Code of Practice For Power System Protection

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Code of practice for power system protection

01. The entire wiring of circuitry for indications, alarms, metering and protection should be
permanent wiring.

02. The leads should be marked and identified by ferrules near terminals.

03. Every lead should end at a terminal point and no junction by twisting is allowed.

04. The wiring should be by copper leads for CT secondary for all cores i.e. metering cores as
well as protection cores and for PT secondary for protection core.

05. The wiring should be by copper leads. The copper lead for above should be stranded but
not single lead type.

06. Aluminium leads can be used for indication, alarms and PT secondary for metering but
stranded wires only are to be used. But copper leads are always preferable for these said
purposes.

07. The terminations should be lugged by ring shape O lugs. U shape lugs should be
avoided since U shape lugs may slip if terminal is loosened.

08. For CT Secondary terminations, two nuts with one spring washer and two flat washers to
be compulsorily used.

09. The CT terminal strips should be stud type with nuts and not screw-in-type.

10. Wherever two sets of batteries are available, the primary protection and back-up
protection should be from different batteries.

11. Where there is only one battery at an Electrical Power Substation, the primary and back-
up protections should be given D.C supply through two individual circuits with independent
fuses run from D.C bus.

12. When CBs have two trip coils, both main protection and backup protection will energize
both the trip coils.

13. D.C and A.C supplies should not be taken through different cores of the same cable.
Totally different cables should be used for DC and AC supplies.

14. Independent D.C cables should be run to each equipment in the yard and looping of D.C.
supply from one equipment to other is not permitted.

15. The D.C. emergency lighting in substation should be through independent cables and not
mixed up with protection and other circuitry.

Prepared By: Vinit J


16. Standard colour codes for wires in control circuit of different sizes should be as follows:

PURPOSE SIZE COLOR


Indication, Alarm, trip, close etc 1.5 mm2 Gray
2
Red Phase Metering PT Circuit 1.5 mm Red
2
Yellow Phase Metering PT Circuit 1.5 mm Yellow
Blue Phase Metering PT Circuit 1.5 mm2 Blue
2
Red Phase Protection PT Circuit 2.5 mm Red
2
Yellow Phase Protection PT Circuit 2.5 mm Yellow
2
Blue Phase Protection PT Circuit 2.5 mm Blue
2
Red Phase Metering and Protection CT Circuit 2.5 mm Red
Yellow Phase Metering and Protection CT Circuit 2.5 mm2 Yellow
2
Blue Phase Metering and Protection CT Circuit 2.5 mm Blue
2
Phase for auxiliary AC supply 2.5 mm Red
Neutral for auxiliary AC supply 2.5 mm2 Black
2
Common star point of CTs 2.5 mm Black
2
Common star point of Protection PTs 2.5 mm Black
2
Common star point of Metering PTs 2.5 mm Black
2
Earthing Connection 2.5 mm Green

17. The lead numbers are also standardized as follows so that anyone can easily identify the
purpose for which the lead is connected:

ALPHABET SERIES PURPOSE EXAMPLE


J Series D.C. Incoming J1, J2, etc.
K Series Control Closing, Tripping, etc. K1, K2, K3 etc.
L Series Alarms, indications and annunciations L1, L2, L3, etc.
M Series Motor Circuit M1, M2, etc.
E Series Potential transformer secondary E1, E2, E3, etc.
H Series LT A.C. Supply H1, H2, H3, etc.
A Series C.T. secondary for special protection A1, A2, A3, etc.
B Series Bus bar protection B1, B2, B3, etc.
C Series Protection Circuits C1, C2, C3, etc.
D Series Metering Circuit D1, D2, D3, etc.

Prepared By: Vinit J


18. The CT ratios available and adopted with number of cores shall be displayed on each
panel as follows: 400 200 100 / 1-1-1.

19. Wherever CT cores are not used SHORTING LOOPS should be provided in CT secondary
terminals and not in marshalling boxes or at panels.

20. The Cable entries in the equipment, marshalling boxes and panels should be through
appropriate size of cable glands. No other means are allowed.

21. Standard lead numbers used in control circuit of protection of power system:

Certain lead numbers are standardized as follows and should be compulsorily adopted with
ferrules at terminations of leads.

Main DC Positive supply J1

Main DC Negative supply J2

DC Positive bus inside panel K1

DC Negative bus inside panel K2

Metering CT secondaries D11, D31, D51, D71 etc.

Protection CT secondaries C11, C31, C51, C71 etc.

Special Protection CT secondaries A11, A31, A51, A71 etc.

PT secondaries E11, E31, E51, E71 etc.

Prepared By: Vinit J

You might also like