This document defines Modbus RTU data points and configuration properties for the Tracer UC800 controller. It includes information about baud rate, parity, supported character sets, and descriptions of data points for CenTraVac equipment. Tables list holding registers that are read/write and input registers that are read only, including the register name, number, type, value, and valid range for each point.

Uploaded by

carlos alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
685 views4 pages

Modbus Point List

This document defines Modbus RTU data points and configuration properties for the Tracer UC800 controller. It includes information about baud rate, parity, supported character sets, and descriptions of data points for CenTraVac equipment. Tables list holding registers that are read/write and input registers that are read only, including the register name, number, type, value, and valid range for each point.

Uploaded by

carlos alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Modbus RTU Data Points and Configuration Property Definitions

Modbus RTU Data Points and Configuration Property


Definitions
The Tracer UC800 controller is an equipment unit controller which provides the equipment system
sequences and performs closed-loop control. In addition, the UC800 integrates with Modbus
systems and devices using Modbus RTU protocol. This section includes information about:
Baud rate, parity, and supported character sets
Data points descriptions and configurations; CenTraVac and Duplex CenTraVac

Protocol: Baud Rate, Parity, and Supported Character Sets

Baud Rate
300, 1200, 2400, 4800, 9600, 19200 (default), 38400, 57600 or 115200

Parity
Even (default) or None

Stop Bits
One (default) or two.

CenTraVac Data Points Descriptions/Configurations

Holding RegistersRead/Write (Sorted by Register)


This function code is used to read the contents of a contiguous block of holding registers in a
remote device.
Table 14. Holding Registers
Register
Register Object Name Register Register Type Value Valid Range
BAS Chiller Auto Stop Command 40001 Binary 0,1
BAS Chiller Mode Command 40002 Enumeration 0=cool; 1=heat; 0 to 3
2=ice; 3=free
cool;
BAS Chilled Water Setpoint 40003 Temperature -17.78C to 23.9C/0F to 75F (depending
on installed options)
BAS Current Limit Setpoint 40004 Percent 0100
BAS Hot Water Setpoint 40005 Temperature 26.7C to 60C/80F to 140F
BAS Base Loading Setpoint 40006 Percent 0100
BAS Base Loading Enable 40007 Binary 0,1
BAS Diagnostic Reset 40008 Binary 0,1
Evaporator Pump Override 40009 Binary 0,1
Condenser Pump Override 40010 Binary 0,1

50 BAS-SVP01M-EN
Modbus RTU Data Points and Configuration Property Definitions

Input RegistersRead Only (Sorted by Register)


This function code is used to read from 1 to 125 contiguous input registers in a remote device.

Table 15. Input Registers


Register Object Name(a) Register Register Type(b) Register Value
Software Type 30001 NA 448=CTV
Software Revision 30002 NA
Chiller Running 30003 Binary
Average Line Current 30004 Percent
Active Current Limit Setpoint 30005 Percent
Active Base Loading Setpoint 30006 Percent
Starter Power Consumption 30007 Power
Calculated Chiller Capacity 30008 Power
Approx Unit Heating Power 30009 Power
Active Cool/Heat Setpoint Temperature 30010 Temperature
Evap Leaving Water Temp 30011 Temperature
Evap Entering Water Temp 30012 Temperature
Cond Entering Water Temp 30013 Temperature
Cond Leaving Water Temp 30014 Temperature
Evaporator Pump Control 30015 Binary
Evaporator Water Flow 30016 Binary
Approx Evap Water Flow 30017 Flow, Water
Evap Differential Wtr Press 30018 Pressure
Condenser Pump Control 30019 Binary
Condenser Water Flow 30020 Binary
Approx Cond Water Flow 30021 Flow, Water
Cond Differential Wtr Press 30022 Pressure
Second Condenser Ent Wtr Temp 30023 Temperature
Second Condenser Lvg Wtr Temp 30024 Temperature
Last Diagnostic Code 30025 Enumeration See footnote (c)
0=off/idle (auto); 1=starting; 2=running;
Chiller Running Status 30026 Enumeration
3=stopping
Chiller Control Mode 30027 Enumeration 0=cool; 1=heat; 2=ice; 3=free cool
0=BAS+external+local; 1=external+local;
Setpoint Source 30028 Enumeration
2=local
Active Chilled Water Setpoint Source 30029 Enumeration 0=front panel; 1=external; 3=BAS
Active Current Limit Setpoint Source 30030 Enumeration 0=front panel; 1=external; 2=ice making; 3=BAS
Active Hot Water Setpoint Source 30031 Enumeration 0=front panel; 1=external; 3=BAS
Active Base Loading Setpoint Source 30032 Enumeration 0=front panel; 1=external; 3=BAS
Front Panel Auto/Stop 30033 Binary
Front Panel Chiller Control Mode 30034 Enumeration 0=cool; 1=heat; 2=ice; 3=free cool
Front Panel Chilled Water Setpt 30035 Temperature
Front Panel Current Limit Setpoint 30036 Percent
Front Panel Hot Water Setpt 30037 Temperature
Front Panel Base Loading Setpt 30038 Percent
Front Panel Base Loading Command 30039 Binary
External Auto Stop 30040 Binary
Ext Chilled Wtr Setpt 30041 Temperature
Ext Current Limit Setpt 30042 Percent
Ext Base Loading Setpt 30043 Percent
Emergency Stop 30044 Binary
Manual Override Exists 30045 Binary
Base Loading 30046 Binary
Alarm Present 30047 Binary
Chiller In Auto 30048 Binary

BAS-SVP01M-EN 51
Modbus RTU Data Points and Configuration Property Definitions

Table 15. Input Registers (continued)


Register Object Name(a) Register Register Type(b) Register Value
Local Setpoint Control 30049 Binary
Maximum Capacity Relay 30050 Binary
Limit Mode Relay Status 30051 Binary
Head Relief Request Relay 30052 Binary
Hot Gas Bypass 30053 Binary
Refrigerant Monitor 30054 Concentration ppm (invalid on warning)
Compressor Running 30055 Binary
Evap Rfgt Pressure 30056 Pressure
Condenser Rfgt Pressure 30057 Pressure
30058,
Differential Refrigerant Pressure Pressure
30121
Lube Pump Suction Pressure 30059 Pressure
Oil Tank Pressure 30059 Pressure
Lube Pump Discharge Pressure 30060 Pressure
Oil Pump Discharge Pressure 30060 Pressure
30061,
Lube Pump Suction Pressure Pressure
30122
30061,
Oil Differential Pressure Pressure
30122
Oil Tank Temperature 30062 Temperature
Evap Sat Rfgt Temp 30063 Temperature
Cond Sat Rfgt Temp 30064 Temperature
Compressor Refrigerant Discharge Temperature 30065 Temperature
IGV1 Position 30066 Percent
IGV2 Position 30067 Percent
Purge Compressor Relay 30068 Binary
Pumpout Relay 30069 Binary
Purge Regen Valve Solenoid 30070 Binary
Carbon Tank Temp 30071 Temperature
Purge Liquid Temp 30072 Temperature
Purge Rfgt Cprs Suction Temp 30073 Temperature
Time Until Next Purge Run 30074 Time Interval
30075 (continued)
Pumpout Chiller On-7 Days 30076 Time Interval
30077 (continued)
Pumpout Chiller Off-7 Days 30078 Time Interval
30079 (continued)
Daily Pumpout-24 Hours 30080 Time Interval
30081 (continued)
Pumpout-Life 30082 Time Interval
30083 (continued)
Refrigeration-Life 30084 Time Interval
30085 (continued)
Compressor Starts 30086 Count
30087 (continued)
Compressor Running Time 30088 Time Interval
30089 (continued)
Starter Voltage Phase AB 30090 Voltage
Starter Voltage Phase BC 30091 Voltage
Starter Voltage Phase CA 30092 Voltage
Starter Average Phase Voltage 30093 Voltage
Starter Current L1 30094 Current
Starter Current L2 30095 Current
Starter Current L3 30096 Current

52 BAS-SVP01M-EN
Modbus RTU Data Points and Configuration Property Definitions

Table 15. Input Registers (continued)


Register Object Name(a) Register Register Type(b) Register Value
Average Starter Phase Current 30097 Current
Starter Current L1 30098 Percent
Starter Current L2 30099 Percent
Starter Current L3 30100 Percent
Average Starter Phase Current 30101 Percent
Power 30102 Power
Starter Load Power Factor 30103 Power Factor
Inboard Bearing Temp 30104 Temperature
Outboard Bearing Temp 30105 Temperature
Motor Winding Temp #1 30106 Temperature
Motor Winding Temp #2 30107 Temperature
Motor Winding Temp #3 30108 Temperature
Frequency 30109 Frequency
AFD Transistor Temp 30110 Temperature
AFD Input Frequency 30111 Frequency
AFD Average Input Current 30112 Current
AFD Output Voltage 30113 Voltage
AFD Input Current L1 30114 Current
AFD Input Current L2 30115 Current
AFD Input Current L3 30116 Current
AFD Inverter Base Temperature 30118 Temperature
AFD Rectifier Base Temperature 30119 Temperature
AFD Output Power 30120 Power
Differential Refrigerant Pressure 30121 Differential Pressure
Oil Differential Pressure 30122 Differential Pressure
AFD Motor Voltage U 30123 Voltage
AFD Motor Voltage V 30124 Voltage
AFD Motor Voltage W 30125 Voltage
AFD IGBT Temperature U 30126 Temperature
AFD Percent RLA Ripple 30127 Temperature
AFD IGBT Temperature V 30128 Temperature
DC Bus Voltage 30129 Percent
AFD IGBT Temperature W 30130 Voltage
Outboard Bearing Pad Temperature 1 30131 Temperature
Outboard Bearing Pad Temperature 2 30132 Temperature
Outboard Bearing Pad Temperature 3 30133 Temperature
(a) Many data points require installing certain options. Registers will read NULL if the option is not installed. For more details, refer to Diagnostic Descriptions,
Troubleshooting Tables, and Control Component Overview Diagnostic Manual listed under Additional Resources, p. 81.
(b) Refer to the Determining Input Register Type table below.
(c) Refer to the Diagnostic Codes and Descriptions listing below.

BAS-SVP01M-EN 53