strength reduction for continuous water exposure over a 6 month period
at 140°F. Although the FRP composite reinforcement was oriented upward, the specimens were
protected from direct sunlight for most of the daylight hours by the fender system. This
prevented direct UV exposure and large temperature swings from solar heating. Since System B
was affected by temperature, it was postulated that System B was not affected in the Tidal
environment by the sea water because of the protection provided by the fender.
The initial drop in the failure strength of System B after 12 months was followed by an
increase in strength to 1.04 after 18 months. The loss in strength for System B after 6 months of
water exposure at elevated temperature was associated with a change to an adhesive failure mode.
30
The relatively small loss in strength and lack of change in failure mode for tidal exposure
indicated that the specimens had not experienced severe strength loss.
System C showed little effect from the tidal exposure to sea water and seemed to behave
more consistently over time than Systems A and B. After 12 months, the loss in strength of one
specimen was 12% and the residual strength of the other two specimens was higher than that of
the control specimen. After 18 months, the strength ratio increased further to 1.23, which may
be due to the buildup of barnacles. System C specimens degraded severely after immersion in
water at elevated temperatures. Thus, it was possible that the relatively cool sea water (less than
room temperature) did not cause degradation of System C. The fact that failure mode of the
room and elevated temperature submerged specimens was delamination but the failure mode of
the tidal specimens was adhesive supports this assertion.
The 18-month strength ratio of concrete beams without CFRP was an average of 1.01.
The plain concrete specimen with barnacles exhibited a higher flexural strength than plain
concrete suggesting that all strength losses were in the CFRP system.
Epoxy coverage
A study was performed to evaluate the relationship between durability and epoxy
coverage for 80%, 100% and 200% of the manufacturers’ recommended coverage rates for
System A. The manufacturers’ recommended epoxy coverage assumes using 100% of the epoxy
on a large area. Laboratory specimens use small amounts of epoxy and total coverage was
influenced by the amount of epoxy mixed, left in the roller, left in the mixing cups and spread to
the side of the CFRP. For this test, coverage was determined by two methods: 1) weighing all
instruments and epoxy prior to application and again after applying epoxy, and 2) weighing the
beam and CFRP without epoxy and weighing after applying epoxy. Both methods yielded
similar results.
The test results showed that strength ratio remains at 1.0 for unexposed specimens,
indicating that coverage does not affect control strength. The strength ratio for 80% coverage at
140°F for 60 days was approximately 0.25. The strength ratio for 100% coverage averages 0.65
and for 200% coverage averages 82%. Strength ratio variation with respect to coverage
suggested epoxy coverage was critical to durability. The testing procedure in Attachment B
31
1.2
1.0
Strength Ratio
0.8
0.6
0.4
Exposed
0.2
Unexposed
0.0
0 50 100 150 200 250
Percent Coverage
Concrete strength
Control specimens exhibited substrate failure. Therefore, the strength of the control was
influenced by the strength of the concrete, which in turn, influenced the strength ratio.
Comparison of test results using different concrete mixtures indicated that epoxy coverage and
width of the CFRP were far more critical to establishing the control strength than the base
concrete strength.
Test results indicated that the recommended test procedures and specimens were capable
of differentiating CFRP durability performance. Furthermore, Figure 3 and Figure 4 indicated
that the flexural test specimen was more consistent in predicting the strength ratio during the first
60 days. The strength ratios of Systems A, B and C indicated a substantial loss of strength.
Comparison of the strength ratios for Systems D and E with Systems A, B, and C suggested that
more durable epoxy formulations are available.
The test program further confirmed the findings in the literature that individual epoxy
systems have highly varied durability characteristics. The variability is seen in these tests and is
observed in the following sections.
32
Comments on System A
The strength reduction for System A in the Group 1 submerged tests and solar exposure
tests were considerably greater than the comparator tests of Group 2 and the pressure vessel tests.
After evaluating the data, there appeared to be two possible explanations. The improved
performance measured for Group 2 specimens may be due, in part, to the UV coating that was
added to those specimens as part of the comparator studies. A consequence of this difference
was the recommendation that UV coating be used in all applications.
The second factor was the quantity of epoxy coverage. Multiple checks of the quantity of
epoxy used in Group 1 specimens indicated that the first set of test specimens was prepared at
the manufacturer’s minimum recommended coverage. Subsequent sets of specimens had
increased the epoxy quantity. The manufacturer’s literature provides recommended coverage,
thus use of more or less epoxy was permissible. When the first set of specimens was adjusted to
account for later higher coverage, the strength ratios generally agree with Group 2. These results
suggested epoxy coverage rate has an impact on durable performance. Field epoxy coverage
rates must be comparable to the coverage rates use in the tests to assure comparable results.
Comments on System B
The System B strength ratio was nearly constant at 6, 12 and 18 months for each of the
86°F, 122°F and 140°F tests. The final strength ratio of 0.5 to 0.7 was consistent for both the
Group 1 and Group 2 data.
Comments on System C
System C specimens showed severe deterioration when submerged in 104°F, 122°F and
140°F water. System C specimens placed in the tidal zone in Florida displayed an increase in
strength. Marine growth by itself does not seem to be the sole cause of the strength gain because
the failure mode resulted from delamination of the pre-cured laminate. Other factors that may
have contributed to the difference in strength between the laboratory-stored and tidal specimens
and the field exposure were the wet/dry cycling and exposure temperature. The Group 1 wet/dry
exposure results were conducted at 104°F and 140°F and had strength reduction similar to the
Group 2 submerged specimens. The control specimen had strength gains comparable to the
33
Group 2 tidal specimens. This leads to the possible explanation that the pre-cured laminate was
particularly sensitive to water submersion at elevated temperature.
Although the test methodology identified a potential defect in the material; the durability
strength reduction factor for this system may be overly conservative. Relative humidity
exposure may be more appropriate, but does not yet ensure consistently conservative results.
Group 2 System D 18-month exposure specimens had flexural strength failure loads
between 0.8 and 0.85 of the control for submersion in water at 122°F and 140°F.
Figure 19. Group 1 specimens had a flexural strength of 0.75 at 140°F. The strength
reduction factors for System E were greater than 90%.
5000
Control 60 d
6 mo 12 mo
4000
18 mo Slotted MOR
Failure Load (lb)
3000
2000
1000
0
Water 30C
Water 40C
Water 50C
Water 60C
Water 30C
Water 40C
Water 50C
Water 60C
Water 60C
D E D
Group 2 Group 1
34
The recommended test procedure provided a durability strength reduction factor for any
CFRP system. Tests on all CFRP systems evaluated in this research had strength reduction
factors for submerged exposure for 60 days and 140°F that were lower than the strength
reduction factor for comparable specimens exposed to Solar or Tidal conditions for 18 months or
for specimens submerged at room temperature for up to 12 months. The elevated temperature
35
compensated for the longer exposure time in both cases; however, the direct correlation of
elevated temperature is, as yet, undefined.
Exposure to 100% relative humidity at 140°F resulted in durability strength reduction
factors higher than those for submerged exposure at room temperature and is recommended as
representative of a structure in Air. As a demonstration of the procedures, the durability
reduction factors for Systems A, B and C for two exposures is given in Table 3. With nearly a
50% difference in durability strength reduction factor between the two environments, the
selection of an exposure environment has both technical and economic ramifications.
System C failed when the CFRP laminate degraded completely in the heated-Wet
(submerged) environment. The tests were confirmed on different batches of CFRP laminate,
different environments and different laboratories. Long-term use of this system in a Wet
environment with elevated temperature is not recommended.
The beginning of this Chapter points out that there was no correlation between
accelerated aging and structure life at this time. Consequently, it is recommended that a field
environment be defined to address durability behavior of CFRP systems. The Wet environment
is applicable for any structure where water can accumulate on the bond surface. Test specimens
indicated durability strength reduction occurs in less than two weeks. Because water migrates
through the concrete faster than through the CFRP this classification extends to any structure in
direct contact with the ground, such as foundations, cut-and-cover structures, and retaining walls.
For safety, the Wet exposure condition is the default and applies to soffits of beams and slabs
with low clearance over water splash zones and soffits of bridge decks when the deck is
frequently wetted.
36
The Air environment applies to applications where water does not accumulate on the
bond surface. Specimens in the tidal exposure exhibited no strength loss after 12 months. This
suggests that the marine encrustations, drying time compared to wetting time, and lower water
temperature, successfully compensated for the wetting effects. Six month exposure tests at less
than 100% RH exhibited less strength loss than the 100% relative humidity exposure. These
tests further confirmed that the 100% RH at 140°F represented a lower bound loss. The
exception to this was the solar specimens, which exhibited large strength loss after an 18-month
exposure. The strength loss in the solar specimens was attributed to the lack of a UV protection
coating; therefore, they were not fully representative of a proper field application. The
performance of the solar exposure specimens reinforced the recommendation that all applications
include a UV coating.
Correlation of laboratory epoxy application and field epoxy coverage rates is a critical
issue. Durable performance was sensitive to the epoxy coverage, especially the first coat that
was applied to the concrete. Changes in coverage rates had no appreciable effect on the control
specimen flexural strength but had an effect on the exposed specimens. Coverage less than the
manufacturer’s recommendations resulted in accelerated deterioration of the CFRP system
compared to systems with the specified coverage. The specimen preparation procedures in
Attachment B specifically address application rates that would be used in the lab. Epoxy applied
on the test specimen in excess of that used in the field will result in a higher than actual, or
unconservative, durability strength reduction factor.
Correlation of lab epoxy coverage and field coverage is complicated by the installation
procedure. Lab specimens are made with the CFRP facing up. Therefore, gravity assists in
retaining the wet epoxy on the surface. Field applications are typically on the soffit of the
structure so the total amount of epoxy that can be absorbed by the concrete may be less.
Engineers will want to consider this when specifying the epoxy coverage as recommended in
Attachment B.
37
The test procedure consists of five standard specimens exposed to either a Wet or Air
environment plus five control specimens. The exposed specimens are conditioned for 60 days at
140°F by either immersion in water for a Wet environment or in 100% relative humidity at
140°F for an Air environment. They are then removed from their exposure chamber, placed in a
room temperature bath for one day, removed from the room temperature bath, and then allowed
to dry for at least 2 hours before testing. Specimens are tested in flexure on a 12-in. span in
three-point bending. The flexural failure loads are reported and are used to compute the strength
reduction factor. Details of the recommended test procedures and epoxy preparation procedures
are given in Attachments A and B and also address recommended coverage rates.
The recommended standard test specimen for the establishment of a durability strength
reduction factor is a 4-in. x 4-in. x 14-in. concrete beam. This specimen provided more
consistent test results than a direct tension test. The tension side of the specimen has a 2-in. deep
saw cut perpendicular to the beam at mid-span to simulate a crack in the structure. The specimen
is strengthened with a 1-in. wide x 8-in. long CFRP fabric strip or laminate centered on the saw
38
cut in accordance with NCHRP Report 514. The test specification is described in detail in
Attachment A.
The durability strength reduction factor, φd, is the ratio of the flexural strength of exposed
test specimens to the flexural strength of control specimens cured at ambient room conditions.
Specimens conditioned by submersion in water for 60 days at 140°F provide the reduction factor
for Wet environments. Specimens conditioned for 60 days in a 100% humidity environment at
140°F provide the reduction factor for Air environments.
The reduction factors are applicable to the CFRP system tested and to the environment
corresponding to the exposure: Wet or Air (submerged or 100% relative humidity). In addition,
the reduction factors have three caveats. The factors are applicable if:
• the epoxy coverage rate in the field is equal to or greater than that used in the test,
• the CFRP is protected from ultraviolet exposure , and
• the concrete strength used in the test specimens corresponds to the field concrete
strength.
Specimens exposed to sustained loads greater than 50% of the CFRP capacity and
immersed in water failed within two weeks. Therefore, use of bonded CFRP for sustained
loading in Wet environments is not recommended. Each CFRP system tested in this program
had a different durability response. Therefore, until a scientifically based model of adhesive
deterioration is defined, experimental validation is the only acceptable method to determine the
strength reduction factor.
The selection of a design environment for field applications recognizes that bonded
CFRP systems are sensitive to water and that deterioration can occur after a short exposure time.
Water migration to the bond surface from either the CFRP or the concrete side of the structure
results in deterioration. Two design environments are suggested: Wet and Air. The default
design environment is a Wet environment. A Wet environment is characterized by an
installation that has extensive exposure to water and where water can accumulate on the bond
surface (the interface between the epoxy and the concrete). Examples would be bridge beams
and decks that are regularly wetted for extended periods, extensive exposure to precipitation and
100% RH, beams with low clearance over water, or beams in splash zones. The alternative Air
39
environment is for structures that have intermittent exposure to water or precipitation that has
time to dry between exposures so the water does not accumulate at the bond surface. If an Air
environment is selected, the Wet environment test is recommended to allow engineer to compare
the relative strength performance associated with both environmental exposures.
The durability strength reduction factor is applied to all strength calculations involving
the strength of bonded CFRP systems where the strength of the CFRP and epoxy is integral to
the performance of the member. The factor is a multiplier and is used in addition to the
resistance factors defined in the AASHTO Bridge Design Specification (AASHTO 2008).
At the initiation of this research, the research team assumed that the deterioration of
epoxy bonding materials would be slower than was found in the experimental program. The
strength losses reported in journal articles cited in Chapter 2, and the time to the stabilized loss
were consistent with this report. In short, the epoxies used today were adequate for control and
nominally dry applications. They were at risk for deterioration in continuously damp or wet
environments. The test procedures in this report allow an assessment of any proposed CFRP
system and allow system suppliers to evaluate and improve products for field application.
Custom epoxies developed for and tested in this program had higher strength reduction ratios
than commercially available adhesives. This response suggested that improvements in the
durability of bonded CFRP systems are possible and cost effective.
40
• The pressure vessel test procedure showed promise of more rapid test results and should be
explored further. Test results suggest that strength reduction factors can be evaluated in
approximately 2-4 weeks instead of 60 days.
• The behavior of pre-cured laminates to wet environments and elevated temperature needs
further refinement. The proposed test specification identified problems but did not provide
insight to potential solutions.
41
REFERENCES
AASHTO LRFD Bridge Design Specifications, Customary U.S. Units, 4th Edition and Interim
Revisions, (2008) AASHTO, Washington DC, 658 pg.
Abanilla MA, Li Y and Karbhari V. M., (2006a), “Durability Characterization of Wet Layup
Carbon/Epoxy Composites Used in External Strengthening”. Composites: B 2006; 37(2-
3):200-12.
Abanilla MA, Li Y and Karbhari V. M., (2006b),”Interlaminar and Intralaminar Durability
Characterization of Wet Layup Carbon/Epoxy Composites Used in External
Strengthening”. Composites: B 2006; 37(7-8):650-61.
ACI 440R-07 (2007) Report on Fiber-Reinforced Polymer (FRP) Reinforcement for Concrete
Structures, ACI Committee 440, American Concrete Institute, Farmington Hills, MI, 100
pg.
ACI 440.2R-02, (2002). Guide for the Design and Construction of Externally Bonded FRP
Systems for Strengthening Concrete Structures, ACI, Farmington Hills, MI, 45 pg.
Aiello, M. A., Frigione, M., and Acierno, D (2002). "Effects of environmental conditions on
performance of polymeric adhesives for restoration of concrete structures", J. Mater. Civ.
Eng., 14, 185-189.
Au, C. and Buyukozturk, O (2006). "Peel and shear fracture characterization of debonding in
CFRP plated concrete affected by moisture", J. Compos. Constr., 10, 35-47.
Brena, S. F, Wood, S. L., and Kreger, M. (2002). “Fatigue Tests of Reinforced Concrete Beams
Strengthened Using Carbon Fiber Reinforced Polymer Composites”, Proceedings of the
Second International Conference on Durability of Fibre Reinforced Polymer Composites
for Construction, 575-586.
Chajes, M.J., Thomson, T.A., and Farschman, C.A. (1995). “Durability of Concrete Beams
Externally Reinforced with Composite Fabrics.” Construction and Building Materials,
9(3), 141-148
Chin, J. W., Haight, M. R., Hughes, W. L., and Nguyen, T. (1998). “Environmental Effects on
Composite Matrix Resins Used in Construction”, Proceedings of CDCC, 229-242
Chun, W,, and Karbhari, V. M., (2005) “Effect of Water Sorption on Performance of Pultruded
E-Glass/Vinylester Composites”, Journal of Materials in Civil Engineering, Vol. 17, No.
1, January/February, pp. 63-71
Deng, J. (2008) “Durability of Carbon Fiber Reinforced Polymer (CFRP) Repair/Strengthening
Concrete Beams”, PhD Dissertation, University of Wyoming.
El-Hawary, M., Al-Khaiat, H., and Fereig, S (2000). "Performance of epoxy-repaired concrete in
a marine environment", Cem. Concr. Res., 30, 259-266.
Gartner A.L. (2007), “Development of a Flexural Bond Strength Test to Determine
Environmental Degradation of Carbon Fiber-Reinforced Polymer (CFRP) Composites
Bonded to Concrete”, MS. Thesis, University of Florida.
42
Gheorghiu, C., Labossiere, P., and Proulx, J., (2005) “Fatigue and Monotonic Strength of RC
Beams Strengthened with CFRPs”. Composites Part A: Applied Science and
Manufacturing, May.
Grace N. F., and Singh, S. B., (2005). “Durability Evaluation of carbon Fiber-Reinforced
Polymer Strengthened Concrete Beams: Experimental Study and Design”. ACI Structural
Journal, Vol. 102, No. 1, January-February.
Haeberle, D. C., Staff, B.C., Lesko, J., and Riffle, J. S. (2002). “Effect on UV Aging on Strength
in Vinyl Ester Matrix Composites”, Proceedings of the Second International Conference
on Durability of Fibre Reinforced Polymer Composites for Construction, 273-284
Hayes, M.D., Garcia, K., Verghese, and Lesko, J.J. (1998). “The Effect of Moisture on the
Fatigue Behavior of a Glass/Vinyl Ester Composite” Fiber Composites in Infrastructure;
Proceeding of the Second International Conference on Composites in Infrastructure,
ICCI’98, Tucson, Arizona.
Hulatt, J., Holloway, L., and Thorne, A. (2002)."Preliminary investigations on the environmental
effects on new heavyweight fabrics for use in civil engineering", Composites: Part B,
33,407–414.
Karbhari V. M., And Abanilla M. A., (2006c), “Design Factors, Reliability, and Durability
Prediction of Wet Layup Carbon/Epoxy Composites Used in External Strengthening”.
Composites: B 2006; 37(7-8):650-61.
Karbhari, V. M., Engineer, M., Eckel, D. A. II (1997). “On the durability of composite
rehabilitation schemes for concrete: use of a peel test”, Journal of Materials Science, 32,
147-156.
Kitane, Y., Aref, A.J., and Lee, G. C., (2004), “Static and Fatigue Testing of Hybrid Fiber-
Reinforced Polymer-Concrete Bridge Superstructure”. Journal of Composites for
Construction, Vol. 8 No. 2, April 1.
Lefebvre, D. R., Takahashi, K. M., Muller, A. J. and Raju V. R. (1991). Degradation of epoxy
coatings in humid environments: the critical relative humidity for adhesion loss, J
Adhesion Sci. Technol., Vol. 5, No. 3, pp. 221-227.
Liao, K, Schultheisz, C.R., Hunston, D.L., and Brinson, L.C. (1998). “Long-term durability of
fiber-reinforced polymer-matrix composite materials for infrastructure applications: A
review.” Journal of Advanced Materials, 30(4), 3-40.
Malvar, L.J., Joshi, N.R., Beran, J.A. and Novison, T. (2003), Environmental Effects on the
Short-Term Bond of Carbon Fiber-Reinforced Polymer (CFRP) Composites, Journal of
Composites for Construction, February.
NCHRP Report 514, (2004), Bonded Repair and Retrofit of Concrete Structures Using FRP
Composites -- Recommended Construction Specifications and Process Control Manual.
NCHRP Report 609, (2008), Recommended Construction Specifications and Process Control
Manual for Repair and Retrofit of Concrete Structures Using Bonded FRP Composites.
Reifsnider, K.K., Schulte, K., and Duke, J. C., (1983). “Long-Term Fatigue Behavior of
Composite Materials” ASTM STP 813, Philadelphia, 1983. pp. 136-159.
43
Sen, R., Shahawy, M., Mullins, G., and Spain, J (1999). "Durability of carbon fiber-reinforced
polymer/epoxy/concrete bond in marine environment", ACI Struct. J., 96, 906-914.
Toutanji, H. A. and Gomez, W., (1997). "Durability characteristics of concrete beams externally
bonded with CFRP composite sheets", Cem. Concr. Compos., 19, 351-358.
Tu, L. and Kruger, D (1996). "Engineering properties of epoxy resins used as concrete
adhesives", ACI Mater. J., 93, 26-35.
Wan, B., Petrou, M.F., and Harries, K.A. (2006), The Effect of the Presence of Water on the
Durability of Bond between CFRP and Concrete, Journal of Reinforced Plastics and
Composites, Vol. 25, No.8.
Wolff, E.G. “Moisture Effects on Polymer Matrix Composites” SAMPE Journal, 1993, 29(3), pp
13-20
Zhou, J., and Lucas, J.P., (1998). Hygrothermal effects of epoxy resin. Part I: the nature of water
in epoxy, Polymer, Vol. 40, p. 5505-5512
44
Scope
a. This test method covers the determination of the durability strength reduction of carbon
fiber reinforced polymer (CFRP) composites bonded to concrete using a simply
supported beam specimen subjected to a three-point loading.
b. The values stated in inch-pound units are to be regarded as the standard.
c. This standard does not purport to address all of the safety concerns, if any, associated
with its use. It is the responsibility of the user of this standard to establish appropriate
safety and health practices and determine the applicability of regulatory limitations prior
to use.
Referenced Documents
AASHTO Standards:
T24-05 Test Method for Obtaining and Testing Drilled Cores and Sawed Beams of
Concrete
T231-05 Practice for Capping Cylindrical Concrete Specimens
T67-05 Practices for Force Verification of Testing Machines
ASTM Standards:
C 192 Practice for Making and Curing Concrete Test Specimens in the Laboratory
C 1077 Practice for Laboratories Testing Concrete and Concrete Aggregates for Use in
Construction and Criteria for Laboratory Evaluation
D 4541 Standard Test Method for Pull-off Strength of Coatings Using Portable Adhesion
Testers
45
b. The results of this test method may be used to determine the durability strength reduction
factor, for validating compliance with specifications, or as a basis for selection of a CFRP
system.
Specimens
The beam specimen shall be a 4 in. x 4 in. x 14 in. long plain concrete beam with a 12 in.
span length loaded at mid-span, Figure 20 below.
Note: A single reinforcing bar may be placed in the specimen to improve the specimen shear
performance. Reinforcement is not required typically for concrete strength above 7000 psi, but may
be needed for lower strength concrete. No reinforcement was included in the tests conducted in
development of this specification. Any reinforcement must be cut at mid-span.
A 3 in. x 3 in. end patch of CFRP may be applied to one end of the specimen for evaluating direct
tension adherence. Direct tension tests are not part of is standard.
14 in.
4 in.
0.1 in. sawcut
4 in.
2 in.
NOTE: Specimen may be 15 in. long with 1-1/2 in. inset from each end to the centerline of the
support.
Figure 20. Durability strength reduction test specimen
a. The test specimen concrete strength shall be either:
i. approximately the same as the proposed field application or,
ii. a range of strength from 4,500 psi to 10,500 psi in 2,000 psi increments.
b. Fabricate the test specimens in accordance with ASTM C 192
c. A minimum of 10 specimens shall be prepared for each concrete strength.
Note: Five specimens are used for the control strength and five for the deteriorated strength. If a decay
curve is desired, five additional specimens are required for each intermediate point. Intermediate points are
recommended at 7, 14 and 28 days.
46
d. Prepare three standard 4 in. x 8 in. or 6 in. x 12 in concrete cylinders at the same time as
the beam specimens.
e. Cure the specimen for a minimum of 28 days prior to application of CFRP.
Specimen Preparation
a. The specimen shall be rotated 90 degrees so the hand finished surface shall be the beam
side face.
The specimen shall be saw cut at mid-span to a depth of 2 in. The width of the saw cut
shall be approximately 0.1 in. and may be either a composite blade or a diamond blade.
The saw cut side becomes the tension face of the specimen. One end of the specimen and
the tension face are sandblasted to an ICRI profile minimum of 3.
b. Define the epoxy coverage rate in oz./sq. ft.
Note: Epoxy coverage rate may be determined by the manufacturer’s literature or preferably by test. The
epoxy coverage used in the test must be specified as the minimum coverage for field applications.
c. A 1 in. + 1/16 in. wide by 8 in. long wide strip of carbon fiber fabric laminate shall be
applied to the tension surface of the specimen following Specification for Mixing Epoxy
for Laboratory Specimens, the manufacturer’s recommendations, and NCHRP Report
514.
Note: Control specimens fail in the concrete substrate. An over width CFRP strip will raise the control
strength and result in a lower durability strength reduction factor for the exposed specimens.
d. Center the carbon fiber on the saw cut.
e. Should the manufacturer’s specification conflict with NCHRP Report 514, then NCHRP
Report 514 shall be used.
f. An optional direct tension strength test patch 3.5 in. square shall be applied to the sand
blasted end of the specimen following the manufacturer’s recommendations and NCHRP
Report 514.
Note: If direct tension tests are not specified, this step may be omitted.
47
Environmental Conditioning
Specimens shall be conditioned for either control, wet or air environment.
a. Control specimens: Cure at 68°F in air.
b. Wet Environment Conditioning: Specimens shall be submerged in water in insulated
chambers heated to 140°F + 5°F for 60 days.
c. Air Environment Conditioning
Place specimens on non-absorbent shelves in the wet conditioning chamber so no part of
the specimen shall be in direct contact with water to expose the specimen to 100%
relative humidity. Cure specimens at 140°F for 60 days.
48
c. All apparatus for making flexure tests of concrete shall be capable of maintaining the
specified span length and distances between load-applying blocks and support blocks
constant within ± 0.05 in.
d. If an apparatus similar to that illustrated in Figure 22 is used: the load-applying and
support blocks shall not be more than 2½ in. high, measured from the center or the axis of
pivot, and should extend entirely across or beyond the full width of the specimen. Each
case-hardened bearing surface in contact with the specimen shall not depart from a plane
by more than 0.002 in. and shall be a portion of a cylinder, the axis of which is
coincidental with either the axis of the rod or center of the ball, whichever the block is
pivoted upon. The angle subtended by the curved surface of each block should be at least
45 degrees (0.79 rad). The load-applying and support blocks shall be maintained in a
vertical position and in contact with the rod or ball by means of spring-loaded screws that
hold them in contact with the pivot rod or ball. The uppermost bearing plate and center
point ball in Figure 22 may be omitted when a spherically seated bearing block is used,
provided one rod and one ball are used as pivots for the upper load-applying blocks.
NOTE:-This apparatus may be used inverted. If the testing machine applies force through a
spherically seated head, the center pivot may be omitted, provided one load-applying block pivots
on a rod and the other on a ball.
Figure 22. Diagrammatic view of a suitable apparatus for flexure test of concrete by three-
point loading method
Testing
a. Test reference cylinders concurrent with control specimens.
b. The test specimen shall conform to all requirements of Practice C 192 applicable to beam
and prism specimens and shall have a test span within 2 % of being three times its depth
as tested. The sides of the specimen shall be at right angles with the top and bottom. All
surfaces shall be smooth and free of scars, indentations, holes, or inscribed identification
marks.
c. The technician performing the flexural strength test shall be certified as an ACI
Technician-Grade II, or by an equivalent written and performance test program.
49
NOTE:-The testing laboratory performing this test method may be evaluated in accordance with Practice
C 1077.
d. Bring the load-applying blocks in contact with the surface of the specimen at the half
point and apply a load of between 3 and 6 % of the estimated ultimate load. Using 0.004
in. and 0.015 in. leaf-type feeler gages, determine whether any gap between the specimen
and the load-applying or support blocks is greater or less than each of the gages over a
length of 1 in. or more. Grind, cap, or use neoprene shims on the specimen contact
surface to eliminate any gap in excess of 0.004 in. in width. Neoprene shims shall be of
uniform 1/4 in. thickness, 1 to 2 in. wide, and shall extend across the full width of the
specimen. Gaps in excess of 0.015 in. shall be eliminated only by capping or grinding.
Grinding of lateral surfaces should be minimized inasmuch as grinding may change the
physical characteristics of the specimens. Capping shall be in accordance with the
applicable sections of Practice C 617.
e. Apply the load at a rate that the specimen fails between 3 and 5 minutes after initiation of
load.
f. A load rate of between 100 and 170 lb/sec or a displacement rate of approximately 0.033
in/min results in failure in the specified time.
Note: A flexure-shear failure of the specimen beyond the limits of the CFRP constitutes an invalid test and
the strength from the invalid test shall be excluded from the test results.
50
Scope
a. This epoxy mixing method applies to bonding carbon fiber reinforced polymer (CFRP)
composites to plain concrete specimens by hand application in the laboratory. This
method can be used as a guideline for mixing epoxy for application to carbon fiber fabric.
b. The values stated in in-lb units are to be regarded as the standard.
c. This standard does not purport to address all of the safety concerns, if any, associated
with its use. It shall be the responsibility of the user of this standard to establish
appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
Referenced Documents
ASTM Standard C192 Practice for Making and Curing Concrete Test Specimens in the
Laboratory
NCHRP Report 514 Bonded Repair and Retrofit of Concrete Structures using FRP
Composites Recommended Construction Specifications and Process Control Manual
51
Premixing Part B
• Use the same mixing procedure from premixing Part A prepare the Part B component
52
Other Mixtures
a. If the CFRP system uses other primers, putties or sealers, repeat the premixing and
mixing steps for each component.
53