CSC-211 Multifunction Protection IED Technical Application Manual - V1.01 PDF
CSC-211 Multifunction Protection IED Technical Application Manual - V1.01 PDF
CSC-211 Multifunction Protection IED Technical Application Manual - V1.01 PDF
Standardized: Li Lianchang
Version V1.01
Doc.Code0SF.451.085(E)
Issued Date2012.8.31
VersionV1.01
Doc. Code: 0SF.451.085(E)
Issued Date2012.8
Copyright owner: Beijing Sifang Automation Co., Ltd
Note: the company keeps the right to perfect the instruction. If equipment does not agree with
the instruction at anywhere, please contact our company in time. We will provide you with
corresponding service.
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and
dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.
The data contained in this manual is intended solely for the IED description and is not to be
deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards
as a result it is possible that there may be some differences between the hardware/software
product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
This manual describes the functions, operation, installation, and placing into
service of IED CSC-211. In particular, one will find:
Target audience
This manual mainly face to installation engineer, commissioning engineer and
operation engineer with perfessional electric and electrical knowledge, rich
experience in protection function, using protection IED, test IED, responsible
for the installation, commissioning, maintenance and taking the protection
IED in and out of normal service.
Technical support
In case of further questions concerning the CSC family, please contact
SiFang compay or your local SiFang representative.
Safety information
Avoid to touching the circuitry when covers are removed. The IED
contains electirc circuits which can be damaged if exposed to static
electricity. Lethal high voltage circuits are also exposed when covers
are removed
Using the isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present
Changing the setting value group will inevitably change the IEDs
operation. Be careful and check regulations before making the
change
Contents
Chapter 1 Introduction .................................................................................................................. 1
1 Overview ..................................................................................................................................... 2
2 Features ...................................................................................................................................... 3
3 Functions..................................................................................................................................... 5
3.1 Protection functions ..................................................................................................... 5
3.2 Control functions .......................................................................................................... 6
3.3 Monitoring functions ..................................................................................................... 6
3.4 Station communication ................................................................................................ 6
3.5 IED software tools ........................................................................................................ 7
Chapter 2 General IED application ............................................................................................... 9
1 Display on LCD screen ............................................................................................................. 10
1.1 LCD screen display function ...................................................................................... 10
1.2 Analog display function .............................................................................................. 10
1.3 Report display function .............................................................................................. 10
1.4 Menu dispaly function ................................................................................................ 10
2 Report record ............................................................................................................................ 11
3 Disturbance recorder ................................................................................................................ 12
3.1 Introduction ................................................................................................................ 12
3.2 Fault recording ........................................................................................................... 12
3.3 Wave recording .......................................................................................................... 12
3.4 Sequence of event record.......................................................................................... 13
3.5 Operation record ........................................................................................................ 13
4 Self-supervision function ........................................................................................................... 14
4.1 Introduction ................................................................................................................ 14
4.2 Self-supervision principle ........................................................................................... 14
4.3 Self-supervision report ............................................................................................... 14
5 Time synchroniation function .................................................................................................... 16
5.1 Introduction ................................................................................................................ 16
5.2 Synchronization principle ........................................................................................... 16
5.2.1 Synchronization from IRIG......................................................................................... 17
5.2.2 Synchronization via PPS or PPM .............................................................................. 17
5.2.3 Synchronization via SNTP ......................................................................................... 17
6 Setting ....................................................................................................................................... 18
6.1 Introduction ................................................................................................................ 18
6.2 Operation principle ..................................................................................................... 18
7 Authorization ............................................................................................................................. 19
7.1 Introduction ................................................................................................................ 19
Chapter 3 Overcurrent protection ............................................................................................... 21
1 Overcurrent protection .............................................................................................................. 22
1.1 Introduction ................................................................................................................ 22
1.2 Protection principle .................................................................................................... 22
1.2.1 Time characteristics ........................................................................................... 22
1.2.2 Inrush restraint function ..................................................................................... 24
1.2.3 Low voltage component ..................................................................................... 24
1.2.4 Direction determination feature .......................................................................... 25
1.2.5 Logic diagram..................................................................................................... 26
1.3 Input and output signals ............................................................................................ 28
1.4 Setting parameters .................................................................................................... 29
1.4.1 Setting list........................................................................................................... 29
1.5 Reports ...................................................................................................................... 30
1.6 Technical data ........................................................................................................... 31
Approx. 0.95 at I/In 0.5 ................................................................................................... 31
Chapter 4 Earth fault protection ................................................................................................. 33
1 Earth fault protection ................................................................................................................. 34
1.1 Introduction ................................................................................................................ 34
1.2 Protection principle .................................................................................................... 35
1.2.1 Time characteristic ............................................................................................. 35
1.2.2 Inrush restraint ................................................................................................... 36
1.2.3 Direction determination feature .......................................................................... 37
1.2.4 Logic diagram..................................................................................................... 39
1.3 Input and output signals ............................................................................................ 41
1.4 Setting parameters .................................................................................................... 42
1.4.1 Setting list........................................................................................................... 42
1.5 IED reports................................................................................................................. 44
1.6 Technical data ........................................................................................................... 44
Approx. 0.95 at I/Ir 0.5 .................................................................................................... 44
Chapter 5 Sensitive earth fault protection .................................................................................. 47
1 Sensitive overcurrent protection ............................................................................................... 48
1.1 Introduction ................................................................................................................ 48
1.2 Protection principle .................................................................................................... 48
1.2.1 Time characteristic ............................................................................................. 48
1.2.2 Direction determination feature .......................................................................... 49
1.2.3 Logic diagram..................................................................................................... 52
1.3 Input and output signals ............................................................................................ 53
1.4 Setting parameters .................................................................................................... 54
1.4.1 Setting list........................................................................................................... 54
1.5 IED reports................................................................................................................. 56
1.6 Technical data ........................................................................................................... 56
Chapter 6 Negative-sequence overcurrent protection ............................................................... 59
1 Negative-sequence overcurrent protection ............................................................................... 60
1.1 Introduction ................................................................................................................ 60
1.2 Protection principle .................................................................................................... 60
1.2.1 Protection function description ........................................................................... 60
1.2.2 Logic diagram..................................................................................................... 61
1.3 Input and output signals ............................................................................................ 62
1.4 Setting parameters .................................................................................................... 62
1.4.1 Setting list ........................................................................................................... 63
1.5 IED reports ................................................................................................................. 64
1.6 Technical data ........................................................................................................... 64
Chapter 7 Thermal overload protection ...................................................................................... 67
1 Thermal overload protection ..................................................................................................... 68
1.1 Introduction ................................................................................................................ 68
1.2 Protection principle .................................................................................................... 68
1.2.1 Function description ........................................................................................... 68
1.3 Input and output signals............................................................................................. 70
1.4 Setting parameters .................................................................................................... 70
1.4.1 Setting list ........................................................................................................... 70
1.5 IED reports ................................................................................................................. 71
1.6 Technical data ........................................................................................................... 71
Chapter 8 Current overload protection ....................................................................................... 73
1 Current overload protection ...................................................................................................... 74
1.1 Function description ................................................................................................... 74
1.1.1 Logic diagram ..................................................................................................... 74
1.2 Input and output signals............................................................................................. 74
1.3 Setting parameter ...................................................................................................... 75
1.3.1 Setting list ........................................................................................................... 75
1.4 IED reports ................................................................................................................. 75
Chapter 9 Overvoltage protection ............................................................................................... 77
1 Overvoltage protection .............................................................................................................. 78
1.1 Introduction ................................................................................................................ 78
1.2 Protection principle .................................................................................................... 78
1.2.1 Overvoltage protection principle ........................................................................ 78
1.2.2 Voltage connection ............................................................................................. 79
1.2.3 Logic diagram ..................................................................................................... 80
1.3 Input and output signals............................................................................................. 81
1.4 Setting parameters .................................................................................................... 81
1.4.1 Setting list ........................................................................................................... 81
1.5 IED reports ................................................................................................................. 82
1.6 Technical data ........................................................................................................... 83
Chapter 10 Undervoltage protection............................................................................................. 85
1 Undervoltage protection ............................................................................................................ 86
1.1 Introduction ................................................................................................................ 86
1.2 Protection principle .................................................................................................... 86
1.2.1 Protection function description ........................................................................... 86
1.2.2 Voltage connection ............................................................................................. 87
1.2.3 Depending on the VT location ............................................................................ 88
1.2.4 Logic diagram ..................................................................................................... 89
1.3 Input and output signals............................................................................................. 91
1.4 Setting parameter ...................................................................................................... 92
1.4.1 Setting list........................................................................................................... 92
1.5 IED reports................................................................................................................. 93
1.6 Technical data ........................................................................................................... 93
Chapter 11 Displacement voltage protection ............................................................................... 95
1 Displacement voltage protection............................................................................................... 96
1.1 Introduction ................................................................................................................ 96
1.2 Protection principle .................................................................................................... 96
1.2.1 Displacement voltage input ................................................................................ 96
1.2.2 Protection description ........................................................................................ 96
1.2.3 Logic diagram..................................................................................................... 97
1.3 Input and output signals ............................................................................................ 98
1.4 Setting parameter ...................................................................................................... 99
1.4.1 Setting list........................................................................................................... 99
1.5 IED reports............................................................................................................... 100
1.6 Technical data ......................................................................................................... 100
Chapter 12 Circuit breaker failure protection.............................................................................. 103
1 Circuit breaker failure protection ............................................................................................. 104
1.1 Introduction .............................................................................................................. 104
1.2 Protection principle .................................................................................................. 104
1.2.1 Protection description ...................................................................................... 104
1.2.2 Current criterion evaluation .............................................................................. 105
1.2.3 Circuit breaker auxiliary contact evaluation ..................................................... 105
1.2.4 Logic diagram................................................................................................... 106
1.3 Input and output signals .......................................................................................... 107
1.4 Setting parameter .................................................................................................... 108
1.4.1 Setting list......................................................................................................... 108
1.5 IED reports............................................................................................................... 108
1.6 Technical data ......................................................................................................... 109
Chapter 13 Dead zone protection ............................................................................................... 111
1 Dead zone protection ...............................................................................................................112
1.1 Introduction ...............................................................................................................112
1.2 Protection principle ...................................................................................................112
1.2.1 Function description ..........................................................................................112
1.2.2 Logic diagram....................................................................................................114
1.3 Input and output signals ...........................................................................................114
1.4 Setting parameter .....................................................................................................115
1.4.1 Setting list..........................................................................................................115
1.5 IED reports................................................................................................................116
1.6 Technical data ..........................................................................................................116
Chapter 14 Synchro-check and energizing check function .........................................................117
1 Synchro-check and energizing check function ........................................................................118
1.1 Introduction ...............................................................................................................118
1.2 Function principle .....................................................................................................118
1.2.1 Synchro-check mode ........................................................................................119
1.2.2 Energizing check mode .................................................................................... 120
1.2.3 Override mode ................................................................................................. 121
1.2.4 Logic diagram ................................................................................................... 121
1.3 Input and output signals........................................................................................... 122
1.4 Setting parameter .................................................................................................... 123
1.4.1 Setting list ......................................................................................................... 123
1.5 IED reports ............................................................................................................... 124
1.6 Technical data ......................................................................................................... 125
Chapter 15 Autoreclosing function ............................................................................................. 127
1 Autoreclosing function ............................................................................................................. 128
1.1 Introduction .............................................................................................................. 128
1.2 Function principle ..................................................................................................... 128
1.2.1 Auto-reclosing initiation modules ..................................................................... 128
1.2.2 Autoreclosing logic ........................................................................................... 129
1.3 Input and output signals........................................................................................... 132
1.4 Setting parameter .................................................................................................... 134
1.4.1 Setting list ......................................................................................................... 134
1.5 IED reports ............................................................................................................... 136
1.6 Technical data ......................................................................................................... 137
Chapter 16 Unbalance protection ............................................................................................... 139
1 Unbalance protection .............................................................................................................. 140
1.1 Introduction .............................................................................................................. 140
1.2 Protection principle .................................................................................................. 140
1.3 Input and output signals........................................................................................... 146
1.4 Setting parameter .................................................................................................... 147
1.4.1 Setting list ......................................................................................................... 147
1.5 IED reports ............................................................................................................... 147
Chapter 17 Under current monitoring ......................................................................................... 149
1 Under current monitoring ........................................................................................................ 150
1.1 Introduction .............................................................................................................. 150
1.2 Protection principle .................................................................................................. 150
1.2.1 Function description ......................................................................................... 150
1.2.2 Logic diagram ................................................................................................... 150
1.3 Input and output signals........................................................................................... 151
1.4 Setting parameter .................................................................................................... 151
1.4.1 Setting list ......................................................................................................... 151
1.5 IED reports ............................................................................................................... 152
Chapter 18 Load shedding protection ........................................................................................ 153
1 Low frequency load shedding protection ................................................................................ 154
1.1 Introduction .............................................................................................................. 154
1.2 Protection principle .................................................................................................. 154
1.2.1 Function description ......................................................................................... 154
1.3 Input and output signals........................................................................................... 155
1.4 Setting parameter .................................................................................................... 156
1.4.1 Setting list......................................................................................................... 156
1.5 IED reports............................................................................................................... 157
2 Low voltage load shedding protection .................................................................................... 158
2.1 Introduction .............................................................................................................. 158
2.2 Protection principle .................................................................................................. 158
2.2.1 Funciton description ......................................................................................... 158
2.3 Input and output signals .......................................................................................... 159
2.4 Setting parameter .................................................................................................... 160
2.4.1 Setting list......................................................................................................... 160
2.5 IED reports............................................................................................................... 161
3 Overload load shedding protection ......................................................................................... 162
3.1 Introduction .............................................................................................................. 162
3.2 Protection principle .................................................................................................. 162
3.2.1 Fucntion description ......................................................................................... 162
3.3 Input and output signals .......................................................................................... 163
3.4 Setting parameter .................................................................................................... 164
3.4.1 Setting list......................................................................................................... 164
3.5 IED reports............................................................................................................... 164
3.6 Technical data ......................................................................................................... 165
Chapter 19 Fast busbar protection scheme ............................................................................... 167
1 Fast busbar protection scheme .............................................................................................. 168
1.1 Function description ................................................................................................ 168
1.2 Input and output signals .......................................................................................... 169
1.3 Setting parameter .................................................................................................... 170
1.3.1 Setting list......................................................................................................... 170
1.4 IED reports............................................................................................................... 170
Chapter 20 Secondary system supervision ................................................................................ 171
1 Current circuit supervision ...................................................................................................... 172
1.1 Function principle .................................................................................................... 172
1.1.1 Function description ......................................................................................... 172
1.1.2 Logic diagram................................................................................................... 172
1.2 Input and output signals .......................................................................................... 172
1.3 Setting parameter .................................................................................................... 173
1.3.1 Setting list......................................................................................................... 173
1.4 IED reports............................................................................................................... 173
2 Fuse failure supervision VT .................................................................................................... 174
2.1 Introduction .............................................................................................................. 174
2.2 Function principle .................................................................................................... 174
2.2.1 Three phases (symmetrical) VT Fail ................................................................ 174
2.2.2 Single/two phases (asymmetrical) VT Fail ....................................................... 175
2.2.3 The fourth voltage U4 VT fail ........................................................................... 175
2.2.4 Logic diagram................................................................................................... 175
2.3 Input and output signals .......................................................................................... 177
2.4 Setting parameter .................................................................................................... 177
2.4.1 Setting list ......................................................................................................... 177
2.5 IED reports ............................................................................................................... 178
2.6 Technical data ......................................................................................................... 178
Chapter 21 Monitoring function .................................................................................................. 181
1 Switching devices status monitoring ....................................................................................... 182
2 Self-supervision ...................................................................................................................... 182
Chapter 22 Station communication ............................................................................................ 183
1 Overview ................................................................................................................................. 184
1.1 Protocol .................................................................................................................... 184
1.1.1 IEC61850-8 communication protocol ............................................................... 184
1.1.2 IEC60870-5-103 communication protocol........................................................ 184
1.2 Communication port ................................................................................................. 185
1.2.1 Front communication port ................................................................................ 185
1.2.2 RS485 communication ports ............................................................................ 185
1.2.3 Ethernet communication ports ......................................................................... 185
1.3 Technical data ......................................................................................................... 185
1.4 Typical substation communication scheme ............................................................. 188
1.5 Typical time synchronizing scheme ......................................................................... 188
Chapter 23 Hardware ................................................................................................................. 189
1 Introduction ............................................................................................................................. 190
1.1 IED structure ............................................................................................................ 190
1.2 IED module arrangement......................................................................................... 190
2 Local human-machine interface .............................................................................................. 192
2.1 Introduction .............................................................................................................. 192
2.2 Liquid crystal display (LCD) ..................................................................................... 192
2.3 LED .......................................................................................................................... 193
2.4 Keyboard ................................................................................................................. 193
2.5 IED menu ................................................................................................................. 194
2.5.1 Menu construction ............................................................................................ 194
2.5.2 Operation status ............................................................................................... 196
2.5.3 Operation status ............................................................................................... 197
2.5.4 Operation configuration .................................................................................... 197
2.5.5 Settings ............................................................................................................ 197
2.5.6 Report............................................................................................................... 197
2.5.7 Communication configuration .......................................................................... 198
2.5.8 Testing .............................................................................................................. 198
2.5.9 Device setup .................................................................................................... 199
2.5.10 Device information ........................................................................................... 200
3 Analog input module ............................................................................................................... 201
3.1 Introduction .............................................................................................................. 201
3.2 Terminals of analog input module ........................................................................... 202
3.3 Technical data ......................................................................................................... 206
4 Fast binary Input & Output module ......................................................................................... 208
4.1 Introduction .............................................................................................................. 208
4.2 Terminals of fast binary input & output module ....................................................... 208
4.3 Technical data ......................................................................................................... 210
5 Fast binary output module ...................................................................................................... 212
5.1 Introduction .............................................................................................................. 212
5.2 Terminals of fast binary output module ................................................................... 212
6 Binary input & output module .................................................................................................. 214
6.1 Introduction .............................................................................................................. 214
6.2 Terminals of binary & output module ....................................................................... 214
7 CPU module............................................................................................................................ 217
7.1 Introduction .............................................................................................................. 217
7.2 Terminals of CPU module ....................................................................................... 217
7.3 Technical data ......................................................................................................... 219
8 Power supply module ............................................................................................................. 221
8.1 Introduction .............................................................................................................. 221
8.2 Terminals of power supply module .......................................................................... 221
8.3 Technical data ......................................................................................................... 223
9 Technical data ......................................................................................................................... 224
9.1 Type tests ................................................................................................................ 224
9.2 IED design ............................................................................................................... 227
9.3 CE certificate ........................................................................................................... 228
Chapter 24 Appendix .................................................................................................................. 229
1 General setting list .................................................................................................................. 230
1.1 Setting list for CSC-211 M01 ................................................................................... 230
1.2 Setting list for CSC-211 M02 ................................................................................... 237
1.3 Setting list for CSC-211 M03 ................................................................................... 244
1.4 Setting list for CSC-211 M05 ................................................................................... 250
1.5 Setting list for CSC-211 M6 ..................................................................................... 255
1.6 Setting list for CSC-211 V01.................................................................................... 259
1.7 Setting list for CSC-211 C01 ................................................................................... 262
1.8 Setting list for CSC-211 C02 ................................................................................... 268
2 General report list ................................................................................................................... 275
2.1 Event report list ........................................................................................................ 275
2.2 Alarm report list ....................................................................................................... 277
3 Typical connection .................................................................................................................. 282
4 Time inverse characteristic ..................................................................................................... 304
4.1 11 kinds of IEC and ANSI inverse time characteristic curves ................................. 304
4.2 User defined characteristic ...................................................................................... 304
4.3 Typical inverse curves ............................................................................................. 305
5 CT Requirement...................................................................................................................... 317
5.1 Overview .................................................................................................................. 317
5.2 Current transformer classification ............................................................................ 318
5.3 Abbreviations (according to IEC 60044-1, -6, as defined) ...................................... 319
5.4 General current transformer requirements .............................................................. 320
5.4.1 Protective checking current.............................................................................. 320
5.4.2 CT class ........................................................................................................... 320
5.4.3 Accuracy class ................................................................................................. 322
5.4.4 Ratio of CT ....................................................................................................... 322
5.4.5 Rated secondary current .................................................................................. 323
5.4.6 Secondary burden ............................................................................................ 323
5.5 Rated equivalent secondary e.m.f requirements ..................................................... 323
5.5.1 Definite time overcurrent protection and earth fault protection ........................ 324
5.5.2 Inverse time overcurrent protection and earth fault protection ........................ 325
Chapter 1 Introduction
Chapter 1 Introduction
1
Chapter 1 Introduction
1 Overview
CSC-211 series are selective, reliable and high speed multifunction
protection IED (Intelligent Electronic Device), which are able to be applied
for protection, control and measurement for following applications:
2
Chapter 1 Introduction
2 Features
Extensive multifunction IED including protection, control and
monitoring functions
3
Chapter 1 Introduction
CB status supervision
4
Chapter 1 Introduction
3 Functions
Voltage protection
3U>
Overvoltage protection 59 PTOV
3U>>
3U<
Undervoltage protection 27 PTUV
3U<<
Displacement voltage protection 64 VE>
Auto-reclosing 79 RREC OI
Other functions
Fast busbar protection using reverse
interlocking
Description
Self-supervision
Fault recorder
Description
6
Chapter 1 Introduction
Communication protocols
Functions
Setting
IED testing
IED configuration
Printing
7
Chapter 1 Introduction
8
Chapter 2 General IED application
9
Chapter 2 General IED application
The LCD screen displays measured analog quantities, report ouputs, menu
and logic linker status.
The analog display includes measured Ia, Ib, Ic, 3I0, Is0, Ua, Ub, Uc, U4, Mea
Ia, Mea Ib, Mea Ic, Mea Ua, Mea Ub, Mea Uc, Mea Uab, Mea Ubc and Mea
Uca.
The Mea means that the measurement analogue quantity, for example, Mea
Ia, means the measurement current for phase A.
The menu dispaly includes main menu and debugging menu, see chapter
Chapter 23 for detail.
10
Chapter 2 General IED application
2 Report record
The report record includes tripping, alarm and operation reports. See Chapter
24 general report list for detail.
11
Chapter 2 General IED application
3 Disturbance recorder
3.1 Introduction
To get fast, complete and reliable information about fault current, voltage,
binary signal and other disturbances in the power system is very important.
This is accomplished by the disturbance recorder function and facilitates a
better understanding of the behavior of the power system and related primary
and secondary equipment during and after a disturbance. An analysis of the
recorded data provides valuable information that can be used to explain a
disturbance, basis for change of IED setting plan, improvement of existing
equipment etc.
The disturbance recorder, always included in the IED, acquires sampled data
from measured analogue quantities, calculated analogue quantity, binary
input and output signals.
The IED can save the latest 40 fault records (be memorized in case of power
disconnection), which can be read via the IED operation interface or
communication port. The fault record consists of the following information:
Operation setting
Wave recording function is used to record the analogue data and status with a
pre-defined length after and before disturbance occurs, reshow the operation
track of the protected IED. The recording wave includes at most 12 analogue
channels, 64 binary channels (32 binary input, 16 binary output and 16
GOOSE signal) and time sequence information. IED records the data as the
sample of 20 points in each cycle, accumulated length of each record is up to
12
Chapter 2 General IED application
8 seconds and 20 latest recording waves can be stored. Wave are searched
and called via dedicated software from the RS232 serial port on panel, and be
converted to COMTRADE format for being used by other recording wave
analysis software or fault simulation software.
The IED monitors and records the change of operation event, alarm event,
binary input, binary output and protection linker, records the event occurrence
time, reason and current status, and transfers the information to the station
control center via the communication port.
Fault wave recorder with great capacity, can record full process of any fault,
and can save the corresponding records. Optional data format or wave format
is provided, and can be exported through serial port or Ethernet port by
COMTRADE format.
13
Chapter 2 General IED application
4 Self-supervision function
4.1 Introduction
The IED may test all hardware components itself, including loop out of the
relay coil. Finding whether or not the IED is in fault through warning LED and
warning characters which shown in LCD and display reports to indicate fault
type.
Information Description
RAM Error RAM is abnormal
EPROM Error EPROM is abnormal
Flash Error Flash is abnormal
BO Abnormal Binary output is abnormal
AD Error AD is abnormal
Zero Offset Zero drift is out of limitation
Invalid SetGr Pointer of setting group is error
14
Chapter 2 General IED application
Information Description
Setting Chk ERR Setting value is error
Logic Scheme ERR Logic file and CPU file do not cooperate
15
Chapter 2 General IED application
5.1 Introduction
Time definitions
The error of a clock is the difference between the actual time of the clock, and
the time the clock is intended to have. The rate accuracy of a clock is
normally called the clock accuracy and means how much the error increases,
i.e. how much the clock gains or loses time. A disciplined clock is a clock that
knows its own faults and tries to compensate for them, i.e. a trained clock.
Synchronization principle
The built in GPS clock module receives and decodes time information from
the global positioning system. The module is located on the CPU Module. The
GPS interfaces to the IED supply two possible synchronization methods,
IRIGB and PPS (or PPM).
The IED accepts PPS or PPM to the GPS interfaces on the CPU Module.
These pulses can be generated from e.g. station master clock. If the station
master clock is not synchronized from a world wide source, time will be a
relative time valid for the substation. Both positive and negative edges on the
signal can be accepted. This signal is also considered as a fine signal.
17
Chapter 2 General IED application
6 Setting
6.1 Introduction
Settings are divided into separate lists according to different functions. The
setting consists of two parts -setting list and communication parameters.
The setting procedure can be ended at any the time by the key SET or
QUIT. If the key SET is pressed, the display shows the content of Select.
The range of setting zone is from 1 to 16. After confirming with the setting
zone-key SET, those new settings will be valid. If key QUIT is pressed
instead, all modifications which have been changed will be ignored.
18
Chapter 2 General IED application
7 Authorization
7.1 Introduction
To safeguard the interests of customers, both the IED and the tools that are
accessing the IED are protected, subject of authorization handling. The
concept of authorization, as it is implemented in the IED and the associated
tools is based on the following facts:
There are different levels (or types) of guest, super user and protection
engineer that can access or operate different areas of the IED and tools
functionality.
19
Chapter 2 General IED application
20
Chapter 3 Overcurrent protection
21
Chapter 3 Overcurrent protection
1 Overcurrent protection
1.1 Introduction
First definite stage and inverse time stage can be set individually to
alarm or trip
The time characteristic for each stage can be chosen as definite time stage
or some type of inverse time characteristic. 11 kinds of inverse time
characteristics are available. It is also possible to create a user defined
time characteristic. Each stage can operate in conjunction with the
integrated inrush restraint and directional functions and operate based on
measured phase current. In addition, an undervoltage control feature is
provided which can be used for definite overcurrent stages.
Pickup value for the definite stage can be set in setting value. Each phase
current is compared with the corresponding setting value with delay time. If
currents exceed the associated pickup value, after expiry of the time delay,
the trip command or alarm signal is issued. The dropout value of the
definite stages is approximately equal to 96% of the pickup value for I/In
0.5. The condition for delay time starting is expressed in the following
formula:
Equation 1
The delay time can be set for each definite stage individually in setting.
After the delay time elapsed, a trip command or alarm signal is issued.
For the delay time of inverse time characteristic, which is calculated here
based on the type of the set characteristic, the magnitude of the current
and a time multiplier, both ANSI and IEC based standard curves are
available, and any user-defined characteristic can be defined using
following formula:
K_OC
Equation 2
where:
23
Chapter 3 Overcurrent protection
The protection IED may detect large magnetizing inrush currents during
transformer energizing. In addition to considerable unbalance fundamental
current, inrush current comprises large second harmonic current which
does not appear in short circuit current. Therefore, the inrush current may
affect the protection functions which operate based on the fundamental
component of the measured current. Accordingly, inrush restraint logic is
provided to prevent overcurrent protection from maloperation.
The inrush restraint function has a maximum inrush current setting. Once
the measuring current exceeds the setting, the overcurrent protection will
not be blocked any longer.
24
Chapter 3 Overcurrent protection
component can be set for each definite stage by the dedicated binary
settings.
Forward 90 IA
Bisector
Ph_Char
0
U BC_Ref
-IA
where:
Ph_Char: The settable characteristic angle
Table 2 Assignment of applied current and reference voltage for directional element
A Ia U bc
B Ib U ca
25
Chapter 3 Overcurrent protection
C Ic U ab
As can be seen from Table 2, the healthy voltages are used in direction
determination. This guarantee corrects direction determination even if the
fault voltage has collapsed totally because of a single-phase short-circuit
fault. For three-phase short-circuit fault, without any healthy phase,
memory voltage values are used to determine direction clearly if the
measured voltage values are not sufficient. The detected direction is
based on the memory voltage of previous power cycles.
Ia2/Ia1 >
Ib2/Ib1 > OR
t<
26
Chapter 3 Overcurrent protection
Ia >
VT Fail
Blk Fun_VTFail AND
UnBlk Fun_VTFail OR
1 OR AND DEF A OK
OC1 Dir Off
Phase A Forward
OC1 Dir On
AND
LV For OC I
1
OC1_V Blk On
OC1 Dir Off AND
1
OC1 V_Blk Off 1
OC1 V_Blk Off
0
OC1 2H_Blk Off
< I_2H_UnBlk
AND
Ia2/Ia1> OC1 2H_Blk On
DEF A OK T Func_OC1
AND Trip/Alarm
0
OC1 2H_Blk Off
Cross BLK
OC1 2H_Blk On
27
Chapter 3 Overcurrent protection
Ia Inverse
VT Fail
Blk Fun_VTFail AND
0
OCInv 2H_Blk Off
< I_2H_UnBlk
AND
Ia2/Ia1> OCInv 2H_Blk On
Cross BLK
OCInv 2H_Blk On
IP1 OC1_Trip
IP2 OC2_Trip
IP3
OC Inv Trip
UP1
UP2
UP3
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
IP3 Signal for current input 3
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
28
Chapter 3 Overcurrent protection
Signal Description
OC1_Trip Overcurrent protection stage 1 trip
OC2_Trip Overcurrent protection stage 2 trip
OC Inv Trip Overcurrent protection inverse time stage trip
Bit 0 1 Explanation
Enable or disable the direction for
1.0 OC1 Dir Off OC1 Dir On
stage 1
Enable or disable the low voltage
1.1 OC1 V_Blk Off OC1_V Blk On
blocking for stage 1
Enable or disable the inrush
1.2 OC1 2H_Blk Off OC1 2H_Blk On
restraint for stage 1
Enable or disable the direction for
1.3 OC2 Dir Off OC2 Dir On
stage 2
Enable or disable the low voltage
1.4 OC2 V_Blk Off OC2 V_Blk On
blocking for stage 2
Enable or disable the inrush
1.5 OC2 2H_Blk Off C2 2H_Blk On
restraint for stage 2
Enable or disable the direction for
1.6 OC Inv Dir Off OC Inv Dir On
inverse stage
Enable or disable the inrush
1.7 OCInv 2H_Blk Off OCInv 2H_Blk On
restraint for inverse stage
Select voltage connection way by
2.9 3Ph V Connect 1Ph V Connect
single phase or three phase
Enable the function of VT fail
2.14 UnBlk Fun_VT Fail Blk Fun_VT Fail
blocking
Stage 1 of overcurrent protection
4.0 OC1 Alarm OC1 Trip
alarm or trip
Inverse stage of overcurrent
4.1 OC Inv Alarm OC Inv Trip
protection alarm or trip
1.5 Reports
Information Description
OC1 Trip Overcurrent protection stage 1 issues trip command
OC2 Trip Overcurrent protection stage 2 issues trip command
OC Inv Trip Overcurrent protection inverse time stage issues trip command
30
Chapter 3 Overcurrent protection
Information Description
Inrush Blk Inrush is detected to block function.
Information Description
OC1 Alarm Overcurrent protection stage 1 issues alarm signal
OC Inv Alarm Overcurrent protection inverse time stage issues alarm signal
Long inverse
ANSI Inverse; 5% setting + 40ms, at 2
31
Chapter 3 Overcurrent protection
32
Chapter 4 Earth fault protection
33
Chapter 4 Earth fault protection
1.1 Introduction
11 kinds of the IEC and ANSI inverse time characteristic curves as well
as optional user defined characteristic
First definite stage and inverse time stage can be set individually to alarm
or trip
The time characteristic for each stage can be chosen as definite time stage or
some type of inverse time characteristic. 11 kinds of inverse time
characteristics are available. It is also possible to create a user defined time
characteristic. Each stage can operate in conjunction with the integrated
inrush restraint and directional functions and operate based on measured
phase current.
The earth fault protection can operate with the measured or calculated zero
sequence current (zero-sequence current IN measured from earth phase CT
or zero-sequence current 3I0 calculated by the summation of three phase
currents, 3I0=IA+IB+IC). These two types of measured quantity can be enabled
or disabled via binary setting. If setting 3I0 Measured is enabled in the
binary setting, the function will operate based on the measured
zero-sequence current, whereas, the 3I0 Calculated is enabled, the
zero-sequence current is calculated from the summation of three phase
currents.
Pickup value for the definite stage can be set in setting value. The measured
or calculated zero-sequence current is compared with the corresponding
setting value with delay time. If zero-sequence current exceed the associated
pickup value, after expiry of the time delay, trip command is issued. The
condition for delay time start is expressed in the following formula
Equation 3
The time delay can be set for each definite stage individually in setting. After
the delay time elapsed, trip command or alarm signal is issued. The drop out
value of the definite stages is approximately equal to 96% of the pickup value
for 3I0/In0.5.
35
Chapter 4 Earth fault protection
The time delay of inverse time characteristic is calculated based on the type
of the set characteristic, the magnitude of the current and a time multiplier.
For the inverse time characteristic, both ANSI and IEC based standard curves
are available, and any user-defined characteristic can be defined using the
following equation:
K_EF
Equation 4
where:
The time is set to count up for a user-defined time delay. The time delay can
be set for each definite stage individually through corresponding settings.
After the user-defined time delays elapsed, a trip command is issued.
The protection IED may detect large magnetizing inrush currents during
transformer energizing. In addition to considerable unbalance fundamental
current, inrush current comprises large second harmonic current which does
not appear in short circuit current. Therefore, the inrush current may affect the
protection functions which operate based on the fundamental component of
the measured current. Accordingly, inrush restraint logic is provided to
prevent earth fault protection from maloperation.
Generally, inrush restraint for earth fault protection is performed based on the
second harmonic contents of three phase currents. However, it is possible to
use the IED only for earth fault protection and therefore, the phase currents
may be not connected to the IED. In such cases, if the binary setting of EF
Chk I02/I01 is enabled, second harmonic content of zero sequence current is
considered if the zero sequence current is measured from neutral CT. As
mentioned previously, the binary setting of 3I0 Measured is enabled for this
situation. So, the inrush condition is recognized if the ratio of second
36
Chapter 4 Earth fault protection
On the contrary, if binary setting of EF Chk I2/I1 is set, the inrush condition is
recognized if the ratio of second harmonic content in each phase current to
their fundamental component exceeds setting value.
37
Chapter 4 Earth fault protection
voltage defines the forward and reverse area. The forward area is in range of
80around the rotated reference voltage. If the vector of the fault current -3I0
is in this area, the fault condition is detected as forward direction. The
zero-sequence direction detection characteristic is shown in Figure 6.
90
3I 0
0
3U 0_Ref
0_Char
Forward Bisector
-3 I 0
where:
can be detected. However, for the condition that the zero sequence voltages
below 2V, no direction determination would be applied, thus, the fault is
considered as reverse direction.
The fault current -3I2 is in phase opposition to the fault current 3I2 and lags
from the voltage 3V2 by the fault angle 2_Char. To satisfy different
applications, the reference voltage can be rotated by adjustable angle
between 0and 90in clockwise direction (negative sign) to be closely
adjusted to the vector of fault current -3I2. This would provide the best
detection result for direction determination. The rotated reference voltage
defines the forward and reverse area. The forward area is in range of 80
around the rotated reference voltage. If the vector of fault current -3I2 is in this
area, the fault condition is detected as forward direction. The negative
sequence direction detection characteristic is shown in Figure 7.
3I2 90
0
3 U 2_ Ref
2_Char
Forward
-3 I 2 Bisector
where:
1 AND Ir BLK EF
EF Chk I02/I01
I02/I01 >
39
Chapter 4 Earth fault protection
Figure 8 Logic diagram for inrush restraint based on measured zero sequence current
Max(Ia1,Ib1,Ic1) >I_2H_UnBlk
1 AND Ir BLK EF
EF Chk I2/I1
Ia2/Ia1 >
Ib2/Ib1 > OR
Ic2/Ic1 >
Figure 9 Logic diagram for inrush restraint based on based on phase currents
UnBlk Fun_VTFail
OR
VT Fail
Blk Fun_VTFail
AND
U0/I0-
3U0>2V OR Forward
3U0 Calculated
VT Fail AND
Blk Fun_VTFail
U2/I2-
EF U2/I2 Dir
OR
AND
UnBlk Fun_VTFail
UnBlk Fun_VTFail
OR
V1p VT Fail
Blk Fun_VTFail
AND
U0/I0-
3U0>2V OR Forward
3U0 Meaured
VT Fail AND
Blk Fun_VTFail
U2/I2-
EF U2/I2 Dir
OR
AND
UnBlk Fun_VTFail
40
Chapter 4 Earth fault protection
I0 >
0
EF1 2H_Blk Off
Ir BLK EF
EF1 2H_Blk On
Func_EF1
1 AND T Trip/Alarm
EF1 Dir Off
Forward
EF1 Dir On
Figure 11 Logic diagram for first definite stage of earth fault protection
I0 Inverse
0
EFInv 2H_Blk Off
Ir BLK EF
EFInv 2H_Blk On
Func_EF Inv
1 AND T Trip/Alarm
EF Inv Dir Off
Forward
EF Inv Dir On
Figure 12 Logic diagram for inverse time stage of earth fault protection
41
Chapter 4 Earth fault protection
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
IP3 Signal for current input 3
IP0 Signal for current input 0
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
Signal Description
EF1 Trip Earth fault protection stage 1 trip
EF2 Trip Earth fault protection stage 2 trip
EF Inv Trip Earth fault protection inverse time stage trip
42
Chapter 4 Earth fault protection
Information Description
EF1 Trip Earth fault protection stage 1 issues trip command
EF2 Trip Earth fault protection stage 2 issues trip command
EF Inv Trip Earth fault protection inverse stage issues trip command
Inrush Blk Inrush is detected to block function.
Information Description
EF1 Alarm Earth fault protection stage 1 issues an alarm signal
EF Inv Alarm Earth fault protection inverse stage issues an alarm signal
44
Chapter 4 Earth fault protection
Long inverse
ANSI Inverse; ANSI/IEEE C37.112,
Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic IEC60255-151
T=
5% setting + 40ms, at 2
<I/ISETTING < 20
Time factor of inverse time, A 0.005 to 200.0s, step
0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
set time Multiplier for step n: k 0.05 to 999.0, step 0.01
45
Chapter 4 Earth fault protection
46
Chapter 5 Sensitive earth fault protection
47
Chapter 5 Sensitive earth fault protection
1.1 Introduction
In networks with high impedance earthing, the phase to earth fault current is
significantly smaller than load current and phase to phase short circuit
currents. Another difficulty for earth fault protection is that the magnitude of
the phase to earth fault current is almost independent of the fault location in
the network.
Sensitive earth fault protection can be used to detect and give selective trip of
phase to earth faults in isolated or compensated networks. The protection
function also can be applied to detect high impedance earth faults in solidly or
low-resistance earthed networks.
Dedicated sensitive CT
48
Chapter 5 Sensitive earth fault protection
The time characteristic for each stage can be chosen as definite time stage or
some type of inverse time characteristic. 11 kinds of inverse time
characteristics are available. It is also possible to create a user defined time
characteristic. Each stage can operate in conjunction with the integrated
directional functions and operate based on measured phase current which is
injected from the dedicated sensitive current transformer.
Pickup value for the definite stage can be set in setting value. The measured
current from sensitive CT input is compared with the corresponding setting
value with delay time. If the measured current exceeds the associated pickup
value, after expiry of the time delay, the trip command or alarm signal is
issued. The dropout value of the definite stages is approximately equal to 96%
of the pickup value.
The time delay of inverse time characteristic is calculated based on the type
of the set characteristic, the magnitude of the current and a time multiplier.
For the inverse time characteristic, both ANSI and IEC based standard curves
are available, and any user-defined characteristic can be defined using the
following equation:
K_SEF
Equation 5
where:
49
Chapter 5 Sensitive earth fault protection
When the U0/I0- or Cos elements used for directional sensitive earth fault
protection, the VT failure condition may result in false or undesired tripping or
alarming. In such situation, it is possible to set operation state for each stage
of sensitive earth fault protection which operates in conjunction with direction
feature by binary setting to block the function or operate without direction
detection. When binary setting is set to UnBlk Fun_VTFail, corresponding
sensitive earth fault stages would not consider direction in case of VT failure.
When it is set to Blk Fun_VTFail, the function will be blocked when VT
failure happens. It is noted that the binary setting affects all the stages of
sensitive earth fault element.
Contrary to the directional phase elements, which work with the un-faulted
voltage as reference voltage, for the sensitive earth fault protection, the zero
sequence voltage is used as the reference voltage for direction determination.
Depending on the connection of voltage transformer (setting 3U0
50
Chapter 5 Sensitive earth fault protection
90 - I NS
Forward
Bisector
NS_Char 0
3U0_Ref
I NS
where:
NS_Char: The settable characteristic angle
51
Chapter 5 Sensitive earth fault protection
IS 90
Forward 0
3U0_Ref
- IS
U0/I0-
SEF Chk U0/I0
AND Forward
3U0>
IsCOS
SEF Chk Iscos
AND Forward
3U0>
52
Chapter 5 Sensitive earth fault protection
UnBlk Fun_VTFail
OR
3U0 Calculated
VT Fail
Blk Fun_VTFail AND
AND
V1p VT Fail
Blk Fun_VTFail
3U0 Measured
OR
UnBlk Fun_VTFail
Is >
Func_SEF1
AND T Trip/Alarm
1
SFF1 Dir Off
Forward Release
SEF1 Dir On
Figure 18 Logic diagram for the first definite stage of sensitive earth fault protection
Is Inverse
Func_SEF Inv
AND T Trip/Alarm
1
SFF Inv Dir Off
Forward Release
SEF Inv Dir On
Figure 19 Logic diagram for the inverse time stage of sensitive earth fault protection
53
Chapter 5 Sensitive earth fault protection
IS SEF1 Trip
UP1 SEF1 Alarm
UP2 SEF2 Trip
UP3 SEF2 Alarm
SEF Inv Trip
SEF Inv Alarm
Signal Description
Is Signal for sensitive current input
UP1 Signal for voltage input 2
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
Signal Description
SEF1 Trip Sensitive earth fault protection stage 1 trip
SEF1 Alarm Sensitive earth fault protection stage 1 alarm
SEF2 Trip Sensitive earth fault protection stage 2 trip
SEF2 Alarm Sensitive earth fault protection stage 2 alarm
Sensitive earth fault protection inverse time
SEF Inv Trip
stage trip
Sensitive earth fault protection inverse time
SEF Inv Alarm
stage alarm
54
Chapter 5 Sensitive earth fault protection
Bit 0 1 Explanation
2.1 SEF1 Dir Off SEF1 Dir On Enable or disable the direction for
55
Chapter 5 Sensitive earth fault protection
Bit 0 1 Explanation
stage 1
Enable or disable the direction for
2.2 SEF2 Dir Off SEF2 Dir On
stage 2
Enable or disable the direction for
2.3 SEF Inv Dir Off SEF Inv Dir On
inverse stage
Direction determination by U0/I0-
2.4 SEF Chk Iscos SEF Chk U0/I0
measurement or IsCos measurement
2.8 3U0 Measured 3U0 Calculated 3U0 measured or calculated
Enable or disable the function of VT fail
2.14 UnBlk Fun_VT Fail Blk Fun_VT Fail
blocking
Stage 1 of sensitive earth fault
4.4 SEF1 Alarm SEF1 Trip
protection alarm or trip
Stage 2 of sensitive earth fault
4.5 SEF2 Alarm SEF2 Trip
protection alarm or trip
Inverse stage of sensitive earth fault
4.6 SEF Inv Alarm SEF Inv Trip
protection alarm or trip
Information Description
SEF1 Trip Sensitive earth fault protection stage 1 issues trip command
SEF2 Trip Sensitive earth fault protection stage 2 issues trip command
SEF Inv Trip Sensitive earth fault protection inverse stage issues trip command
Information Description
SEF1 Alarm Sensitive earth fault protection stage 1 issues an alarm signal
SEF2 Alarm Sensitive earth fault protection stage 2 issues an alarm signal
SEF Inv Alarm Sensitive earth fault protection inverse stage issues an alarm signal
56
Chapter 5 Sensitive earth fault protection
Long inverse
ANSI Inverse; 5% setting + 40ms, at 2
57
Chapter 5 Sensitive earth fault protection
58
Chapter 6 Negative-sequence
overcurrent protection
Chapter 6 Negative-sequence
overcurrent protection
59
Chapter 6 Negative-sequence
overcurrent protection
1 Negative-sequence overcurrent
protection
1.1 Introduction
The first definite stage and inverse stage can be set individually as alarm
or trip stage
Equation 6
60
Chapter 6 Negative-sequence
overcurrent protection
Individual pickup value for each definite stage can be set in setting value. The
calculated negative sequence current from Equation 6 is compared
separately with the corresponding setting value with delay time. If the
calculated negative-sequence current exceeds the associated pickup value,
after expiry of the time delay, the trip command or alarm signal is issued. The
drop out value of the definite stages is approximately equal to 95% of the
pickup value for I/In 0.5.
The time delay of inverse time characteristic is calculated based on the type
of the set characteristic, the magnitude of the current and a time multiplier.
For the inverse time characteristic, both ANSI and IEC based standard curves
are available, and any user-defined characteristic can be defined using the
following equation:
K_NSOC
Equation 7
where:
61
Chapter 6 Negative-sequence
overcurrent protection
CT Fail
AND T1 NS1 Trip/Alarm
3I2 > 3I2_NSOC1 Func_NSOC1 On
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
IP3 Signal for current input 3
Signal Description
Negative sequence overcurrent protection
NSOC1 Trip
stage 1 trip
62
Chapter 6 Negative-sequence
overcurrent protection
63
Chapter 6 Negative-sequence
overcurrent protection
Bit 0 1 Explanation
Stage 1 of negative sequence
4.7 NSOC1 Alarm NSOC1 Trip
overcurrent protection alarm or trip
Inverse stage of negative sequence
4.8 NSOC Inv Alarm NSOC Inv Trip
overcurrent protection alarm or trip
Information Description
NSOC1 Trip Negative sequence current protection stage 1 issues trip command
NSOC2 Trip Negative sequence current protection stage 2 issues trip command
NSOC Inv Trip Negative sequence current protection inverse stage issues trip command
Information Description
NSOC1 Alarm Negative sequence current protection stage 1 issues an alarm signal
NSOC Inv Alarm Negative sequence current protection inverse stage issues an alarm signal
64
Chapter 6 Negative-sequence
overcurrent protection
Long inverse
ANSI Inverse; 5% setting + 40ms, at 2
with IEC60255-151
Time factor of inverse time, A 0.005 to 200.0s, step 0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
65
Chapter 6 Negative-sequence
overcurrent protection
66
Chapter 7 Thermal overload protection
67
Chapter 7 Thermal overload protection
1.1 Introduction
The thermal overload protection in the IED is provided with one trip stage as
well as one alarm stage. It is possible to set the alarm stage at a certain
percentage of the setting value applied at the trip stage. They protection
function operates based on an approximate replica of the protected object in
the event of temperature rise caused by overload. The thermal replica is
implemented based on thermal models (Cold or Hot Curve) of IEC60255-8
standard. The temperature rise is calculated separately for each phase in a
thermal replica from the square of the respective phase current. The
maximum calculated temperature rise of the three phases is decisive for
evaluation of the thresholds.
The IED calculates the temperature rise of the protected equipment in each
phase, based on following differential equation:
68
Chapter 7 Thermal overload protection
Equation 8
where:
: is thermal time constant of heating for the protected object, in seconds. It is usually
determined by manufacturer of the protected object. This parameter can be set in
setting value.
I: is the measured fundamental current flowing through each phase of the protected
object.
: is temperature rise of the protected object in per unit of the final temperature rise
at maximum allowed phase current .
Equation 9
where:
Equation 10
From the Equation 9 and Equation 10 can be seen, the cold curve provides
no memory regarding to previous thermal condition of the protected object,
69
Chapter 7 Thermal overload protection
whereas, by using the hot curve, the protection function is able to represent a
memorized thermal profile of the protected object. It is possible to set which
curve should be considered for thermal overload protection by binary setting
Hot Curve/Cold Curve. If Hot Curve is enabled, tripping time of thermal
overload protection would be calculated based on Equation 9. In contrast, if
applying Cold Curve, Equation 10 would be used for calculation process. It
is noted that binary setting Hot Curve/Cold Curve affects both the alarm and
trip stages.
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
IP3 Signal for current input 3
Signal Description
Thermal OL Trip Thermal overload protection trip
Thermal OL Alarm Thermal overload protection alarm
70
Chapter 7 Thermal overload protection
Bit 0 1 Description
Enable or disable the alarm function of
2.5 Therm Alarm Off Therm Alarm On
thermal overload protection
Enable or disable the Hot Curve or Cold
2.6 Hot Curve Cold Curve
Curve
Information Description
Therm OL Trip Thermal overload protection issues trip command
Information Description
Therm OL Alarm Thermal overload protection issues an alarm signal
71
Chapter 7 Thermal overload protection
I eq2
IEC cold curve t ln 2 2
IEC 602558,
I eq I 5% setting or +40ms
I eq2 I P2
IEC hot curve t ln 2 2
IEC 602558,
I eq I 5% setting or +40ms
72
Chapter 8 Current overload protection
73
Chapter 8 Current overload protection
The purpose of the overload protection is used to protect the capacitor bank
against the faults that occur normally by over-voltage which results in
dielectric breakdown. Alarm function and trip function are provided, which can
be enabled or disabled separately.
Ia>
Func_OL
Ib> OR Talarm Alarm
OL Alarm On
Ic>
Ia>>
Func_OL
Ib>> OR Ttrip Trip
Ic>>
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
74
Chapter 8 Current overload protection
Signal Description
Thermal OL Trip Thermal overload protection trip
Thermal OL Alarm Thermal overload protection alarm
Bit 0 1 Explanation
Enable or disable the alarm
4.7 OL Alarm Off OL Alarm On
function of overload protection
Information Description
75
Chapter 8 Current overload protection
Information Description
OL Trip Over load protection issues trip command
Information Description
OL Alarm Over load protection issues an alarm signal
76
Chapter 9 Overvoltage protection
77
Chapter 9 Overvoltage protection
1 Overvoltage protection
1.1 Introduction
Overvoltage protection element provides two definite time stages which can
be enabled or disabled separately according to the users requirement using
dedicated binary setting Func_OV1 and Func_OV2. The first stage can be
used for tripping or alarming, whereas the second stage is dedicated for
tripping purposes. It is possible to select the operation mode of the first stage
of overvoltage protection using binary setting OV1 Alarm/OV1 Trip. As
expected, setting OV1 Alarm makes it work as an alarming stage, while by
applying OV1 Trip, it is possible to use the first stage as a tripping stage.
Voltage thresholds and time delays can be set individually for each element.
Thus, alarming or tripping can be time-coordinated depending on how severe
the voltage increases are, i.e. in case of a high overvoltage, trip command
can be issued with a short time delay, whereas in case of less severe
overvoltage, trip or alarm command can be issued with a longer time delay. In
this context, settings U_OV1 and T_OV1 correspond to the voltage
threshold and time delay of the first stage. Similarly, settings U_OV2 and
T_OV2 are related to the second stage. The dropout ratio for both the
overvoltage stages can be set through setting Dropout_OV.
78
Chapter 9 Overvoltage protection
A A
B B
C C
VA VA
VB VB
VC VC
VN VN
CSC-211 CSC-211
Case A Case B
A A
B B
C C
VA VA
VB VB
VC VC
VN VN
CSC-211 CSC-211
Case C Case D
As can be seen from Figure 22, overvoltage protection is suitable for different
connections of voltage transformer. Overvoltage protection is capable to
operate not only with three phase to earth voltages connection (Case A and
Case B) but also with only one phase to phase voltage (Case C) or phase to
earth voltage (Case D). If only one phase to phase voltage is connected to the
IED, it can be connected to the VA-VB, VB-VC or VC-VA input of the relay. In
this case, overvoltage protection should be set to operate based on OV PP.
Similarly, by connection of one phase to earth voltage to the device, it can be
connected to the VA-VN, VB-VN or VC-VN input of the relay. Furthermore,
overvoltage protection should be set to operate based on OV PE. It should
be noted that if the IED is only provided with one phase to phase voltage, it is
79
Chapter 9 Overvoltage protection
Ua>
Ub> OR
OV PE
Func_OV1
Uc>
OR T1 Trip/Alarm
Uab>
Ubc> OR
OV PP
Uca>
80
Chapter 9 Overvoltage protection
Ua>>
Ub>> OR
OV PE
Uc>> Func_OV2
OR T2 Trip
Uab>>
Ubc>> OR
OV PP
Uca>>
UP1 OV1_Trip
UP2 OV2_Trip
UP3 OV1 Alarm
OV2 Alarm
Signal Description
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
Signal Description
OV1 Alarm Overvoltage protection stage 1 alarm
OV2 Alarm Overvoltage protection stage 2 alarm
OV1_Trip Overvoltage protection stage 1 trip
OV2_Trip Overvoltage protection stage 2 trip
81
Chapter 9 Overvoltage protection
Bit 0 1 Explanation
Selection overvoltage connection
KG3.3 OV PP OV PE
as PP or PE
Selection overvoltage protection
KG4.12 OV1 Alarm OV1 Trip
as alarm or trip
Information Description
OV1 Trip Overvoltage protection stage 1 issues trip command
OV2 Trip Overvoltage protection stage 2 issues trip command
Information Description
OV1 Alarm Overvoltage protection stage 1 issues an alarm signal
82
Chapter 9 Overvoltage protection
83
Chapter 9 Overvoltage protection
84
Chapter 10 Undervoltage protection
85
Chapter 10 Undervoltage protection
1 Undervoltage protection
1.1 Introduction
Undervoltage protection element provides two definite time stages which can
be enabled or disabled separately according to the users requirement using
dedicated binary settings Fun_UV1 and Fun_UV2. The first stage can be
used for tripping or alarming, whereas the second stage is dedicated for
tripping purposes. It is possible to select the operation mode of the first stage
of undervoltage protection using binary setting UV1 Alarm/ UV1 Trip. As
expected, setting UV1 Alarm makes it work as an alarming stage, while by
applying UV1 Trip it is possible to set the first stage as a tripping
undervoltage stage. Voltage thresholds and time delays can be set
individually for each element. Thus, alarming or tripping can be
time-coordinated depending on how severe the voltage collapses are. In this
context, settings U_UV1 and T_UV1 correspond to the voltage threshold
and time delay of the first stage. Similarly, settings U_UV2 and T_UV2 are
related to the second stage. The dropout ratio for both the undervoltage
stages can be set through setting Dropout_UV.
86
Chapter 10 Undervoltage protection
A A
B B
C C
VA VA
VB VB
VC VC
VN VN
CSC-211 CSC-211
Case A Case B
A A
B B
C C
VA VA
VB VB
VC VC
VN VN
CSC-211 CSC-211
Case C Case D
87
Chapter 10 Undervoltage protection
88
Chapter 10 Undervoltage protection
Ua<
Ub< OR
UV Chk One Phase
Uc<
OR
UV PE
Ua<
Ub< AND
UV Chk All Phase
Uc<
OR UV stg1
Uab<
Ubc< OR
UV Chk One Phase
Uca<
OR
UV PP
Uab<
Ubc< AND
UV Chk All Phase
Uca<
89
Chapter 10 Undervoltage protection
Ua<<
Ub<< OR
UV Chk One Phase
Uc<<
OR
UV PE
Ua<<
Ub<< AND
UV Chk All Phase
Uc<<
OR UV stg2
Uab<<
Ubc<< OR
UV Chk One Phase
Uca<<
OR
UV PP
Uab<<
Ubc<< AND
UV Chk All Phase
Uca<<
UV stg1 Fun_UV1
AND T1 Trip/Alarm
1
UV Chk CB Off
3Ph CB Open
UV Chk CB On
Cur.Flow OR
90
Chapter 10 Undervoltage protection
UV stg2 Fun_UV2
AND T2 Trip
1
UV Chk CB Off
CB Open
UV Chk CB On
Cur.Flow OR
Signal Description
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
Signal Description
Ph A CB Open Phase A open status of CB
Ph B CB Open Phase B open status of CB
Ph C CB Open Phase C open status of CB
91
Chapter 10 Undervoltage protection
Signal Description
UV1 Alarm Undervoltage protection stage 1 alarm
UV1_Trip Undervoltage protection stage 1 trip
UV2_Trip Undervoltage protection stage 2 trip
Bit 0 1 Explanation
2.9 3Ph V Connect 1Ph V Connect Single phase or three phase
92
Chapter 10 Undervoltage protection
Bit 0 1 Explanation
voltage connection
Enable or disable the function of
3.0 UV Chk CB Off UV Chk CB On
checking CB status
Enable or disable the function of
3.1 UV Chk All Phase UV Chk One Phase checking single phase or three
phase voltage
Phase-to-phase or phase-to-earth
3.2 UV PP UV PE
discrimination
Stage 1 of undervoltage
4.11 UV1 Alarm UV1 Trip
protection alarm or trip
Information Description
UV1 Trip Undervoltage protection stage 1 issues trip command
UV2 Trip Undervoltage protection stage 2 issues trip command
Information Description
UV1 Alarm Undervoltage protection stage 1 issues an alarm signal
93
Chapter 10 Undervoltage protection
94
Chapter 11 Displacement voltage protection
95
Chapter 11 Displacement voltage protection
1.1 Introduction
The displacement voltage 3V0 can be directly applied to the IED or can be
calculated based on the connected three phase to ground voltages
(3V0=VA+VB+VC). In the latter case, the three voltage inputs must be
connected to voltage transformers in a ground-wye configuration. If the IED is
only provided with phase to phase voltages or provided only one phase to
earth or phase to phase voltage, it is not possible to calculate a displacement
voltage. In this case, the direction cannot be determined for earth fault or
sensitive earth fault protection.
If the displacement voltage is directly applied to the IED and the binary setting
3U0 Measured is enabled, it is not affected by VT fail detection on
three-phase connected voltage. Similarly, if the displacement voltage is
calculated based on the three-phase voltages and the binary setting 3U0
Calculated is enabled, it would not be blocked as a result of failure detection
in U4 voltage transformer. However, in case of a failure in U4 voltage
transformer, the displacement voltage protection based on measured value
3V0 would be blocked.
96
Chapter 11 Displacement voltage protection
Individual pickup value for each definite stage can be defined by setting
U_3V01 and U_3V02. With these settings, the measured or calculated
displacement voltage is compared separately with the setting value for each
stage. If the respective value is exceeded, a trip or alarm time delay timer is
started. Each timer is set to count up to a user-defined time delay. The time
delay can be set for each definite stage individually via settings T_3V01 and
T_3V02. After the user-defined time delays elapsed, a trip command or an
alarm signal is issued by respective stage.
97
Chapter 11 Displacement voltage protection
BLK
3V0 3V0 1
OP
Func_3V01
AND T1 Trip/Alarm
3U0>
Func_3V02
AND T2 Trip/Alarm
3U0>>
3V0 1 OP
AND Gnd A
VA >
VA <
VB >
AND Gnd B
VB <
VC >
UP1 3V01_Trip
UP2 3V02_Trip
UP3 3V01 Alarm
UP4 3V02 Alarm
98
Chapter 11 Displacement voltage protection
Signal Description
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
UP4 Signal for voltage input 4
Signal Description
Displacement voltage protection stage 1
3V01 Alarm
alarm
Displacement voltage protection stage 2
3V02 Alarm
alarm
3V01_Trip Displacement voltage protection stage 1 trip
3V02_Trip Displacement voltage protection stage 2 trip
Bit 0 1 Explanation
Selection the measured voltage
KG2.8 3U0 Measured 3U0 Calculated or calculated voltage for
displacement voltage protection
Selection the stage 1 of
KG4.9 3V01 Alarm 3V01 Trip displacement voltage protection
to alarm or trip
Selection the stage 2 of
KG4.10 3V02 Alarm 3V02 Trip displacement voltage protection
to alarm or trip
Information Description
3V01 Trip Voltage displacement protection stage 1 issues trip signal
3V02 Trip Voltage displacement protection stage 2 issues trip signal
Information Description
3V01 Alarm Voltage displacement protection stage 1 issues an alarm signal
3V02 Alarm Voltage displacement protection stage 2 issues an alarm signal
PhA Grounded Phase A is grounded
PhB Grounded Phase B is grounded
PhC Grounded Phase C is grounded
100
Chapter 11 Displacement voltage protection
101
Chapter 11 Displacement voltage protection
102
Chapter 12 Circuit breaker failure protection
103
Chapter 12 Circuit breaker failure protection
1.1 Introduction
The circuit breaker failure protection is able to detect a failure of the circuit
breaker during a fault clearance. It ensures fast back-up tripping of
surrounding breakers by tripping relevant bus sections.
In the event of a circuit breaker failure with a busbar fault, a transfer trip signal
is issued to trip the remote end circuit breaker of the feeder.
The current criteria are in combination with three phase currents, zero and
negative sequence current to achieve a higher security.
The function can be set to give three phase re-trip of the own breaker to avoid
unnecessary tripping of surrounding breakers at an incorrect starting due to
mistakes during testing.
Circuit breaker failure protection can be enabled or disabled in the IED via
binary setting Func_CBF. If setting ON is applied, CBF protection would
be enabled. In this case, by operation of a protection function, and
subsequent CBF initiation by respective protection function, a programmed
timer runs toward a preset time delay limit. This time delay is set by user
104
Chapter 12 Circuit breaker failure protection
under the settings T_CBF1. If the circuit breaker has not been opened after
expiration of the preset time limit, the circuit breaker failure protection issues
a command to trip circuit breaker (e.g. via a second trip coil). If the circuit
breaker doesnt respond to the repeated trip command, until another preset
delay time which is set at T_CBF2, the protection issues a trip command to
isolate the fault by tripping other surrounding backup circuit breakers (e.g. the
other CBs connected to the same bus section as the faulty CB).
Initiation of CBF protection can be performed by both the internal and external
protection functions. If it is desired to initiate the CBF protection by means of
external protection functions, specified binary inputs (BI) should be
marshaled. Internal protection functions can initiate the CBF protection
integrated in the IED.
There are two criteria for breaker failure detection: the first one is to check
whether the actual current flow effectively disappeared after a tripping
command had been issued. The second one is to evaluate the circuit breaker
auxiliary contact status.
105
Chapter 12 Circuit breaker failure protection
Ia>
Ib> OR
CBF Chk I0/2 Off
OR Curr. Crit.
Ic>
3I0> AND
OR
3I2>
AND
OR
CBF Chk I0/2 On
AND
AND
3Ph CB Open
CBF INIT
AND
Curr. crit.
OR
106
Chapter 12 Circuit breaker failure protection
CB is closed
CBF Chk CB On
OR
Curr. crit. Func_CBF
AND T1 CBF1
CBF INIT
T2 CBF2
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
IN signal for zero sequence current input
Signal Description
Signal Description
CBF1 Trip Circuit breaker failure protection stage 1 trip
CBF2 Trip Circuit breaker failure protection stage 2 trip
107
Chapter 12 Circuit breaker failure protection
Bit 0 1 Explanation
2.7 3I0 Measured 3I0 Calculated 3U0 is measured or calculated
Enable or disable the function for
3.6 CBF Chk I0/2 Off CBF Chk I0/2 On checking zero or negative
sequence current
Enable or disable the function for
3.7 CBF Chk CB Off CBF Chk CB On
checking CB status
Information Description
CBF1 Trip The first stage CBF issues trip command
CBF2 Trip The second stage CBF issues trip command
108
Chapter 12 Circuit breaker failure protection
Information Description
CBF Initiate CBF function is initiated
Time delay of stage 2 0.00s to 32.00 s, step 0.01s 200% operating setting
109
Chapter 12 Circuit breaker failure protection
110
Chapter 13 Dead zone protection
111
Chapter 13 Dead zone protection
1.1 Introduction
The IED provides this protection function to protect the area between circuit
breaker and CT in the case that CB is open, namely dead zone. Therefore, by
occurrence of a fault in dead zone, the short circuit current is measured by
protection IED while CB auxiliary contacts indicate the CB is open.
When one bus side CT of feeder is applied, once a fault occurs in the dead
zone, the IED trips the relevant busbar zone. Tripping logic is illustrated in
Figure 35.
112
Chapter 13 Dead zone protection
trip
Bus
IFAULT
Legend:
Opened CB
Closed CB
When one line side CT is applied, when a fault occurs in the dead zone,
protection relay sends a transfer trip to remote end relay to isolate the fault.
Tripping logic is illustrated in Figure 36.
113
Chapter 13 Dead zone protection
Inter trip
Busbar
IFAULT
Trip
Relay
Legend:
Opened CB
Closed CB
CBF INIT
3Ph CB Close
114
Chapter 13 Dead zone protection
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
Signal Description
CBF Init CBF initiation
3Ph CB Open Three phase CB open
3Ph CB Close Three phase CB Close
Signal Description
DeadZone_Trip Dead Zone protection trip
115
Chapter 13 Dead zone protection
Information Description
Dead Zone Trip The dead zone function issues trip command
116
Chapter 14 Synchro-check and
Energizing check function
117
Chapter 14 Synchro-check and
Energizing check function
1.1 Introduction
The synchronism and voltage check function ensures that the stability of the
network is not endangered when switching a line onto a busbar. The voltage
of the feeder to be energized is compared to that of the busbar to check
conformances in terms of magnitude, phase angle and frequency within
certain tolerances.
The synchro-check function checks whether the voltages on both sides of the
circuit breaker are synchronizing, or at least one side is dead to ensure
closing can be done safely.
When comparing the two voltages, the synchro check uses the voltages from
busbar and outgoing feeder. If the voltage transformers for the protective
functions are connected to the outgoing feeder side, the reference voltage
has to be connected to a busbar voltage.
If the voltage transformers for the protective functions are connected to the
busbar side, the reference voltage has to be connected to a feeder voltage.
The external automatic reclosing and manual closing are initiated through
corresponding binary input respectively. When a synchronization request is
received to the function, it can work based on different close permission
criteria. The criteria can be selected for auto reclosure or manual closure
separately. The binary settings are AR_Override,AR_Syn
check,AR_EnergChkDLLB,AR_EnergChkLLDB, AR_EnergChkDLDB
for auto reclosure, and MC_Override, MC_Syn check,
MC_EnergChkDLLB, MC_EnergChkLLDB, MC_EnergChkDLDB are
118
Chapter 14 Synchro-check and
Energizing check function
Syn check: by applying this setting, with any synchronization request, the
synchronization condition is checked continuously.
119
Chapter 14 Synchro-check and
Energizing check function
checked continuously. If the line voltages and busbar voltages are larger than
the value of Umin_Syn and meet the synchronization conditions,
synchronized reclosure can be performed.
At the end of the dead time, synchronization request will be initiated and the
synchronization conditions are continuously checked to be met for a certain
time during maximal extended time T_MaxSynExt. By satisfying
synch-check condition in this period, the monitor timer will stop and close
command will be issued for AR.
All three phases voltage U(a,b,c) should be above the setting value
Umin_Syn.
120
Chapter 14 Synchro-check and
Energizing check function
Energizing check for dead line and live bus for AR enabled or disabled,
when the control word AR_EnergChkDLLB is on
Energizing check for live line and live bus for AR enabled or disabled,
when the control word AR_EnergChkLLDB is on
Energizing check for dead line and dead bus for AR enabled or disabled,
when the control word AR_EnergChkDLDB is on
121
Chapter 14 Synchro-check and
Energizing check function
Ua(Ub,Uc) >Umin_Syn
U4>Umin_Syn
Freqdiff<Freq_Syn Diff
Udiff<U_Syn Diff
U4 <Umax_Energ
VT_Line off
AR_EnergChkLLDB on
U4>Umin_Syn
Energizing check meet
OR
Ua(Ub,Uc) AND
<Umax_Energ
VT_Line off
AR_EnergChkDLDB on
U4<Umax_Energ
AND
Ua(Ub,Uc)
<Umax_Energ
AR_EnergChkDLLB on
U4 >Umin_Syn
Ua(Ub,Uc) AND
<Umax_Energ
VT_Line on
AR_EnergChkLLDB on
U4<Umax_Energ
Ua(Ub,Uc) AND
>Umin_Syn
VT_Line on
122
Chapter 14 Synchro-check and
Energizing check function
UP1
UP2
UP3
UP4
BI3/Init AR
BI5/Syn Req
Signal Description
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
UP4 Signal for voltage input 4
Signal Description
BI3/Init AR Binary input 3/Initiation autoreclosing
BI5/Syn Req Binary input 5/Synchronization request
Table 93 Function setting list for synchro-check and energizing check function
123
Chapter 14 Synchro-check and
Energizing check function
Table 94 Logical linker list for synchro-check and energizing check protection
Table 95 Binary setting list for synchro-check and energizing check protection
Information Description
Syn Ok Synchronization check OK
Syn Request Check synchronization
124
Chapter 14 Synchro-check and
Energizing check function
Information Description
Syn Vdiff fail Voltage difference for synchronization check fail
Syn Ang fail Angle difference for synchronization check fail
Syn Fdiff fail Frequency difference for synchronization check fail
Syn Failure Synchronization check timeout
Minimum measuring time 0.05 to 60.00 s, step,0.01 s, 1.5 % setting value or +60
ms
Maximum synch-check 0.05 to 60.00 s, step,0.01 s, 1 % setting value or +50 ms
extension time
125
Chapter 14 Synchro-check and
Energizing check function
126
Chapter 15 Auto-reclosing function
127
Chapter 15 Auto-reclosing function
1 Autoreclosing function
1.1 Introduction
Internal/external AR initiation
CB ready supervision
128
Chapter 15 Auto-reclosing function
In the table, the first and second columns show the protection functions,
respectively, while the third column introduces the binary setting which is
possible to set protection functions to work in conjunction with AR.
To prevent automatic reclosing during feeder dead status (circuit breaker (CB)
open), for example, by relay testing, AR is initiated at first shot only when the
CB has been closed for more than a time period defined by T_AR Reset.
Subsequent to initiation of AR, the dead time do not start until the IED is
informed about open status of CB through binary input. The delay of dead
time can be extended up to time setting T_Max. CB Open. During this time,
whenever CB open status is recognized by the IED, dead time is started. If
129
Chapter 15 Auto-reclosing function
monitoring time T_Max. CB Open elapses and CB open status is not still
detected by the IED, AR function would be blocked for duration of AR reset
time which is defined by T_AR Reset. In this case, reclosing attempt would
be announced as unsuccessful (annunciation AR Failure).
If circuit breaker failure protection (internal or external) is used for the CB,
monitoring time T_Max CB Open should be set shorter than the delay time
for detection of circuit breaker failure. By doing so, make sure that no
reclosing takes place for a faulty circuit breaker. No reclosing would take
place for CBF stage 2 or dead zone function operation.
Regarding the close command, it has a pulse nature which lasts for 500ms at
most. As expected, no synchronization check takes place during this pulse
time. If during this pulse time, the auxiliary contact of CB indicates that the CB
has been closed or a current flow is detected by the IED, the close command
pulse will be reset.
Once the close command pulse is issued (rising edge) to close the circuit
breaker, reclaim time T_Reclaim is started, within this time it is checked
whether the reclosing attempt is successful. If no fault occurs before the
reclaim time elapses, it is thought that fault is cleared. In this case, at the end
of reclaim time, reset time T_AR Reset is started. During reset time AR
function is blocked. If a new fault occurs before the reclaim time elapses, it
results in reset of the reclaim time and starting of next reclosing shot. This
procedure can be repeated until the maximum number of reclosure shots is
reached.
130
Chapter 15 Auto-reclosing function
If none of the reclosing shots is successful, and therefore the fault is still
remained after the last shot, final trip takes place. Furthermore, AR function
would be blocked for a time period defined by T_AR Reset, and
annunciation AR Failure is issued.
It is possible to block AR function for a specified time after any manual closing
command. This can be achieved by marshaling CB close command to binary
input BI4/MC CLS. When the binary input is activated, the IED is informed
about execution of a manual closing. As a result, AR function would be
blocked for T_AR Reset.
There may be cases when it is already obvious that CB cannot perform any
reclosing attempt. For such cases, binary input BI2/CB Faulty is considered
which indicates that CB is not ready for reclosing. CB Faulty should be
checked with a time delay T_CB Faulty, which is set according to the
characteristic of circuit breaker. AR function would be blocked if the IED
detects activation of BI2/CB Faulty, even the AR function would not be
initiated. AR is blocked until the BI disappears. Furthermore, this condition is
checked whenever a close command is received from AR function.
Single-shot reclosure
Multi-shot reclosure
131
Chapter 15 Auto-reclosing function
reclosing shot; it would result in the starting of next reclosing shot with
different dead time. This procedure can be repeated until the whole reclosing
shots which are set inside the IED is performed. Different dead times can be
set for various shots of AR function. This can be performed through settings
T_3P AR1, T_3P AR2, T_3P AR3 and T_3P AR4. If one of the preset
reclosure shots is successful, AR function would be reset after expiration of
the reclaim time. However, if none of reclosing shots is successful, i.e. the
fault doesnt disappear after the last programmed shot, a final trip is issued,
and reclosing attempts are announced to be unsuccessful. Figure 39
illustrates the operation method of two shots reclosure.
Trip Command
CB Open
AR Initiate
Figure 39 Timing diagram showing two reclosure shots, first unsuccessful, second
successful
132
Chapter 15 Auto-reclosing function
IP1 AR Close
IP2 AR Not Ready
IP3 AR Final Trip
UP1 AR Successful
UP2 AR Fail
UP3
UP4
BI1/AR Off
BI2/CB Faulty
BI3/Init AR
BI4/MC CLS
BI8 CB Open
BI9 CB Close
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
UP4 signal for voltage input 4
Signal Description
BI1/AR Off Binary input 1/AR function off
BI2/CB Faulty Binary input 2/CB Faulty
BI3/Init AR Binary input 3/Initiation AR function
BI4/MC CLS Binary input 4/manual closing
MC/AR Block AR block
BI8 CB Open Binary input 8 CB Open
BI9 CB Close Binary input 9 CB Close
Signal Description
AR Close AR Close
AR Not Ready AR Not Ready
AR Final Trip AR Final Trip
AR Successful AR Successful
133
Chapter 15 Auto-reclosing function
AR Fail AR Fail
134
Chapter 15 Auto-reclosing function
135
Chapter 15 Auto-reclosing function
Information Description
AR in progess AR is initiated by internal or external function
Syn Request Check synchronization
Syn OK Synchronization check OK
1st Reclose The first shot reclosing
2nd Reclose The second shot reclosing
3rd Reclose The third shot reclosing
4th Reclose The fourth shot reclosing
AR Success AR successful
AR Failure AR unsuccessful
136
Chapter 15 Auto-reclosing function
Information Description
Syn Vdiff fail Voltage difference for synchronization check fail
Syn Ang fail Angle difference for synchronization check fail
Syn Fdiff fail Frequency difference for synchronization check fail
Syn Failure Synchronization check timeout
Information Description
CB Not Ready BI2 is active to show CB is not ready
Dead time, separated setting for 0.05 s to 60.00 s, step 0.01 s 1 % setting value or +50 ms
shots 1 to 4
Reclaim time 0.50 s to 60.00s, step 0.01 s
Blocking duration time (AR reset 0.05 s to 60.00s, step 0.01 s
time)
Circuit breaker ready supervision 0.50 s to 60.00 s, step 0.01 s
time
137
Chapter 15 Auto-reclosing function
138
Chapter 16 Unbalance protection
139
Chapter 16 Unbalance protection
1 Unbalance protection
1.1 Introduction
Different detecting schemes are described in the following, which are applied
for the unbalance protection.
A
B
C
I1
140
Chapter 16 Unbalance protection
Don not operate when failure happen similarly in all the phases
A
B
C
U1
141
Chapter 16 Unbalance protection
A
B
C
I1
In this scheme, the neutrals of the two banks are grounded through separate
current transformers. The secondary current transformed by the CT is
insensitive to any outside conditions and is affected by two capacitor banks.
There is no any indication for balance failure in this configuration.
A
B
C
U1
Using a voltage transformer connected between the neutral point and ground,
any neutral voltage shift due to the failure of capacitor unit is detected. This
scheme is less sensitive to system unbalance.
142
Chapter 16 Unbalance protection
A
B
C
U1
This protection scheme uses three lines to neutral VTs with the secondary
connected in the broken delta. It is less sensitive to system unbalance.
A
B
C
143
Chapter 16 Unbalance protection
A
B
C
U1
A
B
C
U1
144
Chapter 16 Unbalance protection
A
B
C
U1
U2
U3
A
B
C
I1
I2
I3
145
Chapter 16 Unbalance protection
Unbalance 1>
3Ph CB Open
Unbalance 1>
3Ph CB Open
BI8 CB Open
Signal Description
IC1 signal for current input 1
IC2 signal for current input 2
IC3 signal for current input 3
UC1 signal for voltage input 1
UC2 signal for voltage input 2
UC3 signal for voltage input 3
146
Chapter 16 Unbalance protection
Signal Description
BI8 CB Open Binary input 8 CB Open
Signal Description
UBL Alarm Unbalance protection alarm
UBL Trip Unbalance protection trip
Bit 0 1 Explanation
Enable or disable the alarm
4.8 UBL Alarm Off UBL Alarm On
function of unbalance protection
Information Description
UBL Trip Unbalance protection issues trip command
Information Description
UBL Alarm Unbalance protection issues an alarm signal
148
Chapter 17 Under current protection
149
Chapter 17 Under current protection
1.1 Introduction
Ia<
Func_UC
Ib< AND
AND T Trip
Ic<
3Ph CB Open
150
Chapter 17 Under current protection
IP1 UC Trip
IP2
IP3
BI8 CB Open
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
Signal Description
BI8 CB Open Binary input 8 CB Open
Signal Description
UC Trip Under current monitoring function trip
Table 119 Function setting list for under current monitoring function
Table 120 Logical linker list for under current monitoring function
151
Chapter 17 Under current protection
Information Description
UC Trip Under current protection issues trip command
Inhibit close Drive a contact to inhibit reconnection of capacitor
152
Chapter 18 Load shedding protection
153
Chapter 18 Load shedding protection
1.1 Introduction
Undervoltage checking
CB position checking
154
Chapter 18 Load shedding protection
begins to run toward a pre-defined time limit which is the time delay of the
protection (setting T_LF LS). When the time delay elapsed, the trip
command is issued.
Since the protection based on power frequency from the connected voltages,
the protection should be blocked if some conditions are satisfied as following:
Load current is lower than setting I_Chk. This condition is mainly useful
when the voltage transformer is connected at source side. The setting
applied at I_Chk corresponds to minimum load current which may flow
when circuit breaker is closed. It is possible to disable this feature by
applying setting 0 to I_Chk
IP1 LF LS Trip
IP2
IP3
UP1
UP2
UP3
BI8 CB Open
Signal Description
155
Chapter 18 Load shedding protection
Signal Description
BI8 CB Open Binary input 8 CB open
Signal Description
LF LS Trip Low frequency load shedding trip
Table 125 Function setting list for low frequency load shedding protection
Table 126 Logical linker list for low frequency load shedding protection
156
Chapter 18 Load shedding protection
Table 127 Binary setting list for low frequency load shedding protection
Information Description
LF LS Trip Low frequency load shedding function issues trip command
157
Chapter 18 Load shedding protection
2.1 Introduction
This kind of load shedding is to prevent the voltage collapse and uncontrolled
loss of load.
Low voltage load shedding is necessary when the network is connected with
a huge system with vast power capacity. Under this condition, Low
Frequency Load Shedding Scheme cannot work properly. Low Voltage Load
Shedding Scheme" would be a useful criterion whenever Automatic Voltages
Regulator (AVR) is out of service or not equipped with following conditions
satisfied.
Undervoltage checking
CB position checking
Low voltage load shedding is provided based on bay load shedding principle.
This means that the protection function is implemented in each bay separately,
instead of being applied in an incoming bay and sending trip command to
various outgoing bays. In this regard, coordination between the low voltage
load shedding protection functions applied at various bays can be achieved
by selecting appropriate settings for pickup threshold and time delay of the
protection in various bays. The protection function can be enabled or disabled
via binary setting Func_LV LS. Based on the bay load shedding principle,
only one trip stage is provided for the protection. This protection can operate
based on both three-phase and single-phase voltage input configurations.
The voltage connection is set in the IED by binary setting 3Ph V
158
Chapter 18 Load shedding protection
Load current is lower than setting I_Chk. This condition is mainly useful
when the voltage transformer is connected at source side. The setting
applied at I_Chk corresponds to minimum load current which may flow
when circuit breaker is closed. It is possible to disable this feature by
applying setting 0 to I_Chk
159
Chapter 18 Load shedding protection
IP1 LV LS Trip
IP2
IP3
UP1
UP2
UP3
BI8 CB Open
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
Signal Description
BI8 CB Open Binary input 8 CB open
Signal Description
LF LS Trip Low voltage load shedding trip
Table 132 Function setting list for low frequency load shedding protection
160
Chapter 18 Load shedding protection
shedding protection
Voltage checking setting for low
4. 70 U_Chk V 10.00 120.0
voltage load shedding protection
Current checking setting for low
5. 0.2In I_Chk A 0 2.00In
voltage load shedding protection
Table 133 Logical linker list for low frequency load shedding protection
Table 134 Binary setting list for low frequency load shedding protection
Information Description
Func_LV LS Disable or enable the low voltage load shedding
161
Chapter 18 Load shedding protection
3.1 Introduction
The IED provides a load shedding function based on the load current passing
through feeder. This function will be essential in conditions that feeder is
connected to a huge network with constant frequency and additional AVR is
continuously used for voltage regulation. In this case, load shedding
protection should be done based on load current and monitoring of following
items
Undervoltage checking
If the voltage connected to the IED and the binary setting OL LS Chk V On is
set in binary setting OL LS Chk V Off/OL LS Chk V On, the protection would
be blocked as following conditions:
162
Chapter 18 Load shedding protection
IP1 OL LS Trip
IP2
IP3
UP1
UP2
UP3
BI8 CB Open
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
Signal Description
BI8 CB Open Binary input 8 CB open
Signal Description
163
Chapter 18 Load shedding protection
Table 139 Function setting list for overload load shedding protection
Table 140 Logical linker list for overload load shedding protection
Table 141 Binary setting list for overload load shedding protection
164
Chapter 18 Load shedding protection
Information Description
OL LS Trip Overload load shedding function issues trip command
165
Chapter 18 Load shedding protection
166
Chapter 19 Fast busbar protection scheme
167
Chapter 19 Fast busbar protection scheme
A
Relay A
GOOSE massage-Block
Relay B
B
Trip
Relay C
If the fault occurs on outgoing feeder C, the protection IED C will trip and send
block messenger to IED A to block IED A relevant protection function.
168
Chapter 19 Fast busbar protection scheme
A
Relay A
Trip
Relay B
Relay C
Once the fault located on the busbar, protection IEDs of outgoing feeder do
not trip and therefore there is no any blocking signal. So the IED A will trip and
clear off the fault with short time delay.
IP1
IP2
IP3
UP1
UP2
UP3
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
169
Chapter 19 Fast busbar protection scheme
Information Description
OC Startup Three stages over current protections startup
OC Startup Back Three stages over current protections return
170
Chapter 20 Secondary system supervision
171
Chapter 20 Secondary system supervision
To prevent the IED from wrong trip, interruptions in the secondary circuits of
current transformers is detected and reported by the UED. When the zero
sequence current is always larger than the setting value 3I0_CT Fail for 12s,
CT Fail will be reported and each stage of zero sequence current protection
will be blocked if setting Blk EF_CT Fail is selected.
IP1 CT Fail
IP2
IP3
IN
Signal Description
IP1 signal for current input 1
172
Chapter 20 Secondary system supervision
Signal Description
CT Fail CT Fail
Table 148 Function setting list for current circuit supervision protection
Table 149 Binary setting list for current circuit supervision protection
Information Description
CT Fail CT failure in circuit of current transformer
173
Chapter 20 Secondary system supervision
2.1 Introduction
There are three main criteria for VT failure detection; the first is dedicated to
detect three-phase broken faults. The second and third ones are to detect
single or two-phase broken faults in solid earthed and isolated/resistance
earthed systems, respectively. A precondition to meet these three criteria is
that IED should not be picked up and the calculated zero sequence and
negative sequence currents should be less than setting of 3I02_ VT Fail.
The criteria are as follows:
The calculated zero sequence voltage 3U0 is more than the setting of
Upe_VT Fail. This condition may correspond to single or two-phase broken
fault in secondary circuit of the voltage transformer, if the system starpoint is
solidly earthed and no startup element has been detected.
The calculated zero sequence voltage 3U0 is more than the setting of
Upe_VT Fail, and at the same time, the difference between the maximum
and minimum phase-to-phase voltages is more than the setting of Upp_VT
Fail. This condition may correspond to single or two-phase broken fault in
secondary circuit of the voltage transformer, if the system starpoint is isolated
or resistance earthed and no startup element has been detected.
The IED is also capable to detect VT MCB failure of the forth input voltage U4
through its binary input V1P MCB Fail. In this context, VT fail is detected for
U4, if the respective binary input is active. As mentioned previously, U4 input
voltage can be used for in conjunction with reclosure function (setting 3U0
Calculated) or as 3U0 which can be used for earth fault protection or
displacement voltage protection (setting 3U0 Measured). When the fourth
input voltage is used as 3U0, activation of binary input V1P MCB Fail may
lead to block condition for the corresponding functions which operate based
on the measured 3U0 voltage. Similarly, when it is used as synchronization
purposes, activation of binary input V1P MCB Fail would result in blocking
condition for synchronization function.
175
Chapter 20 Secondary system supervision
setting. Furthermore, alarm report VT Fail is issued after 10s time delay. If
the VT Fail criteria recovers within this 10s time delay, the blocking condition
would be removed if one of the following conditions is met. Furthermore, it
should be noted that no VT MCB fail indication should be present during this
condition.
Without relay pickup, minimum phase voltage becomes more than setting of
Upe_VT Normal for 500ms. It is mentioned that with single phase
connection by setting 1-PH V Connect, only the connected voltage is
checked.
Without relay pickup, minimum phase voltage becomes more than setting of
Upe_VT Normal and at the same time, the calculated zero sequence or
negative sequence current of corresponding side becomes more than the
setting of 3I02_ VT Fail. It is mentioned that with single phase connection by
setting 1-PH V Connect, only the connected voltage is checked.
0
VT Chk CB Off
3Ph CB Open
VT Chk CB On
Max{Ua,Ub,Uc}< AND
3U0 <
Solid Earthed
3U0 >= OR
Isolate/Resist VT Fail On
OR 10S Alarm
AND
Max{Uab,Ubc,Uca}-
Min{Uab,Ubc,Uca}>
V3P MCB Fail VT Fail
Figure 55 VT Logic diagram of VT failure supervision for three phase voltage inputs
V1p VT Fail
176
Chapter 20 Secondary system supervision
IP1 VT Fail
IP2 V1P VT Fail
IP3
IN
UP1
UP2
UP3
UP4
V3P MCB Fail
V1P MCB Fail
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
IN Signal for zero sequence current input
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
UP4 signal for voltage input 4
Signal Description
V3P MCB Fail Three phase MCB VT fail
V1P MCB Fail Single phase MCB VT fail
Signal Description
VT Fail VT fail
V1P MCB Fail Single phase MCB VT fail
177
Chapter 20 Secondary system supervision
Table 154 Function setting list for fuse failure supervision protection
Table 155 Binary setting list for fuse failure supervision protection
Information Description
VT Fail VT failure in circuit of voltage transformer
V1P VT Fail VT failure in circuit of the forth voltage transformer
sequence current
178
Chapter 20 Secondary system supervision
179
Chapter 20 Secondary system supervision
180
Chapter 21 Monitoring function
181
Chapter 21 Monitoring function
The AR function will be blocked and alarm will be issued in case of something
wrong with CB.
2 Self-supervision
All modules can perform self-supervision to its key hardware components
and program as soon as energizing. Parts of the modules are
self-supervised in real time. All internal faults or abnormal conditions will
initiate an alarm. The fatal faults among them will result in the whole IED
blocked
182
Chapter 22 Station communication
183
Chapter 22 Station communication
1 Overview
Each IED is provided with a communication interface, enabling it to connect to
one or many substation level systems or equipment.
1.1 Protocol
IEC 61850-8-1 allows two or more intelligent electronic devices (IEDs) from
one or several vendors to exchange information and to use it in the
performance of their functions and for correct co-operation.
There is a serial RS232 port on the front plate of all the IEDs. Through this
port, the IED can be connected to the personal computer for setting, testing,
and configuration using the dedicated Sifang software tool.
Item Data
Number 1
Connection Isolated, RS232; front panel,
9-pin subminiature connector, for software tools
Communication speed 9600 baud
Max. length of communication cable 15 m
185
Chapter 22 Station communication
Item Data
Number 1, only
Connection 2-wire connector
Rear port in communication module
Max. length of communication cable 1.0 km
Test voltage 500 V AC against earth
Item Data
Electrical communication port
Number 0 to 3
Connection RJ45 connector
Rear port in communication module
Max. length of communication cable 100m
Time synchronization
186
Chapter 22 Station communication
Item Data
Mode Pulse mode
IRIG-B signal format IRIG-B000
Connection 2-wire connector
Rear port in communication module
Voltage levels differential input
187
Chapter 22 Station communication
Switch
Work Station 3
Gateway Switch
or
converter
Chapter 23 Hardware
189
Chapter 23 Hardware
1 Introduction
The modules can be combined through the bus on the rear board. Both
the IED and the other system can be combined through the rear
interfaces.
190
Chapter 23 Hardware
X7 X6 X5 X4 X3 X2 X1
PSM FOM FIO CPU BIO AIM AIM
191
Chapter 23 Hardware
2.1 Introduction
1
4
7
5 6
2. LEDs
3. Arrow keys
4. Reset key
5. Quit key
6. Set key
When operating keys are pressed or in the case of IED alarming or operating
report appearance, the back light will turn on automatically until the preset
time delay elapse after the latest operation or alarm.
2.3 LED
There are 11 LEDs on the left side of the LCD. The definition for each LED is
shown as following table.
2.4 Keyboard
193
Chapter 23 Hardware
The keyboard is used to monitor and operate IED. The keyboard has the
same look and feel in CSC family. As shown in Figure 60, keyboard is divided
into Arrow keys, Reset key, Quit key and Set key. The specific instructions on
the keys as the following table described:
Key Function
Up arrow key Move up in menu
Page up between screens
Increase value in setting
Down arrow key Move down in menu
Page down between screens
Decrease value in setting
Left arrow key Move left in menu
Right arrow key Move Right in menu
Reset key Reset the LEDs
Return to normal scrolling display state directly
Set key Enter main menu or submenu
Confirm the setting change
Quit key Back to previous menu
Cancel the current operation and back to previous menu
Return to scrolling display state
Lock or unlock current display in the scrolling display state (the
lock state is indicated by a "solid diamond" type icon on the botton
right corner of the LCD)
194
Chapter 23 Hardware
Analog BI
Metering Connect
OpStatus
Energy GOOSEINF
Switch Time
OpConfig
Connect GOO Ctrl
Read Switch
Settings
Write Delete
Event Operation
Wave
MainMenu
Eth 1# Serial
Monitor
BO Zero
BI Remote
Testing
LED Test TestMode
Accuracy
Module Print
SysParam Backlit
195
Chapter 23 Hardware
2.5.5 Settings
2.5.6 Report
197
Chapter 23 Hardware
2.5.8 Testing
198
Chapter 23 Hardware
199
Chapter 23 Hardware
200
Chapter 23 Hardware
3.1 Introduction
The analogue input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers.
There are four kinds of AIM, Module A, Module B, Module C and Module D
series.
201
Chapter 23 Hardware
I01
I02
I03
Protection
I04
I05
I06
I07
I08
I09
I10
I11 Metering
I12
Analogue
Terminal Remark
Input
I01 I1 Star point
I02 I1
I03 Null
I04 Null
I05 Null
I06 Null
I07 Null
I08 Null
I09 Null
I10 Null
Star point,
I11 ImB
for metering
For
I12 ImB
metering
I01
I02
U03
Protection
U04
U05
U06
U07
U08
I09
I10
Metering
I11
I12
Analogue
Terminal Remark
Input
I01 I1 Star point
I02 I1
U03 UC1 Star point
U04 UC1
U05 UC2 Star point
U06 UC2
U07 UC3 Star point
U08 UC3
I09 Null
I10 Null
Star point,
I11 ImB
for metering
For
I12 ImB
metering
203
Chapter 23 Hardware
I01
I02
I03
Protection
I04
I05
I06
I07
I08
I09
I10
Metering
I11
I12
Analogue
Terminal Remark
Input
I01 I1 Star point
I02 I1
I03 IC1 Star point
I04 IC1
I05 IC2 Star point
I06 IC2
I07 IC3 Star point
I08 IC3
I09 Null
I10 Null
Star point,
I11 ImB
for metering
For
I12 ImB
metering
204
Chapter 23 Hardware
I01
I02
I03
Protection
I04
I05
I06
I07
I08
I09
Metering
I10
I11
I12
3Ph voltage
U01
U02
U03
U04
1Ph voltage
U05
U06
205
Chapter 23 Hardware
ImA For
I10
metering
Star point
I11 ImC For
metering
For
I12 ImC
metering
206
Chapter 23 Hardware
207
Chapter 23 Hardware
4.1 Introduction
In this module, the fast binary inputs are used to connect with the signals and
alarms. The fast binary outputs are used for the tripping outputs and initiating
outputs for protection functions, or signaling output.
4 binary inputs and 7 binary output relays are provided in this module.
208
Chapter 23 Hardware
01
Binary inputs
02
03
04
DC -
05
06
07
Relay 1
08
09
Relay 2
10
11
Relay 3
Binary outputs
12
13
Relay 4
14
15
Relay 5
16
17
Relay 6
18
19
Relay 7
20
Output
Terminal Definition
relay
01 Binary input 1
02 Binary input 2
03 Binary input 3
04 Binary input 4
Common terminal
05
for all binary inputs
209
Chapter 23 Hardware
Binary inputs
Binary outputs
210
Chapter 23 Hardware
211
Chapter 23 Hardware
5.1 Introduction
This module is used to provide fast tripping outputs and initiating outputs for
protection functions, and signaling output.
10 binary output relays with 10 contacts in 5 groups are provided in the FOM.
01
02
Relay 1
03
04
05
06
Relay 2
07
08
Binary outputs
09
10 Relay 3
11
12
13
14 Relay 4
15
16
17
18 Relay 5
19
20
212
Chapter 23 Hardware
213
Chapter 23 Hardware
6.1 Introduction
In this module, the output contacts are used for controlling and signaling
outputs mainly. The binary inputs are used to connect with the input signals
and alarms. 7 binary inputs and 9 binary output relays have been provided in
this module.
214
Chapter 23 Hardware
01
Relay 1
02
Relay 2
03
04
Relay 3
05
06
Binary outputs
Relay 4
07
Relay 5
08
09
Relay 6
10
Relay 7
11
12
Relay 8
13
Relay 9
14
15
16
17
Binary inputs
18
19
20
21
DC -
22
Common
01 Contact group 1-0
terminal
02 Contact group 1-1 Relay 1
215
Chapter 23 Hardware
216
Chapter 23 Hardware
7 CPU module
7.1 Introduction
The CPU module handles all protection functions and logic, hardware
self-supervision and performs communication and information exchange
between the protection system and external equipments such as HMI, PC,
monitor, control system, substation automation system, engineer station,
RTU and printer, etc. Additionally, the CPU module transmits remote
metering, remote signaling, SOE, event reports and record data. The module
also provides binary inputs, synchronization and communication ports.
The pulse, IRIG-B or SNTP mode can be applied for time synchronization.
There are 7 binary input channels with DC24V in the CPU module.
217
Chapter 23 Hardware
01
02
Binary inputs
03
04
05
06
07
08
Synchro
09
10 Time
11
COM
12
Ethernet ports
Terminal Definition
01 Binary input 1
02 Binary input 2
03 Binary input 3
04 Binary input 4
05 Binary input 5
06 Binary input 6
07 Binary input 7
218
Chapter 23 Hardware
Item Data
Number 1
Connection Isolated, RS232; front panel,
9-pin subminiature connector, for software tools
Item Data
Number 1, only
Connection 2-wire connector
Rear port in communication module
Max. length of communication cable 1.0 km
Test voltage 500 V AC against earth
219
Chapter 23 Hardware
Item Data
Electrical communication port
Number 0 to 3
Connection RJ45 connector
Rear port in communication module
Max. length of communication cable 100m
Time synchronization
Item Data
Mode Pulse mode
IRIG-B signal format IRIG-B000
220
Chapter 23 Hardware
8.1 Introduction
The power supply module is used to provide the correct internal voltages and
full isolation between the terminal and the battery system. The module
provides 9 binary input channels as well.
221
Chapter 23 Hardware
01
02
03
04
Binary inputs
05
06
07
08
09
DC -
10
DC
DC 24V
11 output
24V +
DC
12
24V -
13
Alarm
Relay 1
14
15
DC+
16
Power input
input
17
DC-
18
input
19
20
Terminal Definition
222
Chapter 23 Hardware
01 Binary input 1
02 Binary input 2
03 Binary input 3
04 Binary input 4
05 Binary input 5
06 Binary input 6
07 Binary input 7
08 Binary input 8
09 Binary input 9
Common terminal for all
binary inputs above,
10
connect with AUX.DC
negative terminal
11 AUX.DC 24V+ output
12 AUX.DC 24V- output
13 Alarm contact (NC) 0
14 Alarm contact (NC) 1
15 Isolated terminal, not wired
16 AUX. power input 1, DC +
17 Isolated terminal, not wired
18 AUX. power input 2, DC -
19 Isolated terminal, not wired
20 Terminal for earthing
223
Chapter 23 Hardware
9 Technical data
Insulation test
224
Chapter 23 Hardware
IEC 60255-27
EN 60255-5
ANSI C37.90
GB/T 15145-2001
DL/T 478-2001
225
Chapter 23 Hardware
Mechanical tests
226
Chapter 23 Hardware
Environmental tests
Item Data
Recommended permanent operating temperature -10 C to +55C
(Legibility of display may be impaired above
+55 C /+131 F)
Storage and transport temperature limit -25C to +70C
227
Chapter 23 Hardware
Item Data
Case size 4U1/2 19inch
Weight 5kg
9.3 CE certificate
Item Data
EN 61000-6-2 and EN61000-6-4 (EMC Council
EMC Directive
Directive 2004/108/EC)
Low voltage directive EN 60255-27 (Low-voltage directive 2006/95 EC).
228
Chapter 24 Appendix
Chapter 24 Appendix
229
Chapter 24 Appendix
Description Function
Func_OC1 Disable or enable the over current stage 1
Func_OC2 Disable or enable the over current stage 2
Func_SEF Inv Disable or enable the sensitive earth fault inverse stage
Func_NSOC1 Disable or enable the negative sequence over current stage 1
Func_NSOC2 Disable or enable the negative sequence over current stage 2
Func_NSOC Inv Disable or enable the negative sequence over current inverse stage
Func_3V01 Disable or enable the voltage displacement stage 1
Func_3V02 Disable or enable the voltage displacement stage 2
Func_CBF Disable or enable the circuit breaker function
Func_ThermOL Disable or enable the thermal overload protection
Func_UV1 Disable or enable the under voltage stage 1
Func_UV2 Disable or enable the under voltage stage 2
Func_OV1 Disable or enable the over voltage stage 1
Func_OV2 Disable or enable the over voltage stage 2
Func_LF LS Disable or enable the low frequency load shedding function
Func_LV LS Disable or enable the low voltage load shedding function
Func_OL LS Disable or enable the overload load shedding function
Func_AR Disable or enable the auto-reclosing function
Func_MC Disable or enable the manual close function
Func_DZ Disable or enable the dead zone function
230
Chapter 24 Appendix
Bit 0 1
0 OC1 Dir Off OC1 Dir On
1 OC1 V_Blk Off C1_V Blk On
2 OC1 2H_Blk Off C1 2H_Blk On
3 OC2 Dir Off OC2 Dir On
4 OC2 V_Blk Off C2 V_Blk On
5 OC2 2H_Blk Off C2 2H_Blk On
6 OC Inv Dir Off OC Inv Dir On
7 OCInv 2H_Blk Off OCInv 2H_Blk On
8 EF1 Dir Off EF1 Dir On
9 EF1 2H_Blk Off EF1 2H_Blk On
10 EF2 Dir Off EF2 Dir On
11 EF2 2H_Blk Off EF2 2H_Blk On
12 EF Inv Dir Off EF Inv Dir On
13 EFInv 2H_Blk Off EFInv 2H_Blk On
14 EF Chk I2/I1 EF Chk I02/I01
15 EF U2/I2 Dir Off EF U2/I2 Dir On
Bit 0 1
0 SOTF Off SOTF On
1 SEF1 Dir Off SEF1 Dir On
2 SEF2 Dir Off SEF2 Dir On
3 SEF Inv Dir Off SEF Inv Dir On
4 SEF Chk Iscos SEF Chk U0/I0
5 Therm Alarm Off Therm Alarm On
6 Hot Curve Cold Curve
7 3I0 Measured 3I0 Calculated
8 3U0 Measured 3U0 Calculated
9 3Ph V Connect 1Ph V Connect
10 Isolate/Resist Solid earthed
11 Blk EF_CT Fail UnBlk EF_CT Fail
12 Not used Not used
13 CT Fail Off CT Fail On
14 UnBlk Fun_VTFail Blk Fun_VTFail
15 VT Fail Off VT Fail On
234
Chapter 24 Appendix
Bit 0 1
0 UV Chk CB Off UV Chk CB On
1 UV Chk All Phase UV Chk One Phase
2 UV PP UV PE
3 OV PP OV PE
4 dF(dU)/dt Off dF(dU)/dt On
5 OL LS Chk V Off OL LS Chk V On
6 CBF Chk I0/2 Off CBF Chk I0/2 On
7 CBF Chk CB Off CBF Chk CB On
8 Selection of AR check mode
9
10
11 Selection of MC check mode
12
13
14 Interlock Off Interlock On
15 NR SetGrp Switch BI SetGrp Switch
Bit 0 1
0 OC1 Alarm OC1 Trip
1 OC Inv Alarm OC Inv Trip
2 EF1 Alarm EF1 Trip
3 EF Inv Alarm EF Inv Trip
4 SEF1 Alarm SEF1 Trip
5 SEF2 Alarm SEF2 Trip
6 SEF Inv Alarm SEF Inv Trip
7 NSOC1 Alarm NSOC1 Trip
8 NSOC Inv Alarm NSOC Inv Trip
9 3V01 Alarm 3V01 Trip
10 3V02 Alarm 3V02 Trip
11 UV1 Alarm UV1 Trip
12 OV1 Alarm OV1 Trip
13 CB Faulty Off CB Faulty On
14 DS Faulty Off DS Faulty On
15 ES Faulty Off ES Faulty On
Bit 0 1
0 OC1 Init AR Off
1 OC2 Init AR Off
2 OC Inv Init AR Off
3 EF1 Init AR Off
4 EF2 Init AR Off
5 EF Inv Init AR Off
6 SEF1 Init AR Off
7 SEF2 Init AR Off
8 SEF Inv Init AR Off
9 NSOC1 Init AR Off
10 NSOC2 Init AR Off
11 NSOC Inv Init AR
12~14 Not used Not used
15 3P Fault Init AR 3P Fault Blk AR
Bit 0 1
0 Off OC1&2 Trip
1 Off OC Inv Trip
2 Off EF1&2 Trip
3 Off EF Inv Trip
4 Off SEF1&2 Trip
5 Off SEF Inv Trip
6 Off 3V0 Trip
7 Off NSOC1&2 Trip
8 Off NSOC Inv Trip
9 Off Therm OL Trip
10 Off Load SHED
11 Off OV1 Trip
12 Off OV2 Trip
13 Off UV1 Trip
14 Off UV2 Trip
Note: BO2 Ctr Word, BO3 Ctr Word, BO6 Ctr Word , BO7 Ctr Word are
defined the same as BO1 Ctr Word. Different outputs can be distributed to
different protections. Once a protection is designated to drive BO1, it will
initiate CBF function.
Description Function
Func_OC1 Disable or enable the over current stage 1
Func_OC2 Disable or enable the over current stage 2
Func_SEF Inv Disable or enable the sentitive earth fault inverse stage
Func_NSOC1 Disable or enable the negative sequence over current stage 1
237
Chapter 24 Appendix
Description Function
Func_NSOC2 Disable or enable the negative sequence over current stage 2
Func_NSOC Inv Disable or enable the negative sequence over current inverse stage
Func_3V01 Disable or enable the voltage displacement stage 1
Func_3V02 Disable or enable the voltage displacement stage 2
Func_CBF Disable or enable the circuit breaker function
Func_ThermOL Disable or enable the thermal overload protection
Func_UV1 Disable or enable the under voltage stage 1
Func_UV2 Disable or enable the under voltage stage 2
Func_OV1 Disable or enable the over voltage stage 1
Func_OV2 Disable or enable the over voltage stage 2
Func_MC Disable or enable the manual close funciton
Func_DZ Disable or enable the dead zone funciton
Table7-3 Setting list
NO. Description Scope Unit Note
1 Ctr Word 1 0000~FFFF
2 Ctr Word 2 0000~FFFF
3 Ctr Word 3 0000~FFFF
4 Ctr Word 4 0000~FFFF
5 BO1 Ctr Word 0000~FFFF
6 BO2 Ctr Word 0000~FFFF
7 BO3 Ctr Word 0000~FFFF
8 BO6 Ctr Word 0000~FFFF
9 BO7 Ctr Word 0000~FFFF
10 BO9 Ctr Word 0000~FFFF
11 I_OC1 (0.05~20.00)In A In=1A or 5A
12 T_OC1 0.00~60.00 S
13 I_OC2 (0.05~20.00)In A
14 T_OC2 0.00~60.00 S
15 U_OC_UnBlk 1.00~120.0 V Phase to phase
16 Curve_OC Inv 1~12 Refer to table 7.3.4
17 I_OC Inv (0.05~20.00)In A
18 K_OC Inv 0.05~999.0
19 A_OC Inv 0.005~200.0 S
20 B_OC Inv 0.000~60.00 S
21 P_OC Inv 0.005~10.00
22 Angle_OC 0.00~90.00 degree
23 3I0_EF1 (0.05~20.00)In A
238
Chapter 24 Appendix
24 T_EF1 0.00~60.00 S
25 3I0_EF2 (0.05~20.00)In A
26 T_EF2 0.00~60.00 S
27 Curve_EF Inv 1~12 Refer to table 7.3.4
28 3I0_EF Inv (0.05~20.00)In A
29 K_EF Inv 0.05~999.0
30 A_EF Inv 0.005~200.0 S
31 B_EF Inv 0.000~60.00 S
32 P_EF Inv 0.005~10.00
33 Angle_EF 0.00~90.00 degree
34 Angle_Neg 0.00~90.00 degree
35 I_2H_UnBlk (0.25~20.00)In A
36 3I0_2H_UnBlk (0.25~20.00)In A
37 Ratio I2/I1 0.07~0.50
38 Ratio I02/I01 0.07~0.50
39 T2h_Cross_Blk 0.00~60.00 S
40 I_SEF1 0.005~1.00(SEF) A
(0.05~20.00)In(Normal)
41 T_SEF1 0.00~60.00 S
42 I_SEF2 0.005~1.00(SEF) A
(0.05~20.00)In(Normal)
43 T_SEF2 0.00~60.00 S
44 Curve_SEF Inv 1~12 Refer to table 7.3.4
45 I_SEF Inv 0.005~1.00(SEF) A
(0.05~20.00)In(Normal)
46 K_SEF Inv 0.05~999.0
47 A_SEF Inv 0.005~200.0 S
48 B_SEF Inv 0.000~60.00 S
49 P_SEF Inv 0.005~10.00
50 Angle_SEF 0.00~90.00 degree
51 IsCOS_SEF 0.005~1.00 A
52 U_3V0_SEF 2.00~100.0 V
53 3I2_NSOC1 (0.05~20.00)In A
54 T_NSOC1 0.00~60.00 S
55 3I2_NSOC2 (0.05~20.00)In A
56 T_NSOC2 0.00~60.00 S
57 Curve_NSOC Inv 1~12 Refer to table 7.3.4
58 3I2_NSOC Inv (0.05~20.00)In A
59 K_NSOC Inv 0.05~999.0
60 A_ NSOC Inv 0.005~200.0 S
61 B_ NSOC Inv 0.000~60.00 S
62 P_ NSOC Inv 0.005~10.00
63 U_3V01 2.00~100.0 V
239
Chapter 24 Appendix
64 T_3V01 0.00~60.00 S
65 U_3V02 2.00~100.0 V
66 T_3V02 0.00~60.00 S
67 U_Phase low 10.00~100.0 V
68 U_Phase up 10.00~100.0 V
69 U_UV1 5.00~75.0(PE) V
10.00~150.0(PP)
70 T_UV1 0.00~120.0 S
71 U_UV2 5.00~75.0(PE) V
10.00~150.0(PP)
72 T_UV2 0.00~120.0 S
73 Dropout_UV 1.01~2.00
74 U_OV1 40.00~100.0(PE) V
80.00~200.0(PP)
75 T_OV1 0.00~60.00 S
76 U_OV2 40.00~100.0(PE) V
80.00~200.0(PP)
77 T_OV2 0.00~60.00 S
78 Dropout_OV 0.90~0.99
79 I_Therm OL 0.10~10.00 A
80 T_Const Therm 6.0~9999 S
81 Ratio_Cool 0.100~10.00
82 Ratio_Alarm 0.500~1.000
83 T_AR Reset 0.05~60.00 S
84 T_Syn Chk 0.05~60.00 S
85 T_MaxSynExt 0.05~60.00 S
86 T_MaxSynReq 0.05~60.00 S
87 Phase_UL 1.00~6.00
88 Angle_Syn Diff 1.00~80.00 Degree
89 U_Syn Diff 1.00~40.00 V
90 Freq_Syn Diff 0.02~2.00 HZ
91 Umin_Syn 30.00~65.0(PE) V
60~130.0(PP)
92 Umax_Energ 10~50(PE) V
20.00~100.0(PP)
93 I_CBF (0.05~20.00)In A
94 3I0_CBF (0.05~20.00)In A
95 3I2_CBF (0.05~20.00)In A
96 T_CBF1 0.00~60.00 S
97 T_CBF2 0.10~60.00 S
98 T_Dead Zone 0.00~60.00 S
99 U_Chk 10.00~120.0 V
100 I_Chk (0.00~2.00)In A
240
Chapter 24 Appendix
Bit 0 1
0 SOTF Off SOTF On
1 SEF1 Dir Off SEF1 Dir On
2 SEF2 Dir Off SEF2 Dir On
3 SEF Inv Dir Off SEF Inv Dir On
4 SEF Chk Iscos SEF Chk U0/I0
5 Therm Alarm Off Therm Alarm On
241
Chapter 24 Appendix
Bit 0 1
6 Hot Curve Cold Curve
7 3I0 Measured 3I0 Calculated
8 3U0 Measured 3U0 Calculated
9 3Ph V Connect 1Ph V Connect
10 Isolate/Resist Solid earthed
11 Blk EF_CT Fail UnBlk EF_CT Fail
12 Not used Not used
13 CT Fail Off CT Fail On
14 UnBlk Fun_VTFail Blk Fun_VTFail
15 VT Fail Off VT Fail On
242
Chapter 24 Appendix
1 1 1 Not used
Note: BO2 Ctr Word, BO3 Ctr Word, BO6 Ctr Word , BO7 Ctr Word are defined the same as
243
Chapter 24 Appendix
BO1 Ctr Word. Different outputs can be distributed to different protections. Once a protection is
Description Function
Func_OC1 Disable or enable the over current stage 1
Func_OC2 Disable or enable the over current stage 2
Func_SEF Inv Disable or enable the sentitive earth fault inverse stage
Func_CBF Disable or enable the circuit breaker function
Func_UV1 Disable or enable the under voltage stage 1
Func_UV2 Disable or enable the under voltage stage 2
Func_OV1 Disable or enable the over voltage stage 1
Func_OV2 Disable or enable the over voltage stage 2
Func_LF LS Disable or enable the low frequency load shedding function
Func_LV LS Disable or enable the low voltage load shedding function
Func_OL LS Disable or enable the over load load shedding function
Func_AR Disable or enable the auto reclosure funciton
Func_MC Disable or enable the manual close funciton
Func_DZ Disable or enable the dead zone funciton
Table7-3 Setting list
NO. Description Scope Unit Note
1 Ctr Word 1 0000~FFFF
2 Ctr Word 2 0000~FFFF
3 Ctr Word 3 0000~FFFF
4 Ctr Word 4 0000~FFFF
244
Chapter 24 Appendix
5 AR INITIATION 0000~FFFF
6 BO1 Ctr Word 0000~FFFF
7 BO2 Ctr Word 0000~FFFF
8 BO3 Ctr Word 0000~FFFF
9 BO6 Ctr Word 0000~FFFF
10 BO7 Ctr Word 0000~FFFF
11 I_OC1 (0.05~20.00)In A In=1A or 5A
12 T_OC1 0.00~60.00 S
13 I_OC2 (0.05~20.00)In A
14 T_OC2 0.00~60.00 S
15 U_OC_UnBlk 1.00~120.0 V Phase to phase
16 Curve_OC Inv 1~12 Refer to table 7.3.4
17 I_OC Inv (0.05~20.00)In A
18 K_OC Inv 0.05~999.0
19 A_OC Inv 0.005~200.0 S
20 B_OC Inv 0.000~60.00 S
21 P_OC Inv 0.005~10.00
22 Angle_OC 0.00~90.00 degree
23 3I0_EF1 (0.05~20.00)In A
24 T_EF1 0.00~60.00 S
25 3I0_EF2 (0.05~20.00)In A
26 T_EF2 0.00~60.00 S
27 Curve_EF Inv 1~12 Refer to table 7.3.4
28 3I0_EF Inv (0.05~20.00)In A
29 K_EF Inv 0.05~999.0
30 A_EF Inv 0.005~200.0 S
31 B_EF Inv 0.000~60.00 S
32 P_EF Inv 0.005~10.00
33 Angle_EF 0.00~90.00 degree
34 Angle_Neg 0.00~90.00 degree
35 I_2H_UnBlk (0.25~20.00)In A
36 3I0_2H_UnBlk (0.25~20.00)In A
37 Ratio I2/I1 0.07~0.50
38 Ratio I02/I01 0.07~0.50
39 T2h_Cross_Blk 0.00~60.00 S
40 I_SEF1 0.005~1.00(SEF) A
(0.05~20.00)In(Normal)
41 T_SEF1 0.00~60.00 S
42 I_SEF2 0.005~1.00(SEF) A
(0.05~20.00)In(Normal)
43 T_SEF2 0.00~60.00 S
44 Curve_SEF Inv 1~12 Refer to table 7.3.4
45 I_SEF Inv 0.005~1.00(SEF) A
245
Chapter 24 Appendix
(0.05~20.00)In(Normal)
46 K_SEF Inv 0.05~999.0
47 A_SEF Inv 0.005~200.0 S
48 B_SEF Inv 0.000~60.00 S
49 P_SEF Inv 0.005~10.00
50 Angle_SEF 0.00~90.00 degree
51 IsCOS_SEF 0.005~1.00 A
52 U_3V0_SEF 2.00~100.0 V
53 U_UV1 5.00~75.0(PE) V
10.00~150.0(PP)
54 T_UV1 0.00~120.0 S
55 U_UV2 5.00~75.0(PE) V
10.00~150.0(PP)
56 T_UV2 0.00~120.0 S
57 Dropout_UV 1.01~2.00
58 U_OV1 40.00~100.0(PE) V
80.00~200.0(PP)
59 T_OV1 0.00~60.00 S
60 U_OV2 40.00~100.0(PE) V
80.00~200.0(PP)
61 T_OV2 0.00~60.00 S
62 Dropout_OV 0.90~0.99
63 F_LF LS 45.00~60.00 HZ
64 T_LF LS 0.05~60.00 S
65 U_LV LS 50.00~110.0 V
66 T_LV LS 0.10~60.00 S
67 I_OL LS 0.05~20.00 A
68 T_OL LS 0.10~60.00 S
69 dF/dt_LS 1.00~10.00 HZ/S
70 dU/dt_LS 1.00~100.0 V/S
71 T_3P AR1 0.05~60.00 S
72 T_3P AR2 0.05~60.00 S
73 T_3P AR3 0.05~60.00 S
74 T_3P AR4 0.05~60.00 S
75 Times_AR 1.00~4.00
76 T_Reclaim 0.05~60.00 S
77 T_AR Reset 0.05~60.00 S
78 T_Max. CB Open 0.05~60.00 S
79 T_Syn Chk 0.05~60.00 S
80 T_MaxSynExt 0.05~60.00 S
81 T_MaxSynReq 0.05~60.00 S
82 Phase_UL 1.00~6.00
83 Angle_Syn Diff 1.00~80.00 Degree
246
Chapter 24 Appendix
247
Chapter 24 Appendix
Bit 0 1
0 SOTF Off SOTF On
1 SEF1 Dir Off SEF1 Dir On
2 SEF2 Dir Off SEF2 Dir On
3 SEF Inv Dir Off SEF Inv Dir On
4 SEF Chk Iscos SEF Chk U0/I0
5 Not used Not used
6 Not used Not used
7 3I0 Measured 3I0 Calculated
8 3U0 Measured 3U0 Calculated
9 3Ph V Connect 1Ph V Connect
10 Isolate/Resist Solid earthed
11 Blk EF_CT Fail UnBlk EF_CT Fail
12 Not used Not used
13 CT Fail Off CT Fail On
14 UnBlk Fun_VTFail Blk Fun_VTFail
15 VT Fail Off VT Fail On
248
Chapter 24 Appendix
249
Chapter 24 Appendix
BO1 Ctr Word. Different outputs can be distributed to different protections. Once a protection is
Description Function
Func_OC1 Disable or enable the over current stage 1
Func_OC2 Disable or enable the over current stage 2
Func_SEF Inv Disable or enable the sentitive earth fault inverse stage
Func_LF LS Disable or enable the low frequency load shedding function
Func_LV LS Disable or enable the low voltage load shedding function
Func_OL LS Disable or enable the over load load shedding function
Func_AR Disable or enable the auto reclosure funciton
Bit 0 1
0 SOTF Off SOTF On
1 Not used Not used
2 Not used Not used
3 Not used Not used
4 Not used Not used
5 Not used Not used
6 Not used Not used
7 3I0 Measured 3I0 Calculated
8 Not used Not used
253
Chapter 24 Appendix
Bit 0 1
9 3Ph V Connect 1Ph V Connect
10 Isolate/Resist Solid earthed
11 Blk EF_CT Fail UnBlk EF_CT Fail
12 Not used Not used
13 CT Fail Off CT Fail On
14 Not used Not used
15 VT Fail Off VT Fail On
254
Chapter 24 Appendix
Word ,BO8 Ctr Wordare defined the same as BO1 Ctr Word. Different outputs can be distributed
to different protections. Once a protection is designated to drive BO1, it will initiate CBF function.
255
Chapter 24 Appendix
Description Function
Func_SEF Inv Disable or enable the sensitive earth fault inverse stage
Bit 0 1
0~1 Not used Not used
2 OC1 2H_Blk Off C1 2H_Blk On
3~4 Not used Not used
5 OC2 2H_Blk Off C2 2H_Blk On
6 Not used Not used
7 OCInv 2H_Blk Off OCInv 2H_Blk On
8 Not used Not used
9 EF1 2H_Blk Off EF1 2H_Blk On
10 Not used Not used
11 EF2 2H_Blk Off EF2 2H_Blk On
12 Not used Not used
13 EFInv 2H_Blk Off EFInv 2H_Blk On
14 EF Chk I2/I1 EF Chk I02/I01
15 Not used Not used
257
Chapter 24 Appendix
Bit 0 1
0 SOTF Off SOTF On
1~6 Not used Not used
7 3I0 Measured 3I0 Calculated
8~10 Not used Not used
11 Blk EF_CT Fail UnBlk EF_CT Fail
12 Not used Not used
13 CT Fail Off CT Fail On
14~15 Not used Not used
Bit 0 1
0~13 Not used Not used
14 Interlock Off Interlock On
15 NR SetGrp Switch BI SetGrp Switch
Bit 0 1
0 OC1 Alarm OC1 Trip
1 OC Inv Alarm OC Inv Trip
2 EF1 Alarm EF1 Trip
3 EF Inv Alarm EF Inv Trip
4 SEF1 Alarm SEF1 Trip
5 SEF2 Alarm SEF2 Trip
6 SEF Inv Alarm SEF Inv Trip
7~12 Not used Not used
13 CB Faulty Off CB Faulty On
14 DS Faulty Off DS Faulty On
15 ES Faulty Off ES Faulty On
Bit 0 1
0 Off OC1&2 Trip
1 Off OC Inv Trip
2 Off EF1&2 Trip
3 Off EF Inv Trip
4 Off SEF1&2 Trip
5 Off SEF Inv Trip
258
Chapter 24 Appendix
Note: BO7 Ctr Word, BO8 Ctr Word, BO9 Ctr Word are defined the same
as BO6 Ctr Word. Different outputs can be distributed to different
protections. Once a protection is designated to drive BO1, it will initiate CBF
function.
Description Function
Func_3V01 Disable or enable the voltage displacement stage 1
Func_3V02 Disable or enable the voltage displacement stage 2
Func_UV1 Disable or enable the under voltage stage 1
Func_UV2 Disable or enable the under voltage stage 2
Func_OV1 Disable or enable the over voltage stage 1
Func_OV2 Disable or enable the over voltage stage 2
Table7-3 Setting list
NO. Description Scope Unit Note
1 Ctr Word 1 0000~FFFF
2 Ctr Word 2 0000~FFFF
3 Ctr Word 3 0000~FFFF
4 BO1 Ctr Word 0000~FFFF
5 BO2 Ctr Word 0000~FFFF
6 BO3 Ctr Word 0000~FFFF
7 BO4 Ctr Word 0000~FFFF
8 BO5 Ctr Word 0000~FFFF
9 BO6 Ctr Word 0000~FFFF
10 BO7 Ctr Word 0000~FFFF
11 BO8Ctr Word 0000~FFFF
12 BO9 Ctr Word 0000~FFFF
13 U_3V01 2.00~100.0 V
14 T_3V01 0.00~60.00 S
15 U_3V02 2.00~100.0 V
16 T_3V02 0.00~60.00 S
17 U_Phase low 10.00~100.0 V
18 U_Phase up 10.00~100.0 V
19 U_UV1 5.00~75.0(PE) V
10.00~150.0(PP)
20 T_UV1 0.00~120.0 S
21 U_UV2 5.00~75.0(PE) V
259
Chapter 24 Appendix
10.00~150.0(PP)
22 T_UV2 0.00~120.0 S
23 Dropout_UV 1.01~2.00
24 U_OV1 40.00~100.0(PE) V
80.00~200.0(PP)
25 T_OV1 0.00~60.00 S
26 U_OV2 40.00~100.0(PE) V
80.00~200.0(PP)
27 T_OV2 0.00~60.00 S
28 Dropout_OV 0.90~0.99
29 Upe_VT Fail 7.00~20.0 V
30 Upp_VT Fail 10.00~30.0 V
31 Upe_VT Normal 40.00~65.00 V
32 Ratio_VT 0.01~2.00
Bit 0 1
0 Not used Not used
1 Not used Not used
2 Not used Not used
3 Not used Not used
4 Not used Not used
5 Not used Not used
6 Not used Not used
7 Not used Not used
8 3U0 Measured 3U0 Calculated
9 3Ph V Connect 1Ph V Connect
10 Isolate/Resist Solid earthed
11 VT Chk CB Off VT Chk CB On
12 Not used Not used
13 Not used Not used
14 Not used Not used
15 VT Fail Off VT Fail On
260
Chapter 24 Appendix
261
Chapter 24 Appendix
BO1 Ctr Word. Different outputs can be distributed to different protections. Once a protection is
Name Function
Func_SEF Inv Disable or enable the sensitive earth fault inverse stage
262
Chapter 24 Appendix
Name Function
263
Chapter 24 Appendix
Bit 0 1
0 OC1 Dir Off OC1 Dir On
1 OC1 V_Blk Off C1_V Blk On
2 OC1 2H_Blk Off C1 2H_Blk On
3 OC2 Dir Off OC2 Dir On
4 OC2 V_Blk Off C2 V_Blk On
5 OC2 2H_Blk Off C2 2H_Blk On
6 OC Inv Dir Off OC Inv Dir On
7 OCInv 2H_Blk Off OCInv 2H_Blk On
8 EF1 Dir Off EF1 Dir On
9 EF1 2H_Blk Off EF1 2H_Blk On
10 EF2 Dir Off EF2 Dir On
11 EF2 2H_Blk Off EF2 2H_Blk On
12 EF Inv Dir Off EF Inv Dir On
13 EFInv 2H_Blk Off EFInv 2H_Blk On
14 EF Chk I2/I1 EF Chk I02/I01
15 EF U2/I2 Dir Off EF U2/I2 Dir On
265
Chapter 24 Appendix
Bit 0 1
0 Not used Not used
1 SEF1 Dir Off SEF1 Dir On
2 SEF2 Dir Off SEF2 Dir On
3 SEF Inv Dir Off SEF Inv Dir On
4 SEF Chk Iscos SEF Chk U0/I0
5 Not used Not used
6 Not used Not used
7 3I0 Measured 3I0 Calculated
8 3U0 Measured 3U0 Calculated
9 3Ph V Connect 1Ph V Connect
10 Isolate/Resist Solid earthed
11 Blk EF_CT Fail UnBlk EF_CT Fail
12 Not used Not used
13 CT Fail Off CT Fail On
14 UnBlk Fun_VTFail Blk Fun_VTFail
15 VT Fail Off VT Fail On
Bit 0 1
0 UV Chk CB Off UV Chk CB On
1 UV Chk All Phase UV Chk One Phase
2 UV PP UV PE
3 OV PP OV PE
4 Not used Not used
5 Not used Not used
6 CBF Chk I0/2 Off CBF Chk I0/2 On
7 CBF Chk CB Off CBF Chk CB On
8 Not used Not used
9 Not used Not used
10 Not used Not used
11 Not used Not used
12 Not used Not used
13 Not used Not used
14 Interlock Off Interlock On
15 NR SetGrp Switch BI SetGrp Switch
266
Chapter 24 Appendix
Bit 0 1
0 OC1 Alarm OC1 Trip
1 OC Inv Alarm OC Inv Trip
2 EF1 Alarm EF1 Trip
3 EF Inv Alarm EF Inv Trip
4 SEF1 Alarm SEF1 Trip
5 SEF2 Alarm SEF2 Trip
6 SEF Inv Alarm SEF Inv Trip
7 OL Alarm Off OL Alarm On
8 UBL Alarm Off UBL Alarm On
9 3V01 Alarm 3V01 Trip
10 3V02 Alarm 3V02 Trip
11 UV1 Alarm UV1 Trip
12 OV1 Alarm OV1 Trip
13 CB Faulty Off CB Faulty On
14 DS Faulty Off DS Faulty On
15 ES Faulty Off ES Faulty On
Bit 0 1
0 Off OC1&2 Trip
1 Off OC Inv Trip
2 Off EF1&2 Trip
3 Off EF Inv Trip
4 Off SEF1&2 Trip
5 Off SEF Inv Trip
6 Off OL Trip
7 Off UC
8 Off UV Trip
9 Off OL Trip
10 Off OV1 Trip
11 Off OV2 Trip
12 Off UV1 Trip
13 Off UV2 Trip
Note: BO2 Ctr Word, BO3 Ctr Word, BO6 Ctr Word , BO7 Ctr Word ,
BO9 Ctr Word are defined the same as BO1 Ctr Word. Different outputs
can be distributed to different protections. Once a protection is designated to
drive BO1, it will initiate CBF function.
267
Chapter 24 Appendix
Description Function
Func_OC1 Disable or enable the over current stage 1
Func_OC2 Disable or enable the over current stage 2
Func_SEF Inv Disable or enable the sentitive earth fault inverse stage
Func_3V01 Disable or enable the displacement voltage protection stage 1
Func_3V01 Disable or enable the displacement voltage protection stage 1
Func_CBF Disable or enable the circuit breaker function
Func_UV1 Disable or enable the under voltage stage 1
Func_UV2 Disable or enable the under voltage stage 2
Func_OV1 Disable or enable the over voltage stage 1
Func_OV2 Disable or enable the over voltage stage 2
Func_UBL Disable or enable unbalance detection function
Func_OL Disable or enable the over load function
Func_UC Disable or enable under current function
Func_DZ Disable or enable the dead zone funciton
Table7-3 Setting list
NO. Description Scope Unit Note
1 Ctr Word 1 0000~FFFF
2 Ctr Word 2 0000~FFFF
3 Ctr Word 3 0000~FFFF
4 Ctr Word 4 0000~FFFF
5 BO1 Ctr Word 0000~FFFF
6 BO2 Ctr Word 0000~FFFF
7 BO3 Ctr Word 0000~FFFF
8 BO6 Ctr Word 0000~FFFF
9 BO7 Ctr Word 0000~FFFF
268
Chapter 24 Appendix
Bit 0 1
0 Not used Not used
1 SEF1 Dir Off SEF1 Dir On
2 SEF2 Dir Off SEF2 Dir On
3 SEF Inv Dir Off SEF Inv Dir On
4 SEF Chk Iscos SEF Chk U0/I0
5 Not used Not used
6 Not used Not used
7 3I0 Measured 3I0 Calculated
271
Chapter 24 Appendix
Bit 0 1
8 3U0 Measured 3U0 Calculated
9 3Ph V Connect 1Ph V Connect
10 Isolate/Resist Solid earthed
11 Blk EF_CT Fail UnBlk EF_CT Fail
12 Not used Not used
13 CT Fail Off CT Fail On
14 UnBlk Fun_VTFail Blk Fun_VTFail
15 VT Fail Off VT Fail On
272
Chapter 24 Appendix
273
Chapter 24 Appendix
274
Chapter 24 Appendix
275
Chapter 24 Appendix
Two kinds of alarm report are included in the IED, which are shown in the
following table:
Alarm I is severe alarm. When alarm I happens, the alarm LED on the
front panel of the IED will flash, all of protection function will be out of
service and the trip power of protection will be blocked by the IED.
Alarm II is other alarm. When alarm II happens, the alarm LED on the
front panel of the IED will flash (except BI Set SetGr2 and BI Set
SetGr1), and will not block the trip power of protection.
278
Chapter 24 Appendix
279
Chapter 24 Appendix
280
Chapter 24 Appendix
281
Chapter 24 Appendix
3 Typical connection
A. For incoming or outgoing feeder protection or line backup
protection
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
Figure 70 Application of feeder protection to measure three phase and earth currents
282
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
Figure 71 Application of feeder protection to measure three phase and earth currents and
three phase voltages (bus side)
283
Chapter 24 Appendix
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
Figure 72 Application of feeder protection to measure three phase and earth currents and
three phase voltages (line side)
284
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
Figure 73 Application of feeder protection to measure three phase and earth currents and
single phase voltage (Ph-Ph) (bus side)
285
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
Figure 74 Application of feeder protection to measure three phase and earth currents and
single phase voltage (Ph-E) (bus side)
286
Chapter 24 Appendix
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
I01
*
I1
I02
Figure 75 Application of feeder protection to measure three phase currents, earth current,
and sensitive earth current
287
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08
IN
AIM1
I01
*
I1
I02
Figure 76 Application of feeder protection to measure three phase currents, earth current
and sensitive earth current, and three phase voltages (bus side)
288
Chapter 24 Appendix
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM1
* I01
I1
I02
Figure 77 Application of feeder protection to measure three phase currents, earth current
and sensitive earth current, and three phase voltages (line side)
289
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I1
I02
Figure 78 Application of feeder protection to measure three phase currents, earth current
and sensitive earth current, and single phase voltage (Ph-Ph) (bus side)
290
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I1
I02
Figure 79 Application of feeder protection to measure three phase currents, earth current,
and sensitive earth current, and single phase voltage (Ph-E) (bus side)
291
Chapter 24 Appendix
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02
I1
292
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
293
Chapter 24 Appendix
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM1
* I01
I02 I1
294
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
295
Chapter 24 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
296
Chapter 24 Appendix
A
B
C
A
B
C
AIM2
U05
U4
U06
U01
UA
U02
UB
U03
UC
U04
UN
297
Chapter 24 Appendix
A
B
C
AIM2
U05
U4
U06
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
298
Chapter 24 Appendix
A
B
C
I04 IC1
* I05
I06
IC2
* I07
I08 IC3
Figure 87 Typical connection for capacitor bank unbalanced current protection with three
current inputs
A
B
C
U06 UC2
U07
U08 UC3
Figure 88 Typical connection for capacitor bank unbalanced voltage protection with three
voltage inputs
299
Chapter 24 Appendix
A
B
C
I04 IC1
*
I05
I06
IC2
I07
I08 IC3
Figure 89 Typical connection for capacitor bank unbalanced current protection with one
current input
A
B
C
AIM1
Capacitor bank U03
U04 UC1
U05
U06 UC2
U07
U08 UC3
Figure 90 Typical connection for capacitor bank unbalanced voltage protection with one
voltage input
300
Chapter 24 Appendix
A A
B B
C C
I1
I1
I2
Figure 91 Unbalanced current detection for
I3
grounded capacitor bank
Figure 94 Three unbalanced currents
A detection for capacitor bank
B
C
A
B
C
I1
U1
I1
U1
Figure 93 Neutral current protection for
ungrounded split-Wye capacitor bank
Figure 96 Neutral voltage unbalanced
detection for ungrounded split-Wye
capacitor bank
301
Chapter 24 Appendix
A A
B B
C C
U1
U1
Figure 99 Neutral voltage protection for
ungrounded split-Wye capacitor bank
Figure 97 Summation of Intermediate
tap-point voltage for grounded Wye A
B
capacitor bank C
A
B
C
U1
U2
U3
U1
302
Chapter 24 Appendix
303
Chapter 24 Appendix
8 ANSI MODERATELY
0.0103 0.02 0.0228
INV.
Equation 11
304
Chapter 24 Appendix
where:
305
Chapter 24 Appendix
0.001
0.0001
1 10 100
Id/I_Inv
306
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC INV. Curve in the
following figure:
1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1.0
K=1.25
0.1
0.01
1 10 100
I/Is
307
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC VERY INV. Curve in
the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
308
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC EXTREMELY INV.
Curve in the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
309
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC LONG INV. Curve in
the following figure:
1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.1
0.01
1 10 100
I/Is
310
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ASNI INV. Curve in the
following figure:
10
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
311
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI SHOTR INV. Curve
in the following figure:
0.1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
0.0001
I/Is
312
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI LONG INV. Curve in
the following figure:
1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.1
0.01
1 10 100
I/Is
313
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI MODETATELY INV.
Curve in the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
314
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSIVERY INV. Curve in
the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
315
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI EXTREMELY INV.
Curve in the following figure:
0.1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
0.01
K=1.5
0.001
1 10 100
0.0001
I/Is
316
Chapter 24 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI DEFINITE INV.
Curve in the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
5 CT Requirement
5.1 Overview
317
Chapter 24 Appendix
Class P CT
Class PR CT
CT with limited remanence factor for which, in some cased, a value of the
secondary loop time constant and/or a limiting value of the winding
resistance may also be specified.
Class PX CT
Class TPS CT
Class TPX CT
Class TPY CT
318
Chapter 24 Appendix
transient duty cycle. Remanent flux not to exceed 10% of the saturation
flux..
Class TPZ CT
319
Chapter 24 Appendix
For different protections, Ipcf is the selected fault current in proper fault
position of the corresponding fault, which will flow through the verified CT.
Last but not least, Ipcf calculation should be based on the future possible
system power capacity
To reduce the influence of transient state, Kalf, Accuracy limit factor of CT,
should be larger than the following requirement
5.4.2 CT class
320
Chapter 24 Appendix
The selected CT should guarantee that the error is within the required
accuracy limit at steady symmetric short circuit current. The influence of short
circuit current DC component and remanence should be considered, based
on extent of system transient influence, protection function characteristic,
consequence of transient saturation and actual operating experience. To fulfill
the requirement on a specified time to saturation, the rated equivalent
secondary e.m.f of CTs must higher than the required maximum equivalent
secondary e.m.f that is calculated based on actual application.
For TPS class CT, Eal (rated equivalent secondary limiting e.m.f) is generally
determined as follows:
Where
For TPX, TPY and TPZ class CT, Eal (rated equivalent secondary limiting
e.m.f) is generally determined as follows:
Where
321
Chapter 24 Appendix
For the CTs applied to 110 - 220kV voltage level transmission line protection,
110 - 220kV voltage level transformer differential protection, 100-200MW
generator-transformer set differential protection, and large capacity motor
differential protection, the influence of system transient state to CT is so less
that the CT selection is based on system steady fault state mainly, and leave
proper margin to tolerate the negative effect of possible transient state.
Therefore, P, PR, PX class CT can be always applied.
For P class and PR class CT, Esl (the rated secondary limited e.m.f) is
generally determined as follows:
For the CTs applied to protection for110kV voltage level and below system,
the CT should be selected based on system steady fault state condition. P
class CT is always applied.
The CT accuracy class should guarantee that the protection relay applied is
able to operate correctly even at a very sensitive setting, e.g. for a sensitive
residual overcurrent protection. Generally, the current transformer should
have an accuracy class, which have an current error at rated primary current,
that is less than 1% (e.g. class 5P).
If current transformers with less accuracy are used it is advisable to check the
actual unwanted residual current during the commissioning.
5.4.4 Ratio of CT
The current transformer ratio is mainly selected based on power system data
like e.g. maximum load. However, it should be verified that the current to the
protection is higher than the minimum operating value for all faults that are to
be detected with the selected CT ratio. The minimum operating current is
different for different functions and settable normally. So each function should
be checked separately.
322
Chapter 24 Appendix
Too high flux will result in CT saturation. The secondary e.m.f is directly
proportional to linked flux. To feed rated secondary current, CT need to
generate enough secondary e.m.f to feed the secondary burden.
Consequently, Higher secondary burden, need Higher secondary e.m.f, and
then closer to saturation. So the actual secondary burden Rb must be less
than the rated secondary burden Rb of applied CT, presented
Rb > Rb
Rb = Rlead + Zb
Where
Sr: the burden of IED current input channel per phase, in VA;
For earth faults, the loop includes both phase and neutral wire, normally twice
the resistance of the single secondary wire. For three-phase faults the neutral
current is zero and it is just necessary to consider the resistance up to the
point where the phase wires are connected to the common neutral wire. The
most common practice is to use four wires secondary cables so it normally is
sufficient to consider just a single secondary wire for the three-phase case.
323
Chapter 24 Appendix
to saturate.
Where
Where
Where
324
Chapter 24 Appendix
Where
Where
Where
Where
Where
325
Chapter 24 Appendix
Where
Where
326