Pess Li 1310
Pess Li 1310
Pess Li 1310
Introduction
In North America, we have the NERC Reliability
Standards in place. In other regions around the world,
local grid codes have similar requirements.
The Excitation System SC will report on our many
recent activities related to testing and modeling of
excitation systems, associated controllers and limits to
support meeting these requirements
See also our companion presentation 16PESGM2680
The Impact of Grid Codes Upon Generator Excitation System
Design and Standards
3
Presentations
Presentation Presenter Organization
421.2 Guide for Identification, Testing and
Rich Schaeffer Basler Electric
Evaluation of Dynamic Performance
421.5 Recommended Practice for Models for
Les Hajagos Kestrel Power
Power System Stability Studies
Robert Thornton-
Overview of grid codes Jones
Brush Electric
manufacturer and type of excitation system (e.g. static, brushless, rotating dc, etc.)
model for each excitation system / voltage regulator control system with associated
gains, time constants, and limits
model for each power system stabilizer with associated gains, time constants, and limits
Vpf/VAr Q, pf
PF/VAr
CONTROLLER
VUEL P, Q, V, I
UNDEREXCITATION
LIMITER
VC VOLTAGE VC1 V, I
CURRENT
MEASUREMENT
COMPENSATOR
TRANSDUCER
VOEL
OVEREXCITATION
LIMITER
VFE EFD
SYNCHRONOUS
EXCITATION
EXCITER MACHINE AND
CONTROL
POWER SYSTEM
ELEMENTS EFE IFD
VREF
VS VST VSI
POWER SYSTEM
STABILIZER
DISCONTINUOUS
EXCITATION
CONTROL
14
SE(EFD)
VX
(a)
sKF
1+sTF
footnotes:
(a) VX = EFDSE(EFD)
15
VSI1max VSTmax
PSS
VSI1 sTW1 sTW2 1 1+sT8 N
1+sT1 1+sT3 1+sT10 1+sT12 VST
output
S S KS1
1+sTW1 1+sTW2 1+sT6 + (1+sT9)M + 1+sT2 1+sT4 1+sT11 1+sT13 logic
VPSS
+ (b)
VSI1min VSTmin
KS3
VSI2max
VSI2 sTW3 u1
block
1+sTW3 bypass y KS2
sTW4 logic 1+sT7
VSI2min u2
(a)
1+sTW4
KACT
VOELmin3
Iinst
VOELmin2 VOELmin1
Terr
TFCL
+
OEL
1 1 S
ramp rate
1+sTAoel s logic
Iref Z (f) Tlim
OEL
5 types of OEL input
(d)
KSCALE
1+sTRoel
Ipu
c1
K1[(Ipu/ITFpu) 1]
Ilim
IERRinv1
(e) ITFpu
VINVmax Tmax
Inputs to all
(a) OEL activation logic uses user-selected parameters Ten, Toff, ITHoff, Ireset (e) Parameter KSCALE should be calculated to convert from the per unit base
and Iinst. It also uses the signals Terr, Iact and Iref shown in the block used for the OEL input signal to a per unit base corresponding to the
diagram. rated value for the selected OEL input signal. All other parameters in the
model are expressed in per unit of rated value.
IF {(Terr 0) or [(Iact > Iref) for longer than Ten]} or (Ten =0)
2 UEL types
inputs to all excitation types
VURmax
summation and takeover styles
y2 VUR
y2=|KURVT|
VT
y1 VUerr KUI 1+sTU1 1+sTU3 VUEL
y1=|KUCVTjIT| S KUL+ Q (pu)
VUC + s 1+sTU2 1+sTU4
IT
VUImin VUImin
ra d
VF VUF ius
=K
Center = KUC
KUF UR
UEL not
QT
limiting P (pu)
PT
KUR - KUC
Vars
op. in ()
point UEL
limiting
19
overexcited range
VSCLmax
LV Ioex1
gate A KIoex
KPoex+
2 SCL types
IT 1 Ioex2 B
y = (u) K s
1+sTIT u y
SW1
delayed reactive
+ VSCLmin 0
ISCLlim ISCLerr
power logic
(b)
S VSCL
(c) S
1 + ISCLinv
IQ +
1 S SW1
IQmin
1+sTINV
Iuex2 B
(b) VSCLmax
KIuex
excitation types
S
LV
gate Iuex1
A
KPuex+
s
VSCLmin 0
underexcited range
footnotes:
(b)
The reactive current IQ is defined in this model as the reactive power output of the generator (QT) divided
by the magnitude of the terminal voltage (VT). In other words, IQ is positive for over-excited operation.
SW1 is a user-selected option. When position A is selected, the SCL response is derived from the
takeover styles
reactive current. When position B is selected, the SCL response is derived from reactive power.
(c) The delayed reactive power logic uses user-selected parameters SW2, TDSCL and VSCLdb. It also uses the
signals ISCLerr and ISCLinv shown in the block diagram, and the generator reactive power output QT:
IF [(SW2 = 0) and (ISCLerr > 0 for longer than TDSCL)] or [(SW2 0) and (ISCLinv > 0)] THEN
IF QT > VSCLdb THEN
Ioex2 = ISCLerr
Iuex2 = 0
ELSEIF QT < VSCLdb THEN
Ioex2 = 0
Iuex2 = ISCLerr
ELSE
Ioex2 = 0
Iuex2 = 0
ENDIF
ELSE
Ioex2 = 0
Iuex2 = 0
ENDIF
20
IT VPFLMT
footnotes:
(a) The output of the model (VPF) is an incremental variable that should be added
to the voltage reference setpoint (VREF) in the excitation system model.
(b) The signal PFnorm is the normalized power factor of the machine, while
PFREFnorm is the desired (reference) setpoint, using the same normalization as
PFnorm.
(c) The PF controller logic uses user-selected parameters VITmin, VVTmin, and VVTmax.
It also requires the signals PFerr and the magnitudes of the generator terminal
voltage (VT) and current (IT). The logic also depends on the status of the
excitation limiters, OEL, UEL and/or SCL.
Verr = 0
IF OEL and UEL and SCL are inactive
IF (IT > VITmin) and (VT > VVTmin) and (VT < VVTmax)
Verr = PFerr
ENDIF
ENDIF
21
ST3C General Electric Compound Power Source and Potential Power Source GENERREX excitation
systems (GENERREX is a trademark of General Electric Co.)
ST4C Basler DECS applied to static excitation, Brush PRISMIC applied to static excitation, General
Electric EX2000/2100/2100e bus fed potential source and static compound source and
GENERREX-PPS or GENERREX-CPS; Canadian General Electric SILCOmatic 5, Basler/Eaton
Cutler-Hammer ECS2100 static excitation system, Andritz Hydro THYNE applied to static
excitation, Emerson/Emerson Ovation DGC or REIVAX static excitation systems.
ST5C UNITROL D, P, F, and 5000 (trademarks of Asea Brown Boveri); Brush DCP.
ST6C THYRIPOL (a trademark of Siemens AG) and Basler/Eaton Cutler-Hammer ECS2100 static
excitation systems.
ST7C ALSTOM excitation systems Eurorec, Microrec K4.1, ALSPA P320 (ALSPA P320 is a trademark
of ALSTOM), ControGen HX.
ST8C Andritz Hydro THYNE applied to static excitation
ST9C GE Power Conversion SEMIPOL
ST10C UNITROL F, 5000, 6080, 6800 (trademarks of Asea Brown Boveri) applied to static excitation
23
421.2 Purpose
Provide a basis for evaluating the closed loop
performance of excitation control systems
Confirm the adequacy of mathematical
models for excitation control systems for use
in analytical studies of power systems
3
manufacturer and type of excitation system (e.g. static, brushless, rotating dc, etc.)
model for each excitation system/voltage regulator control system with associated
gains, time constants, and limits
model for each power system stabilizer with associated gains, time constants, and limits
Associated generator model
4
Frequency
Response
Measurement
for PSS
compensation
*figure courtesy KPE
Built-in Dynamic System Analyzer to perform
Generator Frequency Response with Bode Plot
Introduction
In North America, we have the NERC Reliability
Standards in place. In other regions around the world,
local grid codes have similar requirements.
The Excitation System SC will report on our many
recent activities related to testing and modeling of
excitation systems, associated controllers and limits to
support meeting these requirements
See also our companion presentation 16PESGM2680
The Impact of Grid Codes Upon Generator Excitation System
Design and Standards
3
Presentations
Presentation Presenter Organization
421.2 Guide for Identification, Testing and
Rich Schaeffer Basler Electric
Evaluation of Dynamic Performance
421.5 Recommended Practice for Models for
Les Hajagos Kestrel Power
Power System Stability Studies
Robert Thornton-
Overview of grid codes Jones
Brush Electric
Leading Var Capability of 0.7 Power Factor at 35% Registered Power Capacity.
More Onerous Than Other Grid Codes.
Need to be Prepared to Demonstrate.
Panel Session
Use of the New Revisions of IEEE Std. 421.2 and 421.5 to
Satisfy International Grid Code Requirements
Introduction
North American reliability standards
NERC Std. MOD-026 and MOD-027
Transmission Planner has 90 calendar days to respond if
provided models are usable or not.
Models initialize without error
No spurious behavior during a no-disturbance (flat) simulation
Adequate response (stable response) following a disturbance that is
otherwise stable
Usability in these Standards is not related to an
assessment of adequacy of the dynamic response of
the equipment
3
Simplified Tests
Open Circuit Step Response
Response Ratio Test
Online Voltage Reference Step Response
PSS model testing
Excitation limiter testing
Turbine/speed governor testing
5
Synthetic System
et E
iG
Re Xe
iline
Pload +j Qload
(MW)
P
2700
PSS
SMIB 2500
20.1
no PSS
(kV)
Et
19.7
XE = 20% 19.5
200
150
(Vdc)
100
Efg
50
0
-50
0.0010
0.0005
speed
0
(pu)
-0.0005
-0.0010
-0.0015
0 2 4 6 8 10
Time (seconds)
12
Inter-area
(MW)
2800
P
2760
PSS
SMIB 2720
20.2
no PSS
(kV)
Et
19.8
19.6
XE = 200% 19.4
200
150
(Vdc)
100
Efg
50
0
-50
0.00075
0.00025
speed
(pu)
-0.00025
-0.00075
0 5 10 15
Time (seconds)
13
No PSS
3100
2900
(MW)
P
2700
2500 XE=20 pu
XE=2.0 pu
2300 XE=0.2 pu
0.002
0.001
spd dev
(pu)
-0.001
-0.002
0 5 10 15 20 25
Time (seconds)
14
Pload +j Qload
60.2
60.15
60.1
60.05
60
frequency (Hz)
59.95
59.85
59.8
59.75
59.7
59.65
0 10 20 30 40 50 60
time (seconds)
1
PSS
Application of PSS appears as an element in
the 421 series of IEEE standards:
421.5 includes standard models of PSS
equipment used by manufacturers
421.2 includes information on dynamic
performance testing of excitation systems that
incorporate PSS
4
VSI1max VSTmax
PSS
VSI1 sTW1 sTW2 1 1+sT8 N
1+sT1 1+sT3 1+sT10 1+sT12 VST
output
S S KS1
1+sTW1 1+sTW2 1+sT6 + (1+sT9)M + 1+sT2 1+sT4 1+sT11 1+sT13 logic
VPSS
+ (b)
VSI1min VSTmin
KS3
VSI2max
VSI2 sTW3 u1
block
1+sTW3 bypass y KS2
sTW4 logic 1+sT7
VSI2min u2
(a)
1+sTW4
1
5
421.2
Basic requirements for tuning AVRs, with and
without PSS
Small signal, time domain performance indices
(step response rise time, overshoot, regulation,
damping ratio)
Performance measurements required to
determine PSS effectiveness
Frequency domain methods and measurements
9
421.2
AVR response
Transient Stability
vs.
Small Signal Stability
10
421.2
Testing Basics
11
Tuning requirement
PSS Elements
Signal conditioning
And mixing Gain Compensation Limiter
VSI1max VSTmax
PSS
VSI1 sTW1 sTW2 1 1+sT8 N
1+sT1 1+sT3 1+sT10 1+sT12 VST
output
S S KS1
1+sTW1 1+sTW2 1+sT6 + (1+sT9)M + 1+sT2 1+sT4 1+sT11 1+sT13 logic
VPSS
+ (b)
VSI1min VSTmin
KS3
VSI2max
VSI2 sTW3 u1
block
1+sTW3 bypass y KS2
sTW4 logic 1+sT7
VSI2min u2
(a)
1+sTW4
1
PSS Requirements*
(*as specified in some regions)
Compensation (e.g.,
within 30 degrees)
Washout (maximum time)
VSI1max VSTmax
PSS
VSI1 sTW1 sTW2 1 1+sT8 N
1+sT1 1+sT3 1+sT10 1+sT12 VST
output
S S KS1
1+sTW1 1+sTW2 1+sT6 + (1+sT9)M + 1+sT2 1+sT4 1+sT11 1+sT13 logic
VPSS
+ (b)
VSI1min VSTmin
KS3
VSI2max
VSI2 sTW3 u1
block
1+sTW3 bypass y KS2
sTW4 logic 1+sT7
VSI2min 1+sTW4 u2
(a) Gain Limiter (minimum
1
(minimum requirement) requirement, e.g.,
5 percent)
14
Adequate?
AVR and PSS application are some of the most
difficult topics for reliability organizations, grid
codes, compliance offices
The combination of the 421 standard series
(including the referenced PSS tutorial)
provides more than enough information for
the purposes of reliability standards
15
More
If anything, these documents should be
referenced and consulted more
Voltage regulation requirements are usually very
simplistic
PSS requirements are lesser known, but are
tending to become more technical
Grid codes are just starting to get a handle on
performance requirements/standards, so these
documents will be essential
1
Introduction
In North America, we have the NERC Reliability
Standards in place. In other regions around the world,
local grid codes have similar requirements.
The Excitation System SC will report on our many
recent activities related to testing and modeling of
excitation systems, associated controllers and limits to
support meeting these requirements
See also our companion presentation 16PESGM2680
The Impact of Grid Codes Upon Generator Excitation System
Design and Standards
3
Presentations
Presentation Presenter Organization
421.2 Guide for Identification, Testing and
Rich Schaeffer Basler Electric
Evaluation of Dynamic Performance
421.5 Recommended Practice for Models for
Les Hajagos Kestrel Power
Power System Stability Studies
Robert Thornton-
Overview of grid codes Jones
Brush Electric
NERC PRC-019-2 Verification that generator voltage regulator controls and limit
functions are coordinated with the generators capabilities and protective relays
Study results with plots or data that could be plotted for the following:
Any other limit that could restrict the megawatt or megavar capability.
NERC PRC-019-2 Verification that generator voltage regulator controls and limit
functions are coordinated with the generators capabilities and protective relays
Excitation Limiters
Over-Excitation Limiters (OEL)
Under-Excitation Limiters (UEL)
Over-Voltage (O/V) and V/Hz
Stator Current Limiter (SCL)
10
Example: 40
SCL
Stator Limit
UEL
PQ Monitor Trip
NERC PRC-019 Coordination Minimum Field
40 Zone 2
30 40 Zone 1
Rated PF 0.9
0.95 PF
coordination of limiters,
10
protection and capability and
-20
-50
11
HV Grid
Unit
Breaker
Main
Transformer
24T
Overview of PT Relays
Protective 40 21 32 59 24
Devices Controls
Limiters
CT
Service Transformer
Exciter
M M M
~ Generator
51V
Auxiliary
Loads
50
5IE
12
Coordination may include the excitation limiter, relays, the generator and other
equipment, here the GST. Often equipment damage curves are not available
and we instead refer to applicable protection standards *example plot courtesy KPE
14
directional
-0.2
UEL
LOE
-0.4
-0.6
0 0.2 0.4 0.6 0.8 1.0 1.2
LOE
-0.4
-0.6
NO UEL
-0.8
0 2 4 6 8 10
Time (seconds)
16
LOE
-0.8
-1.0
0.5 0.7 0.9 1.1 1.3 1.5