Analysis of Synchronous Generator Internal Insulation Failures
Analysis of Synchronous Generator Internal Insulation Failures
E.B. Bakie, Student Member, IEEE, B. K. Johnson, Member, IEEE, H. L. Hess, Senior Member, IEEE,
and J. D. Law, Member, IEEE
Abstract-Winding insulation failures within a synchronous There are many resources regarding synchronous machines
generator cause extensive damage and are expensive to repair. and the transient effects associated with fault conditions [2].
The understanding of the machine behavior during internal However, these resources focus primarily on the effects of
failures is very important for the full protection of the machine. external fault conditions and little is written on the effects of
Within the literature, little is written relating to modeling, internal fault conditions. Most of the literature written on the
analysis, and experimental testing of synchronous generators
effects of internal faults of synchronous machines focuses on
during internal fault conditions. This paper provides a
summary of an experimental approach taken to capture this
modeling and analysis rather than experimentation.
phenomenon. These results will discuss real-time measurements This paper focuses on experimental measurement and
taken during controlled internal faults on a laboratory scale analysis of internal fault conditions of a 220-volt, 20 h.p.
generator. This data will also be compared to data recorded by laboratory synchronous generator. The internal faults
protective relays during an evolving internal insulation failure explored in the experimentation include controlled turn-to-
of a 145 MVA utility generator. turn, turn-to-ground, and turn-to-turn-to-ground. This paper
only discusses the data taken for turn-to-ground faults. The
I. INTRODUCTION results include turn-to-ground internal faults for two
Full protection of synchronous generators during fault generator-operating points. A commercial protective relay
conditions is an essential part of power system reliability. was used collect data during the fault conditions. The system
Failures of these machines result in lost revenues, expensive tested was high resistance grounded.
repair costs, losses in production capacity and possibly This paper also compares and analyzes data collected by
service to customers. There is an ongoing need for a better protective relays during an internal fault of a utility generator
understanding of the effects of internal faults within to the data collected during the experimentation. The utility
synchronous machines in order to provide better generator generator failure resulted initially from an internal turn-to-
protection. ground fault that evolved into a more severe fault condition.
Stator ground fault protection of synchronous generators is Only the time period where the turn-to-ground was present
very important because of the potential amount of damage will be compared to the experimental results in this paper.
caused by ground faults. The goal of the protection is to The primary goal of the experimentation is to analyze
detect the first ground fault quickly while the current is low internal faults and provide recommendations for updating
before the fault evolves into a double-line-to-ground fault, relay settings for 100% stator winding protection.
which will cause extensive damage and higher repair costs
[1]. The protection needs to be configured so an insulation II. EXPERIMENTAL SETUP
failure anywhere in the winding is detected and corrective The experimental setup consists of an induction machine
action taken to limit the damage to the generator. with pilot exciter, a microprocessor relay, circuit breakers,
Stator ground faults can cause extensive damage to the instrumentation transformers, and other auxiliary equipment.
stator winding insulation, the stator conductors as well as The general layout of the system is shown in Fig. 1. The
damage to the core structure. Mechanical damage could also synchronous generator tested is a 6 pole, 220V, 20-hp
occur. With properly configured generator protection, the machine driven by an induction motor in a motor-generator
damage caused by internal faults can be reduced. set.
One hundred percent stator ground fault protection can be
achieved on high resistance grounded synchronous
generators by implementing a differential over-voltage
scheme (59G) across the grounding resistor [1]. Both the 60
Hz and 180 Hz voltages across the grounding resistor are
monitored. Based on the percentage of the above quantities,
the protective relay can detect a ground fault condition along
the entire length of the stator windings.
Table I
Stator Winding Tap Locations and Number of Turns from the Neutral
Terminal.
107
VA in Fig. 6. Fig. 6 also shows the fault current and the
phase-B and C voltages during the fault, as well as the
neutral-to-ground voltage. During this fault the tripping of
the generator excitation was delayed as shown. The tripping
of the field was delayed to collect more data with the fault
was on the stator. This is shown in Fig. 6 with the SELogic 3
line at the bottom of the figure. The line gets thicker when
the relay detects the fault and the T indicates when the
relay sent the trip command. The dotted vertical line
indicates when the relay event record triggered. The relay is
set to record eight cycles of pre-fault data.
108
Second, a light load was added to the generator and the and a circuit breaker was added in the fault path so the
fault was repeated at the same location and terminal voltage internal fault could be removed. During this fault the
of 110VLL. Fig. 8 shows the data captured during the fault. machine operated under the same conditions as the first case.
IA in Fig. 8 is the measured fault current; VA is the voltage Fig. 10 shows the data captured during this condition. Fig.
at the fault point. Again, the tripping of the generator 10 shows the fault current magnitude to be the same as Fig.
excitation was delayed. Comparing Fig. 8 to Fig. 6, the fault 6. However, looking at the SELogic 3 line at the bottom of
current has a higher magnitude and the neutral-to-ground the figure the relay detected the fault much quicker. Also
voltage contains more harmonics. notice that the fault current goes to zero, indicating that the
protection system actually cleared the fault. Note, once the
generator excitation is tripped, the fault current begins to
decay.
Fig. 8. Internal fault 10% up from the neutral with light load on the generator
Fig. 10. Internal Fault 10% up from the neutral with no load on the
and excitation tripping delayed.
generator and excitation tripping not delayed.
For the third case, the tripping of the field was not delayed
109
REFERENCES
[1] J. L. Blackburn, Protective Relaying: Principles and Applications, 2nd
ed, New York: Marcel Dekker, 1998, pp. 231-274.
[2] P. P. Reichmeider, D. Querry, C. A. Gross, D. Novosel, S. Salon,
"Partitioning of Synchronous Machine Windings for Internal Fault
Analysis," IEEE Trans. on Energy Conversion, vol 3, Dec. 2000, p. 1.
[3] P. M. Anderson, Analysis of Faulted Power Systems, Iowa State
University Press, 1973, p. 202.
APPENDIX
Table II
Generator Technical Data
Rated Voltage 220V
Rated Current 56 A
Power 20 h.p.
Fig.11: Initial stator ground fault detected by protection relays on a 145- Frequency 60 Hz
MVA utility generator. Number of Phases 3
Number of Poles 6
The initial stator ground fault on the utility generator Speed 1200 RPM
evolved into a more severe phase-to-phase-to-ground fault Number of Slots/Phase/Pole 6
condition and later a three-phase fault with current Turns/Coil 10
Turns/Slot 20
magnitudes reaching values above 13kA. This fault led to Pitch 7/9
the entire machine needing to be rewound. Fig. 12 shows the Number of Damper Bars/Pole 5
current waveforms captured during the later part of the Number of Slots 54
internal fault. Fig. 12 shows the fault currents beginning to Xd 2.8 ohm
decay, as did the laboratory generator when the relay Xq 2.7 ohm
Rf 16 ohm
detected the fault. This case is different because the currents
Lf 3H
begin to rise again rather than continue decaying as the case Tdo 186 msec
shown in Fig. 6.
BIOGRAPHIES
Eric B. Bakie received the B.S. degree in electrical from the University of
Idaho, Moscow, ID in 2003. He is presently pursuing his Master of Science
in electrical engineering at the University of Idaho. His research interests
include power system protection, short circuit studies, and electrical
machines. Mr. Bakie is also a certified EIT in the state of Idaho.
110