Kumar
Kumar
Kumar
Contents
1 Product overview 5
Indices 185
POWER DISTRIBUTION COMPONENTS PG01414001U March 2015 3
4 POWER DISTRIBUTION COMPONENTS PG01414001U March 2015
Product overview
1
IP3X robust steel enclosure Modern, curved full door, covers all devices
to suit all applications
Gland plate
4 x screws, nuts
and washers
provided
Covers fit within enclosure dimensions
allowing adjacent mounting
Cable trunking interface kit fitting diagram Cable trunking interface kit available
Type B TPN standard distribution boards Incoming devices 125A standard TPN board
The optimised design for 125A TPN applications provides a The most popular choice will be the 125A switch disconnector
choice of boards in sizes 4, 6, 8, 12, 18 and 24 TP ways. 12, incomer option, but other choices include a 4-pole TPSN, 2P
18 & 24 TP way variants are also suitable for 250A applications, SPSN, a range of RCCB switches and a contactor controlled
where the number of MCB ways could require a larger supply incomer with switch disconnector for remote control of
current rating. A choice of incomers are available to suit different the supply to the board. A direct connection option is also
applications including RCCB options and a single phasing available for applications that do not require local isolation.
kit to provide a large single phase board arrangement.
18 22 + 2
24
440mm 440mm
200A TPN type B distribution board, with Metering solutions type A metered boards
integrated split meter for power/lighting
Type A SPN boards with integrated meter.
TPN distribution board with smart Split load versions utilise a two channel
meter for power and lighting loads. meter, feeding two independent busbars
Unique meter design calculates net values and groups of MCB/RCBOs.
for each busbar section and total board load. Split load versions provide independent
Meter has both Pulsed and monitoring of Power and
Modbus outputs as standard. Lighting loads and total load.
Embedded vt technology and RJ 11 Aids compliance with Part L2 of the
connections at meter minimises visible wiring. Building Regulations (England & Wales).
Supplied complete with factory fitted 200A See page 127 for dimensions.
Switch Disconnector incomer switch.
Suitable for TPN and SPN applications
as supplied (shorting link included). Metering solutions type B
meter pack assemblies
Increased earthing options
supplied as standard. Eatons Memshield 3 meter packs provide
simple integration with matched aesthetics.
Split metering for separate small power and
lighting has been added to the range to meet
The feature packed Eaton the needs of the L2 Regulations introduced in
meter packs and boards England and Wales in 2006. The meters provide
a pulsed output for kWh and display other
To meet the needs of part L2 of the Building useful parameters, including line voltage and
Regulations introduced in England and Wales in current. Modbus versions are also available
2006, Eatons Memshield 3 meter packs provide and provide remote access to additional
simple integration with matched aesthetics. The electrical parameters. For details refer to
EBMMPCT250 employs a multi-function, DIN rail page 36. For dimensions refer to page 127.
mounted meter to measure electrical parameters
on LV supplies to TPN distribution boards. It can
also be used to meter single-phase loads. The
unit is supplied complete with CTs and wiring
terminals. This version is suitable for 100A250A
applications and as well as a pulsed output
for kWh, the meter can be used to monitor
other parameters, including line voltage and
current. Electrical connection to the associated
distribution board does not occupy any of the
outgoing circuits. Modbus and MID certified
meter versions are also available see page 36.
The EBMMPDC120 is supplied as a 120A direct
connection solution, not requiring CTs. Cabling
is simple and the meter provides a pulsed
output for kWh. The meter is an MID certified
unit, providing clear kWh information.
Double meter pack for two standard TPN
distribution boards facilitate separate
monitoring of small power and
lighting from one main supply.
For single phase EAM boards, a 65A meter
pack provides simple integration. (Amps, kW,
kWh, kVar and kVarh pulsed output, MID
compliant. See page 32 for single phase
EAM boards with factory fitted meters,
including split power and lighting boards.)
Benefits
Easily programmable on front of device.
Computer aided programming software available.
Compact 18 mm design for restricted space opportunities.
Separate IP40 covers are available for direct wall mounting.
High level of accuracy.
Automatic summer and winter time adjustment.
Holiday & Random program settings.
High power reserve up to 10 years.
Notes: 1) Automatic calculation of sunrise and sunset times throughout the year, including the possibility of astro times + / -2 hour shift.
2) The DCF-signal can only be received within a 1000 km radius.
Technical characteristics
Designed according to IEC 60947-4-1 and IEC 61095 standards.
Suitable for applications in general control, heating & lighting applications.
Available in 20, 25, 40 & 63 A ratings with up to 4-pole contacts.
Optional add-on auxiliary contact available.
DIN modular profile.
Spacers available to extend lifetime (it is recommended to use 1 spacer between every 2 contactors installed).
Day/night contactors available with manual override function.
Surge protection devices (SPD) for MCB distribution boards and MCCB panelboards
In order to enable designers, specifiers, and installers to comply with surge protection requirements
in BS 7671 - IET Wiring Regulations - 17th Edition (Section 534), Eaton has a combined lightning
current and surge arrester, as well as an individual surge arrester to provide a coordinated
solution for lightning protection and surge suppression fully tested to BS EN 62305. This range of
coordinated enclosed kits provides peace of mind that all equipment has comprehensive transient
overvoltage protection caused by lightning strokes and switching in low voltage systems.
Enclosures
Surface-mounting enclosures comprise heavy gauge steel body plates incorporating cast iron
frame members and are rustprotected, with a light grey paint finish (RAL7004). Front access
doors, which are detachable, are fitted with dust-excluding gaskets and are interlocked to
prevent opening when the switch is on. The interlock can be defeated by a competent person
for maintenance purposes. Operating handles may be locked in both the on and off positions.
Castell type interlocks can be supplied to special order. Internal fixing holes allow units to
be mounted closely side by side and all models have removable top and bottom end plates.
These are pierced for connections, divided into front and rear (fixed) portions to simplify cabling
using Eatons MEM series split-type cable boxes, and provided with undrilled cover plates.
Fuses
Glasgow units are designed for use with HRC cartridge fuse links to BS88: Part 2. 63A and 100A
units employ off-set contact fuse links. Details of suitable types of HRC cartridge fuse links are
listed on page 101. All performance tests have been carried out using Eaton BS88 fuselinks.
Motor ratings
The motor ratings assigned to TPN switch-disconnector units are utilisation category AC23A
(frequent operation) to BS EN 60947-3, which calls for make and break testing at 10 and 8
times rated current respectively for units having a motor rating up to and including 100 Amps.
Ratings for switch-disconnector-fuses are dependent on suitable HRC fuses being fitted.
Auxiliary equipment
A comprehensive range of extension boxes and spreader boxes is available. Units are
fitted with HRC Fuselinks of maximum rating but will accept fuselinks of a lower rating,
refer to the Paramount HRC Fuselinks section on page 101. SPSN and TPSN indicate
switched neutral. Neutral makes first and breaks last. If DP fuse-switch-disconnectors are
required, use SPSN and replace the supplied switch link with a compatible fuselink.
Spreader boxes
Cast metal split pattern, supplied with fixing bolts and plain bushes. Two types are available,
suitable for straight or angled entry. They permit conductor spreading of larger PVC cables
and fit directly on to Glasgow fuse-switch-disconnectors and switch-disconnectors.
Busbar chambers
These are produced in 100, 200, 400, 630 and 800 Amp. ratings and in four nominal lengths.
100, 200 and 400 Amp units are available in all four sizes; 630 and 800 Amp ratings are offered in
the three longest units only. All units in the range share the same height and depth dimensions.
Similarly the twin busbars are located in precisely the same positions throughout the range and
vary in size only in their front-to-back dimensions according to rating. Detachable end plates enable
all units to be extended by coupling to a second busbar chamber using extension sets. Both top
and bottom plates are also readily detachable so that marking out and machining can be carried out
conveniently on a bench to accommodate Eatons switchgear either above or below the chamber.
Complete mounting kits, including templates, are available for mounting all Exel and Glasgow
switchgear. Eaton chambers are fabricated from rust-protected sheet steel with a light grey paint
finish. They have been type tested to BS EN 61439 with a rated conditional short circuit current
rating of 63kA at Ue 550V and a rated short-time withstand current Icw 20 times nominal rated
current for one second. They are designed for use in factory-built assemblies to BS EN 61439. All
chambers are subjected to an on-line dielectric test unit which provides a high voltage test between
poles; and from poles to earth. Earth continuity is also tested. Rated insulation voltage 660V.
Motor ratings
The motor ratings assigned to TPN switch-disconnector units are utilisation category AC23A
(frequent operation) to BS EN 60947-3, which calls for make and break testing at 10 and 8
times rated current respectively for units having a motor rating up to and including 100 Amps.
Ratings for switch-disconnector-fuses are dependent on suitable HRC fuses being fitted.
Cable size
Maximum cable sizes are: 20A6mm2, 32A10mm2, 63A35mm2, 100/125A70mm2.
Rotary isolators
Changeover switches
Safety carriers
A range of safety carriers are available for insertion in a fusebase when its normal
fuse carrier has been removed for isolation. The safety carriers are marked
yellow for identification and have no provision for fuselink fixing.
Enclosures
Rust protected sheet steel IP4X enclosures have a light grey paint finish and are fitted with internal
fixing holes. Enclosures have a robust, reliable construction. Enclosures for units from 20A to
100A are of all welded construction, 200A IP4X units have cast corner pieces. Removable top
and bottom endplates incorporate knockouts on 20A and 32A units while 63200A boards have
blank endplates. Blank endplates are available on request for 20A and 32A boards. The enclosure
allows gasketed access doors to be reversed for left hand or right hand opening. All sides are
free from external projections and fuseboards can be mounted in inverted form if required.
Main terminations
32A, 2-way fuseboards have the main phase termination (tunnel type) attached to the fusebanks.
All other fuseboards have the main terminations mounted on the back of the enclosure and are
intended for use with cable sockets (sweating or crimp type) which are not provided. Busbar
and main terminals are fully shrouded. A cable shroud to cover the cable socket is provided.
Eatons wide range of Motor Control Gear and Heating and Lighting Control
equipment is an integral part of our single source commitment.
Since the late 1920s we have built countless motor starters, fitted and trusted by generations of
contractors, while the increasing requirements of our markets have led us to constantly update and
expand our ADS range to allow for an increased choice of current ratings and ingress protection.
This wealth of experience and expertise in the design and manufacture of Motor Control Gear is
mirrored by our Heating and Lighting range which offers a versatile and comprehensive choice.
Standards
IEC 60947-4-1
VDE 0660
IEC 60269
BS EN 60947-4-1
Enclosures moulded
9kW DOL max
Tough polycarbonate in grey provides high IP protection to IP65
Start and stop pushbuttons
Internal earth terminals
Cable entries 20mm knockouts for M20 threaded glands
Enclosures metalclad
Attractively styled rust protected pressed steel finished in grey polyester powder paint
Start and mushroom-headed stop pushbuttons
Substantial earth terminal
Cable entries 20mm knockouts for M20 threaded glands
Switch-disconnectors
Means of isolation and switching for mechanical maintenance
Padlocking facility available
Isolators type tested for on-load disconnection
Interlocked with main cover
Overload relays
Adjustable thermal pattern connected directly to contactor
Ambient temperature compensated between -40C to +60C
Phase failure sensitive relays
Changeover trip contact
Simple Auto-reset
Contactors
Modern block type
615 x 106 mechanical and 1.5 x 106 electrical operations AC3 duty.
Provisions for fitting additional auxiliary contacts either N/O or N/C depending on version
Open contactors
18A, 25A and 32A, 4-pole, with optional auxiliary contacts
Enclosed contactors
25A and 40A, 4-pole; 40A and 64A, 2-pole; 70A and 112A, single pole with fitted neutral link
Robust pressed steel enclosures, rust protected with grey paint finish
220240V units available with or without rectifiers for silent running
90-225A, 3-pole enclosed contactors can be supplied with switch-
disconnector-fuse including HRC main fuses
What do I have to do to save money? Our engineers will be pleased to check this for you.
Protection system
Each element is fitted with a protection system which ensures an
extended capacitor life and complete end of life safety.
Elements are self healing and have an over pressure double pole automatic
disconnect feature that ensures that if the element fails it is electrically safe.
Capacitor features
Low loss less than 0.5 Watts per kvar, including discharge resistors.
Environmentally safe The dry type construction eliminates flammable
impregnants and does not cause leakage or pollution problems.
Protection system
Each element is fitted with a protection system which ensures an
extended capacitor life and complete end of life safety.
Elements are self healing and have an over pressure double pole automatic
disconnect feature that ensures that if the element fails it is electrically safe.
Capacitor features
Low loss less than 0.5 Watts per kvar, including discharge resistors.
Environmentally safe The dry type construction eliminates flammable
impregnants and does not cause leakage or pollution problems.
Cubicle construction
Each Eaton capacitors 300 cubicle can house up to 300 kvar of capacitors
switched in stages of 25 to 100 kvar dependent upon requirements.
The control equipment comprises:
Set of DIN removable fuses and carriers per 1 or 2 switching stages.
Suitably rated contactor per switching stage.
Hand/Off/Auto selector switch per switching stage when required.
Capacitor Energised indication lamp per switching stage when required.
Set of control fuses.
The cubicle has throughgoing busbars and all internal wiring and
interconnections. Control wiring is clearly labelled.
All switching stages are clearly numbered and the panel is
complete with all necessary information labels.
Cubicle construction
Each Eaton capacitors 300 cubicle can house up to 250 kvar of
capacitors switched in stages of 25 to 100 kvar dependent
upon requirements.
Reactor details:
Aluminium or Copper windings (on request, dependant on customer specification).
Low losses.
Low noise.
High overloading capacity.
7% de-tuning factor as standard, others available on request.
189Hz as standard.
EAMMP65 Metered SPN, type A distribution boards & standard meter packs
Type A SPN boards, fitted with multifunction meters, can display; Amps, kW, kWh, kVar
and kVarh pulsed output etc.
Split load versions utilise a two channel meter, feeding two independent busbars and groups of MCB/RCBOs
Split load versions provide independent monitoring of Power and Lighting loads and total load.
Aids compliance with Part L2 of the building regulations (England & Wales and Section 6 Scotland)
IP3X
Description Rating Total no. of Installed meter, Eaton list
(A) outgoing ways characteristics3) number
Meterpack for SPN, type A distribution boards 65 Pulsed output, kWh EAMMP65
9 way SPN, type A distribution board1) 65 9 Pulsed output, kWh EAM9M
9 way SPN, type A distribution board1) 65 9 Modbus EAM9MB
12 way SPN, type A distribution board1) 65 12 Pulsed output, kWh EAM12M
12 way SPN, type A distribution board1) 65 12 Modbus EAM12MB
Split metered SPN, type A distribution board1), 2) 100 9 + 3 Pulsed output, kWh EAMSL93M
Split metered SPN, type A distribution board1), 2) 100 9 + 3 Modbus EAMSL93MB
Split metered SPN, type A distribution board1), 2) 100 6 + 6 Pulsed output, kWh EAMSL66M
Split metered SPN, type A distribution board1), 2) 100 6 + 6 Modbus EAMSL66MB
1) Includes factory fitted switch disconnector and single channel meter
2) Includes two channel meter, 65A max load per channel
3) Output type is Pulsed or Modbus
EMCH116R30C Outgoing devices, RCBOs single pole trip type C 30mA sensitivity
Eatons range of residual current circuit breakers with integral overload protection (RCBOs), are manufactured to IEC/
EN 61009 and meet the latest European and international standards.
For other RCBO sensitivity options refer to full details on page 49.
Description Rating Trip type Sensitivity Eaton list
(A) (mA) number
EMBH116R30C Outgoing devices, RCBOs single pole trip type B 30mA sensitivity
Description Rating Trip type Sensitivity Eaton list
(A) (mA) number
Meterpack for TPN, type B distribution boards 250 Pulsed output, kWh EBMMPCT250
Meterpack for TPN, type B distribution boards 250 Modbus + pulsed output, kWh EBMMPCT250M
Meterpack for TPN, type B distribution boards 250 MID certified meter EBMMPCT250MID
Double meterpack for 2 x TPN, type B distribution boards 250 Pulsed output, kWh EBMMPSL250
Double meterpack for 2 x TPN, type B distribution boards 250 Modbus + pulsed output, kWh EBMMPSL250M
Double meterpack for 2 x TPN, type B distribution boards 125 Pulsed output, kWh EBMMPSL125
Double meterpack for 2 x TPN, type B distribution boards 125 Modbus + pulsed output, kWh EBMMPSL125M
Meterpack for TPN, type B distribution boards 120 MID certified meter EBMMPDC120
EBMSL642MB Split metered power and lighting board 200A TPN, type B
Includes factory fitted 200A switch disconnector and two channel meter
Adequate integral cabling space means that no extension box is required.
IP4X
Meter has both pulsed and Modbus outputs as standard.
Fitted with door lock as standard.
Single phasing kit included to be used if required
Description Rating Total no. of Installed meter, Eaton list
(A) outgoing ways characteristics number
Split metered TPN, type B distribution board 200 6+4 Modbus + pulsed output, kWh EBMSL642MPMB
Split metered TPN, type B distribution board 200 8+6 Modbus + pulsed output, kWh EBMSL862MPMB
Split metered TPN, type B distribution board 200 10+8 Modbus + pulsed output, kWh EBMSL1082MPMB
Split metered TPN, type B distribution board 200 14+10 Modbus + pulsed output, kWh EBMSL14102MPMB
Enclosed surge protection kit for TPN boards type 1&2 EM3SSK3T12
Enclosed surge protection kit for TPN boards type 2 EM3SSK3T2
EMCS1100 Outgoing devices (for 250A high load distribution board only) MCBs, single pole
Rated current Width Short circuit rating Eaton list number
In (A) (mm) (IEC/EN 60947-2) Trip type B Trip type C Trip type D
EMCS3125 Outgoing devices (for 250A high load distribution board only) MCBs, three pole
Rated current Width Short circuit rating Eaton list number
In (A) (mm) (IEC/EN 60947-2) Trip type B Trip type C Trip type D
EMCH116R30C Outgoing devices, RCBOs single pole trip type C 30mA sensitivity
Eatons range of residual current circuit breakers with integral overload protection (RCBOs), are manufactured to IEC/
EN 61009 and meet the latest European and international standards.
For other RCBO sensitivity options refer to full details on page 49.
Description Rating Trip type Sensitivity Eaton list
(A) (mA) number
EMBH116R30C Outgoing devices, RCBOs single pole trip type B 30mA sensitivity
Description Rating Trip type Sensitivity Eaton list
(A) (mA) number
Interiors & incoming devices for single phase and three phase Technical characteristics
Eaton MCB pan assemblies offer a high degree of flexibility for Eaton MCB pan assemblies are suitable for
custom applications. SPN types are available with 4, 7, 10, 13, and inclusion in other factory built assemblies and as
16 ways. TPN types are available with 4, 6, 8, 12,18 and 24 ways. replacements for distribution board interiors.
MCB pan assemblies feature fully shrouded busbars.
See pages 129 -130 for the technical details of Eaton MCB pan assemblies.
EAMP10 125A SPN type A pan assemblies with earth & neutral bars
Description Rating Total no. of Eaton list
(A) outgoing ways number
EBMP61 125A/250A TPN type B pan assemblies with earth & neutral bars
Description Rating Total no. of Eaton list
(A) outgoing ways number
3.3 RESIDUAL CURRENT CIRCUIT BREAKER WITH OVERCURRENT PROTECTION (RCBOs) .................................................. 49
MCBs are available in current ratings from 1A63A, with trip types B, C and D, 10kA to IEC 60898 and 15kA to IEC 60947-2
See page 135 for technical data and overall dimensions
EMBH125N Miniature circuit breakers dual rated 10/15kA, single pole + neutral
Description Rated Width Short circuit Eaton list number
current (A) (mm) rating (kA) Trip type B Trip type C Trip type D
Universal device lockout attachment fits MCBs, RCCBs and RCBOs ASPDL
Lockout attachment for 27mm MCBs ASPDL27
Padlock PD2
Technical characteristics
This auxiliary switch allows remote indication of the position of the MCB contacts.
Auxiliary and Alarm contact ratings:
AC14 240 Vac 50Hz, 6A.
DC14 125 Vdc, 1A.
The auxiliary contact will not differentiate between an MCB that is off or tripped.
The auxiliary contact can be used in conjunction with a remote supply and signal lamps, bells or buzzers.
Description Quantity Eaton list
per carton number
Technical characteristics
Suitable for all Eaton MCBs including those with either auxiliary or alarm contacts.
A shunt trip and undervoltage release can be fitted together on one MCB.
Each is incorporated in a 1 module (18 mm) casing with terminals protected to IP 20 capable of accepting
cable up to 2.5 mm2.
The shunt trip and UVR are simply clipped to the left hand side of an MCB and have terminals at one end to allow
connection to pan assemblies and comb busbar.
A shunt release provides remote trippping of an MCB with three voltage options for AC & DC applications.
Description dc characteristics ac characteristics Quantity Eaton list
per carton number
4.2 CONTACTORS
4.3 TRANSFORMERS AND EARTH LEAKAGE RELAYS
The Eaton range comprises of a wide variety of different or GPS signal reception .
2)
device itself. 1)
O
Automatic
High powercalculation
reserve upoftosunrise and sunset times throughout
10 years.
Twilight Switches are supplied with a remote light sensor, which the year, including the possibility of astro times + / -2 hour shift.
Notes:
can be easily installed on the outside wall where the required 1)
2) Automatic
The calculation
DCF-signal of sunrise
can only and sunset
be received within times throughout
a 1000 km radius.
the year, including the possibility of astro times + / -2 hour shift.
light intensity threshold can be simply adjusted on the modular
device itself. 2)
The DCF-signal can only be received within a 1000 km radius.
Universal declaration
Universal declaration type
type coding
coding
Type coding - digital switches and accessories Type coding - twilight switches
TS A DCF SR S D 1NO -
TS A GPSKIT SR S W 1NO -
TS A MEMKIT SR C D 1CO -
TS A MEM SR S D 1CO W
TS =
Switch SR = Twilight switch
A =
Accessory S/C = With or without sensor
DCF =
DCF-antenna D/W = DIN rail mounting / surface mounting
GPSKIT =
Antenna for GPS signal reception including 1NO / 1CO = Create / change (contact configuration)
power supply W = Wide adjustable sensitivity (2 - 50000 lux)
MEMKIT = Programming software kit
MEM = iMemory
Quartz,
Week DCF / GPS 1 CO 10 year 1 sec. 84 35.8 mm TSDW1CODG 1 167382
Quartz with
Week astronomical 1 CO 10 year 1 min. 56 35.8 mm TSDW1COA 1 167381
Technical characteristics
Operating voltage 220 - 240 V / 50 - 60 Hz.
1 channel.
Controlled by external light sensor (supplied).
Built-in time delay included for unwanted switching e.g. due to car lamp influences (adjustable to
type SRSD1COW and SRCD1CO).Manual ON (and depending on type OFF) switching.
Text-oriented user guidance in display.
Switching status indication.
Adjustable light intensity level.
SRCD1CO
Manual ON and OFF switching.
Back lit display.
Automatic summer and winter time adjustment.
Holiday programme.
Zero crossing switching relay for longer life.
Integrated operating hour counter.
Memory interface.
Test function.
Twilight switch with light sensor 1 2 - 100 lux NO 17.5 mm SRSD1NO 1 167375
Antenna for GPS signal reception, includes power supply TSAGPSKIT 1 167385
Programming software kit including adaptor cable, software and memory card TSAMEMKIT 1 167386
Memory card TSAMEM 1 167387
See pages 139-144 for timers and twilight switches technical data and overall dimensions.
Auxiliary 6 9 1 NO + 1 NC CRA611
Auxiliary 6 9 2 NO CRA620
Earth leakage relay Adjustable 30mA,100mA, 300mA, 500mA, 1A, 3A, 5A Adjustable 0.02, 0.1, 0.3, 0.5, 1, 3, 5s 36mm PFR-5
5.1 INCOMING DEVICE RATINGS UP TO 250A OUTGOING DEVICE RATINGS UP TO 160A ................................................. 66
5.2 INCOMING DEVICE RATINGS UP TO 400A OUTGOING DEVICE RATINGS UP TO 160A ................................................. 70
5.3 INCOMING DEVICE RATINGS UP TO 400A OUTGOING DEVICE RATINGS UP TO 250A .................................................. 74
5.4 INCOMING DEVICE RATINGS UP TO 630A OUTGOING DEVICE RATINGS UP TO 250A ................................................. 78
5.5 INCOMING DEVICE RATINGS UP TO 800A OUTGOING DEVICE RATINGS UP TO 400A ................................................. 82
Specification Features
Panelboards to IEC61439-2. Form 3b Type 2 4, 6, 8, or 12 outgoing TP ways
Busbar system KEMA certified 50kA Icc, Icw 25kA 1s Outgoing devices; NZM1 16A125A SP & 20A160A TP
IP3X construction Tinplated busbars
MCCBs to IEC60947-2. kA ratings shown are Ics=Icu at 400V ac Can be configured for incomer device at top of panelboard
Switch disconnectors to IEC60947-3 Removable side gland plates as standard
Wide range of extension boxes, metering, surge
protection, and earth leakage incomer options available
16 NZMB1-1-AF16
20 NZMB1-1-AF20 NZMB1-A20
32 NZMB1-1-AF32 NZMB1-A32
40 NZMB1-1-AF40 NZMB1-A40
50 NZMB1-1-AF50 NZMB1-A50
63 NZMB1-1-AF63 NZMB1-A63
80 NZMB1-1-AF80 NZMB1-A80
100 NZMB1-1-AF100 NZMB1-A100
125 NZMB1-1-AF125 NZMB1-A125
160 NZMB1-A160
1)
36kA triple pole also available, change B to C in list number, ie NZMC1-A125
2)
50kA triple pole also available, change B to N in list number, ie NZMN1-A125
EPBN1BP1 Accessories
Description Eaton list
number
For use where top/bottom/meter boxes are fitted in conjunction with side cable boxes EPBN1CX250
For housing din rail mounted command/control equipment, ie timers/contactors 250mm 15 EPBN1EXDIN
Incomer meter enclosure (can be fitted to top or bottom of panelboard). Meter not included EPBN1EX250M
Multifunction meter measuring parameters:
Voltage (P-P / P/N) (individual/average)
Current (I1, I2, I3) (individua/average)
Frequency
Power factor (individual/average)
Active, reactive, apparent power (individual/total)
Active, reactive, apparent energy (total) EPBMETER1
Voltage supply to meter tap off kit (includes protection fuses). One per panelboard required, irrespective of number of meters EPBN1SUPM
EPBN1SPD123 Transient voltage surge suppression units, externally mounted in own enclosure
See page 90 for full technical specification
Includes 63A TP NZM1 MCCB for protection/isolation
See page 131 for dimensions
Description Eaton list
number
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes III and IV in accordance with IEC 62305 EPBN1SPD123
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes I, II, III and IV in accordance with IEC 62305 EPBN1SPD1234
Earth leakage protection add-on kit for incomer device. 250mm high extension box included EPBKEL250
Specification Features
Panelboards to IEC61439-2. Form 3b Type 2 6 or 12 outgoing TP ways
Busbar system KEMA certified 50kA Icc, Icw 30kA 1s Outgoing devices; NZM1 16A125A SP & 20A160A TP
IP3X construction Tinplated busbars
MCCBs to IEC60947-2. kA ratings shown are Ics=Icu at 400V ac Can be configured for incomer device at top of panelboard
Switch disconnectors to IEC60947-3 Removable side gland plates as standard
Wide range of extension boxes, metering, surge
protection, and earth leakage incomer options available
16 NZMB1-1-AF16
20 NZMB1-1-AF20 NZMB1-A20
32 NZMB1-1-AF32 NZMB1-A32
40 NZMB1-1-AF40 NZMB1-A40
50 NZMB1-1-AF50 NZMB1-A50
63 NZMB1-1-AF63 NZMB1-A63
80 NZMB1-1-AF80 NZMB1-A80
100 NZMB1-1-AF100 NZMB1-A100
125 NZMB1-1-AF125 NZMB1-A125
160 NZMB1-A160
1)
36kA triple pole also available, change B to C in list number, ie NZMC1-A125
2)
50kA triple pole also available, change B to N in list number, ie NZMN1-A125
EPBDLK1 Accessories
Description Eaton list
number
For use where top/bottom/meter boxes are fitted in conjunction with side cable boxes EPBN2CX250
For housing din rail mounted command/control equipment, ie timers/contactors 250mm 15 EPBN2EXDIN
Incomer meter enclosure (can be fitted to top or bottom of panelboard). Meter not included EPBN2EX250M
Multifunction meter measuring parameters:
Voltage (P-P / P/N) (individual/average)
Current (I1, I2, I3) (individual/average)
Frequency
Power factor (individual/average)
Active, reactive, apparent power (individual/total)
Active, reactive, apparent energy (total) EPBMETER1
Voltage supply to meter tap off kit (includes protection fuses). One per panelboard required, irrespective of number of meters EPBN3SUPM
EPBN1SPD123 Transient voltage surge suppression units, externally mounted in own enclosure
See page 90 for full technical specification
Includes 63A TP NZM1 MCCB for protection/isolation
See page 131 for dimensions
Description Eaton list
number
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes III and IV in accordance with IEC 62305 EPBN1SPD123
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes I, II, III and IV in accordance with IEC 62305 EPBN1SPD1234
Specification Features
Panelboards to IEC61439-2. Form 3b Type 2 6, 12 or 18 outgoing TP ways
Busbar system KEMA certified 50kA Icc, Icw 35kA 1s Outgoing devices; these panelboards utilise two
IP3X construction frame sizes of MCCB: NZM2 125A250A TP, and
NZM1 SP 16A125A or TP 20A160A
MCCBs to IEC60947-2. kA ratings shown are Ics=Icu at 400V ac
Tinplated busbars
Switch disconnectors to IEC60947-3
Can be configured for incomer device at top of panelboard
Removable side gland plates as standard
Wide range of extension boxes, metering, surge
protection, and earth leakage incomer options available
Incoming rating up to 400A, NZM3 MCCB or N3 Switch Disconnector 400 6 (2 x 250A + 4 x 160A) EPBN2640
outgoing ratings up to 250A or direct lugs connection 12 (2 x 250A + 10 x 160A) EPBN21240
18 (2 x 250A + 16 x 160A) EPBN21840
16 NZMB1-1-AF16
20 NZMB1-1-AF20 NZMB1-A20 NZMC1-A20
32 NZMB1-1-AF32 NZMB1-A32 NZMC1-A32
40 NZMB1-1-AF40 NZMB1-A40 NZMC1-A40
50 NZMB1-1-AF50 NZMB1-A50 NZMC1-A50
63 NZMB1-1-AF63 NZMB1-A63 NZMC1-A63
80 NZMB1-1-AF80 NZMB1-A80 NZMC1-A80
100 NZMB1-1-AF100 NZMB1-A100 NZMC1-A100
125 NZMB1-1-AF125 NZMB1-A125 NZMC1-A125
160 NZMB1-A160 NZMC1-A160
1)
50kA triple pole also available, change C to N in list number, ie NZMN1-A125
EPBN1BP1 Accessories
tunnel terminals Description Eaton list
number
For use where top/bottom/meter boxes are fitted in conjunction with side cable boxes EPBN2CX250
For housing din rail mounted command/control equipment, ie timers/contactors 250mm 18 EPBN2EXDIN
Incomer meter enclosure (can be fitted to top or bottom of panelboard). Meter not included EPBN2EX250M
Multifunction meter measuring parameters:
Voltage (P-P / P/N) (individual/average)
Current (I1, I2, I3) (individual/average)
Frequency
Power factor (individual/average)
Active, reactive, apparent power (individual/total)
Active, reactive, apparent energy (total) EPBMETER1
Voltage supply to meter tap off kit (includes protection fuses). One per panelboard required, irrespective of number of meters EPBN3SUPM
EPBN1SPD123 Transient voltage surge suppression units, externally mounted in own enclosure
See page 90 for full technical specification
Includes 63A TP NZM1 MCCB for protection/isolation
See page 131 for dimensions
Description Eaton list
number
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes III and IV in accordance with IEC 62305 EPBN1SPD123
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes I, II, III and IV in accordance with IEC 62305 EPBN1SPD1234
Specification Features
Panelboards to IEC61439-2. Form 3b Type 2 6, 12 or 18 outgoing TP ways
Busbar system KEMA certified 50kA Icc, Icw 50kA 1s Outgoing devices; these panelboards utilise two
IP3X construction frame sizes of MCCB: NZM2 125A250A TP, and
NZM1 SP 16A125A or TP 20A160A
MCCBs to IEC60947-2. kA ratings shown are Ics=Icu at 400V ac
Tinplated busbars
Switch disconnectors to IEC60947-3
Can be configured for incomer device at top of panelboard
Removable side gland plates as standard
Wide range of extension boxes, metering, surge
protection, and earth leakage incomer options available
Door lock included
Incoming rating 630A, NZMLW MCCB or NLW CBS 630 8 (4 x 250A + 4 x 160A) EPBN2863
outgoing ratings up to 250A or direct lugs connection 12 (4 x 250A + 8 x 160A) EPBN21263
18 (4 x 250A + 14 x 160A) EPBN21863
16 NZMB1-1-AF16
20 NZMB1-1-AF20 NZMB1-A20 NZMC1-A20
32 NZMB1-1-AF32 NZMB1-A32 NZMC1-A32
40 NZMB1-1-AF40 NZMB1-A40 NZMC1-A40
50 NZMB1-1-AF50 NZMB1-A50 NZMC1-A50
63 NZMB1-1-AF63 NZMB1-A63 NZMC1-A63
80 NZMB1-1-AF80 NZMB1-A80 NZMC1-A80
100 NZMB1-1-AF100 NZMB1-A100 NZMC1-A100
125 NZMB1-1-AF125 NZMB1-A125 NZMC1-A125
160 NZMB1-A160 NZMC1-A160
1)
50kA triple pole also available, change C to N in list number, ie NZMN1-A125
EPBN1BP1 Accessories
Description Eaton list
number
For use where top/bottom/meter boxes are fitted in conjunction with side cable boxes EPBN2CX250
For housing din rail mounted command/control equipment, ie timers/contactors 250mm 30 EPBN3EXDIN
Incomer meter enclosure (can be fitted to top or bottom of panelboard). Meter not included EPBN3EX250M
Multifunction meter measuring parameters:
Voltage (P-P / P/N) (individual/average)
Current (I1, I2, I3) (individual/average)
Frequency
Power factor (individual/average)
Active, reactive, apparent power (individual/total)
Active, reactive, apparent energy (total) EPBMETER1
Voltage supply to meter tap off kit (includes protection fuses). One per panelboard required, irrespective of number of meters EPBN3SUPM
EPBN1SPD123 Transient voltage surge suppression units, externally mounted in own enclosure
See page 90 for full technical specification
Includes 63A TP NZM1 MCCB for protection/isolation
See page 131 for dimensions
Description Eaton list
number
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes III and IV in accordance with IEC 62305 EPBN1SPD123
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes I, II, III and IV in accordance with IEC 62305 EPBN1SPD1234
Specification Features
Panelboards to IEC61439-2. Form 3b Type 2 8, or 12 outgoing TP ways
Busbar system KEMA certified 50kA Icc, Icw 50kA 1s Outgoing devices; these panelboards utilise three frame
IP3X construction sizes of MCCB: NZM3 250A -400A, NZM2 125A250A
TP, and NZM1 SP 16A125A or TP 20A160A
Outgoing MCCBs to IEC60947-2. kA ratings
shown are Ics=Icu at 400V ac Tinplated busbars
Incoming MCCB/circuit breaker switch to Can be configured for incomer device at top of panelboard
IEC60947-2 Icu 50kA, Ics 25kA Removable side gland plates as standard
Wide range of extension boxes, metering, surge
protection, and earth leakage incomer options available
Door lock included
Incoming rating 800A, NZMLW MCCB or NLW CBS 800 8 (2 x 400A + 2 x 250A + 4 x 160A) EPBN3880
outgoing ratings up to 400A 12 (2 x 400A + 4 x 250A + 6 x 160A) EPBN31280
250 NZMN3-A250-BT
320 NZMN3-A320-BT
400 NZMN3-A400-BT
16 NZMB1-1-AF16
20 NZMB1-1-AF20 NZMB1-A20 NZMC1-A20
32 NZMB1-1-AF32 NZMB1-A32 NZMC1-A32
40 NZMB1-1-AF40 NZMB1-A40 NZMC1-A40
50 NZMB1-1-AF50 NZMB1-A50 NZMC1-A50
63 NZMB1-1-AF63 NZMB1-A63 NZMC1-A63
80 NZMB1-1-AF80 NZMB1-A80 NZMC1-A80
100 NZMB1-1-AF100 NZMB1-A100 NZMC1-A100
125 NZMB1-1-AF125 NZMB1-A125 NZMC1-A125
160 NZMB1-A160 NZMC1-A160
1)
50kA triple pole also available, change C to N in list number, ie NZMN1-A125
EPBN3BP3 Accessories
Description Eaton list
number
For use where top/bottom/meter boxes are fitted in conjunction with side cable boxes EPBN2CX250
For housing din rail mounted command/control equipment, ie timers/contactors 250mm 30 EPBN3EXDIN
Incomer meter enclosure (can be fitted to top or bottom of panelboard). Meter not included EPBN3EX250M
Multifunction meter measuring parameters:
Voltage (P-P / P/N) (individual/average)
Current (I1, I2, I3) (individual/average)
Frequency
Power factor (individual/average)
Active, reactive, apparent power (individual/total)
Active, reactive, apparent energy (total) EPBMETER1
Voltage supply to meter tap off kit (includes protection fuses). One per panelboard required, irrespective of number of meters EPBN3SUPM
EPBN1SPD123 Transient voltage surge suppression units, externally mounted in own enclosure
See page 90 for full technical specification
Includes 63A TP NZM1 MCCB for protection/isolation
See page 131 for dimensions
Description Eaton list
number
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes III and IV in accordance with IEC 62305 EPBN1SPD123
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes I, II, III and IV in accordance with IEC 62305 EPBN1SPD1234
Supply tap-off
Provision to fit tap-off to either the left and/or right hand side of the pan assembly.
Only 1 per panelboard is required but provision to fit two is an option.
When configuring panelboard outgoing metering, simply identify Meter connection arrangement
panelboard and number of outgoing breaker type, then order
the following modules detailed in the selection chart below:
1. Outgoing CT kit
2. Outgoing side mounted meter extension box
3. Meter
4. Voltage supply to meter tap-off kit
5. Extra long meter to meter voltage linking kit to feed to meter
extension box on other side of panelboard if necessary
6. Extra long CT to meter linking cable if required
7. Three phase splitter box to allow separate monitoring of a three
phase current transformer on individual energy meters if required
Plug-in connectivity is provided between meter, CT and supply.
Outgoing metering can be configured with incoming metering.
EPBN11225
EPBN11240
EPBN21240
EPBN21840
EPBN21263
EPBN21863
EPBN31280
EPBN1425
EPBN1625
EPBN1825
EPBN1640
EPBN2640
EPBN2863
EPBN3880
Outgoing metering module selection
Meter module Panelboard
In order to enable designers, specifiers, and installers to comply EPBN1SPD1234 technical summary:
with surge protection requirements in BS 7671 - IET Wiring
For the protection of low voltage distribution systems
Regulations - 17th Edition (Section 534), these combined
against direct lightning strike into the overhead power
lightning arrester and surge suppression devices have been
supply line or external lightning protection system and
developed specifically for applications with MCCB panelboards
against indirect lightning strike and switching operations.
ensuring outstanding product performance for all sensitive,
mission critical and general purpose loads. Providing protection Application according to IEC 60364-5-53 Clause 534.
from direct and indirect lightning strikes, the IEC 61643 Test class I, II, III in accordance with IEC 61643-1.
tested devices have impressive voltage protection levels (Up),
SPD-type T1, T2, T3 in accordance with EN 61643-11.
nominal discharge current (8/20) s In & maximum discharge
current Imax for transient surge suppression, combined with No discharge of ionised gases during operation.
impulse current Iimp (10/350) s for lightning strike protection. Lightning protection classes I, II, III and IV
These devices are fully compliant with BS EN 62305. in accordance with IEC 62305.
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes III and IV in accordance with IEC 62305 EPBN1SPD123
SPD-type T1, T2, T3 in accordance with EN 61643-11, lightning protection classes I, II, III and IV in accordance with IEC 62305 EPBN1SPD1234
Memshield 3 panelboard pan assembly 250A, 4 Way. Outgoing up to 160A 250 4 EPBPN1425
Memshield 3 panelboard pan assembly 250A, 6 Way. Outgoing up to 160A 250 6 EPBPN1625
Memshield 3 panelboard pan assembly 250A, 8 Way. Outgoing up to 160A 250 8 EPBPN1825
Memshield 3 panelboard pan assembly 250A, 12 Way. Outgoing up to 160A 250 12 EPBPN11225
Memshield 3 panelboard pan assembly 400A, 6 Way. Outgoing up to 160A 400 6 EPBPN1640
Memshield 3 panelboard pan assembly 400A, 12 Way. Outgoing up to 160A 400 12 EPBPN11240
Memshield 3 panelboard pan assembly 400A, 6 Way. Outgoing up to 250A 400 6 EPBPN2640
Memshield 3 panelboard pan assembly 400A, 12 Way. Outgoing up to 250A 400 12 EPBPN21240
Memshield 3 panelboard pan assembly 400A, 18 Way. Outgoing up to 250A 400 18 EPBPN21840
Memshield 3 panelboard pan assembly 630A, 8 Way. Outgoing up to 250A 630 8 EPBPN2863
Memshield 3 panelboard pan assembly 630A, 12 Way. Outgoing up to 250A 630 12 EPBPN21263
Memshield 3 panelboard pan assembly 630A, 18 Way. Outgoing up to 250A 630 18 EPBPN21863
Memshield 3 panelboard pan assembly 800A, 8 Way. Outgoing up to 400A 800 8 EPBPN3880
Memshield 3 panelboard pan assembly 800A, 12 Way. Outgoing up to 400A 800 12 EPBPN31280
63 50CSB 50CSBA
100 50CSB 50CSBA
160/200 60CSB 60CSBA
315/400 70CSB 70CSBA
500/630 90CSB 90CSBA
800 90CSB 90CSBA
Extension boxes
For fitting to Glasgow switch units to provide additional space for spreading multi-core PVC insulated
cables with solid aluminium conductors and for some larger cables with stranded copper conductors
Nominal unit Fuse switch-disconnector/switch-disconnector Eaton list
rating (A) number
63 61GNC 1PCB1)
63GNC/63GNL 2PCB1)
64GC
100 101GNC 1PCB2)
103GNC/103GNL 2PCB2)
104GC
160 151GNC 2PCB3)
153GNC 3PCB3)
154GC
200 201GNC 2PCB
203GNC/203GNL (315A AC21) 3PCB
204GC
315 303GNC 4PCB
304GC
400 403GNC/use 403GNL (630A AC21)
404GC
500 503GNC 5PCB4)
504GC
630 603GNC/use 603GNL (1000A, AC21)
604GC
800 803GNC/use 803GNL (1000A, AC21)
804GC
1)
Not required for copper cables or al. below 35mm2
2)
Not required for copper cables or al. below 50mm2
3)
Not required for copper cables
4)
For parallel cables use 6 PCB + 802 GCC + 2 x 90 CSB or CSBA (see diagram on page 156)
142 BBC
100 550
900 143 BBC
1350 144 BBC
1800 146 BBC
242 BBC
200 550
900 243 BBC
1350 244 BBC
1800 246 BBC
442 BBC
400 550
900 443 BBC
1350 444 BBC
1800 446 BBC
643 BBC
630 900
1350 644 BBC
1800 646 BBC
843 BBC
800 900
1350 844 BBC
1800 846 BBC
630 81 BBL
800 81 BBL
For busbar supports, see page 158 for details
Exel 2 Spares
Description Rating Quantity required Eaton list
(A) number
xxxxx
207149-GV Rotary isolators
20A to 63 A
IP65
Red/yellow handle
Lockable in the 0 (Off) position
Surface mounting
IEC 60947-3
Rated current Iu (A) Motor rating AC-23A, 400V, Poles Auxiliary contact Eaton
50 - 60 Hz (kW) List Number
20 6.5 3 1 NO 207149-GV
20 6.5 3+N 207151-GV
20 6.5 3+N 1 NO + 1 NC 207153-GV
20 6.5 6 1 NO + 1 NC 207161-GV
25 13 3 1 NO + 1 NC 226902-GV
25 13 3+N 227860-GV
32 13 3+N 1 NO + 1 NC 207202-GV
32 13 6 1 NO + 1 NC 207210-GV
32 13 8 207212-GV
63 30 3 1 NO + 1 NC 207348-GV
63 30 3+N 207349-GV
63 30 3+N 1 NO + 1 NC 207350-GV
63 22 6 1 NO + 1 NC 207246-GV
63 22 8 207248-GV
Changeover switches
20A to 63 A
IP65
Black handle
Surface mounting
IEC 60947-3
Rated current Iu (A) Motor rating AC-23A, 400V, Poles Eaton List
50 - 60 Hz (kW) Number
20 6.5 207136-GV
4
32 13 207191-GV
4
63 22 207230-GV
4
IP4X enclosures
20 SPN 4 95 6 4 SA2 20 MFH 20 MFS 204XSNC
6 95 6 4 SA2 20 MFH 20 MFS 206XSNC
8 120 6 4 SA2 20 MFH 20 MFS 208XSNC
12 120 6 4 SA2 20 MFH 20 MFS 212XSNC
TPN 4 95 6 4 SA2 20 MFH 20 MFS 204XTNC
6 95 6 4 SA2 20 MFH 20 MFS 206XTNC
8 120 6 4 SA2 20 MFH 20 MFS 208XTNC
32 SPN 4 95 16 5.5 SB3 32 MFH 32 MFS 304XSNC
6 95 16 5.5 SB3 32 MFH 32 MFS 306XSNC
8 150 16 5.5 SB3 32 MFH 32 MFS 308XSNC
12 150 16 5.5 SB3 32 MFH 32 MFS 312XSNC
TPN 4 95 16 5.5 SB3 32 MFH 32 MFS 304XTNC
6 95 16 5.5 SB3 32 MFH 32 MFS 306XTNC
8 150 16 5.5 SB3 32 MFH 32 MFS 308XTNC
10 150 16 5.5 SB3 32 MFH 32 MFS 310XTNC
12 150 16 5.5 SB3 32 MFH 32 MFS 312XTNC
63 TPN 2 240 35 8 SB3 & SB4 63 MFH 63 MFS 602XTNC
4 240 35 8 SB3 & SB4 63 MFH 63 MFS 604XTNC
6 240 35 8 SB3 & SB4 63 MFH 63 MFS 606XTNC
8 240 35 8 SB3 & SB4 63 MFH 63 MFS 608XTNC
100 TPN 4 240 70 12 SD51) 100 MFH 100 MFS 1004XTNC
6 5002) 70 12 SD51) 100 MFH 100 MFS 1006XTNC
2)
8 500 70 12 SD51) 100 MFH 100 MFS 1008XTNC
2)
200 TPN 4 630 150 18 SF6 200 MFH 200 MFS 2004XTNC
All units are supplied without fuselinks which must be ordered separately.
1)
SB3, SB4 and SO fuselinks may be fitted if used with adaptor Eaton list number 100MFLK.
1)
Can be adapted to allow fitment of 2240mm2 max. cable sockets with suitable copper spacing piece Eaton list number WA1212 (set of 4).
68 17 16 ESD16 16SP
20 ESD20 20SP
25 ESD25 25SP
32 ESD32 32SP
40 40ES 40GO5 ESD40 40SP
50 50ES 50GO5 ESD50 50SP
63 63ES 63GO5 ESD63 63SP
10 10SA2 1 SCHF
20 20SA2 2 SCHF
32 32SB3 3 SCHF
63 63SB4 6 SCHF
100 100SD5 100SCHF
20MFA Complete fuse units (carriers and bases) bolt-in type A (front/busbar)
Nominal Colour Neutral link Suitable Eaton Eaton list
rating, In (A) HRC fuselinks number
32MFB Complete fuse units (carriers and bases) bolt-in type B (front/front)
Nominal Colour Neutral link Suitable Eaton Eaton list
rating, In (A) HRC fuselinks number
63MFC Complete fuse units (carriers and bases) bolt-in type C (back/back)
Nominal Colour Suitable Eaton Eaton list
rating, In (A) HRC fuselinks number
Front/Front
32 Black 2-32SN2 32CFF
White 2-32SN2 32CFFW
63 Black 16-63SP 63CFF
White 16-63SP 63CFFW
This chapter covers the ADS8 range of DOL, DOL Reversing and See page 117 for overload relays.
Star Delta starters with associated overload relays. Overload See page 176 for trip and electrical life curves.
relays are supplied separately and enclosures are IP54 metal clad. See page 166 for dimensional drawings.
A higher rated IP65 moulded 9kW DOL starter is also available.
IEC / EN60947-4
18 9 220240 28ADSM1X
380415 48ADSM1X
18 9 220240 28ADS1X
380415 48ADS1X
25 11 220240 28ADS2X
380415 48ADS2X
18 9 220240 28ADSA1X
380415 48ADSA1X
25 11 220240 28ADSA2X
380415 48ADSA2X
18 9 220240 28ARD1X
380415 48ARD1X
25 11 220240 28ARD2X
380415 48ARD2X
31 15 220240 28SDA2X18
380415 48SDA2X18
43 22 220240 28SDA3X25
380415 48SDA3X25
4.36.9 3 8TT90SD
6.910.4 5.5 8TT91SD
9.513.8 7 8TT98SD
12.117.3 9 8TT92SD
17.322.5 11 8TT93SD
22.531 15 8TT94SD
3143 22 8TT104SD
25 M8 35 M8 6 EP2541E
50 M8 35 M8 8 EP5041E
75 M10 60 M10 16 EP7541E
100 M10 60 M10 18 EP10041E
25 1 x 25 20 Fusebase MC25M1
21 Fuseswitch MC25M1S
MCCB MC25M1M
50 2 x 25 25 Fusebase MC50M2
26 Fuseswitch MC50M2S
MCCB MC50M2M
75 3 x 25 31 Fusebase MC75M3
33 Fuseswitch MC75M3S
MCCB MC75M3M
100 4 x 25 35 Fusebase MC100M4
37 Fuseswitch MC100M4S
MCCB MC100M4M
If you require a specific KVAR rating other than the above, please contact Eaton for further details.
SPLIT METERED POWER AND LIGHTING BOARD 200A TPN, MEMSHIELD 3 METER PACK ASSEMBLIES ................. 128
27MM MINIATURE CIRCUIT BREAKERS (FOR 250A HIGH LOAD DISTRIBUTION BOARDS) ........................................... 136
Responding time (rate of voltage rise 5 kV/s) L-N/N-PE/L-PE < 25ns/< 100ns/< 100ns < 25ns/< 100ns/< 100ns
Maximum continuous operating voltage UC L-N/N-PE 335VAC/260VAC 280VAC/260VAC
Temporary overvoltage test value UT (5 s) L-N 415 VAC 350 VAC
(200 ms) N-PE 1200 VAC 1200 VAC
Rated frequency 50/60 Hz 50/60 Hz
Nominal discharge current In L-N/N-PE/L-PE 20 kA (8/20)s 20 kA (8/20)s
Voltage protection level Up at In L-N/N-PE/L-PE 1600V/1000V/1650V 1000V/1000V/1300V
Maximum discharge current Imax L-N/N-PE/L-PE 40 kA (8/20)s 40 kA (8/20)s
126 POWER DISTRIBUTION COMPONENTS PG01414001U March 2015
Technical data
Memshield 3 type A SPN, type B TPN distribution boards 10.1
Memshield 3 type A SPN Distribution Board, Memshield 3 type B TPN Distribution Board,
dimensional drawing dimensional drawing
10 326
10
130
130 100
100
M6 Keyhole
440 fixing
83
A
Cable
terminations
37.6
B A
161 254
M6 KEYHOLE FIXINGS
B
= = 180
or Cable Box
250
List No. A (mm) B (mm)
(if fitted)
130
100
M6 Keyhole
440 fixing
83
B A
270
EAMP4 190 105.5 107.7 48.8 180 160 96 70 77 238 (W) x 254 (L)
EAMP7 274 129.5 160.9 79 180 214 96 70 107 292 (W) x 254 (L)
EAMP10 328 164 214.1 127.5 180 266 96 70 127.5 346 (W) x 254 (L)
EAMP13 382 183.5 267.3 131.3 192 319 109 82 161 440 (W) x 260 (L)
EAMP16 435 226.5 320.5 141.5 198 372 105 79 171 495 (W) x 260 (L)
279
EM3SSK1T2 EM3SSKT2/EM3SSKT12
EBMMPCD120
EBMMPCT250/EBMMPCT250M/EBMMPCT250MID
EBMMPSL250/EBMMPSL250M
EBMMPSL125/EBMMPSL125M
18mm miniature circuit breakers (MCBs), technical data Tripping characteristic type B, C & D
7200
Eatons range of 10/15kA high performance miniature circuit
3600 2
breakers (MCBs) are manufactured and tested to IEC EN 60898, 1
and IEC EN 60947-2, meeting the latest UK, European and 1200 1 conventional non-tripping current
international standards, with ratings from 1A to 63A as standard. 600
Int = 1.13 IN : t > 1 h
comb type busbar systems, Eatons MCBs are suitable for use 120
3
2.55 IN : t = 160 s (IN < 32A)
t = 1-120 s (IN > 32A)
on 230/400 VAC systems and are calibrated for use at 40C. 3 4 Type B: 3 IN : t > 0.1 s
60 5 IN : t < 0.1 s
These devices suite with the other modular devices including 5
Distribution boards and a wide range of other applications. 10 8 Type D: 10 IN : t > 0.1 s
9 20 IN : t < 0.1 s
The Eaton MCBs are fitted with box clamp terminals suitable 5
t [sec]
for use with cables up to 25mm2, and have a unique box 2
clamp barrier to prevent incorrect cable insertion. 1
3
Eaton miniature circuit breakers are available with B, C and 0.5
t [sec]
Product standard IEC EN 60947-2 2
No of poles 1p, 3p 1
3
Mechanical specification 0.5
Note : Values take account of minimum voltage factor Cmin - in accordance with
BS7671 Amendment 3
4P
Terminology
RCD Residual current device:- This is the generic term covering a
range of devices that are able to detect residual currents sometimes
also referred to as earth leakage current. The residual current is
measured by detecting the difference between the current flowing
in the live and neutral conductors of a circuit and where the residual
current is above a predefined level the RCD will trip. RCDs are
available in a range of trip sensitivities for different applications.
RCCB Residual current circuit breaker is an RCD which
will cause disconnection of the electrical supply should it
detect a residual current passing through the device, above a
specified tripping current limit e.g. 30mA. This device does not
provide over current protection and is therefore also referred
to as an RCCB without integral over-current protection.
RCBO Residual current circuit breaker, with overload protection,
is an RCCB which will cause disconnection of the electrical supply
should it detect a residual current above a specified tripping
current limit, combined with integral overload, over-current, and RCCB technical data
shortcircuit protection associated with a miniature circuit breaker. Specifications 2-pole RCCB 4-pole RCCB
The 17th Edition of the IEE wiring regulations BS7671 now places Product standard IEC EN 61008 IEC EN 61008
much greater emphasis on the use of 30mA RCDs to provide No of poles 2p 4p
additional protection in many areas covered by the regulations, Mechanical specification
such as circuits feeding socket outlets and for Device width 35 mm 70 mm
the protection of concealed wiring.
Terminal type Box clamp Box clamp
Terminal capacity 1.535mm2 35mm2
Trip sensitivities
Terminal Screw M5 combination M5 combination
10mA Provides the highest degree of RCD protection in Terminal torque 2.4Nm max 2.4Nm max
hazardous environments where supplementary protection against
Mounting DIN rail DIN rail
electric shock is required. This very high sensitivity should only
be applied to final circuits where a high degree of risk exists. Degree of protection IP 20 IP 20
Positive contact indication Yes (toggle position) Red/green flag
30mA Provides a high degree of protection against electric
Electrical specification
shock due to direct and indirect contact. A 30mA RCD will trip
within 40mS when a fault current of 150mA is detected. Rated voltage 230/400 V AC 230/400 V AC
Current ratings 16, 40, 63, 80,100 A 16, 40, 63, 80,100 A
This type of RCD is required to satisfy the requirements for
additional protection in accordance with BS7671 (IEE wiring regs.) Rated impulse 4kV (1.2/50) u sec 4kV (1.2/50) u sec
and withstand voltage
100mA Provides a degree of protection against Rated short circuit capacity 10kA (with back up) 10kA (with back up)
electric shock resulting from indirect contact, and is Sensitivity AC AC
generally used to protect a group of circuits as well
Tripping characteristic
as providing overall protection against Fire risk.
Rated tripping currents 10, 30, 100, 300 mA 10, 30, 100, 300 mA
300mA Provides a lower level of RCD protection in
Tripping type Instantaneous Instantaneous
the form of an overall protection against the risk of
Number of >4000 >4000
fire resulting from faults in electrical wiring etc.
operating cycles elec
Number of >20000 >20000
operating cycles mech
Residual current circuit breakers with overload protection (RCBOs) technical data
Eatons range of residual current circuit breakers with integral overload protection (RCBOs), are
manufactured to IEC EN 61009 and meet the latest European and International standards.
Trip Sensitivity
Provides a high degree of protection against electric shock due to direct contact. A 30mA
RCD will trip within 40mS when a fault current of 150mA is detected.
This type of RCD is required to satisfy the requirements for additional protection in accordance with BS7671 (IET wiring regs.)
General
Operating voltage 230V AC 230 V AC 110 - 230 V AC 110 - 230 V AC 230 - 240 V AC
Frequency 50 Hz 50 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
Stand-by power 0.5 W 0.5 W 0.5 W 0.5 W 0.5 W
Time control Net Net Quartz Quartz Quartz
Accuracy acc. Net acc. Net 1 sec. / day 1 sec. / day 1 sec. / day
Power reserve - - 200 hrs / 200 hrs/
/ 100 hrs at 110 V 100 hrs at 110 V 3 days
Battery type - - NiMH NiMH NiMH
Degree of protection (EN 60529) IP20 IP20 IP20 IP20 IP20
Ambient temperature -20 C...+55 C -20 C...+50 C -20 C...+55 C -20 C...+55 C -10 C...+50 C
Protection class (EN 60730-1) II II II II II
Switching contact(s)
Type of switching contact 1 x CO 1 x NO 1 x CO 1 x CO 1 x NO
Switching capacity at 250 V~, cos = 1 16 A 16 A 16 A 16 A 16 A
Switching capacity at 250 V~, cos = 0,6 4A 4A 4A 4A 4A
Programming features
Period of program Day Day Week Day Day
Number of channels 1 1 1 1 1
Minimum cycle time 15 min. 15 min. 2 hrs 15 min. 15 min.
Programmable every 15 min. every 15 min. every 2 hrs every15 min. every 15 min.
Program steps 96 96 84 96 96
Manual / Hand / Permanent switching 1) On, Off, Auto On, Off, Auto On, Off, Auto On, Off, Auto On, Off, Auto
Switching status indication x x x x x
Dimensions and weight
Number of module width 3 1 3 3 1
Dimensions Width 52.5 mm 17.5 mm 52.5 mm 52.5 mm 17.5 mm
Height 90 mm 90 mm 90 mm 90 mm 90 mm
Depth 65.5 mm 65.5 mm 65.5 mm 65.5 mm 65.5 mm
Mounting DIN-rail DIN-rail DIN-rail DIN-rail DIN-rail
Terminals
Terminal screw size M3.5 M3.5 M3.5 M3.5 M3.5
1
) Remark
ON = Permanent ON
OFF = Permanant OFF
Hands = ON or OFF. valid until next program cycle overrules
Auto = According program
. .
.
7
.
.
Analogue
Analoguedaily
dailyand
andweekly
weeklytime switches,
time wiring
switches, diagrams
wiring diagrams
General
Nominal operating voltage 220 - 240 V AC 240 V AC 220 - 240 V AC 230 - 240 V AC 230 - 240 V AC
Frequency 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
Stand-by power 0,8 W 0,4 W 0,8 W 0,8 W 1,4 W
Time base control 1) Quartz Quartz Quartz Astro Quartz or DCF / GPS
Accuracy 0,5 sec. / day 0,5 sec. / day 0,5 sec. / day 0,5 sec. / day 0,5 sec. / day
Power reserve 10 year 10 year 10 year 10 year 10 year
Type of battery Lithium Lithium (exchangeable) Lithium Lithium Lithium
Protection class (acc. EN 60529) IP20 IP20 IP20 IP20 IP20
Permissible ambient temperature -30 C...+55 C -25 C...+55 C -30 C...+55 C -30 C...+55 C -30 C...+55 C
Protection class at proper installation (acc. EN 60730-1) II II II II II
Switching contact(s)
Type of switching contact 1 x CO 1 x CO 2 x CO 1 x CO 1 x CO
Switching capacity at 250 V~, cos = 1 16 A 16 A 16 A 16 A 16 A
Switching capacity bij 250 V~, cos = 0,6 10 A 6A 10 A 10 A 10 A
Switching capacity for lighting
- Incandescent lamp 2600 W 1000 W 2600 W 2600 W 2600 W
- Halogen lamp 2600 W 1000 W 2600 W 2600 W 2600 W
Programming features
Period of programme Week Week Week Week Week
Number of channels 1 1 2 1 1
Minimum switching capacity 10 mA - 10 mA 10 mA -
Minimum cycle time 1 min. 1 min. 1 min. 1 min. 1 sec.
Maximum programming steps in memory 56 56 56 56 84
Summer / wintertime automatic (or manual on/off) Yes Yes Yes Yes Yes
Random programme No No No No Yes (2)
Holiday programme Yes Yes Yes Yes Yes
Cycle programme No No No No Yes
Astro function No No No Yes No
Pulse switching No No No No Yes
Manual switching 2) On, Off, Auto On, Off, Auto On, Off, Auto On, Off, Auto On, Off, Auto
LCD backlighting Yes - Yes Yes Yes
PIN code Yes Yes Yes Yes Yes
Dimensions and weight
Number of module width 2 1 2 2 2
Dimensions Width 35.8 mm 17.5 mm 35.8 mm 35.8 mm 35.8 mm
Height 90.1 mm 90 mm 90.1 mm 90.1 mm 90.1 mm
Depth 69.2 mm 65.5 mm 69.2 mm 69.2 mm 69.2 mm
Mounting DIN-rail DIN-rail DIN-rail DIN-rail DIN-rail
Terminals
Terminal type Spring Screw Spring Spring Spring
1) Remark: ) Remark:
2
. .
. . .
. . .
7
.
.
.
. .
. . . .
. . . . . .
. .
. .
142 POWER DISTRIBUTION COMPONENTS PG01414001U March 2015 CA081003EN - January 2013 TECHNICAL DATA 15
Technical data
Control and switching devices dimensions and data 10.1
Twilight switches and combination with timer
SRSD1NO SRSD1COW SRCD1CO SRSW1NO
General
Nominal operating voltage 220 - 240 V AC 220 - 240 V AC 220 - 240 V AC 220 - 230 V AC
Frequency 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
Stand-by power 0,8 W 1,1 W 1,3 W 0,6 W
Photosensitivity 2 - 100 lux 2 - 2000 lux 2 - 2.000 lux 2 - 2.000 lux
Maximum cable length for sensor 25 mtr. 100 mtr. 100 mtr. -
Maximum cable length for sensor -25 C...+50 C -30 C...+55 C -30 C...+55 C -35 C...+55 C
Protection class at proper installation - modular device II II II II
Switching contact(s)
Type of switching contact 1 x NO 1 x CO 1 x CO 1 x NO
Contact type Floating Floating Floating (not for SELV) Floating 230 V
Switching capacity at 250 V~, cos = 1 16 A 16 A 16 A 16 A
Switching capacity at 250 V~, cos = 0,3 - - 10 A 10 A
Maximum lamp load:
- Incandescent lamp 2300 W 2300 W 2600 W 2300 W
- Energy saving lamp 9 x 7 W, 7 x 11 W, 9 x 7 W, 7 x 11 W, 22 x 7 W, 18 x 11 W, 9 x 7 W, 7 x 11 W,
7x 15 W, 7 x 20W, 7x 15 W, 7 x 20W 16 x 15 W, 16 x 20 W, 7 x 15 W, 7 x 20 W,
7 x 23 W 7 x 23 W 14 x 23 W 7 x 23 W
- Fluorescent lamp load - single fitting 2300 VA 2300 VA 2300 VA 2300VA
uncompensated (inductive)
Switching delay off 20 sec. 0 - 20 min. 0 - 59 min. 2 - 100 sec.
Switching status indication (not delayed) Yes Yes - Yes
Programming features
Period of programme - - Week -
Number of channels - - 1 -
Programming using software and memory - - Yes -
Summer / wintertime automatic (or manual on/off) - - Yes -
Random programme - - No -
Holiday programme - - Yes -
Cycle programme - - No -
LCD backlighting - - Yes -
Dimensions and weight
Number of module width 1 2 3 -
Dimensions Width 17.5 mm 54 mm 72 mm 85 mm
Height 85.5 mm 86 mm 86 mm 118.4 mm
Depth 65.5 mm 65.5 mm 65.5 mm 49.4 mm
Terminals
Terminal type Screw Spring Spring (duo fix) -
. .
.
7
. .
.
.
Twilight switches
Twilight and
switches combinations
and with
combinations timer,
with wiring
timer, diagrams
wiring diagrams
Rating 20 A 25 A 40 A 63 A 6A
General
Standards IEC 60947-4-1, IEC 61095 IEC 60947-5-1
Nominal operating voltage 1-phase Ue 1-ph. 230 V 230 V 230 V 230 V 230 V
Nominal operating voltage 3-phase Ue 3-ph. 400 V 400 V 400 V - -
Overvoltage protection on coil 430 V (*5) 430 V (*5) 430 V 430 V
Mechanical endurance (switching cycles) 3.000.000 3.000.000 3.000.000 3.000.000 3.000.000
Protection class (acc. DIN 40 050, IEC 529) IP20 IP20 IP20 IP20 IP20
Permissible ambient temperature -5+55 C -5+55 C -5+55 C -5+40 C -5+55 C
Storage temperature -30+80 C -30+80 C -30+80 C -30..+80 C -30+80 C
Contact rating
Rated insulation voltage Ui 440 V 440 V 500 V 500 V 500 V
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Rated impulse withstand voltage Uimp 4 kV 4 kV 4 kV 4 kV 4 kV
Rated thermal current Ith 20 A 25 A 40 A 63 A 6A
AC1/AC7a Rated operational current Ie 20 A 25 A 40 A 63 A
AC1/AC7a Operational power rating at Ue = 230 Vac Pmax 4 kW 9 kW 16 kW 24 kW
AC1/AC7a Operational power rating at Ue = 400 Vac Pmax 16 kW 26 kW 40 kW
AC3/AC7b Operational power rating at Ue = 230 Vac Pmax 1,3 kW (*1) 2,2 kW 5,5 kW 8,5 kW
AC3/AC7b Operational power rating at Ue = 400 Vac Pmax 4 kW 11 kW 15 kW -
DC1 Rated thermal current at Ue = 24 Vdc Ie 20 A 25 A 40 A 63 A
DC1 Rated thermal current at Ue = 110 Vdc Ie 1A 2A 4A 4A
DC1 Rated thermal current at Ue = 220 Vdc Ie 0,5 A 0,5 A 0,8 A 0,8 A
DC1 Rated thermal current at Ue = 24 Vdc
(2-poles in series) Ie 20 A 25 A 40 A 63 A
DC1 Rated thermal current at Ue = 110 Vdc
(2-poles in series) Ie 3 A 4 A 10 A 10 A
DC1 Rated thermal current at Ue = 220 Vdc
(2-poles in series) Ie 1,5 A 1,5 A 6 A 6 A
DC1 Rated thermal current at Ue = 24 Vdc
(3-poles in series) 25 A 40 A 63 A
DC1 Rated thermal current at Ue =110 Vdc
(3-poles in series) 6:00 AM 30 A 35 A
DC1 Rated thermal current at Ue = 220 Vdc
(3-poles in series) 2,5 A 20 A 30 A
Electrical endurance
Maximum operating cycles at AC1/AC7a application 200.000 x 200.000 x 100.000 x 100.000 x
Maximum operating cycles at AC3/AC7b application 300.000 x 500.000 x 150.000 x 150.000 x
Maximum operating cycles at AC5a application 100.000 x 100.000 x 100.000 x 100.000 x
Maximum operating cycles at AC5b application 100.000 x (*2) 100.000 x (*2) 100.000 x (*3) 100.000 x (*4)
Maximum operating cycles per hour 600 x 600 x 600 x 600 x 600 x
Power dissipation per contact at In 1,7 W 2,2 W 4 W 8 W
Maximum back-up fuse 25 A gL 35 A gL 63 A gL 80 A gL
Rating 20 A 25 A 40 A 63 A 6A
Operating coil (for combined ac/dc types only CR)
Coil inrush power (for all voltage ratings) 2,5 W 3 W 5 W 5 W
Coil consumption (for all voltage ratings) 2,5 W 3 W 5 W 5 W
Closing delay 15-25 ms 15-30 ms 15-20 ms 15-20 ms
Opening delay 35-45 ms 50-80 ms 35-45 ms 35-45 ms
Operating coil (for ac types only CRA)
Coil inrush power (for all voltage ratings) 13 W/15 VA 17 W/27 VA
Coil consumption (for all voltage ratings) 2 W/5 VA 1 W/2.7 VA
Closing delay 15 ms 15-25 ms
Opening delay 10 ms 35-45 ms
Dimensions
Width 18 mm 35 mm 54 mm 54 mm 9 mm
Height 85 mm 85 mm 85 mm 85 mm 85 mm
Depth 60 mm 60 mm 60 mm 60 mm 60 mm
Terminals for main & auxiliairy contacts
Terminal capacity fine stranded wire 16 mm2 16 mm2 116 mm2 116 mm2 12,5 mm2
Terminal capacity solid wire 110 mm2 110 mm2 125 mm2 125 mm2 12,5 mm2
Terminal screw size M3,5 M3,5 M5 M5 M3
Terminal screw head type (Pozidrive) PZ Size 1 PZ Size 1 PZ Size 2 PZ Size 2 PZ Size 1
Maximum torque 1,2 Nm 1,2 Nm 2,0 Nm 2,0 Nm 0,8 Nm
Terminals for operating coils
Terminal capacity fine stranded wire 12,5 mm2 12,5 mm2 12,5 mm2 12,5 mm2
Terminal capacity solid wire 12,5 mm2 12,5 mm2 12,5 mm2 12,5 mm2
Terminal screw size M3 M3 M3 M3
Terminal screw head type (Pozidrive) PZ Size 1 PZ Size 1 PZ Size 1 PZ Size 1
Maximum torque 0,6 Nm 0,6 Nm 0,6 Nm 0,6 Nm
Remarks:
*1) Only applicable for normally open contact(s)
*2) At 1,5 kW
*3) At 3 kW
*4) At 5 kW
*5) For CR types only (combined ac/dc types), NOT for CR A types
Type A B C D E
Note : Values take account of minimum voltage factor Cmin - in accordance with BS7671 Amendment 3
Panelboard dimensions
Description Eaton list Dimensions (mm)
number A B C D E F G
The six dedicated buttons are labelled as V, I, VAF, PF, P, E. The parameters available by pressing each key are detailed below:
Measurements available via:
Button 1 (V) Line to neutral voltage of three phase and average line to line voltage
Line to line voltage of three phase and average line to line voltage
Button 2 (I) Phase current of three phase and average phase current.
Phase current of three phase and maximum phase current.
Button 3 (VAF) Voltage, current, power factor of first phase and frequency
Voltage, current, power factor of second phase and frequency
Voltage, current, power factor of third phase and frequency
Average value of voltage, current, power factor of three phase and frequency
Button 4 (PF) Power factor of three phase and average power factor
Button 5 (P) Active power of three phase and total active power
Reactive power of three phase and total reactive power
Apparent power of three phase and total apparent power
Active, reactive, apparent power and power factor of first phase
Active, reactive, apparent power and power factor of second phase
Active, reactive, apparent power and power factor of third phase
Total active, reactive, apparent power and average power factor of three phase
Maximum active power demand, reactive power demand, apparent power demand
Minimum active power demand, reactive power demand
Button 6 (E) Active energy of three phase
Apparent energy of three phase
Reactive energy of three phase
Accuracy Accuracy
Measurement Accuracy Measurement Accuracy
Eaton list A B C D
number
Eaton list A B C D E F G H J K
number
EPBPN2863 167 N/A 543.5 996 1052.5 1240 1291 177 96.75 601.5
EPBPN21263 167 N/A 724.5 1177 1233.5 1421 1472 267.5 187.25 692
EPBPN21863 167 438.5 996 1448.5 1505 1692 1743 403.25 323 828
EPBPN3880 167 N/A 580.5 1033 1089.5 1277 1328 177 96.75 638.5
EPBPN31280 167 N/A 761.5 1214 1270.5 1458 1509 222.25 142 794.5
Units have retractable handles. D dimension indicates fully extended operating position.
Operational performance
In accordance with BS EN 60947-3: A categories all ratings have been tested to values specified below:
Rated operational current, Ie (A) Operating cycles Total
Without current With current
35
CRS
Parallel cable connection
A = 803GNC
B = 6PCB
C = 90CSB/A CRS
Straight entry
50 CSB 83 232 170 67 171 4 M6
60 CSB 108 283 260 89 216 4 M8
70 CSB 133 384 322 114 318 4 M8
90 CSB 133 530 450 114 457 4 M10
45 Angled entry
50 CSBA 83 232 250 67 171 4 M6
60 CSBA 108 283 310 89 216 4 M8
70 CSBA 133 384 390 114 318 4 M8
90 CSBA 133 530 510 114 457 4 M10
Operational performance
In accordance with BS EN 60947-3 all ratings have been tested to values specified below:
Description Cycles
Switch-disconnectors
20 159 193 92 127 112 114 5.6 38.5 34
32 173 245 101 137 116 114 114 6.4 38.5 34
63 230 310 129 173 152 168 168 6.7 58 54
100/125 329 367 167 210 241 221 221 6.7 58 54
Switch-disconnector-fuses
20 219 193 92 127 171 114 5.6 38.5 34
32 267 245 101 137 209 114 114 6.4 38.5 34
63 351 310 129 173 273 168 168 6.7 58 54
100/125 503 367 167 210 416 221 221 6.7 58 54
Performance values
Unit Short time withstand current Short circuit making capacity Rated fused short-circuit
(r.m.s. amps for 1 second) (peak amps at 415v ac) (prospective r.m.s. amps at 415v ac)
2 1
4 0.8 0.9 0.9 0.9 0.9
6 0.8 0.8 0.8 0.8
8 0.66 0.8 0.8 0.8
10 0.66
12 0.66
Therefore, incomer rating =
2 126A
4 640A 360A 227A 115A 72A
6 480A 302A 154A 96A
8 528A 403A 205A 128A
10 211A
12 253A
20A 87 79 27 50 63 56 6 5.5 12
32A 109 101 31 62 60 78 6 5.5 12.7 6.4 12
32A clip-in 75 25 57.7 6 5.5 4.4
63A 118 110 35 72 71 79 8 5.5 12.7 6.4 14.5
63A clip-in 88.7 31.5 66.34 8 5.5 4.8
100A 154 154 54 108 80 117 10 6.5 19 22 18.5
Compact range
32A 87 79 27 56 6 5.5 12
63A 109 101 31 78 6 5.5 12.7 6.4 12
100A 118 110 35 72 71 79 8 5.5 12.7 6.4 14.5
200A 154 154 54 108 80 117 10 6.5 19 22 18.5
Dimensions (mm)
I ON
o B A
OFF
o
OFF
H H
C D E
F G
Dimensions (mm)
I ON
o B A
OFF
o
OFF
H H
C D E
F G
0.07
0.1 0.7 0.6 0.4 0.4 0.3
0.12 1 0.9 0.5 0.5 0.3
0.18 1.3 1.2 0.8 0.7 0.4
0.25 1.6 1.5 0.9 0.9 0.6
0.37 2.5 2.3 1.4 1.3 0.8
0.56 3.1 2.8 1.8 1.6 1.1
0.75 3.5 3.2 2 1.8 1.4
1.1 5 4.5 2.8 2.6 1.9
1.5 6.4 5.8 3.7 3.4 2.6
2.2 9.5 8.7 5.5 5 3.5
3 12 11 7 6.5 4.7
3.7 15 13 8 8 6
4 16 14 9 8 6
5.5 20 19 12 11 8
7.5 27 25 16 15 11
9.3 34 32 20 18 14
10 37 34 22 20 15
11 41 37 23 22 16
15 64 50 31 28 21
18.5 67 62 39 36 26
22 74 70 43 39 30
30 99 91 57 52 41
9kW DOL starter without switch disconnect, IP 65 moulded surface mounting enclosure, dimensional drawings
2 X 5.3mm DIA
Elongated Fixing Holes
4 X 21.5mm
50.5 mm Conduit Knockouts
20mm
120.0 mm
140.0 mm
150 mm
166 mm
150 mm 5.3
88 mm
11kW DOL starter without switch disconnect, IP 54 metalclad surface mounting enclosure, dimensional drawings
Dimensions in brackets refer to type 2528ADS(2X) size enclosure
(30.0 mm)
28.5 mm
159.4 mm
(223 mm)
129.2 mm
105.8 mm
(172 mm)
(141mm)
18 mm
25 mm 38 mm 6-20mm
(47 mm) Conduit Knockout
(7-20/25mm
Conduit Knockout)
(41.mm)
29 mm
(165.0mm)
117.5mm
(168.5 mm)
(154 mm)
125.5 mm
112 mm
= =
159.5 mm
154 mm
140mm
185mm
)
29 mm
171.5 mm
4-6.0 Diameter
Fixing Holes
114 mm
11kW DOL reversing starter without switch disconnect, IP 54 metalclad surface mounting enclosure, dimensional drawings
8 X 20.9mm (3/4) conduit knockouts are provided for cable entry at top,bottom and side of the enclosure and the earth
terminal may be reversed for external connection but the components must be assembled in the same order as supplied.
34 mm
Forward Reverse
159.5 mm
MEM
154 mm
166.5 mm
140mm
171.5 mm
4-6.0 Diameter
Fixing Holes
114 mm
20 MM CONDUIT KNOCKOUTS
221.5 mm
29 mm*
34 mm
159.5 mm
MEM
154 mm
(53 mm)
29 mm
140 mm
166.5 mm (155 mm)
= =
171.5 mm
4 - 6.0 mm
= = Diameter
Fixing Holes
114 mm
=
=
11kW DOL starter without switch disconnect, moulded & metal surface mounting enclosure, wiring diagrams
Supply 17 18 A2
Start
Remote
Push Inch
Y Z Buttons
A1 L1 L2 L3 Stop
13
14 17
A2 1 3 5
Motor
B. Single phase motors-DOL starter. Local 3-wire (pushbutton) control.
17 18 A2
Connect Supply
Cable N L Start
Remote
Push
Buttons Stop
Y Z
A1 L1 L2 L3 13
17
A2 1 3 5 14
N L
Motor
Coil phase to neutral: remove connector Y, connect Neutral to A1
Separate coil supply: remove connectors Y and Z, connect coil supply to A1 and 96.
Coil voltage: Ensure correct voltage coil is fitted for separate coil supply and phase to neutral applications.
External interlock: Remove connection Z and insert interlock between 5 and 96.
Alarm circuit: At trip an alarm signal voltage equal to the coil voltage is available between 98 and A1
when a link is added between 96 & 97. The switch is rated at 440VA, 500V maximum.
Control circuit fuses (10A MAX).
Coil connected Phase to neutral (1 fuse): remove connector Z and connect fuse between 5 and 96.
Coil Connected Phase to Phase (2 fuses): remove connector Z and connect fuse between
5 and 96. Remove connector Y and connect fuse between 1 and A1.
Note: the voltage rating of the fuse(s) must be suitable for the control circuit voltage.
Short circuit protection: Maximum sizes of fuses or MCBs to give short-circuit protection to this starter are tabulated on page 173.
To reverse direction of rotation (3-Phase Motors): Interchange any two supply lines 1, 3 or 5.
Supply 17 18 A2
(L1) (L2) (L3)
1 3 5
Start
Remote
Push Inch
Buttons
Y Z
A1 L1 L2 L3 13 Stop
17
A2 1 3 5 14
Start
18 Isolator
Switch Remote start/inch/stop control
96 97
Connect as above except remove lead
O X and add connections shown
2 4 6 95 Stop
98
X
Motor
Connect
Supply 17 18 A2
Cable (L) (N)
1 5 Start
Remote
Push
Buttons Stop
P
Y Z
A1 L1 L2 L3 13
14 17 Local & remote 3-wire
A2 1 3 5
Start (pushbutton) control
18 Connect as above except remove lead
Isolator
96 97 Switch X and add connections shown
95 O
2 4 6 Stop
X 98
Motor
11kW DOL reversing starter without switch disconnect, IP 54 metalclad surface mounting enclosure, wiring diagrams
95 REMOTE PB 96
1 3 5 1 3 5 95
17 53 17 53 REMOVE LINK FOR
OFF
REMOTE OPERATION
F F R R
2 4 6 2 4 6 17 53 17 53
F R 18 54 18 54
21 21 F F R R
R F 54
ON(R) ON(F) 18 18 54
22 22
A2 A2
F R 21 21
2 4 6 R F
A1 A1 22 22
A2 A2
Y F R
A1 A1
1 R
L1
L2 Mechanical Iinterlock
L3 1 R
A1 1 5
98 97 95 96 53
2 4 6 F R
R 54 54
U V W
14
95
M
3 96
Option for Remote Control
Control Connections
ON
to be made X X
OFF
Direct on line
8TT87 0.631 4 EMCH306
8TT88 11.6 6 EMCH306
8TT89 1.62.5 10 EMCH306
8TT90 2.54 16 EMCH310
8TT91 46 16 EMCH310
8TT98 5.58.0 20 EMCH316
8TT92 710 25 EMCH320
8TT93 1013 32 EMCH320
8TT94 1318 40 EMCH332
8TT104 1825 50 EMCH340
Star Delta
8TT90SD 4.36.9 16 EMCH310
8TT91SD 6.910.4 16 EMCH310
8TT98SD 9.513.8 20 EMCH316
8TT92SD 12.117.3 25 EMCH320
8TT93SD 17.322.5 32 EMCH320
8TT94SD 22.531 40 EMCH332
8TT104SD 3143 50 EMCH340
6-20mm
(34.5 mm)
Conduit Knockout
21 mm
(7-20/25mm
Conduit Knockout)
(159.4 mm)
117.5 mm
(165 mm)
(223 mm)
(80 mm)
(3-Fixing Holes
6.3 mm DIA)
DIMENSIONS
Additional IN BRACKETS
side mounting ( ) REFER
auxilary contacts TO:-
for DOL, DOL reversing, Star Delta starters and Autoline
1NC Ith 10A Ui228ALCSPNR*,
228ALCSPN,
1 NO, 600v 428ALCFP, 448ALCFP, 428ALCDP, 428ALCDPR *, 428ALCSPN,
428ALCSPNR
Description * Current rating Coil voltage Starter list Maximum side Eaton list
(A) number mount auxilaries number
8TA1DN11
28SDA2X18
8TA1DN11
28SDA2X25
8TA1DN11
28SDA2X32
8TA1DN11
48SDA2X18
8TA1DN11
48SDA2X25
8TA1DN11
48SDA2X32
228ALCFP 1.7
248ALCFP 1.7
428ALCFP 2.5
448ALCFP 2.5
228ALCFPR 1.7
428ALCFPR 2.5
228ALCDP 3.0
428ALCDP 3.5
228ALCDPR 3.0
428ALCDPR 3.0
228ALCSPN 3.5
428ALCSPN 4.0
228ALCSPNR 4.0
428ALCSPNR 4.0
M20 M20
44
66.5
80
C M4
33
b
a
M20/M25
17.8
56
FIXING HOLES
12mm DIA
C
A
D
E
KVAR (415V) A B C D E
FIXING HOLES
12mm DIA
G
FIXING HOLES
12mm DIA
G
E
D
B A E
F
KVAR (415V) A B C D E F G
G
FIXING HOLES
16mm DIA
C
D
J
H
B A
E
125 600 600 2100 2000 680 455 487 440 430
150 600 600 2100 2000 680 455 487 440 430
175 600 600 2100 2000 680 455 487 440 430
200 600 600 2100 2000 680 455 487 440 430
225 600 600 2100 2000 680 455 487 440 430
250 600 600 2100 2000 680 455 487 440 430
275 600 600 2400 2300 680 455 487 440 430
300 600 600 2400 2300 680 455 487 440 430
1)
Not applicable for direct connection
Terminal compartment
A terminal compartment is fitted as standard complete
with suitably rated incoming connection points*.
Alternatively, an incoming protective device
can be fitted to the incoming section.
The device can be fitted to the top or bottom of the capacitor bank.
A detachable undrilled gland plate is fitted as standard.
To accept top or bottom cable entry. Cable entry
will be bottom, unless otherwise specified.
G FIXING HOLES
16mm DIA
C
D
F
J
H
B A
E
100 600 600 2400 2300 680 455 487 440 430
125 600 600 2400 2300 680 455 487 440 430
150 600 600 2400 2300 680 455 487 440 430
175 1200 600 2400 2300 680 455 487 440 430
200 1200 600 2400 2300 680 455 487 440 430
225 1200 600 2400 2300 680 455 487 440 430
250 1200 600 2400 2300 680 455 487 440 430
275 1200 600 2400 2300 680 455 487 440 430
300 1200 600 2400 2300 680 455 487 440 430
325 1200 600 2400 2300 680 455 487 440 430
350 1200 600 2400 2300 680 455 487 440 430
375 1200 600 2400 2300 680 455 487 440 430
400 1200 600 2400 2300 680 455 487 440 430
425 1800 600 2400 2300 680 455 487 440 430
450 1800 600 2400 2300 680 455 487 440 430
475 1800 600 2400 2300 680 455 487 440 430
500 1800 600 2400 2300 680 455 487 440 430
525 1800 600 2400 2300 680 455 487 440 430
550 1800 600 2400 2300 680 455 487 440 430
575 1800 600 2400 2300 680 455 487 440 430
600 1800 600 2400 2300 680 455 487 440 430
1)
Not applicable for direct connection
First number
Protection against solid foreign objects Meaning protection of persons against
IP Requirements access to hazardous parts with:
0 No protection non-protected
1 Full penetration of 50mm diameter sphere not allowed. Contact with hazardous parts not permitted back of hand
2 Full penetration of 12.5mm diameter sphere not allowed finger
The jointed test finger shall have adequate clearance from hazardous parts
3 The access probe of 2.5mm diameter shall not penetrate tool
4 The access probe of 1.0mm diameter shall not penetrate wire
5 Limited ingress of dust permitted (no harmful deposit) wire
6 Totally protected against ingress of dust wire
Second number
Protection against harmful ingress of water Meaning protection from water
IP Requirements
0 No protection. non-protected
1 Protected against vertically falling drops of water limited ingress permitted vertically dripping
2 Protected against vertically falling drops of water dripping up to 15 from the vertical
with enclosure tilted 15 from the vertical limited ingress permitted
3 Protected against sprays to 60 from the vertical limited ingress permitted limited spraying
4 Protected against water splashed from all directions limited ingress permitted splashing from all directions
5 Protected against low pressure jets of water from all directions limited ingress permitted hosing jets from all directions
6 Protected against strong jets of water limited ingress permitted strong hosing jets from all directions.
7 Protected against the effects of immersion between 15cm and 1m temporary immersion
8 Protected against long periods of immersion under pressure continuous immersion
Additional letter
(Optional) Meaning protection of persons against
IP Requirements access to hazardous parts with:
A for use with O Penetration of 50mm diameter sphere up to guard face must not contact hazardous parts. back of hand
B for use with 0 & 1 Test finger penetration to a maximum of 80mm must not contact hazardous parts. finger
C for use with 1 & 2 Wire of 2.5mm diameter x 100mm long must not contact tool
hazardous parts when spherical stop face is partially entered.
D for use with 1, 2 & 3 Wire of 1.0mm diameter x 100mm long must not contact wire
hazardous parts when spherical stop face is partially entered.
Note: limited penetration allowed with all four additional letters.
N3-400...................................................................................70 PFR-03....................................................................................63
N3-4-400................................................................................70 PFR-5......................................................................................63
NLW-4-630.............................................................................78 PFR-W-105.............................................................................63
NLW-4-800.............................................................................82 PFR-W-140.............................................................................63
NLW-630................................................................................78 PFR-W-20...............................................................................63
NLW-800................................................................................82 PFR-W-210.............................................................................63
NZM1-1-XKSA...............................................67, 71, 75, 79, 83 PFR-W-30...............................................................................63
NZM1-XKSA...................................................67, 71, 75, 79, 83 PFR-W-35...............................................................................63
NZM2-XKSA...............................................................75, 79, 83 PFR-W-70...............................................................................63
NZMB1-1-AF100............................................67, 71, 75, 79, 83 SH265SP..............................................................................101
NZMB1-1-AF125............................................67, 71, 75, 79, 83 SH754SP..............................................................................101
NZMB1-1-AF16..............................................67, 71, 75, 79, 83 SNT4LP11K......................................................................79, 83
NZMB1-1-AF20..............................................67, 71, 75, 79, 83 TR-G3/8..................................................................................63
NZMB1-1-AF32..............................................67, 71, 75, 79, 83 UVH4LP11K......................................................................79, 83
NZMB1-1-AF40..............................................67, 71, 75, 79, 83 WA1212...............................................................................103
NZMB1-1-AF50..............................................67, 71, 75, 79, 83
NZMB1-1-AF63..............................................67, 71, 75, 79, 83
NZMB1-1-AF80..............................................67, 71, 75, 79, 83
NZMB1-A100.................................................67, 71, 75, 79, 83
NZMB1-A125.................................................67, 71, 75, 79, 83
NZMB1-A160.................................................67, 71, 75, 79, 83
NZMB1-A20...................................................67, 71, 75, 79, 83
NZMB1-A32...................................................67, 71, 75, 79, 83
NZMB1-A40...................................................67, 71, 75, 79, 83
NZMB1-A50...................................................67, 71, 75, 79, 83
NZMB1-A63...................................................67, 71, 75, 79, 83
NZMB1-A80...................................................67, 71, 75, 79, 83
NZMC1-A100.............................................................75, 79, 83
NZMC1-A125.............................................................75, 79, 83
NZMC1-A160.............................................................75, 79, 83
NZMC1-A20...............................................................75, 79, 83
NZMC1-A32...............................................................75, 79, 83
NZMC1-A40...............................................................75, 79, 83
NZMC1-A50...............................................................75, 79, 83
NZMC1-A63...............................................................75, 79, 83
NZMC1-A80...............................................................75, 79, 83
NZMC2-4-A160KCO...............................................................66
NZMC2-4-A200KCO...............................................................66
NZMC2-4-A250KCO...............................................................66
NZMC2-A125-BT........................................................75, 79, 83
NZMC2-A160-BT........................................................75, 79, 83
NZMC2-A160KCO..................................................................66
NZMC2-A200-BT........................................................75, 79, 83
NZMC2-A200KCO..................................................................66
NZMC2-A250-BT........................................................75, 79, 83
NZMC2-A250KCO..................................................................66
NZMLW-4-A630.....................................................................78
NZMLW-4-A800.....................................................................82
NZMLW-A630........................................................................78
NZMLW-A800........................................................................82
NZMN2-4-A160KCO..............................................................66
NZMN2-4-A200KCO..............................................................66
NZMN2-4-A250KCO..............................................................66
NZMN2-A125-BT.......................................................75, 79, 83
NZMN2-A160-BT.......................................................75, 79, 83
NZMN2-A160KCO..................................................................66
NZMN2-A200-BT.......................................................75, 79, 83
NZMN2-A200KCO..................................................................66
NZMN2-A250-BT.......................................................75, 79, 83
NZMN2-A250KCO..................................................................66
NZMN3-4-A250...............................................................70, 74
NZMN3-4-A320...............................................................70, 74
NZMN3-4-A400...............................................................70, 74
NZMN3-A250...................................................................70, 74
NZMN3-A250BT....................................................................83
NZMN3-A320...................................................................70, 74
NZMN3-A320BT....................................................................83
NZMN3-A400...................................................................70, 74
NZMN3-A400BT....................................................................83
OBK103SP..............................................................................97
OLV725SP.............................................................................101
OLV726SP.............................................................................101
OLV727SP.............................................................................101
OLV728SP.............................................................................101
PD1...............................................................34, 40, 41, 97, 103
PD2.............................................................................34, 40, 51
PD4.......................................................................................101
PFR-003..................................................................................63