Valves
Valves
Valves
Types of Vaporizers
Vertical vaporizer (vertical bayonet): It is widely used for chlorine, ammonia,
propane, methanol, sulfur dioxide, etc. Sizes range from 50,000 to 15,000,000 Btu/h
(12,500 to 3,750,000 kcal/h). Very compact, high productivity, easily combined
with built-in superheater with common control. Many heating media can be
used, including steam, hot water, and heat transfer fluids such as Dowtherm,
Therminol, etc. Electric heated vaporizers also available. Small footprint. (See
Fig. V-7.)
Indirect fluid heater: Very useful for high-pressure or corrosive fluids where
special metallurgy (i.e., corrosion-resistant metals) can be used in smaller, less
costly containment than traditional shellside boiling. Heating medium (steam/
dowtherm/electric, etc.) heats an intermediate bath of water/NH3/Therminol or
similar heat-transfer fluid that then heats a second coil at much lower cost than
shellside heating or boiling. (See Fig. V-8.)
Tubular low-temperature vaporizers/superheaters: Combination large flow rate
liquid heatup and subsequent boiling or superheating of mixed fluids with diverse
boiling points. Needs special stress analysis and mechanical design. Can preheat,
boil, and superheat in same vessel. (See Fig. V-9.)
Impedance electric heaters: Electric heater for process fluids. Lowest cost
heater for life of equipment. Easily cleanable, very safe, very long life, simple
maintenance, good for high temperature boiling/heat to 2000F (1093C), very
useful for remote locations of corrosive fluids or gases. Electric current flows
through the containment tube and generates heat that is transferred to the fluid.
(See Fig. V-10.)
Electric resistance vaporizers: Classic reboilers or submerged resistance heating
elements in normal shells for pool boiling duty. Useful for low to medium capacity
loads and more common metals of construction. Can have combined superheat coils
in the same containment vessel. (See Fig. V-11.)
Vaporizers with controls: Indirect fluid electric vaporizer with controls mounted.
Very high-pressure heater of corrosive fluid. Fluid side 3175 psi (223 kg/cm2 or
216 ATM) design pressure. (See Fig. V-12.)
V-1
V-2 Vaporizers; Vaporizer Applications
FIG. V-1 Very large low-temperature vaporizer/superheater, steam heated. Unit size 132 in
(3353 mm) in diameter by 42 ft (13 cm) long. Duty to boil and superheat very low-temperature
organic liquid. (Source: Armstrong Engineering Associates.)
FIG. V-2 One of six all-stainless-steel vertical vaporizers for vertical location above tower in
Mideastern refinery. Unit size 59 in (1500 mm) in diameter by 20 ft (6100 mm) high. (Source:
Armstrong Engineering Associates.)
FIG. V-3 Indirect fluid electric heater insulated and mounted on skid with all controls in place. One
of several at the same site in South America, vaporizing organic fluids. (Source: Armstrong
Engineering Associates.)
Vaporizers; Vaporizer Applications V-3
FIG. V-4 Large-sized ethylene vaporizer (steam in shell) with entering temperature of ethylene
-67F (-55C) installed in India. Steam-heated steel shell with stainless steel heat-transfer surface.
(Source: Armstrong Engineering Associates.)
FIG. V-5 Seven large hydrocarbon fluid vaporizers for chemical plant in Middle East. Unit size 36 in
(914 mm) in diameter, overall height 135 in (3430 mm). (Source: Armstrong Engineering Associates.)
FIG. V-6 In-tube cryogenic vaporizer/superheater with steam in shell and mixed hydrocarbons on
tubeside. Steel shell with balance stainless steel for U.S. installation. (Source: Armstrong
Engineering Associates.)
V-4 Vaporizers; Vaporizer Applications
FIG. V-12 Vaporizers with controls or on skids with controls mounted. (Source: Armstrong
Engineering Associates.)
from ships or rail cars needing heatup to avoid fracture of steel or other nonductile
piping systems of user. Sizes can be up to 12 ft (3.6 m) in diameter and 40 ft
(12 m) long. Shells often steel with tubes of stainless steels 304/316, etc. (See
Fig. V-14.)
Multiplier to Convert
U.S. or SI and
British Metric SI/Metric British to
Units Units to British SI/Metric
Specifications
Shell. Ruggedly fabricated welded steel. Shells 24 in (610 mm) and below are
made of SA-106 Gr.B pipe. Larger shells are welded of steel plate of SA-516 Gr.70
normally. Tubesheets are normally of SA-516 Gr.70 material, but are also available
in stainlesses, nickel alloys, Hastelloy, etc.
Tube bundle. Removable on all sizes if required. Standard design of size A and
B units may not have a removable tube bundle. Tubes are normally 1 in (25.4 mm)
V-8 Vaporizers; Vaporizer Applications
FIG. V-15 Vertical bayonet vaporizer dimensions. (Source: Armstrong Engineering Associates.)
Plates SA 516 Gr 6070 A St 4552 DIN 17135 BS 1501-224-490 JIS G 3118 SGV 49
SA 515 Gr 60 H II DIN 17155 BS 1501-161-430 JIS G 3103 SB 42
Pipes SA 53 Gr B ST 45 DIN 1629 BS 3601 HFS-430 STPG42-G3454
(seamless) SA 106 Gr A ST 35.8 DIN 17175 BS 3602 HPS-360 STPT 38-G3456
SA 106 Gr B ST 45.8 DIN 17175 BS 3602 HFS-430 STPT42-G3456
Tubes SA 214 ST 37.2 DIN 1626 BS 3059 ERW-320 STB 35E-G3461
SA 179 ST 35.8 DIN 17175 BS 3059 CDS-320 STB 30S-G3461
Forgings SA 105 C22.8Vd TUEV 350/3 BS 1503-221-490 S25C-G4051
Studs SA 193 GR B7 21CrMoV57 DIN 17240 BS 4882 Gr B7 SNB7-G4107
Nuts SA 194 GR 2H 24CrMo5 DIN 17240 BS 4882 Gr 2H S45C-G4051
O.D., 0.083 in (2.1 mm) Bwg. but can be changed to meet customer specifications.
Top ends of tubes are securely welded shut on all units. Tubes on sizes A and B
normally have external longitudinal fins in contact with liquid being vaporized,
multiplying the external surface about eight times, but can also be supplied with
bare internal heating tubes.
Tubes are welded to the tubesheet and then rolled and expanded for additional
holding power. Rolled joints alone are not sufficient for extended periods of service.
For special services, these tubes can be of steel, stainless steel, or other materials.
Bayonet tubes are roller expanded into lower tube plate.
Vaporizers; Vaporizer Applications V-9
TABLE V-3 Approximate Dimensions* (for Steam-Heated Vessels) (Dimensions Are in Millimeters)
* Dimensions and outlet sizes may be varied to suit individual job conditions. Gauge connection is 3/4 in. All nozzles 21/2 in and over are
flanged.
NOTE: Outlets with screwed connections also available upon request (at lower cost).
Design working pressure. On the process side, normally 250 psi (17.6 kg/cm2). In
steam or hot water space, 100 psi (7 kg/cm2) (higher pressures available if needed).
All vaporizers built in the U.S. are designed, inspected, and National Board
stamped in accordance with the ASME Code. Vaporizers built outside the U.S. may
be supplied per ASME, TUV, Stoomwezen or other local codes as required.
When operating pressure goes below 25 psi on propane or butane, check with the
factory to avoid difficulty from pressure drop through nozzles. (See Table V-4.)
The 1-in-O.D. (25.4 mm) 0.083 in (2.1 mm) wall tubes, seal-welded and rolled,
give more clearance for condensate and steam. Thicker tube used in design adds to
the life of the bundle. The seal-welding, and rolling gives strength needed against
the fairly rapid variations in pressure and temperature encountered under some
conditions. To avoid a loss of process fluid through leakage (and the peril of a
potential explosion), the OEM seal-welds the tubes to the tubesheet.
See Figs. V-16 through V-18.
Design features
The tubes are free to expand or contract. Since the tubes are only secured at the bottom
end, there is no tendency for the tubes to flex or twist from temperature stress. This
is a marked advantage over units with tubesheets at both ends, where repeated
temperature stress may cause failure at the tube end.
V-10 Vaporizers; Vaporizer Applications
FIG. V-16 16-in-diameter (406-mm) chlorine vaporizer. (Source: Armstrong Engineering Associates.)
FIG. V-17 Four typical vertical vaporizers for large Mideastern refiner. Note the inlet belts on three
of the vaporizers, often used to improve shell side distribution for improved boiling and excessive
tube impingement. (Source: Armstrong Engineering Associates.)
Bottom steam feed protects against freezeup. The condensate is constantly warmed by
incoming hot steam or hot water (if that is the heating medium). Even though
the vaporizing temperature in the shell falls below freezing temperature, the
condensate does not run the risk of freezing with consequent bursting of a tube.
For boiling below 25F (-4C), consult the information source.
The tube bundle is removable and can be replaced in the field. It is no longer necessary to
remove the whole unit in the event that the tubes begin to corrode out. A
replacement bundle can be bought and installed in the field with a minimum
amount of downtime.
the load drops, the fluid level in the vaporizer drops until the output matches
demand. This automatic turndown applies to any operating level in the vertical
vaporizer. No special turndown control is needed.
2. It is easy to include a superheat section by adding height to the bundle (added
surface) sufficient to achieve the desired superheat. This is impossible in either
jacketed shell or reboiler-type vaporizers without the addition of a separate
superheating element at substantial added cost.
3. These units protect against freezeup when boiling near the freezing point of the
steam of other heating medium. The vaporizer can operate with boiling
temperatures somewhat below the freezing point. The bottom steam feed
protects the tubes against freezing so that the vaporizer can operate at boiling
temperatures below the freezing point of the heating medium condensate.
Consult factory for specific design figures in such cases.
4. The hold-up volume of process fluid is well below that in other types of
vaporizers.
5. The footprint of the vaporizer is less than any horizontal unit. It is also normally
lower than any other type of vertical in-tube or jacketed unit because of the
greater output of the vaporizer.
6. The vaporizer is a standardized design and preliminary layout drawings are
available early to enable plant layout to proceed quickly.
7. The tube bundle is removable and can easily be replaced or changed in the field.
V-12 Vaporizers; Vaporizer Applications
8. The tubes are secured only at one end and are free to expand or contract so there
is no thermal stress originating due to temperature variations in the bundle.
9. Code approval is normally easy since almost all code supervision agencies in the
world have experienced submissions of vaporizers in past years.
Steam failure. The steam controls should be arranged such that the steam cannot
be shut off at any time when cold process liquid can be in the shell at or below 32F
(0C) and the operating instructions to personnel should stress this fact.
As an example, if a thermostatic steam valve or similar control is used in the
inlet steam line, it should be limited in such a way that it cannot shut off completely
when the process fluid in the shell is below 32F (0C). A hand valve in the steam
line as a bypass around the control valve may be used to provide a positive steam
supply.
Startup procedure would be to first establish steam supply to the unit before
permitting cold process liquid to enter the shell, and shutdown procedure would be
to first stop the process fluid flow before stopping the steam. If there is a failure of
the steam supply, some precaution is desirable to stop the process fluid flow and to
immediately remove the cold process fluid from the shell.
Suggestions would include a temperature control switch in the condensate line
to sound an alarm and/or stop process fluid flow. A control indicating steam pressure
failure may also be used.
Condensate backup. The steam and condensate lines must be free draining. In the
case of a condensate return line to the boiler, care must be taken that the steam
pressure is high enough to avoid a static head in the condensate line, which may
result in backing up of condensate into the steam space of the vaporizer. This
condensate may then freeze if cold process fluid is present in the shell.
Steam trap. The steam trap must be adequately sized to avoid backup. Also, a trap
with minimum holdup of condensate is preferable. If the steam fails, condensate
will re-evaporate and return to the tubes, so an absolute minimum condensate
volume in the trap is desirable. Thermostatic traps have proven satisfactory for
many applications.
Separate trap on steam chamber. A separate trap is recommended to carry away
condensate that forms in the steam feed line and in the steam chamber.
Trap not too high. The trap on the main condensate outlet should be installed
enough below the vaporizer condensate outlet connection to avoid backing up of
condensate inside the vaporizer due to equalizing loads.
Strainers on traps. The traps should be equipped with strainers to ensure foreign
materials will not plug the trap.
Positive steam pressure. The steam should be operated at a high enough pressure
to overcome any pressure loss in lines, valves, fittings, etc., and to ensure operation
Vaporizers; Vaporizer Applications V-13
of the steam trap. Typically a pressure of 5 to 15 psig (0.35 to 1.05 kg/cm2) is used
as a minimum.
Steam trap stoppage is, arguably, the single most prevalent cause of freeze-up in
vaporizers. For critical installations, duplicate traps may be installed in parallel.
The vaporizer usually has enough surface, figured to operate below the liquid level,
to preheat the liquid and boil it.
Any surface required to superheat must be above the boiling area.
Three basic approaches to superheat are used:
1. Extension of tube bundle above liquid boiling level to add superheating surface.
2. A completely separate external superheater can be used.
3. For many fluids, reducing the pressure of discharged saturated vapor will
produce some superheat. This method may invite surging. Consult factory.
Extension of the tube bundle. This usually requires more surface than #2 (above) as
the vapor velocity is lower. Control of the gas outlet temperature is somewhat
difficult since there is only one steam supply. However, by maintaining the boiling
in the vaporizer at a fixed pressure, and setting a steam control to a fixed gas outlet
temperature, control is possible.
This method is often somewhat more compact and also less costly if the amount
of superheat is not too great.
Reasons for superheating
Superheat may be required where outlet vapor lines are long, uninsulated, or
exposed to low temperatures, so that recondensation could take place. Initial
superheat allows for line temperature losses and the vapor can be delivered intact
at the pipeline outlet end.
Some controls contain elements subject to freeze-up or damage at temperatures
below 32F (0C). Superheat of the vapor will avoid this danger.
Controlled superheat may often be required for process reasons.
Separate external superheater. This is most desirable in cases where a large amount
of superheat is needed. Superheaters are often made with finned tubes, which give
a less costly heat exchanger than one with bare tubes for this duty.
Control is simple.
See Figs. V-19 and V-20.
V-14 Vaporizers; Vaporizer Applications
FIG. V-20 The above control hookup shows a typical external superheater. The advantage of the
separate superheater is twofold. First, by having a separate steam feed on the superheater
controlled by gas outlet temperature, definite temperature control can be gained. Second, the
superheating surface is much cheaper as finned tubing than it would be in adding bare tube
surface to the vaporizer bundle for boiling. Every installation using this system has been quite
successful, although there are a number of jobs on which superheat was obtained merely by
incomplete immersion of the bundle. This does take quite a bit more surface; however, each job
should be individually calculated. (Source: Armstrong Engineering Associates.)
Vaporizers; Vaporizer Applications V-15
Propane Acetaldehyde
Acetic acid
Acetone Oxidation of propane
Formaldehyde
MEK, Methanol
Propanol
Carbon tetrachloride Propane chlorination
Perchloroethylene Propane chlorination
Nitromethane
Nitroethane Propane nitration
Propylene Acetone Wacker
Acrolein Propylene based
Acrylonitrile Sohio
Glycerine Propylene based
Polypropylene Various
Propylene oxide Glycerine Propylene oxide based
Sulfur trioxide Alkyl benzene sulfonates Various
Vinyl chloride Vinylidene chloride Acetylene based
Fluid F C
Uses of cryogenic vaporizers. These are used on vaporizing process upset fluids such
as ethylene, propylene, etc., on flare systems, where quantities exceed normal
capacity of flare drums, or to vaporize ethylene, nitrogen, etc., for consumption out
of atmospheric storage systems. They all also used on LNG tankers to vaporize
nitrogen, for padding, for loading or transfer of cargo, or in areas between tanks to
reduce explosion hazard.
See Figs. V-21 and V-22.
V-18 Vaporizers; Vaporizer Applications
FIG. V-21 Large mixed hydrocarbon vaporizer for feed temperature approximately -150F (-101C)
for installation in Eastern Gulf refinery. Unit size 132 in (3353 mm) in diameter 23 ft (7000 mm)
long. (Source: Armstrong Engineering Associates.)
FIG. V-22 Vertical vaporizer/superheater with internal helical coil. Shell is steel with internals of
stainless steel. 1412-kW (1,215,000-kcal/h) unit installed on LNG tanker to heat product and assist
pump transfer from hold. Vertical format reduces footprint when necessary. (Source: Armstrong
Engineering Associates.)
Vaporizers; Vaporizer Applications V-19
Ultra-low
Direct steam heated vaporizers for fluids boiling as low as -327F (-200C).
temperature vaporizers are designed to avoid freezeup of steam condensate since
the steam is on the shellside and condensate is always in contact with the steam.
Indirect systems often require relatively larger equipment and much more costly
instrumentation plus the maintenance and supervision that goes with that
instrumentation. Direct heated vaporizers require simpler controls than indirect
heaters plus avoid any danger of condensate freezeup except if the steam trap gets
blocked and traps condensate inside the shell. Desuperheaters can be added to give
maximum flexibility to exit vapor control temperature.
Direct heated cryogenic vaporizers have a long history of successful field
experience, using direct steam as a heating medium to boil and superheat fluids
from as low as -327F (-200C). None of these many direct-heated vaporizers, which
are in a variety of fluid duties, has ever failed from freezeup of steam condensate
to our knowledge.
Vaporizers have considerable antifatigue designs built in for grid loadout duties
where the vaporizer may operate on highly fluctuating/cyclic flow rates.
The design and method is thoroughly proven from a great many field installations
of sizes up to 40,000,000 Btu/h (10,000,000 kcal/h) per individual vaporizer.
Typical duties
1. Heating of liquid ammonia, ethylene, LPG, etc., for transfer from ship or other
low-temperature storage to ordinary steel pipelines or shipping tanks.
2. Defrosting of fluid circulating systems.
3. Vaporizing oxygen, nitrogen, etc., at temperatures down to -327F (-200C) and
pressures up to 6000 psi (422 kg/cm2) using steam or hot water as a heating
medium.
4. Heating of very corrosive fluids in separate tube bundles of metal such as Monel,
Nickel 200, Inconel 600, Incoloy 800, silicon bronze, etc.
5. Very high-pressure liquid flow can be up to 10,000 psi (703 kg/cm2 or
680 atm).
Often it is convenient to use a combined two bundle unit in a single shell, or two
separate shells using steam to vaporize an intermediate fluid, for example
methanol. The vaporized methanol then rises to the top bundle, heating up the fluid
passing through the tubes. Since methanol is not subject to freezing, and the boiling
temperature of the methanol is kept above 32F (0C), there is no freezeup hazard.
See Figs. V-23 and V-24.
FIG. V-23 Intermediate fluid transfer antifreeze heater. (Source: Armstrong Engineering Associates.)
FIG. V-24 Direct heated transfer heater. Horizontal antifreeze heater for cold ammonia, entering
temperature -28F (-33C) (or below if necessary). Steam heated. Steel and stainless steel
construction. Removable bundle. Can also be electric heated. (Source: Armstrong Engineering
Associates.)
FIG. V-25 Typical arrangement for electric water heater skid mounted unit to vaporize whatever
fluid desired. (Source: Armstrong Engineering Associates.)
FIG. V-26 Electric indirect heated (glycol bath) vaporizer, for boiling of propane, LPG, HCl, SO2, etc.
(Source: Armstrong Engineering Associates.)
FIG. V-27 Line of 36 in (914 mm) 8 in (2438 mm) indirect heated LPG vaporizers showing
insulation and controls. Installed in large apartment complex in Hong Kong. (Source: Armstrong
Engineering Associates.)
V-22 Vaporizers; Vaporizer Applications
FIG. V-28 Electric heated vaporizer: Circulating pumped water bath. System includes electric
immersion water heater, pump, piping, controls, and expansion tank, all factory piped up and
delivered on skid ready to operate. (Source: Armstrong Engineering Associates.)
fluid that might offer severe corrosive attack to the sheath metal of the electric
heater. This typed unit is often used for C3H8, Cl2, C4H10, SO2, Freons, etc.
See Figs. V-29 and V-30.
FIG. V-29 Electric indirect vaporizer in process and flow. (Source: Armstrong Engineering
Associates.)
FIG. V-30 Direct electrically heated ammonia vaporizer. (Source: Armstrong Engineering
Associates.)
V-24 Vaporizers; Vaporizer Applications
FIG. V-31 The above vaporizer hookup shows an arrangement that is often used for ammonia and
other gases in addition to propane. The liquid level is important to make sure the liquid will flow by
gravity or otherwise into the vaporizer. The pipelines must be large enough to overcome any
hydraulic loss in the flow system, to make sure that the vaporizer tube bundle will be covered.
Otherwise, at low levels, the vaporizer will not have full capacity. The pressure-actuated valve may
not be absolutely necessary, but is desirable in many cases. Since it is usually better to keep the
steam on at all times, this avoids excess boiling at times when the tank may already have
adequate pressure. (Source: Armstrong Engineering Associates.)
the beginning of operation at the low temperature; get the whole body of the tank
and its stored liquid up to the operating temperature, say 70F (21C), and then
furnish enough heat to overcome the convection heat loss from the outside surface
of the tank to the ambient air. Also, sufficient capacity is needed to heat the fresh
incoming liquid as it arrives by tank car, assuming that it also has cooled down to
the outdoor temperature.
To illustrate the application, take an example of a 30,000 U.S. gallon uninsulated
storage tank, 9 ft in diameter by 63 ft long, to be filled with 10,000 U.S. gallons
of liquid anhydrous ammonia in a 10-h day, assuming 70F required tank
temperature, and with an ambient outdoor temperature of -30F. The outside
surface area of the tank is 1827 ft2. The convection heat loss can be taken
conservatively as 5 Btu/h/ft2/F at a wind speed of 20 mph.
Ambient heat loss is then
Note: 120.5 is enthalpy of liquid at 70F (21C); 10.7 is enthalpy of liquid at -30F
(-34C).
Vaporizers; Vaporizer Applications V-25
Note: 66.94 kcal/kg is enthalpy of liquid ammonia at 21C; 5.94 kcal/kg is enthalpy
of liquid ammonia at -34C.
This duty is added to the amount of vapor withdrawn from the tank to process, if
any.
1. Since there is wide variety in preferences as to method, make, and type of control,
it often takes several times as long to work up quotations on units with controls
as it does to quote bare vaporizers.
V-26 Vaporizers; Vaporizer Applications
FIG. V-33 Process vaporizer with controls factory mounted. Note float and float-operated valve,
liquid level gauge, thermostatic steam valve, condensate traps, bursting disc relief valves, and
miscellaneous hand valves, including bypasses and strainers. (Source: Armstrong Engineering
Associates.)
Vaporizers; Vaporizer Applications V-27
FIG. V-34 Typical control hookup for routine fluid vaporizing. Note presence of shellside float
valve. This operates to stop liquid feed when flow level gets too high due to excessive draw of
fluid from the vaporizer. The valve shuts down flow of the liquid feed to the vaporizer to avoid
carryover of liquid into the exit line. (Source: Armstrong Engineering Associates.)
FIG. V-35 Typical control setup when specific superheated temperature is required. For normal
chlorine vaporizing see separate diagram. (Source: Armstrong Engineering Associates.)
V-28 Vaporizers; Vaporizer Applications
2. It usually takes several weeks longer to supply vaporizers with controls than it
does to complete a bare vaporizer.
Liquid to vaporizervapor direct to load (vapor does not return to storage tank). Figure
V-34 shows the most common dependable hookup for automatic operation. Liquid
from the tank enters either by gravity, differential pressure, or may be fed by liquid
pump when necessary to ensure adequate pressure to go through the reducing
valves. This liquid enters the three lines and may go alternatively through the valve
under normal operation, or through the hand bypass if the pilot valve is out. The
pilot valve is controlled by a float on the shell that limits the level to which the
liquid can rise above the tubesheet face.
There may or may not be a pressure-reducing valve between the storage tank
and the controls shown in the figure, and depending on the duty, there may be a
further vapor pressure-reducing valve after the outlet, before the load.
In most cases, the steam is fed by hand feed only, and is left on all the time. A
trap may be used to drain the regular condensate outlet, and another one to also
drain the condensate that forms in the steam chamber.
Vaporizers; Vaporizer Applications V-29
FIG. V-37 Viscosity temperature for various fluids. (Source: Armstrong Engineering Associates.)
If the unit is operating normally and the vapor outlet line is suddenly closed due
to load variations, the steam being on, the pressure would normally build up rapidly
with the liquid being confined in the vaporizer. This might cause the relief valve to
blow and lose fluid. To avoid this, the center bypass check is installedcalled a
blowback. When the vaporizer pressure exceeds the feed pressure, the flow will
reverse, allowing the liquid to leave the vaporizer and return to the tank. Obviously,
this blowback line must take into consideration the particular design of pump and
pressure relief valves, if either are present, and must be arranged to bypass them
if they will not permit reverse flow.
Constant vapor outlet temperature. The hookup illustrated in Fig. V-35 shows an
alternate arrangement that is sometimes used to give a fairly constant vapor outlet
temperature. It may be combined with a constant pressure arrangement through
use of pumps and reducing valves if the pressure must also be controlled to obtain
constant gas density for the requirements of mixing valves.
This sketch also shows an alternate arrangement sometimes used to get a
constant gas density for an air-gas mixing valve. The thermostatic valve will
maintain a constant gas-off temperature and a constant propane pressure in the
vaporizer.
V-30 Vaporizers; Vaporizer Applications
FIG. V-38 Latent heattemperature for various fluids. (Source: Armstrong Engineering Associates.)
FIG. V-39 Heat capacityspecific heattemperature for various fluids. (Source: Armstrong
Engineering Associates.)
Vibration Measurement V-31
Vaporizers will furnish superheat if operated at lower ratings than those shown.
The amount of superheat available by operating at reduced liquid level and using
the upper part of the bundle for superheating, however, is limited. If a large amount
of superheat is required, then a separate superheater may be advisable from a cost
standpoint, as it often takes a great deal more surface to superheat the gas than
to vaporize the liquid.
Vents are provided on a storage tank so that the tank can breathe. Inhale
happens if a temperature drop causes a liquid volume reduction. It also can occur
if liquid is withdrawn from the tank. Exhale happens in the reverse
circumstances. Required thermal venting capacity is determined from tank capacity
and fluid flashpoint. A tank supplier will ask what fluid your tanks will hold and
the steady temperature and pressure at which the fluid is to be held. Vent capacity
can then be determined. Conservation vent valves have just a slightly different
design to minimize evaporative losses.
Flame arrestors are provided on tanks storing fluids with a flashpoint of less than
110F. Flame arrestors should also be provided on storage tanks for liquids with a
flashpoint above 110F, where a combustible environment exists or other potentially
hazardous condition, such as the heating of heavy oils.