Cable Sizing For Main Cable - DB

This document summarizes cable calculations for four circuits: 1) A main cable from the WWTP MCC to a new distribution board, selecting a 1C x 630 mm2 copper cable. 2) A cable from the new distribution board to a chiller plant panel, selecting 4C x 400 mm2 copper cable. 3) A cable from the new distribution board to a water treatment plant panel, selecting 4C x 2.5 mm2 copper cable. 4) A cable from the new distribution board to an irrigation pump package, selecting 4C x 10 mm2 copper cable.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
521 views8 pages

Cable Sizing For Main Cable - DB

This document summarizes cable calculations for four circuits: 1) A main cable from the WWTP MCC to a new distribution board, selecting a 1C x 630 mm2 copper cable. 2) A cable from the new distribution board to a chiller plant panel, selecting 4C x 400 mm2 copper cable. 3) A cable from the new distribution board to a water treatment plant panel, selecting 4C x 2.5 mm2 copper cable. 4) A cable from the new distribution board to an irrigation pump package, selecting 4C x 10 mm2 copper cable.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Cable calculations for New DB (Main I/C Cable) 16-03-17

Circuit Desc. WWTP MCC to NEW DB

Cable selected: 1 Run, 1C x 630 mm2 Cu/XLPE/SWA/LSOH

Installation method: In Trench, Tray & Duct


Current rating of cable: 846 A

Parameter for current rating Conditions for manufacturers current rating Site Derating
(OMAN CABLE) conditions factor
Ambient air temperature 50 C 50 C 1.000
Soil temperature 35 C 40 C NA
Grouping Correction Factor - 9 0.660
Thermal resistivity of Soil 1.2 K.m/W NA NA

Overall derating factor 0.66


Derated cable current carrying capacity: 558.4 A
Nominal voltage 400 V
cos 0.85
sin 0.53
Design load 230 kW
Additional spare capacity 25% Rated according to load
Total design load incl spare 287.5 kW
Number of loaded phases 3
Numbers of cables per. Phase 1
Full load current (I) 287.5/(3*400/3*0,001*0.85) = 488.20 A
Current load per. Cable 488.20 A
Percent of current rating 87.4 %

Voltage drop:
Cable resistance and reactance
Resistance at 90 C conductor temp R= 0.043 /km
Reactance X= 0.087 /km
cable length (L) 50 m
Voltage drop (Even 3-phase load)SQRT(3)* I * L * ( R cos + X sin ) 3.5 V

Voltage drop, % of 400 V 0.87 %

1/2
Cable calculations for Chiller Plant Panel 16-03-17

Circuit Desc. NEW DB to Chiller Plant Panel

Cable selected: 4C x 400 mm2 Cu/XLPE/SWA/LSOH

Installation method: In Trench, Tray & Duct


Current rating of cable: 597 A

Parameter for current rating Conditions for manufacturers current rating Site Derating
(OMAN CABLE) conditions factor
Ambient air temperature 50 C 50 C 1.000
Soil temperature 35 C 40 C NA
Grouping Correction Factor - 6 0.710
Thermal resistivity of Soil 1.2 K.m/W NA NA

Overall derating factor 0.71


Derated cable current carrying capacity: 423.9 A
Nominal voltage 400 V
cos 0.85
sin 0.53
Design load 200 kW
Additional spare capacity 20% Rated according to load
Total design load incl spare 240 kW
Number of loaded phases 3
Numbers of cables per. Phase 1
Full load current (I) 240/(3*400/3*0,001*0.85) = 407.54 A
Current load per. Cable 407.54 A
Percent of current rating 96.1 %

Voltage drop:
Cable resistance and reactance
Resistance at 90 C conductor temp R= 0.066 /km
Reactance X= 0.070 /km
cable length (L) 100 m
Voltage drop (Even 3-phase load)SQRT(3)* I * L * ( R cos + X sin ) 6.6 V

Voltage drop, % of 400 V 1.64 %


Cable calculations for WTP Panel 16-03-17

Circuit Desc. NEW DB to WTP Panel

Cable selected: 4C x 2.5 mm 2 Cu/XLPE/SWA/LSOH

Installation method: In Trench, Tray & Duct


Current rating of cable: 37 A

Parameter for current rating Conditions for manufacturers current rating Site Derating
(OMAN CABLE) conditions factor
Ambient air temperature 50 C 50 C 1.000
Soil temperature 35 C 40 C NA
Grouping Correction Factor - 4 0.760
Thermal resistivity of Soil 1.2 K.m/W NA NA

Overall derating factor 0.76


Derated cable current carrying capacity: 28.1 A
Nominal voltage 400 V
cos 0.85
sin 0.53
Design load 4 kW
Additional spare capacity 25% Rated according to load
Total design load incl spare 5 kW
Number of loaded phases 3
Numbers of cables per. Phase 1
Full load current (I) 5/(3*400/3*0,001*0.85) = 8.49 A
Current load per. Cable 8.49 A
Percent of current rating 30.2 %

Voltage drop:
Cable resistance and reactance
Resistance at 90 C conductor temp R= 9.45 /km
Reactance X= 0.099 /km
cable length (L) 100 m
Voltage drop (Even 3-phase load)SQRT(3)* I * L * ( R cos + X sin ) 11.9 V

Voltage drop, % of 400 V 2.97 %


Cable calculations for IRRIGATION Pump Package 16-03-17

Circuit Desc. NEW DB to IRRIGATION Pump Package

Cable selected: 4C x 10 mm 2 Cu/XLPE/SWA/LSOH

Installation method: In Trench, Tray & Duct


Current rating of cable: 64 A

Parameter for current rating Conditions for manufacturers current rating Site Derating
(OMAN CABLE) conditions factor
Ambient air temperature 50 C 50 C 1.000
Soil temperature 35 C 40 C NA
Grouping Correction Factor - 4 0.760
Thermal resistivity of Soil 1.2 K.m/W NA NA

Overall derating factor 0.76


Derated cable current carrying capacity: 48.6 A
Nominal voltage 400 V
cos 0.85
sin 0.53
Design load 16 kW
Additional spare capacity 25% Rated according to load
Total design load incl spare 20 kW
Number of loaded phases 3
Numbers of cables per. Phase 1
Full load current (I) 20/(3*400/3*0,001*0.85) = 33.96 A
Current load per. Cable 33.96 A
Percent of current rating 69.9 %

Voltage drop:
Cable resistance and reactance
Resistance at 90 C conductor temp R= 2.33 /km
Reactance X= 0.084 /km
cable length (L) 100 m
Voltage drop (Even 3-phase load)SQRT(3)* I * L * ( R cos + X sin ) 11.9 V

Voltage drop, % of 400 V 2.98 %


CU / XLPE / GSWA CURRENT & VOLTAGE DROP RATING
TABLE NO. 41, PAGE NO. 34

ATTACHMENT-1 SHEET 1 OF 4
CU / XLPE / GSWA CURRENT & VOLTAGE DROP RATING
TABLE NO. 43, PAGE NO. 38

ATTACHMENT-1 SHEET 2 OF 4
CU/XLPE/GSWA CABLE TEMP. DE-RATING FACTORS
TABLE NO. 64 & 53, PAGE NO. 50 & 46

ATTACHMENT-1 SHEET 3 OF 4
CU/XLPE/GSWA ELECTRICAL AC PARAMETERS
TABLE NO. 68, PAGE NO. 54

ATTACHMENT-1 SHEET 4 OF 4