P139 EN M A88 Vol1
P139 EN M A88 Vol1
P139 EN M A88 Vol1
Feeder Management
and Bay Control
Version: -304/306/307 -
405/406/407/408/409/410/411/412/413 -
605/611/612
Technical Manual
Volume 1 of 2
P139/EN M/A88
Contains:
V605 P139/EN M/B33 (AFSV.12.09450.D)
V611 P139/EN AD/A77 (AFSV.12.09690.D)
V612 P139/EN AD/A88 (AFSV.12.09950 D)
MiCOM P139
Feeder Management
and Bay Control
Version 304 405/406/407 -605
Technical Manual
Volume 1 of 2
P139/EN M/B33
(AFSV.12.09450 D)
! Warning
When electrical equipment is in operation, dangerous voltage will be present in certain parts of the
equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the device must be isolated. Where stranded conductors
are used, wire end ferrules must be employed.
Proper and safe operation of this device depends on appropriate shipping and handling, proper
storage, installation and commissioning, and on careful operation, maintenance and servicing.
For this reason only qualified personnel may work on or operate this device.
Any modifications to this device must be in accordance with the manual. If any other modification
is made without the express permission of AREVA T&D, it will invalidate the warranty, and may
render the product unsafe.
Qualified Personnel
are individuals who
! are familiar with the installation, commissioning, and operation of the device and of the system to which it is being
connected;
! are able to perform switching operations in accordance with safety engineering standards and are authorized to
energize and de-energize equipment and to isolate, ground, and label it;
! are trained in the care and use of safety apparatus in accordance with safety engineering standards;
! are trained in emergency procedures (first aid).
Note
The operating manual for this device gives instructions for its installation, commissioning, and operation. However, the
manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of
questions or specific problems, do not take any action without proper authorization. Contact the appropriate AREVA
technical sales office and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of AREVA, including settlement
of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the operating
manual.
Stckprfbescheinigung P139
Routine Test Certificate P139
Fertigung und Prfung der Schutzeinrichtungen erfllen die Anforderungen von EN ISO 9001.
AREVA Energietechnik GmbH has been awarded the DNV certificate by the internationally recognized, independent and impartial
association for the certification of quality assurance systems, DNV (DET NORSKE VERITAS CERTIFICATION FRANCE), thereby
certifying that AREVA has introduced and uses a state-of-the-art quality assurance system that complies with all requirements stated
in EN ISO 9001 that apply to its products and services.
Stckprfung
Routine Test
2 Isolationsprfung
Insulation test
3 Operation 3-1
3.1 Modular Structure 3-1
3.2 Operator-Machine Communication 3-3
3.3 Configuration of the Bay Panel, the Indication (LOC) 3-4
Panel and the Measured Value Panels;
Selection of the Control Point
3.4 Serial Interfaces 3-12
3.4.1 PC Interface (PC) 3-12
4 Design 4-1
4.1 Designs 4-1
4.2 Modules 4-8
7 Settings 7-1
7.1 Parameters 7-1
7.1.1 Device Identification 7-2
7.1.2 Configuration Parameters 7-6
7.1.3 Function Parameters 7-45
7.1.3.1 Global 7-45
7.1.3.2 General Functions 7-53
7.1.3.3 Parameter Subsets 7-77
7.1.3.4 Control 7-99
7.2 Protection of Increased-Safety Machines 7-108
7.2.1 General 7-108
7.2.2 Restrictive Safety-Oriented Configuration 7-108
9 Commissioning 9-1
9.1 Safety Instructions 9-1
9.2 Commissioning Tests 9-3
10 Troubleshooting 10-1
11 Maintenance 11-1
12 Storage 12-1
Appendix AP-1
Content AP-2
A Glossary A-1
B List of Signals B-1
C List of Bay Types C-1
D Terminal Connection Diagrams D-1
E Address List E-1
(The Address List is available as a PDF file.
It is not included in the printed manual.)
F Upgrade Documentation F-1
The P139 time-overcurrent protection and control device is a one-box solution for
protection and control.
The protection functions available in the device provide selective short-circuit protection,
ground fault protection, and overload protection in medium- and high-voltage systems.
The systems can be operated as impedance-grounded, resonant-grounded, grounded-
neutral or isolated-neutral systems. The multitude of protection functions incorporated
into the device enable the user to cover a wide range of applications in the protection of
cable and line sections, transformers and motors. The relevant protection parameters
can be stored in four independent parameter subsets in order to adapt the device to
different operating and power system management states.
The control functions are designed for the control of up to six electrically operated
switchgear units equipped with plant status signaling and located in the bay of a
medium-voltage substation (or a high-voltage station with basic topology). The P139
has more than 250 predefined Bay Types stored for selection and it is also possible to
load user-defined bay templates.
External auxiliary devices are largely obviated by the integration of binary signal inputs
operating from any auxiliary voltage, and versatile relay output contacts, by the direct
connection option for current and voltage transformers, and by the comprehensive
interlocking capabilities. This simplifies the handling of switch bay protection and control
technology from planning to commissioning.
During operation, the user-friendly interface makes it easy to set the device parameters
and allows safe operation of the substation by preventing non-permissible switching
operations.
The P139 is equipped with a large number of protection and control functions. These
can be individually configured and de-configured.
These features give the user the means to adapt the device to the protection and control
capacity required in a specific application.
The powerful programmable logic provided by the device also makes it possible to
accommodate special applications.
General functions
Functions listed in the tables above are self-contained function groups (except for
ILOCK) and can be individually configured or de-configured according to the specific
application requirements. Unused or de-configured function groups are hidden to the
user, thus simplifying the menu.
This concept provides a large choice of functions and makes wide-ranging application of
the protection device possible, with just one model version. On the other hand simple
and clear parameter settings can be made.
In this way the protection and control functions (except for ILOCK) can be included in or
excluded from the configuration; they are arranged on the branch "General Functions" of
the menu tree.
Control functions
Switchgear contact positions are acquired by the P139 through up to 20 binary signal
inputs, that can signal and process a maximum of 10 two-pole contact positions. A
maximum of 12 output relays are available to control a maximum of 10 two-pole
switchgear units.
Up to 40 operation signals can be acquired though binary signal inputs and they are
processed according to their primary significance (e.g. CB readiness). Each binary
signal input for signals from switchgear and single-pole operations can have the
debouncing and chatter suppression from eight groups assigned, for which the
debouncing and chatter time can be individually set.
A binary signal input is configurable to acquire a binary counter value. The binary
integrated total is stored should the supply voltage fail. Counting continues from the
stored total as the starting value when the device restarts.
The P139 sends control signals only after it has checked the readiness and validity to
carry out such commands, and it then monitors the operating time of the switchgear
units. If the device concurs that a switchgear unit has failed, it will signal this information
(e.g. by configuration to a LED indicator).
Before a switching command is issued the interlocking logic on the P139 checks if this
new switchgear status corresponds with the bay and station topology. The interlocking
logic is stored in form of bay interlocking, with and without station interlocking, for each
Bay Panel in the default setting. The interlocking conditions can be adapted to the
actual bay and station topology. Interlocking display and operation correspond with the
programmable logic.
When a P139 is included in a station control system the local interlocking can easily be
integrated with the overall system interlocking.
When the device is not included in a station control system then bay interlocking is
applied without station interlocking.
If the bay and station topology are found to be valid the switching command is issued. If
a non-permissible status would result from the switching action the issuing of such a
switching command is refused and an alarm is issued.
If not all binary outputs are required by the bay type then these vacant binary outputs
can be freely utilized for other purposes.
Global functions
In addition to the listed features, and extensive self-monitoring, the P139 is equipped
with the following global functions:
Design
The P139 is modular in design. The plug-in modules are housed in a robust aluminum
case and electrically interconnected via one analog p/c board and one digital p/c board.
# 4 current-measuring inputs
# 4 or 5 voltage-measuring inputs
# 8 or 14 output relays, freely-configurable
# 6 binary signal inputs (opto-coupler) and 6 output relays to control 3 switchgear units
or
# 12 binary signal inputs (opto-coupler) and 12 output relays to control 6 switchgear
units
# 4, 8 or 28 additional binary signal inputs with user-definable function assignment
With the maximum number of binary signal inputs and output relays fitted, 10 switchgear
units can be monitored and 6 of these can be electrically controlled.
The nominal currents and nominal voltages of the standard measuring inputs in the P139
can be set. As an option, currents and voltages from non-conventional instrument
transformers can be connected to the NCIT module.
The nominal voltage range of the binary signal inputs (opto-coupler) is 24 to 250 V DC.
As an option binary signal input modules with a higher switching threshold are available.
The auxiliary voltage input for the power supply is also designed for an extended range.
The nominal voltage ranges are 48 to 250 V DC and 100 to 230 V AC. As an option
there is a variant available for the lower nominal voltage range 24 V to 36 V DC.
All output relays can be utilized for signaling and command purposes.
The optional (up to 10) inputs for resistance thermometers on the temperature p/c board
are lead-compensated and balanced.
Two selectable measured variables (cyclically updated measured operating data and
stored measured fault data) can be output as a burden-independent direct current via
the two optional 0 to 20 mA outputs. The characteristics are defined by 3 adjustable
interpolation points allowing a minimum output current (4 mA, for example) for slave-side
open-circuit monitoring, knee-point definition for fine scaling, and a limitation to lower
nominal currents (10 mA, for example). Where sufficient output relays are available, a
selectable measured variable can be output in BCD-coded form by contacts.
External clock synchronization can be accomplished by using the optional IRIG-B input.
A direct link to other MiCOM protection devices can be set up by applying the optional
InterMiCOM protective interface (channel 3).
2 Technical Data
2.1 Conformity
Notice
Applicable to P139, version -301 -401 -601.
Declaration of conformity
(Per Article 10 of EC Directive 72/73/EC.)
The product designated P139 Time-Overcurrent Protection and Control Unit has been
designed and manufactured in conformance with the European standards EN 60255-6
and EN 61010-1 and with the EMC Directive and the Low Voltage Directive issued by
the Council of the European Community.
Installation Position
Vertical 30.
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52; IP 20 for rear connection space with flush-mounted case.
Weight
40 TE case: Approx. 7 kg
84 TE case: Approx. 11 kg
Terminals
2.3 Tests
Type tests
All tests per EN 60255-6 or IEC 255-6.
Electromagnetic
compatibility (EMC)
Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A.
Insulation
Voltage Test
Per DIN EN 61010-1 and IEC 255-5
2 kV AC, 60 s
Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supply
inputs. The PC interface and the NCIT current and voltage measuring inputs must not
be subjected to the voltage test.
Mechanical robustness
Vibration Test
Per EN 60255-21-2 or IEC 255-21-1, test severity class 1
Frequency range in operation: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Frequency range during transport: 10 to 150 Hz, 1 g
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 1
Frequency range:
5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s2, 3 x 1 cycle.
Voltage Test
Per IEC 255-5
2.2 kV AC, 1 s
Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supply
inputs.
The PC interface must not be subjected to the voltage test.
Environment
Temperatures
Recommended temperature range: -5C to +55C or +23F to +131F
Limit temperature range: -25C to +70C or -13F to +158F.
Solar Radiation
Direct solar radiation on the front of the device must be avoided.
Measuring inputs
Current Measuring Inputs (conventional)
Nominal current Inom: 1 and 5 A AC (adjustable)
Nominal consumption per phase: < 0.1 VA at Inom
Load rating:
continuous 4 Inom
for 10 s: 30 Inom
for 1 s: 100 Inom
Nominal surge current: 250 Inom
or
Current Measuring Inputs (NCIT)
Per IEC 60044-8
NCIT voltage 22,5 mA at 50 A
or
Voltage Measuring Inputs (NCIT)
Per IEC 60044-7
NCIT voltage 3.25 V / 3 at Vnom,prim / 3
Frequency
Nominal frequency fnom: 50 Hz and 60 Hz (adjustable)
Operating range: 0.95 to 1.05 fnom
Frequency protection: 40 to 70 Hz
Resistance thermometer
Resistance thermometer:
Only PT 100 permitted for analog (I/O) module, mapping curve per IEC 75.1
PT 100, Ni 100 or Ni 120 permitted for temperature p/c board (the RTD module)
Value range: -40.0C to +215.0C (-40F to +419F)
3-wire configuration: max. 20 per conductor
Open and short-circuited input permitted
Open-circuit monitoring: > +215C and < -40C ( > +419F and < -40F)
Output relays
Rated voltage: 250 V DC, 250 V AC
BCD-coded measured
data output
Maximum numerical value that can be displayed: 399
Analog measured
data output
Value range: 0 to 20 mA
Load permitted: 0 to 500
Maximum output voltage: 15 V
2.6 Interfaces
PC interface
Transmission rate: 300 to 115,200 baud (adjustable)
Communication interface
The communication module A can be provided with up to three communication channels,
depending on the module variant. Channel 1 and 3 may either be equipped to connect
wire leads or optical fibers and channel 2 is only available to connect wire leads.
Wire Leads
Per RS 485 or RS 422, 2 kV isolation
Distance to be bridged:
Point-to-point connection: max. 1200 m
Multipoint connection: max. 100 m
1)
Distance to be bridged given for identical optical outputs and inputs at both ends, a
system reserve of 3 dB, and typical fiber attenuation.
IRIG-B interface
B122 format
Amplitude-modulated signal
Carrier frequency: 1 kHz
BCD- coded variable data (daily)
1)
Distance to be bridged given for identical optical outputs and inputs at both ends, a
system reserve of 3 dB, and typical fiber attenuation.
2.8 Settings
Time-voltage protection
Operate time including output relay (measured variable from nominal value to 1.2-fold
operate value or measured variable from nominal value to 0.8-fold operate value):
40 ms, approx. 30 ms
Reset time (measured variable from 1.2-fold operate value to nominal value or measured
variable from 0.8-fold operate value to nominal value):
45 ms, approx. 30 ms
Resetting ratio for V<>: 1 to 10 % (adjustable)
for operate values > 0,6 Vnom and Vnom/3: approx. 0,95
for operate values < 0,6 Vnom and Vnom/3: approx. 1.05
2.9 Deviations
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient
temperature 20C (68F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Measuring-circuit
monitoring
Operate values Ineg, Vneg
Deviation: 3 %
Definite-time and inverse-
time overcurrent protection
Phase and Residual Current Stages
Deviation: 5 %
Short-circuit direction
determination
Deviation: 10
Unbalance protection
Deviation: 5 %
Time-voltage protection
Operate Values
Deviation: 5 % (referred to the nominal value 1 %)
Over-/underfrequency
protection
Operate Values
Deviation: 3 % (referred to the nominal value 1 %)
Power directional
protection
Operate Values P<>, Q<>
Deviation: 5 %
Sector angle:
Deviation: 1
Deviation
Deviation relative to the setting under reference conditions.
Definite-time stages
Deviation: 1% + 20 ms to 40 ms
Inverse-time stages
Deviation when I 2 Iref:
5 % + 10 to 25 ms
For IEC characteristic 'extremely inverse' and for thermal overload protection:
7.5 % + 10 to 20 ms
2.9.3 Deviations of Measured Data Acquisition
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient
temperature 20C (68F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Operating data
measurement
Measuring Input Currents
Deviation: 1 %
Load Angle
Deviation: 1
Frequency
Deviation: 10 mHz
Temperature
Deviation: 2C
Fault data
Short-Circuit Current and Voltage
Deviation: 3 %
Internal clock
With free running internal clock:
Deviation: < 1 min/month
Overload memory
Number: The 8 most recent overload events
Scope: All signals relating to an overload event; from a total of 1024 different logic state
signals (see Overload Memory in the Address List)
Depth: 200 entries per overload event
Fault memory
Number: The 8 most recent fault events
Signals
Time resolution: 1 ms
Fault values
Time resolution: 20 sampled values per period
Phase currents
Dynamic range: 100 Inom / 25 Inom (adjustable)
Amplitude resolution: 6.1 mA r.m.s. / 1.5 mA r.m.s. at Inom = 1 A
30.5 mA r.m.s. / 7.6 mA r.m.s. at Inom = 5 A
Residual current
Dynamic range: 16 Inom / 2 Inom (adjustable)
Amplitude resolution: 0.98 mA r.m.s. / 0.12 mA r.m.s. at Inom = 1 A
4.9 mA r.m.s. / 0.61 mA r.m.s. at Inom = 5 A
Voltages
Dynamic range: 150 V AC
Amplitude resolution: 9.2 mVr.m.s.
The following equation is used to calculate the specifications of a current transformer for
the offset maximum primary current:
(
Vsat = (R nom + R i ) n Inom R op + R i k I1,
'
max)
with:
Vsat: saturation voltage (IEC knee point)
'
I1,max : non-offset maximum primary current, converted to the secondary side
Inom : rated secondary current
n: rated overcurrent factor
k: over-dimensioning factor
Rnom : rated burden
Rop actual connected operating burden
Ri : internal burden
The specifications of a current transformer can then be calculated for the minimum
required saturation voltage Vsat as follows:
( )'
Vsat R op + R i k I1,max
(R op + R i ) '
I1,max (Pop + Pi ) '
I1,max
n k = k
(R nom + R i ) Inom (Pnom + Pi ) Inom
with:
2
Pnom = R nom Inom
2
Pop = R op Inom
2
Pi = R i Inom
Theoretically, the specifications of the current transformer could be calculated for lack of
saturation by inserting instead of the required over-dimensioning factor k its maximum
value:
k max 1 + T1
with:
: system angular frequency
T1: system time constant
If the P139 is to be used for definite-time overcurrent protection, then the over-
dimensioning factor k that is to be selected is primarily a function of the ratio of the
maximum short-circuit current to the set operate value and, secondly, of the system time
constant T1. The required over-dimensioning factor can be read from the empirically
determined curves in Figure 2-1. When inverse-time maximum current protection is
used, the over-dimensioning factor can be taken from Figure 2-2.
10
T1= 10 ms
T1= 25 ms
T1= 50 ms
T1= 250 ms
0.01
1 10 100
I' /I
1,max operate
2-1 Required over-dimensioning factor for definite-time overcurrent protection with fnom = 50 Hz
25
k 20
15
10
0
0 50 100 150 200 250
T1 / ms
2-2 Required over-dimensioning factor for inverse-time maximum current protection with fnom = 50 Hz
When the P139 is equipped with a CT/VT-Board with NCIT, non-conventional instrument
transformers per IEC 60044-8 (electronic current transformers) and IEC 60044-7
(electronic voltage transformers) can be connected to the P139 instead of conventional
CTs or VTs.
This feature will enable the user to utilize the advantages that the non-conventional
instrument transformer technology offers and because of the diversity of available
sensors their numbers in the bay may be reduced. Up to five devices can be connected
to one NCIT. (Designing with 200 k terminal resistors is required.)
In addition transformer saturation is avoided and thermal loading of cables and
protection inputs is low because signals are low level/low burden.
*
A A
D D
*option
NCIT_1_EN
2-3 Connecting NCITs to the P139 equipped with a CT/VT-Board with NCIT
The NCIT inputs I1 to I3 on the MiCOM P30 series are designed as follows:
! Rated range of the primary phase currents from 50 to 4000 A, adjustable in steps of
50 A (M A I N : I n o m p r i m . N C I T )
! Dynamic range of measuring input designed for 25 kA
! Optimization of the dynamic range through an internal amplification factor which is
defined by the set rated range
! Dynamic range 25 Inom / 100 Inom (setting depends on model) similar to standard
processing of measured values
Residual current measurement IN with the NCIT inputs on the MiCOM P30 range:
! Generating the residual current by analog summation in order to obtain the highest
sensitivity for the measurand with its own amplification factor
! No individual core balance transformer necessary for the measurement of the
sensitive earth fault (residual current)
! Rated range of the primary residual currents from 10 to 800 A, adjustable in steps of
10 A (M A I N : I N , n o m p r i m . N C I T )
X3
4 + +
A (100 x Inom)
5 + -
A' (25 x Inom)
1 + +
B (100 x Inom)
2 + -
B' (25 x Inom)
7 + +
C (100 x Inom)
+ -
8
C' (25 x Inom)
IN (16 x Inom)
IN' (2 x Inom)
NCIT_2_EN
2-4 NCIT inputs on the MiCOM P30 range (dynamic range dependent on model)
V X1
4 +
O
L 5 - V1
B
TB 1 +
A1 -
2 V2
G
E 7 +
8 - V3
X2
V 4
+
O -
LB 5
+
TB 1
Vref
A2 2
-
G +
7
E -
8
NCIT_3_EN
3 Operation
The P139, a numeric device, is part of the MiCOM P 30 family of devices. The device
types included in this family are built from identical uniform hardware modules.
Figure 3-1 shows the basic hardware structure of the P139.
The external analog and binary quantities electrically isolated are converted to the
internal processing levels by the peripheral modules T, Y, and X. Commands and
signals generated by the device internally are transmitted to external destinations via
floating contacts through the binary I/O modules X. The external auxiliary voltage is
applied to the power supply module V, which supplies the auxiliary voltages that are
required internally.
The analog data are always transferred from the transformer module T to the processor
module P by way of the analog bus module.The processor module contains all the
elements necessary for the conversion of measured analog variables, including
multiplexers and analog/digital converters. The analog data processed by analog
module Y are fed to the processor module P by way of the digital bus module. Binary
signals are fed to the processor module by the binary I/O modules X via the digital bus
module. The processor handles the processing of digitized measured variables and of
binary signals, generates the protective trip as well as the control commands and
signals, and transfers them to the binary I/O modules X via the digital bus module. The
processor module also handles overall device communication. As an option,
communication module A can be mounted on the processor module to provide serial
communication with substation control systems.
The control and display elements of the integrated local control panel and the integrated
PC interface are housed on control module L.
The following interfaces are available for the exchange of information between operator
and device:
All setting parameters and signals as well as all measured variables and control
functions are arranged within the branches of the menu tree following a scheme that is
uniform throughout the device family. The main branches are:
Parameters branch
This branch carries all setting parameters, including the device identification data, the
configuration parameters for adapting the device interfaces to the system, and the
function parameters for adapting the device functions to the process. All values in this
group are stored in non-volatile memory, which means that the values will be preserved
even if the power supply fails.
Operation branch
This branch includes all information relevant for operation such as measured operating
data and binary signal states. This information is updated periodically and consequently
is not stored. In addition, various control parameters are grouped here, for example
those for resetting counters, memories and displays.
Events branch
The third branch is reserved for the recording of events. Therefore all information
contained in this group is stored. In particular the start/end signals during a fault, the
measured fault data as well as sampled fault records are stored here and can be read
out at a later time.
Settings and signals are displayed either in plain text or as addresses, in accordance
with the users choice. The appendix documents the settings and signals of the P139 in
the form of an address list. This address list is complete and thus contains all settings,
signals and measured variables used with the P139.
Normally the local control panel will display the Bay Panel, which represents a selected
bay and shows the up-to-date switching status. The configuration of the local control
panel also permits the installation of Measured Value Panels on the LCD display.
Different panels are automatically displayed for certain system operating conditions.
Priority increases from normal operation to operation under overload conditions and
finally to operation following a short circuit in the system. Thus the P139 provides the
measured data relevant for the prevailing conditions.
3.3 Configuration of the Bay Panel and of the Measured Value Panels;
Selection of the Control Point (Function Group LOC)
The layout of a bay with its switchgear units is displayed on the Bay Panel. A Bay Panel
usually consists of one Bay Panel image as a standard but after applying the bay editor
from the PC Access Software MiCOM S1 and having loaded a customized Bay Panel it
can be sub-divided into up to eight images. The graphic LCD also permits the display of
Event and configurable Signal Panels. In addition the P139 offers Measured Value
Panels, which display the measured values relevant at a given time.
During normal power system operation; the Bay Panel or if activated the Operation
Panel is displayed. If the Operation Panel is activated as an event occurs, the display
switches to the appropriate Event Panel provided that measured values have been
selected for the Event Panels. In the event of overload or ground fault events, the
display will automatically switch to the Operation Panel at the end of the event. In the
event of a fault, the Fault Panel remains active until the LED indicators or the fault
memories are reset.
Bay Panel
The P139 offers a selection of pre-defined bay types. Should the required bay type be
missing from the standard selection then the user can contact the manufacturer of the
P139 to request the definition of a customized bay type to download into the P139. By
applying the bay editor from the PC Access Software MiCOM S1 the user can also
define new bay types. The number of this additional bay type will then be displayed at
MAIN: Customized bay type.
The Bay Panel displays the up-to-date switching status of the selected bay as a single
line (phase) diagram. The activation of the Bay Panel display is described in the
Chapter entitled "Local Control Panel". The user can switch between two character sets
to represent the switchgear units on the Bay Panel display. The character sets are also
described in Chapter "Local Control Panel". Each external device represented in the
Bay Panel is identified by an external device designation as selected by the user. The
user can also select the designations for busbars and busbar sections. The display of
external device designations can be deactivated. The display of the control point (local
or remote control) and interlocking can also be deactivated.
The switchgear unit to be controlled needs to be selected first. The selection is valid for
the set time L O C : R e t u r n t i m e s e l e c t .
The measured values that will be displayed on the Bay Panel can first be selected
separately for the numerical and the bar chart display by an m out of n parameter.
Measured values to be displayed in bar chart form must also be selected for display as
numerical measured values. However, not all measured values that can be displayed in
numerical form can also be displayed in bar chart form. In such cases, a dummy or
placeholder must be included in the selection list for the bar chart display at the same
point at which a measured value that cannot be displayed in bar chart form appears in
the selection list for numerical measured values.
For the bar chart display, the orientation of the bar and the scaling can be selected (the
latter separately for the current and voltage data). Display of the scaling can be
deactivated.
Signal Panel
The Signal Panel is displayed when it is selected and when at least one signal has been
configured. From all physical and logical binary states that the device has available up
to 28 signals can be selected for display on the Signal Panel by an m out of n
parameter. This occurs without influencing the Event Panel, which is additionally
available. When more signals are selected for display than the LC display can
accommodate, then the display will switch to the next set of signals at intervals defined
by the setting at L O C : P a n e l H o l d - T i m e or when the appropriate key on the local
control panel is pressed. If automatic switching to the Signal Panel is configured at
L O C : A u t . a c t i v . S i g n . P a n e l then the Signal Panel is automatically selected
when there is a change of state for a signal configured in the panel.
Signal
m out of n
Signal
Signal LOC: Autom. LOC: Autom.
return time
return time
Signal
LOC: Hold-time LOC: Hold-time
Selected signals for Panels for panels
LOC: Aut.activ.
LOC: Indicat.Sign. Sign.Panel
Panel
LOC: Stat.ind.
Sign.Panel
no signal.
flash. panel LOC: Sign.caus.
Sign.Panel
flash. lines
Selection
C
LOC: Chg.Sig.
Panel stat.
Sig. Panel
LOC:Chg.Sig.
Panel flash.
Operation Panel
The Operation Panel is displayed when it is selected and when at least one measured
value has been configured. The user can select which of the measured operating values
will be displayed on the Operation Panel by means of an m out of n parameter. If more
measured values are selected for display than the LC display can accommodate, then
the display will switch to the next set of values at intervals defined by the setting at
L O C : H o l d - T i m e for P a n e l s or when the appropriate key on the local control
panel is pressed.
Fault Panel
The Fault Panel is displayed in place of another data panel when there is a fault,
provided that at least one measured value has been configured. The Fault Panel
remains on display until the LED indicators or the fault memories are cleared.
The user can select the measured fault values that will be displayed on the Fault Panel
by setting an 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at L O C : H o l d - T i m e f o r P a n e l s or
when the appropriate key on the local control panel is pressed.
The user can select the measured values that will be displayed on the Ground Fault
Panel by setting a 'm out of n' parameter. If more measured values are selected for
display than the LC display can accommodate, then the display will switch to the next set
of values at intervals defined by the setting at L O C : H o l d - T i m e f o r P a n e l s or
when the appropriate key on the local control panel is pressed.
Overload Panel
The Overload Panel is automatically displayed in place of another data panel when there
is an overload, provided that at least one measured value has been configured. The
Overload Panel remains on display until the overload ends, unless a fault occurs. In this
case the display switches to the Fault Panel.
The user can select the measured values that will be displayed on the Overload Panel
by setting a 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at L O C : H o l d - T i m e f o r P a n e l s or
when the appropriate key on the local control panel is pressed.
Selection of the
control point
Switchgear units can be controlled from a remote location or locally. Switching between
local and remote control is achieved using either the L/R key on the local control panel or
an external key switch. The position of this switch is interrogated via an appropriately
configured input (configuration at M A I N : I n p . a s g . L / R k e y s w .) If the input is
configured 'to L/R key switch' then the L/R key on the local control panel is without
function. This setting at L O C : F c t . a s s i g n . L / R k e y determines whether the
switching (using either the L/R key or the key switch) is between local and remote control
(LR) or between local+remote and local control (R&LL).
If only remote control is enabled then there will be a local access blocking. If only local
control is enabled then there will be a remote access blocking.
LOC: Rem.acc.
block.active
Local LOC: Loc.acc.
Remote block.active
Remote & Local LOC:Remote&
local control
MAIN: Inp.asg
L/R key sw.
Signal
Signal
Signal
Signal
Without function
Selected signal
If the communication module A with two communication channels is installed, settings for
two communication interfaces will be available. The setting of communication interface 1
(COMM1) may be assigned to the physical communication channels 1 or 2 (see section
"Main Functions"). If the COMM1 settings have been assigned to communication
channel 2, then the settings of communication interface 2 (COMM2) will automatically be
active for communication channel 1. Communication channel 2 can only be used to
transmit data to and from the P139 if its PC interface is inactive. As soon as the PC
interface is used to transmit data, communication channel 2 becomes "dead".
If tests are run on the P139, the user is advised to activate the test mode. In this way the
PC or the control system will recognize all incoming test signals accordingly (see section
"Main Functions").
Communication between the device and a PC is through the PC interface. In order for
data transfer between the P139 and the PC to function, several settings must be made in
the P139.
There are several different interface protocols available at the communication interface
1. The following user-selected interface protocols are available for use with the P139:
In order for data transfer to function properly, several settings must be made in the P139.
Address mode
003 168
3-11 Communication interface 1, settings for the IEC 60870-5-103 interface protocol
(The address mode is not supported with P139 605)
3-12 Communication interface 1, settings for the IEC 870-5-101 interface protocol
Checking spontaneous
signals
For interface protocols based on IEC 60870-5-103, IEC 870-5-101, or ILS_C it is
possible to select a signal for test purposes. The transmission of this signal to the control
station as sig. start or sig. end can then be triggered via the local control panel.
In order for data transfer to function properly, several settings must be made in the P139.
Checking spontaneous
signals
It is possible to select a signal for test purposes. The transmission of this signal to the
control station as sig. start or sig. end can then be triggered via the local control panel.
Application
Communication interface 3 is designed to establish a digital communication link between
two MiCOM devices over which up to 8 binary protection signals may be transmitted.
Whereas communication interfaces 1 and 2 are designed as information interfaces to
connect to data acquisition subsystems and for use in remote control, communication
interface 3 is designed as a protective interface that will transmit signals in real time
(InterMiCOM protective interface). Its main application is to transmit signals from
protective signaling (function group PSIG). In addition any other internal or external
binary device signals may also be transmitted.
Physical medium
COMM3 is provided as an asynchronous, full-duplex communication interface. To
transmit data the following physical media are available:
Digital network:
! Asynchronous data interface of primary multiplexing equipment
Telegram configuration
The communication baud rate is settable (C O M M 3 : B a u d r a t e ) to adapt to the
transmission channel requirements. Sending and receiving addresses (C O M M 3 :
S o u r c e a d d r e s s and C O M M 3 : R e c e i v i n g a d d r e s s can be set to different
values, thus avoiding that the device communicates with itself.
! Binary signals 1 to 4:
Operating mode settable to 'Blocking' or 'Direct intertrip'
! Binary signals 5 to 8:
Operating mode settable to 'Permissive' or 'Direct intertrip'
Speed
fast
Blocking
Permissive
high high
Direct
Security Intertrip Dependability
3-20 Comparison of speed, security and dependability offered by the three operating modes.
Communication monitoring
C O M M 3 : T i m e - o u t c o m m . f a u l t is used for monitoring the transmission channel
(this timer is re-triggered with each complete and correct received telegram). The wide
setting range allows adaptation to the actual channel transmission times and above all
this is needed for time-critical schemes such as the blocking scheme. After the timer
has elapsed, signals C O M M 3 : C o m m u n i c a t i o n s f a u l t and
S F M O N : C o m m u n i c . f a u l t C O M M 3 are issued and the received signals are
automatically set to their user-defined default values
(C O M M 3 : D e f a u l t v a l u e r e c . x , with x = 1 to 8). As the main application for this
protective signaling the fault signal may be mapped to the corresponding input signal in
function group PSIG with the C O M M 3 : S i g . a s g . c o m m . f a u l t setting.
New start of
[120 043] COMM3:
monitoring 1
Communications fault
timer stages
Supervision of
communication link quality
After a syntax check of each received message, InterMiCOM updates the ratio of
incorrectly received messages, based on a total of the last 1000 received messages.
The result is provided as updating measurand C O M M 3 : N o . t e l . e r r o r s p . u .
and the overall maximum ratio can be read from
COMM3: No.t.err.,max,stored.
If the set threshold C O M M 3 : L i m i t t e l e g r . e r r o r s is exceeded the
corresponding signals C O M M 3 : L i m . e x c e e d . , t e l . e r r .
and S F M O N : L i m . e x c e e d . , t e l . e r r . will be issued. All corrupted telegrams are
counted (C O M M 3 : N o . t e l e g r a m e r r o r s ) . This counter as well as the stored
maximum ratio of corrupted messages can be reset via
COMM3: Reset No. tel.errors.
Commissioning tools
The actual values of send and receive signals can be read from the device as physical
state signals (C O M M 3 : S t a t e s e n d x and C O M M 3 : S t a t e r e c e i v e x , with x
= 1 to 8). In addition, InterMiCOM provides 2 test facilities for commissioning of the
protection interface.
For a loop-back test, the send output is directly linked back to the receive input. After
setting the bit pattern wanted (as an equivalent decimal number at
C O M M 3 : L o o p b a c k s e n d ) the test can be triggered via
C O M M 3 : L o o p b a c k t e s t . This bit pattern is sent for the duration of the hold time
set at C O M M 3 : H o l d t i m e f o r t e s t . Only for this test, the source address is set to
'0', a value that is not used for regular end-end communication. The test result can be
checked as long as the hold-time is running by reading the measured operating data
C O M M 3 : L o o p b a c k r e s u l t and C O M M 3 : L o o p b a c k r e c e i v e . As soon
as the hold-time has expired, the loop back test is terminated and InterMiCOM reverts to
the normal sending mode (i.e. sending the actual values of the configured send signals,
using the set source address).
Thus in case of communication problems, the loop back test can be used to verify or to
exclude a defective device. The transmission channel including the receiving device can
be checked manually by setting individual binary signals
(C O M M 3 : S e n d s i g n a l f o r t e s t ) to user-defined test values
(C O M M 3 : L o g . s t a t e f o r t e s t ). After triggering the test by
C O M M 3 : S e n d s i g n a l , t e s t , the preset binary signal is sent with the preset value
for the set hold time C O M M 3 : H o l d t i m e f o r t e s t . The 7 remaining binary
signals are not affected by this test procedure and continue to be sent with their real
values. During the hold time, a received signal can be checked at the receiving device,
e.g. by reading the physical state signal. After the hold time has expired, the test mode
is reset automatically and the actual values of all 8 signals are transmitted again.
3.5 Time Synchronization via the IRIG-B Interface (Function Group IRIGB)
If a GPS receiver with an IRIG-B connection is available, for example, then the internal
clock in the P139 can be synchronized to GPS time through the optional IRIG-B
interface. The user must keep in mind that the IRIG-B signal contains only one piece of
information about the date (the day as numbered since the beginning of the year). On
the basis of this piece of information about the date, the P139 calculates the current date
(DD.MM.YY) based on the year set in the P139.
Synchronization readiness
Once the IRIG-B interface has been enabled and is receiving a signal, the P139 checks
the received signal for plausibility. Non-plausible signals are rejected by the P139. If a
correct signal is not received by the P139 continuously, then the synchronization function
is no longer ready.
3.6 Configuration and Operating Mode of the Binary Inputs (Function Group INP)
The P139 has optical coupler inputs for processing binary signals from the substation.
The functions that will be activated by triggering these binary signal inputs are defined by
the configuration of the binary signal inputs. The trigger signal must persist for at least
30 ms in order to be recognized by the P139.
In this manual, we assume that the required functions (marked 'EXT' in the address
description) have been assigned to binary signal inputs by configuration.
There is a second optional analog module available for the P139. In addition to the
analog (I/O) module Y with analog inputs and outputs there is now a second analog
module obtainable, the temperature p/c board (also called the RTD module).
When the P139 is equipped with the analog (I/O) module Y it has two analog inputs
available for measured data input. Direct current is fed to the P139 through the 20 mA
analog input (input channel 1). The other input is designed for connection of a PT 100
resistance thermometer.
The temperature p/c board (the RTD module) mounted in the P139 has 9 analog inputs
available to connect temperature sensors T1 to T9. These analog inputs are designed
for connection of PT 100, Ni 100 or Ni 120 resistance thermometers.
The input current IDC present at the analog (I/O) module Y is displayed as a measured
operating value. The current that is conditioned for monitoring purposes (ID,Clin) is also
displayed as a measured operating value. In addition, it is monitored by the Limit Value
Monitoring function to detect whether it exceeds or falls below set thresholds (see "Limit
Value Monitoring").
The measured temperatures are also displayed as measured operating values and
monitored by the Limit Value Monitoring function to determine whether they exceed or
fall below set thresholds (see "Limit Value Monitoring").
All measured variables are also forwarded to the Thermal Overload Protection function.
With this protection it is possible to set whether the PT 100 resistance thermometer, the
20 mA analog input or if configured one of the temperature sensors T1 to T9 is to be
used for the thermal replica (see "Thermal Overload Protection").
When setting the characteristic the user must remember that only a rising/rising or
falling/falling curve sense is allowed (no peak or vee-shapes). If the setting differs, the
signal C H E C K : I n v a l i d s c a l i n g I D C will be generated.
IDClin / IDC,nom
1.2
1.1
1
IDClin20
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
IDClin1 0
0 0.1 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6 IDC/ IDC,nom
IDC1 IDC20
D5Z52KDA
19Z5266A_EN
IDClin / IDC,nom
0,8
Interpolation points
IDClin20 0,7
0,6
IDClin4 0,5
0,4
IDClin3 0,3
IDClin2 0,2
IDClin1 0,1
0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,1 1,2
3-26 Example of a characteristic with five interpolation points (characteristic with zero suppression setting of 0.1 IDC,nom is shown as a broken
line)
Zero suppression
Zero suppression is defined by setting M E A S I : E n a b l e I D C p . u . If the direct
current does not exceed the set threshold, the per-unit input current IDC p.u. and the
current IDC,lin will be displayed as having a value of 0.
The input current is monitored in order to protect the 20 mA analog input against
overloading. If it exceeds the set threshold of 24.8 mA, the signal M E A S I :
O v e r l o a d 2 0 m A i n p u t is issued.
Backup sensors
The open circuit signal on the 20 mA analog input from the function group MEASI is
forwarded to the Thermal Overload Protection function. Here it is possible to set
whether the resistance thermometer connected to the PT 100 input or if configured
one of the temperature sensors T1 to T9, connected to the temperature p/c board (the
RTD module), is to be used as a backup sensor (see "Thermal Overload Protection").
Beyond the linearization described above, the user has the option of scaling the
linearized values. Thereby negative values, for example, can be displayed as well and
are available for further processing by protection functions.
3.7.2 Connecting a Resistance Thermometer to the "PT 100 Analog Input" on the
Analog (I/O) Module Y
This analog input on the analog (I/O) module Y is designed to connect a PT 100
resistance thermometer. The mapping curve R = f(T) of PT 100 resistance
thermometers is defined in standard IEC 751. If the PT 100 resistance thermometer is
connected using the 3-wire method, then no further calibration is required.
Open-circuit monitoring
If there is an open measuring circuit due to a broken wire, the signal M E A S I : O p e n
c i r c . P T 1 0 0 is issued.
MEASI: Enabled
SFMON: PT100
open circuit
MEASI: Temperature
T
MEASI: Temperature
p.u. T
MEASI: Temperature
Tmax
19Z5262A_EN
3-29 Temperature measurement using a PT 100 resistance thermometer connected to the analog (I/O) module
Backup sensors
The open circuit signal on the PT 100 analog input from the function group MEASI is
forwarded to the functions Thermal Overload Protection and Limit Value Monitoring.
In the Thermal Overload Protection it is possible to set whether the 20 mA input or if
configured one of the temperature sensors T1 to T9, connected to the temperature p/c
board (the RTD module), is to be used as a backup (see "Thermal Overload Protection").
In the Limit Value Monitoring function the limit values assigned to the faulty PT 100 are
blocked.
3.7.3 Connecting Temperature Sensors to the Temperature P/C Board (the RTD
Module)
The temperature p/c board (the RTD module) mounted in the P139 has 9 analog inputs
available to connect temperature sensors T1 to T9. These analog inputs are designed
for connection of PT 100, Ni 100 or Ni 120 resistance thermometers.
If the PT 100 resistance thermometer is connected using the 3-wire method, then no
further calibration is required.
All nine temperature sensors must be of the same type, which is set under M E A S I :
Type of TempSensors
Open-circuit monitoring
If one of the measuring circuits is open due to a broken wire, the signal M E A S I :
O p e n c i r c . P T 1 0 0 T x (x = 1 to 9) is issued.
MEASI: Enabled
SFMON: PT100 T1
open circuit
MEASI: Temperature
T1
MEASI: Temperature
p.u. T1
MEASI: Temperature
T1max
19Z5263A_EN
3-30 Temperature measurement with temperature sensor T1 connected to the temperature p/c board. The same applies to sensors T2 to T9.
In the data model P139-605 the temperature sensors T1 to T9 are identified as U 301 to U 309.
In future software versions this designation will be adapted to the new device identifier scheme. The input designation will then be
U81 to U89 (as in the terminal connection diagram).
Backup sensors
The open circuit signals from temperature sensors, issued by function group MEASI, are
forwarded to the Thermal Overload Protection function. Should the main temperature
sensor (that has been set in the Thermal Overload Protection) fail, it is possible to select
in whether the 20 mA input or if configured one of the temperature sensors T1 to T9,
connected to the temperature p/c board (the RTD module), is to be used as a backup
sensor (see "Thermal Overload Protection").
In addition to this, the open circuit signals from the temperature sensors, issued by the
function group MEASI, are forwarded to the Limit Value Monitoring function. The
selection of such backup sensors for the Limit Value Monitoring function is made in the
function group M E A S I .
For this purpose the temperature sensors connected to the temperature p/c board (RTD
board) are divided into three groups:
If the backup temperature sensor from group 2 also fails it will be replaced by the
corresponding sensor from group 3, under the assumption that M E A S I :
B a c k u p T e m p S e n s o r P S x is set to Group 1 2/3.
Main sensor Backup sensor from group 2 Backup sensor from group 3
With setting: With setting:
Group 1 -2 Group 1 2/3
or
Group 1 -2/3
T1 T4 T7
T2 T5 T8
T3 T6 T9
Should temperature sensor T1 fail, with the setting Group 1 2/3, it will replaced by T4.
Should temperature sensor T4 also fail it will replaced by T7.
For further details refer to section with the description of the "Limit Value Monitoring".
Application example
A motor protection application is shown in the figure below with temperature sensors T1
to T9 connected to the temperature p/c board (RTD module) and a "PT 100" resistance
thermometer connected to the analog (I/O) module Y.
RTD
RTD
RTD
RTD
RTD
RTD
RTD
RTD Stator
RTD
RTD
Rotor
Bearing Bearing
19B5236A_EN
3-31 Temperature measurements on a motor to be used with the Limit Value Monitoring function (L I M I T )
and the Thermal Overload protection (THERM)
The P139 has output relays for the output of binary signals. The binary signals to be
issued are defined by configuration.
3-32 Configuration, setting the operating mode, and blocking the output relays
Measurands made available by the P139 can be provided in BCD (binary coded
decimal) form through output relays or in analog form as direct current output. Output as
direct current can only occur if the device is equipped with analog module Y. BCD-
coded output is always possible, whether the device is equipped with analog module Y
or not.
! The measured data output function is reset from the integral local control panel or
through an appropriately configured binary signal input.
! There is a general reset.
! LED indicators are reset.
Scaling
Scaling is used to map the physical measuring range to the device inherent setting
range.
Scaling of analog output is also suited for directional-signed output of some fault
measurands, in particular fault location in percent.
The user can select a measurand for output in BCD-coded form by assigning output
relays.
The selected measurand is available in BCD-coded form for the duration of the set hold
time M E A S O : H o l d T i m e O u t p u t B C D . If the selected variable was not
measured, then there is no output of a value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is re-
started. If the hold time has been set to "blocked", the measured operating value that
has been output will be stored until the measured data output function is reset.
The BCD display range should be set so that the value 399 is never exceeded. If this
should occur or if the measurand is outside the acceptable measuring range, then the
value for "Overflow" (all relays triggered) is transmitted.
Measurands Range
Measurands of the Mx,RL1 ... Mx,RL2
variable Mx
Associated scaled 0 ... 1
measurands
Scaling is made with reference to the complete range of values for the selected
measurand (variable Mx). The complete range of values is defined by their end values
Mx,RL1 and Mx,RL2. (Mx,RL1 and Mx,RL2 are listed in the operating program S&R-103
- PC Access Software MiCOM S1 - under "minimum" and "maximum".)
Measurands Range
Fault measurand: -320,00% ... +320,00%
FT_DA: Fault
locat. percent
Associated scaled 0 ... 1
measurands
/Parameter/Config.parameters/
Address Description Current value
056 020 MEASO: Function group MEASO 'With'
The following figure displays the values output as a function of the fault location. The
BCD-coded value and the signal M E A S O : V a l i d B C D v a l u e = 'Yes' are only
issued in the value range 0% to 200%.
200
BCD
value
0
-320% 0% 200% 320%
Note:
Except from radial, single circuit lines the fault location value gives a reasonable value
only for faults up to the line end. For any fault on a subsequent line the fault location is
more or less incorrect due to unknown fault current infeed in the remote substation.
It is recommended to limit the calculation of a fault location to a practical and sensible
range on the line by setting F T _ D A : O u t p u t f a u l t l o c a t . = 'Only aft.tr.t1/t1,ze'.
MEASO: 1-digit
bit
MEASO: 1-digit
bit
Setting blocked MEASO: 1-digit
bit
measured
MEASO: Fct.
assignm. BCD value
Measured value 1
Measured value 2
Measured value 3
Measured value n
Scaling of the
Selected meas. val. BCD output
++
MEASO: Output
value x
19Z5264A_EN
3-38 BCD-coded measured data output Overflow behavior is displayed in BCD example (see previous figure)
The user can select two of the measurands available in the P139 for output in the form of
load-independent direct current. Three interpolation points per channel can be defined
for specific adjustments such as adjustment to the scaling of a measuring instrument.
The direct current that is output is displayed as a measured operating value.
The selected measurand is output as direct current for the duration of the set hold time
M E A S O : H o l d T i m e O u t p u t A - x . If the selected variable was not measured,
then there is no output of a measurand value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is re-
started. If the hold time has been set to "blocked", the measured operating value that
has been output will be stored until the measured data output function is reset.
Configuration of output
relays assigned to the
output channels
The user must keep in mind that direct current output only occurs when the output relays
assigned to the output channels are configured for M E A S O : V a l u e A - x O u t p u t ,
since the output channels would otherwise remain short-circuited (see terminal
connection diagrams).
Measurands Range
Measurands of the Mx,RL1 ... Mx,RL2
variable Mx
Associated scaled 0 ... 1
measurands
Measurands Range
Measurands of the 0 V ... 150 V
variable Mx
Associated scaled 0 ... 1
measurands
/Parameter/Config.parameters/
Address Description Current value
056 020 MEASO: Function group 'With'
MEASO
031 074 MEASO: General enable 'Yes'
USER
053 000 MEASO: Fct. assignm. A-1 MAIN:
Voltage A-B PU
010 114 MEASO: Hold time output A-1 1.00 s
037 104 MEASO: Scaled min. val. A-1 0.013 (corresponds with 0.02 Vnom)
037 105 MEASO: Scaled knee val. A-1 0.067 (corresponds with 0.10 Vnom)
037 106 MEASO: Scaled max. val. A-1 0.667 (corresponds with 1.00 Vnom)
037 107 MEASO: AnOut min. val. A-1 4 mA
037 108 MEASO: AnOut knee point A- 16 mA
1
037 109 MEASO: AnOut max. val. A-1 18 mA
Note:
A check of the set characteristic and its acceptance by the device, if the setting was
properly entered, will only occur after the device, with the setting M A I N : D e v i c e o n -
l i n e is again switched on-line.
Ia / mA
20
Max.
output value18
Knee point
16
output value
14
12
10
6
Min.
output value 4
2
0
0 0.02 0.1 1 1.2 1.3 1.4 1.5 Vnom
0,013 0,067 0,667 1,0Mx,scal
D5Z52KFA
19Z5265A_EN
3-39 Example of a characteristic curve for analog measured data output . In this example the range starting value is = 0; also possible is
directional-signed output (see corresponding example in section BCD-coded Measured Data Output).
Measured data from external devices, which must be scaled to 0 ... 100%, can be written
to the following parameters of the P139 via the communications interface.
These "external" measured values are output by the P139 either in BCD-coded data
form or as load-independent direct current, provided that the BCD-coded measured data
output function or the channels of the analogue measured data output function are
configured accordingly.
The P139 has 17 LED indicators for the indication of binary signals. Four of the LED
indicators are permanently assigned to functions. A further LED has a default
assignment but may be reconfigured if required. The other LED indicators are freely
configurable.
In the acquisition of signals for control purposes, the functions real time acquisition (time
tagging), debouncing and chatter suppression are included as standard. Each of these
signals can be assigned to one of eight groups and for each of these groups the
debouncing time and chatter suppression can be set. Matching of these two parameters
achieves the suppression of multiple spurious pickups.
3-42 Group assignment and setting of debouncing and chatter suppression, illustrated for group 1
Debouncing
The first pulse edge of a signal starts a timer stage running for the duration of the set
debouncing time. Each pulse edge during the debouncing time re-triggers the timer
stage. If the signal is stable until the set debouncing time elapses, a telegram containing
the time tag of the first pulse edge is generated.
If the signal has not changed its state from the occurrence of the first pulse edge to the
elapsing of the set debouncing time, no telegram is generated.
Chatter suppression
Sending of the first telegram starts a timer stage running for the duration of the set
monitoring time. While the timer stage is elapsing, telegrams are generated for the
admissible signal changes. The number of admissible signal changes can be set. After
the first "inadmissible" signal change, no further telegrams are generated and the timer
stage is re-triggered. While the timer stage is elapsing, it is re-triggered by each new
signal change. Once the timer stage has elapsed, each signal change triggers a
telegram.
The P139 is designed to control up to six switchgear units. The Bay Panel type defines
the layout of a bay with its switchgear units.
The P139 offers a selection from pre-defined bay types. Should the required bay type
be missing from the standard selection then the user can contact the manufacturer of the
P139 to request the definition of a customized bay type to download into the P139. By
applying the bay editor from the PC Access Software MiCOM S1 the user can define
new bay types. The number of this additional bay type will then be displayed at M AIN :
Customized bay type .
Once the user has selected a bay type, the P139 can automatically configure the binary
inputs and outputs with function assignments for the control of switchgear units. The
assignment of inputs and outputs for an automatic configuration is shown in the List of
Bay Types in the Appendix.
The secondary phase currents of the system transformers are fed to the P139. There is
the option of connecting up to five voltage transformers. The measured variables are
electrically isolated converted to normalized electronics levels. Air-gap transformers
are used in the phase current path to suppress low frequency (DC decays and offsets)
signal components. The analog quantities are digitized and are thus available for further
processing.
Settings that do not refer to nominal quantities are converted by the P139 to nominal
quantities. The user must therefore set the secondary nominal currents and voltages of
the system transformers.
The connection direction of the measuring circuits on the P139 must also be set.
Figure 3-46 shows the standard connection. By this setting the phase of the digitized
currents is rotated by 180.
If the P139 is to operate with the GFDSS function (ground fault direction determination
using steady-state values), current transformer T4 needs to be connected to a current
transformer in Holmgreen connection (dashed lines in Figure 3-46 ) or to a core balance
current transformer.
When the P139 is equipped with the NCIT module (non conventional instrument
transformer) the conventional CTs are exchanged by NCITs as shown in the following
figure ("Connecting the P139 measuring circuits"), and described in Chapter
2\"Conecting NCITs to the NCIT Module" and in Annex D\"Connecting NCITs".
When the P139 is equipped with the temperature p/c board (RTD module) further
resistance thermometers, in addition to the PT 100 resistance thermometer connected to
the analog module (I/O), can be connected to the RTD module as described in Chapter
3\"Measuring Data Input"\"Connecting resistance thermometers to the RTD module" and
in Annex D\"Temperature p/c board for PT 100, Ni 100 or Ni 120 (RTD module)".
3-46 Connecting the P139 measuring circuits (when the P139 is equipped with the NCIT module or the RTD module; see references in previous
text)
The P139 has an operating data measurement function for the display of currents and
voltages measured as well as quantities derived from these measured values. For the
display of measured values, set lower thresholds need to be exceeded, to avoid
fluctuating small values from noise. If these lower thresholds are not exceeded, the
value "not measured" is displayed. The following measured variables are displayed:
The measured data are updated at 1 s intervals. Updating is interrupted when a general
starting signal is issued or if the self-monitoring function detects a hardware fault.
3-50 Determining the minimum and maximum phase-to-ground and phase-to-phase voltages
MAIN: General
starting int.
MAIN: Hardware
fault
V G > 1,5 V
MAIN: Angle
phi N
MAIN: Appar.
power S p.u.
MAIN: Active
power P p.u.
MAIN: Reac.
power Q p.u.
MAIN: Active
MAIN: Inom C.T. power factor
prim.
MAIN: Reac.
power Q prim.
19Z5240A_EN
3-54 Measured operating data - power, active power factor, and angle
Phase relation IN
The P139 checks if the phase relations of calculated residual current and measured
residual current agree. If the phase displacement between the two currents is 45,
then the indication Equal phase is displayed.
Frequency
The P139 determines the frequency from the voltage VA-B. This voltage needs to exceed
a minimum threshold of 0.65 Vnom in order for frequency to be determined.
There are two procedures available to determine active and reactive energy. If
procedure 1 is selected, active and reactive energy are determined every 2 s
(approximately) as in software versions 601. If procedure 2 is selected, active and
reactive energy are determined every 100 ms (approximately) thus achieving higher
accuracy. Whenever the maximum value of 655.35 MWh or 655.35 Mvar h is exceeded,
a counter is incremented and the determination of the energy output is restarted. The
value that exceeded the range is transferred to the new cycle.
3-57 Determining the active and reactive energy output and input
1 ! Determination of the active and reactive energy ! Constant load and slow load variations (no
every 2 s (approximately) significant load variations within 1 second).
! Reduced system loading ! Phase angles below 70 (cos > 0.3 ).
5%
2%
3-58 Error of measurement in the determination of energy output resulting from the phase angle error of the P139
Cancelling a device
function
The following conditions must be met before a device function can be cancelled or
removed:
! No functions of the device function being cancelled can be selected in a list setting.
If the above conditions are met, proceed through the 'Configuration' branch of the menu
tree to access the setting relevant for the device function to be cancelled. If, for
example, the "LIMIT" function group is to be cancelled, the setting L I M I T : F u n c t i o n
g r o u p L I M I T is accessed and its value is set to "Without". To re-include the "LIMIT"
function in the device configuration, the same setting is accessed and its value is
changed to "With".
The device function to which a setting, a signal, or a measured value belongs is defined
by the function group designation (example: "LIMIT"). In the following description of the
device functions, it is presumed that the corresponding device function is included in the
configuration.
Enabling or disabling a
device function
Besides cancelling device functions from the configuration, it is also possible to disable
protection via a function parameter or binary signal inputs. Protection can only be
disabled or enabled through binary signal inputs if the M A I N : D i s a b l e P r o t e c t .
E X T and M A I N : E n a b l e p r o t e c t . E X T functions are both configured. When
neither or only one of the two functions is configured, the condition is interpreted as
"Protection externally enabled". If the triggering signals of the binary signal inputs are
implausible i.e. both are at logic level = "1" then the last plausible state remains
stored in memory.
Note: If the protection is disabled via a binary signal input that is configured for
M A I N : D i s a b l e P r o t e c t . E X T , the signal
M A I N : B l o c k e d / F a u l t y is not issued.
Enabling of the residual current systems of the DTOC/IDMT protection depends on the
setting at M A I N : S y s t . I N e n a b l e d U S E R . If this enabling function has been
activated, it can be disabled or enabled from the local control panel or through
appropriately configured binary signal inputs. The local control panel and the binary
signal inputs have equal status in this regard. If only the M AIN : System IN en a b l e
E X T function is assigned to a binary signal input, then the residual current systems of
the DTOC/IDMT protection will be enabled by a positive edge of the input signal and
disabled by a negative edge. If only the M AIN : Sys te m IN d i s a b l e E X T function
has been assigned to a binary signal input, then a signal at this input will have no effect.
3-60 Enabling or disabling the residual current systems of the DTOC/IDMT protection
For several of the protection functions, it is possible for the duration of the set hold time
to switch over to other settings - the "dynamic parameters" via an appropriately
configured binary signal input. If the hold time is set to 0 s, switching is effective as long
as the binary signal input is being triggered.
The inrush stabilization function detects high inrush current flows that occur when
transformers or machines are switched on, and, if detected, it will then block the
following functions:
The inrush stabilization function identifies an inrush current by evaluating the ratio of the
second harmonic current components to the fundamental. If this ratio exceeds the set
threshold, then the inrush stabilization function operates. Another settable current
trigger blocks inrush stabilization if the current exceeds this trigger. The setting of the
operating mode determines whether inrush stabilization will operate phase-selectively or
across all phases.
By including function blocks in the bay interlock conditions, switching operations can be
prevented independent of the switching status at the time, for example, by an external
signal "CB drive not ready" or by the trip command from an external protection device.
Two multiple blocking conditions can be defined via 'm out of n' parameters. The items
available for selection are found in the Address List. The functions defined by selection
may be blocked via an appropriately configured binary signal input.
3.11.10 Blocked/Faulty
3.11.11 Coupling between Control and Protection for the CB Closed Signal
Bay type selection defines the external device (DEV01 or DEV02 or ...) that represents
the circuit breaker. Coupling between control and protection for the Closed position
signal is made by the setting M AIN : Si g . a s g . C B c l o s e d . As a result, the CB
status signal needs to be assigned to one binary signal input only if this coupling is
implemented.
3-66 Coupling between control and protection for the CB closed signal
The circuit breaker can be closed by the auto-reclosing control function (ARC), by the
automatic synchronism check function (ASC), from the integrated local control panel, or
via an appropriately configured binary signal input on the P139. The close command
from the local control panel or binary signal input is only executed if there is no trip
command present and no trip has been issued by a protection device operating in
parallel. Moreover, the close command is not executed if there is a CB closed position
signal. The duration of the close command can be set.
If the ARC function issues a close request while the ASC function is enabled, then the
close command requires a close enable by the ASC function.
The multiple signals 1 and 2 are formed by the programmable logic function using OR
operators. The programmable logic output to be interpreted as multiple signaling is
defined by the configuration of the binary signal input assignment with the corresponding
multiple signaling. Both an updated and a stored signal are generated. The stored
signal is reset by the following actions:
! General reset
! Latching reset
! LED indicators reset
! A command received through the communication interface.
If the multiple signaling is still present at the time of a reset, the stored signal will follow
the updated signal.
If a ground fault has been detected by either the GFDSS function (ground fault direction
determination by steady-state values) or the TGFD function (transient ground fault
direction determination), the P139 analyzes the phase-to-ground voltages and identifies
the phase on which the ground fault has occurred.
During a ground fault, the P139 determines the lowest phase-to-ground voltage and
checks if the two other phase-to-ground voltages exceed the threshold of 0.2 Vnom. In
addition, the two higher phase-to-ground voltages must exceed the lowest phase-to-
ground voltage by a factor of 1.5. If these conditions are met, a ground fault signal is
issued for the phase with the lowest phase-to-ground voltage.
Ground fault signals generated either by ground fault direction determination using
steady-state values (GFDSS) or transient ground fault direction determination (TGFD)
are grouped together to form multiple signaling.
Phase-selective starting
signals
Common phase-selective starting signals are formed from the internal phase-selective
starting signals of definite-time overcurrent protection and of inverse-time overcurrent
protection.
An adjustable timer stage is started by the phase-selective starting signals, the residual
current starting signal and the negative-sequence starting signal. While this timer stage
is running, the starting signals are blocked. The starting signals are also blocked directly
by the motor protection if the startup of a motor has been detected. Blocking is
suspended if a trip signal is present.
The operate delays for the residual current and negative-sequence current stages of the
DTOC and IDMT protection functions can be blocked for a single-pole or multi-pole
starting (depending on the setting).
General starting
The general starting signal is formed from the starting signals of the DTOC and IDMT
protection functions. A setting governs whether the residual current stages and the
negative-sequence current stage will be involved in forming the general starting signal.
If the operate signal from one of the residual current stages and the negative-sequence
current stage does not cause a general starting (due to the setting) then the associated
operate delays will be blocked. As a result, a trip command cannot be issued by residual
current and negative-sequence current stages.
Trip command
The P139 provides two trip commands. The functions required to issue a trip can be
selected by setting a 'm out of n' parameter independently for each of the two trip
commands. The minimum trip command closure time may be set. The trip signals are
present only as long as the conditions for the signal are met.
! The binary signal input configured for tripping is set to a logic value of '1' or the
selected trip command from the P139 is present.
! At the binary signal input configured as CB trip a logic value of '1' is present.
The CB trip signal from an external device can also be signaled. For this task, two
binary signal inputs need to be configured as CB trip enable ext. and as CB trip ext..
Before a switching unit within the bay is closed or opened by the control functions of the
P139, the P139 first checks whether the switch command may be executed. A switch
command will be executed if the optional control enable has been issued and the
interlock conditions are met. The interlock conditions are defined in the interlocking logic
for each switching unit within the bay that is subject to control actions and for each
control direction (Open/Close). Different conditions are defined for the bay interlock
equations to operate with or without station interlock. The check of bay or station
interlock equations can be cancelled for all electrically controllable switchgear units
within a bay. If the station interlock is active, it may be cancelled selectively for each
switching unit and each control direction (see Control and Monitoring of Switchgear
Units).
If Local has been selected as the control point, the bay and station interlocks may be
cancelled through an appropriately configured binary signal input.
3-78 General enable for switch commands issued by the control functions; activating or cancelling the interlocks
For bays with direct motor drive control of load disconnecting switches, isolating links or
grounding switches, a monitoring function is provided to protect motors from
overheating.
The number of switching operations within a set monitoring period is counted. If the
number of switching operations within the monitoring period exceeds the set limit, the
signal M AIN : M o n . m o t. d r i ve s tr . is issued. For the duration of the set cooling
time, no control commands to motor-driven switchgear units will be executed. Once the
set cooling time has elapsed, the control commands are enabled again.
If a link to the control station cannot be established or if the link is interrupted, the signal
"Communication error" will be issued. This signal will also be issued if communication
module A is not fitted.
The data stored in the operating data memory, the monitoring signal memory and the
event memories are date- and time-tagged. For correct tagging, the date and time need
to be set in the P139.
Stored data such as event logs, measured fault data etc, can be cleared in several ways.
The following resetting actions are possible:
! Automatic resetting of the event signals provided by LED indicators (given that the
LED operating mode has been set accordingly) and of the display of measured event
data on the local control panel LCD whenever a new event occurs.
! Resetting of LED indicators and measured event data displayed on the local control
panel LCD by pressing the "Clear" key ! located on the local control panel.
! Selective resetting of a particular memory type (e.g. only the fault memory) from the
local control panel or through appropriately configured binary signal inputs
! General reset
In the first two cases listed above only the displays on the local control panel LCD are
cleared but not the internal memories such as the fault memory.
In the event of a cold restart, namely simultaneous failure of both internal battery and
substation auxiliary supply, all stored signals and values will be lost.
3-83 General reset, LED reset and measured event data reset from the local control panel
Depending on the design version of the communications module A there are up to two
communications channels available (see "Technical Data"). These physical
communications channels may be assigned to communications interfaces COMM1 and
COMM2.
If tests are run on the P139, the user is advised to activate the test mode so that all
incoming signals via the serial interfaces will be identified accordingly.
The P139 allows the user to pre-set four independent parameter subsets. The user can
switch between parameter subsets during operation without interrupting the protection
function.
If, after the supply voltage is turned on, no logic value of 1 is present at any of the
binary signal inputs selected for the parameter subset selection, then the parameter
subset selected via a function parameter will become active once the stored energy time
has elapsed. The previous parameter subset remains active while the stored energy
timer stage is running.
Parameter subset selection may also occur during a starting condition. When subset
selection is handled via binary signal inputs, a maximum inherent delay of approximately
100 ms must be taken into account.
Settings for which only one address is given in the following sections are equally
effective for all four parameter subsets.
Comprehensive monitoring routines in the P139 ensure that internal faults are detected
and do not lead to malfunctions.
The selection of the warning function assignment includes self-monitoring signals from
communications monitoring, measuring circuit monitoring (V, Vref, I), open circuit
monitoring (20mA input, temperature sensors) as well as logic outputs 30 to 32 and 30(t)
to 32(t).
Cyclic tests
After startup has been successfully completed, cyclic self-monitoring tests will be run
during operation. In the event of a positive test result, a specified monitoring signal will
be issued and stored in a non-volatile memory the monitoring signal memory along
with the assigned date and time (see also Monitoring Signal Recording).
The self-monitoring function monitors the built-in battery for any drop below the minimum
acceptable voltage level. If the associated monitoring signal is displayed, then the
battery should be replaced within a month, since otherwise there is the danger of data
loss if the supply voltage should fail. Chapter 11 gives further instructions on battery
replacement.
Signaling
The monitoring signals are also signaled via the output relay that is configured for
SF MON : Wa rn ing . The output relay operates as long as an internal fault is detected.
Device response
The response of the P139 is a function of the type of monitoring signal. The following
responses are possible:
! Signaling Only
If there is no malfunction associated with the monitoring signal, then only a signal is
issued, and there are no further consequences. This situation exists, for example,
when internal data acquisition memories overflow.
! Selective Blocking
If a fault is diagnosed solely in an area that does not affect the protective functions,
then only the affected area is blocked. This would apply, for example, to the
detection of a fault on the communication module or in the area of the PC interface.
! Warm Restart
If the self-monitoring function detects a fault that might be eliminated by a system
restart such as a fault in the hardware , then a procedure called a warm restart is
automatically initiated. During this procedure, as with any startup, the computer
system is reset to a defined state. A warm restart is characterized by the fact that no
stored data and, in particular, no setting parameters are affected by the procedure. A
warm restart can also be triggered manually by a control action. During a warm
restart sequence, both the protective functions and communication through serial
interfaces will be blocked. If the same fault is detected after a warm restart has been
triggered by the self-monitoring system, then the protective functions remain blocked,
but communication through the serial interfaces will usually be possible again.
! Cold Restart
If a corrupted parameter subset is diagnosed during the checksum test, which is part
of the self-monitoring procedure, then a cold restart is carried out. This is necessary
because the unit cannot identify which parameter in the subset is corrupt. A cold
restart causes all internal memories to be reset to a defined state. This means that all
device settings are also erased after a cold restart. The settings that then apply are
the underlined values given in the column headed Range of Values in the Address
List (see Appendix). In order for a safe initial state to be established, the default
values have been selected so that the protective functions are blocked. Both the
monitoring signal that triggered the cold restart and the signal indicating parameter
loss are entered in the monitoring signal memory.
3-88 Operating data recording and counter for signals relevant to system operation
The monitoring signals generated by the self-monitoring function are recorded in the
monitoring signal memory. A listing of all possible entries in this monitoring signal
memory is given in the address list (see Appendix). The memory depth allows for a
maximum of 30 entries. If more than 29 monitoring signals occur without interim memory
clearance, the SFMON: O v e r f l o w M T _ R C signal is entered as the last entry.
Monitoring signals prompted by a hardware fault in the unit are always entered in the
monitoring signal memory. Monitoring signals prompted by a peripheral fault can be
entered into the monitoring signal memory, if desired. The user can select this option by
setting an 'm out of n' parameter (see Self-Monitoring).
If at least one entry is stored in the monitoring signal memory, this fact is signaled by the
red LED indicator H 3 on the local control panel. Each new entry is indicated by a
flashing light.
The monitoring signal memory can only be cleared manually by a control action. Entries
in the monitoring signal memory are not even cleared automatically if the corresponding
test in a new test cycle has a negative result. The contents of the monitoring signal
memory can be read from the local control panel or through the PC or communication
interface. The time and date information assigned to the individual entries can be read
out through the PC or communication interface or from the local control panel.
Overload duration
In the event of an overload, the P139 determines the overload duration. The overload
duration is defined as the time between the start and end of the OL_RC : R ecor d. i n
p rogr ess signal.
Acquisition of measured
overload data by the motor
protection function
During motor startup, the measured data for the startup time, the maximum startup
current and the startup heating are determined and stored at the end of the startup
process.
OL_DA: Start-up
current
MP IP
r.m.s./Iref
OL_DA: Heat.
dur. start-up
19Z5280A_EN
Acquisition of the
measured overload data of
thermal overload protection
The measured overload data are derived from the measured operating data of the
thermal overload protection function. They are stored at the end of the overload event.
Time tagging
The date that is assigned to each overload event by the internal clock is stored. An
overload events individual start or end signals are likewise time-tagged by the internal
clock. The date and time assigned to an overload event when the event begins can be
read out from the overload memory on the local control panel or through the PC and
communication interfaces. The time information (relative to the onset of the overload)
that is assigned to the signals can be retrieved from the overload memory or through the
PC or one of the communication interfaces.
Overload logging
Protection signals during an overload event are logged in chronological order with
reference to the specific event. A total of eight overload events, each involving a
maximum of 200 start or end signals, can be stored in the non-volatile overload
memories. After eight overload events have been logged, the oldest overload log will be
overwritten, unless memories have been cleared in the interim. If more than 199 start or
end signals have occurred during a single overload event, then OL_RC : O ver l. m em .
o ver flow will be entered as the last signal.
In addition to the signals, the measured overload data are also entered in the overload
memory.
The overload logs can be read from the local control panel or through the PC or
communication interfaces.
In the event of a ground fault, the P139 acquires the following measured ground fault
data:
3-96 Measurement and storage of ground fault duration, steady-state power evaluation
Residual current
The residual current that is present at the time the timer stage GFDSS: tVNG> elapses is
stored in memory. In addition, the active or reactive component of the residual current at
the time of the direction decision output is also stored. All measured data are output as
per-unit quantities referred to the nominal current Inom of the device.
Neutral displacement
voltage
The neutral displacement voltage that is present at the time the timer stage
GFDSS: tVNG> elapses is stored in memory.
3-97 Residual current and neutral-displacement voltage for steady-state power evaluation
MAIN: General
reset
execute
MAIN: Reset LED
19Z5208_EN
3-98 Measurement and storage of ground fault duration, steady-state current evaluation
Residual current
Both the unfiltered and the filtered residual current at the time when the operate delay
G F D SS: O p e r a te d e l a y IN elapses are stored.
3-100 Measurement and storage of ground fault duration, admittance evaluation mode
Acquisition of admittance,
conductance and
susceptance
Conductance and susceptance are stored at the time when the direction decision is
issued. The acquisition of the admittance data value is carried out at the time when
timer stage GFDSS: Operate delay Y(N)> elapses.
Residual current
The residual current that is present at the time the timer stage GFDSS: tVNG> elapses is
stored in memory. The measured data value is output as per-unit quantity referred to the
nominal current Inom of the device.
Neutral displacement
voltage
The neutral displacement voltage that is present at the time the timer stage
GFDSS: tVNG> elapses is stored in memory.
3-101 Measured ground fault data for the admittance evaluation mode
! A ground fault has been detected by the GFDSS function (ground fault direction
determination using steady-state values).
! A ground fault has been detected by transient ground fault direction determination.
Ground fault counting
The ground faults are counted and identified by sequential number.
Time tagging
The date that is assigned to each ground fault by the internal clock is stored. A ground
faults individual start or end signals are likewise time-tagged by the internal clock. The
date and time assigned to a ground fault event when the event begins can be read out
from the ground fault memory on the local control panel or through the PC and
communication interfaces. The time information (relative to the onset of the ground fault
event) that is assigned to the signals can be retrieved from the ground fault memory or
through the PC or communication interfaces.
In addition to the signals, the measured ground fault data are also entered in the ground
fault memory.
The ground fault recordings can be read from the local control panel or through the PC
or communication interfaces.
GF_RC: Record.
in progress
GF_RC: GF memory
Signal overflow
Signal
Signal
Signal
Measured value 1
Measured value 2
Measured value 3
Measured value n
MAIN: Time tag
FT_RC: Record.
in progress
MAIN: General
reset GF_RC: Reset
recording
execute GF_RC: Ground flt.record. n
don't execute
execute
19Z5241A_EN
When there is a fault in the system, the P139 collects the following measured fault data:
! Running time
! Fault duration
! Fault current (short-circuit current)
! Fault voltage (short-circuit voltage)
! Short-Circuit Impedance
! Fault reactance (short-circuit reactance) in percent of line reactance and in
! Fault angle
! Fault distance
! Ground fault current
! Ground fault angle
! Fault location in %
! Fault location in km
! End of fault
Acquisition at the end of the fault.
! Trigg./Trip/GS end
Acquisition at one of the following points:
" Triggering of an appropriately configured binary signal input during a general
starting state
" Issue of a general trip signal
" End of a general starting state
Output of fault location occurs depending on the setting either when there is a
general starting signal or when there is both a general starting signal and a simultaneous
general trip signal.
3-105 Enabling of measured fault data acquisition and fault location output
Acquisition of measured
fault data
The P139 selects a measuring loop based on the phase-selective starting decision. The
short-circuit impedance (fault impedance) and fault direction are determined from this
measuring loops voltage and current. In the case of single-pole starting with ground
fault detection, the currents corrected by the ground factor are selected as measured
variables. In the case of three-phase starting, either grounded or ungrounded, the
minimum voltage of the phase-to-phase voltages and the associated phase-to-phase
current are selected as measured variables.
The fault must last for at least 60 ms so that the fault data can be determined.
The fault data are determined using the measured variables Imeas and Vmeas selected by
measured variable selection, if the fault is detected by fault data acquisition. One phase
current is selected as the fault current in accordance with the measuring loop selected.
In the case of multi-phase starting this is the current of the leading phase in the cycle.
The primary fault reactance is calculated from the per-unit fault reactance using the
nominal data for the set primary current and voltage transformers.
The ground fault data are only determined if a phase-to-ground loop has been selected
for measurement in conjunction with the fault data acquisition function. The vector sum
of the three phase currents is displayed as the ground fault current. The ground fault
angle is the phase displacement between ground fault current and selected measuring
voltage.
If there is an m.c.b. trip signal or the transformer module is not fitted with a voltage
transformer, then only fault current is determined, and the maximum phase current is
displayed.
Fault current and voltage are displayed as per-unit quantities referred to Inom and Vnom.
If the measured or calculated values are outside the acceptable measuring range, the
Overflow indication is displayed.
! Load impedance
! Load angle
! Residual current
The same measuring loop used to determine fault impedance is used to determine load
impedance and load angle. The load current and the voltage must exceed the
thresholds 0.1 Inom and 0.1 Vnom , respectively, in order for the load data to be
determined. If the thresholds are not reached or if the general starting signal does not
last as long as 60 ms, the display Not measured appears.
In addition, the user can set an 'm out of n' parameter in order to configure signals
whose appearance will trigger fault recording.
Fault counting
Faults are counted and identified by sequential number.
Time tagging
The date that is assigned to each fault by the internal clock is stored. A faults individual
start or end signals are likewise time-tagged by the internal clock. The date and time
assigned to a fault when the fault begins can be read out from the fault memory on the
local control panel or through the PC and communication interfaces. The time
information (relative to the onset of the fault) that is assigned to the signals can be
retrieved from the fault memory or through the PC or communication interfaces.
Fault recordings
Protection signals during a fault, including the signals during the settable pre-fault and
post-fault times, are logged in chronological order with reference to the specific fault. A
total of eight faults, each involving a maximum of 200 start or end signals, can be stored
in the non-volatile fault memories. After eight faults have been recorded, the oldest fault
recording will be overwritten, unless memories have been cleared in the interim. If more
than 199 start or end signals have occurred during a single fault, then F T _ R C : F a u l t
m e m . o ve r fl o w will be entered as the last signal. If the time and date are changed
during the pre-fault time, the signal F T _ R C : F a u l ty ti m e ta g is generated.
In addition to the fault signals, the measured fault data are also entered in the fault
memory.
The fault recordings can be read from the local control panel or through the PC or
communication interfaces.
! Phase currents
! Phase-to-ground voltages
! Residual current, measured by the P139 at the T 4 transformer
! Neutral-displacement voltage, measured by the P139 at the T 90 transformer
The signals are recorded before, during and after a fault. The times for recording before
and after the fault can be set. A maximum time period of 16.4 s is available for
recording. This period can be divided among a maximum of eight faults. The maximum
recording time per fault can be set. If a fault, including the set pre-fault and post-fault
times, lasts longer than the set maximum recording time, then recording will terminate
when the set maximum recording time is reached.
The pre-fault time is exactly adhered to if it is shorter than the set maximum recording
time. Otherwise; the pre-fault time is set to the maximum recording time minus a
sampling increment, and the post-fault time is set to zero.
If the maximum recording time of 16.4 s is exceeded, the analog values for the oldest
fault are overwritten, but not the binary values. If more than eight faults have occurred
since the last reset, then all data for the oldest fault are overwritten.
The analog data of the fault record can only be read out through the PC or
communication interfaces.
When the supply voltage is interrupted or after a warm restart, the values of all faults
remain stored.
FT_RC: Record.
in progress
FT_RC: Max.
recording time
FT_RC: Pre-fault
time
FT_RC: Post-fault
time
A Analog channel 1
B Analog channel 2
C Analog channel 3
G Analog channel 7
V -G Analog channel 8
V Analog channel 9
MAIN: General
reset
execute
FT_RC: Reset
recording
execute
19Z5242A_EN
Enabling or disabling
DTOC protection
DTOC protection can be disabled or enabled from the local control panel. Enabling can
be carried out separately for each setting group.
When the inrush stabilization function (see: Main Functions of the P139) is triggered,
the 1st stage of the DTOC function is blocked.
The trip signals from all phase current stages are blocked by the auto-reclosing control
function (ARC) when this function is able to issue a trip command.
The trip signals from the DTOC function (stages I> and I>> only) can be blocked by the
short-circuit direction determination function. Depending on the setting of the short-
circuit direction determination function, the trip signal of stages I> or I>> will be enabled.
Negative-sequence
current stages
The P139 calculates the negative-sequence current from the three phase current values
according to this formula. The result depends on the rotary field direction setting for
phase rotation.
The timer stages can be blocked by appropriately configured binary signal inputs. In
addition these timer stages can also be automatically blocked by single-pole or multi-
pole starting (depending on the setting).
The trip signals from the negative-sequence current stages are only enabled if the
operating mode for the general starting has been set to "With starting IN, Ineg.
When the inrush stabilization function (see: Main Functions of the P139) is triggered,
the 1st stage of the negative-sequence current function is blocked.
When the short-circuit direction determination function (SCDD) is active, trip signals from
the DTOC negative-sequence current stages have no directional dependence.
The trip signals from all negative-sequence current stages are blocked by the auto-
reclosing control function (ARC) when this function is able to issue a trip command.
DTOC: Enabled
MAIN: Enable
protect.
MAIN: Rush restr.
trig.
MAIN: Rush restr.
selec. fct.
DTOC: tIneg>
DTOC: Block.
tIneg> EXT
MAIN: Block tim. DTOC: Ineg>
st. IN,neg
MAIN: Dynam. DTOC: tIneg>
param. active elapsed
DTOC: Ineg>
MAIN: Rotary
field
DTOC: Starting
A Ineg>
B neg DTOC: Trip signal
C tIneg>
ARC: Blocking
trip
DTOC: tIneg>>
DTOC: Block.
tIneg>> EXT DTOC: Ineg>>
DTOC: Starting
Ineg>>
DTOC: tIneg>>>
DTOC: Block.
tIneg>>> EXT DTOC: Ineg>>>
DTOC: Starting
Ineg>>>
MAIN: Gen.
starting mode DTOC: Trip signal
tIneg>>>
with starting
IN,Ineg
DTOC: Ineg> DTOC: Ineg> DTOC: Ineg>> DTOC: Ineg>>
set
set
set
set
DTOC: Ineg>>> DTOC: Ineg>>> DTOC: tIneg> DTOC: tIneg>> DTOC: tIneg>>>
set
set
set
set
19Z5281A_EN
MAIN: Gen.
starting mode
with Starting
IN,Ineg
19Z5282A_EN
Enabling or disabling
DTOC residual current
stages
DTOC residual current stages can be disabled or enabled from the local control panel.
The timer stages can be blocked by appropriately configured binary signal inputs. In
addition these timer stages can also be automatically blocked by single-pole or multi-
pole starting (depending on the setting).
The trip signals from the residual current stages are only enabled if the operating mode
for the general starting has been set to "With starting IN, Ineg.
The trip signals from all residual current stages are blocked by the auto-reclosing control
function (ARC) when this function is able to issue a trip command.
The trip signals from the DTOC function (stages IN> and IN>> only) can be blocked by
the short-circuit direction determination function (SCDD). Depending on the setting of
the short-circuit direction determination function, the trip signal of stages IN> or IN>> will
be enabled.
! As the IN> starting in the residual current stage commences, the hold time is reset.
At the same time, the starting time is accumulated when IN> starting commences.
! As IN> starting ends, the timer stage D T O C : P u l s . p r o l . I N > , i n t P S x is started
and the charging of the accumulation buffer is thereby lengthened by the set value of
the timer stage.
! The accumulation result is compared with the settable limit value
DTOC: tIN>, interm. PSx.
! If the limit value is reached and a general starting is present, then a trip results,
provided that it is permitted by the relevant MAIN settings:
" MAIN: Block tim.st. IN,neg
(Address 017 015)
" MAIN: Gen. starting mode
(Address 017 027)
" MAIN: Fct.assig.trip cmd.1
(Address 021 001)
" MAIN: Fct.assig.trip cmd.2
(Address 021 002)
! If the limit value is reached while the timer stage
D T O C : P u l s . p r o l . I N > , i n t P S x is running, then a trip will occur when the next
general starting phase commences.
! With each release of the trigger stage IN>, the set hold-time
D T O C : H o l d - t. tIN > ,i n tm PSx is restarted. When the hold time has elapsed or
after the hold-time logic has issued a trip
(D T O C : T r i p s i g . t I N > , i n t m .), accumulation is stopped and the accumulation
buffer is cleared.
3-122 Signal flow for values below the accumulation limit value
DTOC: Pulse
prolong. runn.
DTOC: t2 N
Startings not
illustrated
have occured
here.
Settings
DTOC: Puls.prol. DTOC: tIN,interm. DTOC: Hold-t.
IN>,intPSx PSx tIN>,intmPSx
Setting Setting Setting
19Z5243A_EN
The inverse-time overcurrent protection (IDMT) function operates with three separate
measuring systems:
! Phase currents
! Negative-sequence current
! Residual current
Either the short-circuit direction determination function or the auto-reclosing control may
intervene in the functional sequence of the IDMT function.
Disabling or enabling
IDMT protection
IDMT protection can be disabled or enabled from the integrated local control panel.
Moreover, enabling can be carried out separately for each parameter set.
Time-dependent
characteristics
The measuring systems for the evaluation of the three phase currents, the negative-
sequence current system and the residual current operate independently and can be set
separately. The user can select from a large number of characteristics (see table
below). The measured variable is the maximum phase current, the negative-sequence
current, or the residual current, depending on the measuring system. The tripping
characteristics available for selection are shown in Figures 3-125 to 3-128.
1000 1000
100 100
k=10
10 10 k=10
t/s k=1
t/s
1 1 k=1
k=0.1
0.1 k=0.05 0.1
k=0.1
k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K1A S8Z50K2A
1000 1000
100 100
k=10
10 10
k=1
t/s t/s
k=10
1 1
k=0.1
k=1 k=0.05
0.1 0.1
k=0.1
0.01 k=0.05 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K3A S8Z50K4A
1000 1000
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/Iref I/Iref
S8Z50K5C S8Z50K6C
1000
100
10
t/s
k=10
1
k=1
0.1
k=0.1
0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50K7C
Characteristic No. 7
1000 1000
100 100
10 10
t/s t/s
k=10
1 1
k=10
k=1
0.1 0.1
k=1
k=0.1 k=0.1
0.01 k=0.05 0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K8C S8Z50K9C
1000
100
k=10
10
t/s k=1
1
k=0.1
0.1 k=0.05
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50KAC
Characteristic No. 10
1000 1000
100 100
k=10
k=10
10 10
t/s k=1 t/s
k=1
1 1
k=0.1
k=0.1
k=0.05
0.1 0.1 k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50KBA S8Z50KCA
When the inrush stabilization function (see: Main Functions of the P139) is triggered,
the phase current stage is blocked.
The trip signals of the IDMT function can be blocked by the short-circuit direction
determination function or by the auto-reclosing control function. Depending on the
settings for the short-circuit direction determination function, the trip signal may be
enabled. The trip signals of the phase current stage are blocked by the auto-reclosing
control function (ARC) if the ARC is able to form a trip command.
Negative-sequence current
stage
The P139 determines the negative-sequence current based on the set rotary field
according to the following formulas:
a = e j120
a 2 = e j240
The negative-sequence current is monitored by the P139 to detect when it exceeds the
set thresholds. Alternatively, two different threshold types can be active. The dynamic
threshold is active for the set hold time of the dynamic parameters (see Activation of
Dynamic Parameters); the normal threshold is active when no hold time is running.
The IDMT protection function issues a starting signal if the negative-sequence current
exceeds a value of 1.05 times the set reference current. As a function of the set
characteristic and of the residual current, the P139 will determine the tripping time.
Furthermore, a minimum trip time can be set; the trip time will not fall below this
minimum independent of the magnitude of the negative-sequence current.
When the inrush stabilization function (see: Main Functions of the P139) is triggered,
the negative-sequence current stage is blocked.
If short-circuit direction determination is enabled, then the trip signal issued by the IDMT
negative-sequence current stage is always non-directional.
The trip signals of the negative-sequence current stage are blocked by the auto-
reclosing control function (ARC) if the ARC is able to form a trip command.
Selection of measured
variables for the residual
current stage
A setting specifies which current will be used by the P139 as the residual current: either
the residual current calculated from the three phase currents or the residual current
measured at the fourth transformer.
The trip signals of the IDMT function can be blocked by the short-circuit direction
determination function or by the auto-reclosing control function. Depending on the
settings for the short-circuit direction determination function, the trip signal may be
enabled. The trip signals of the residual current stage are blocked by the auto-reclosing
control function (ARC) if the ARC is able to form a trip command.
Holding time
As a function of the current, the P139 will determine the tripping time and start a timer
stage. The setting for the holding time defines the period for the elapsed IDMT starting
time to be stored after the starting has dropped out. If the starting time returns while the
hold time elapses, the new starting time is added to the stored time. If the sum of the
starting times reaches the tripping time determined by the P139 then the appropriate
message is issued. If the starting time does not return while the hold time elapses then
the memory storing the sum of the starting times will in accordance with the setting -
be cleared either without delay or according to the set characteristic. The phase current
stage serves as an example to illustrate the effect of the holding time in Figure 3-135.
3-135 The effect of the holding time illustrated for the phase current stage as an example
Case A: The determined tripping time is not reached.
Case B: The determined tripping time is reached
For a single-pole fault in A-G, for example, the current A and the voltage VB-C are
selected as measured variables, and a characteristic angle P of +45 is used (see
Figure 3-137).
The reference quantity is the vector of the selected phase-to-phase voltage. The
characteristic angle P specifies the measurement relation to the reference quantity.
Different characteristic angles corresponding to fault type are specified by the P139.
The measuring position is defined as the bisector of the forward direction zone. The
forward direction applies if the vector of the selected phase current is in the range
90 of the measurement relation.
The backward direction applies if the vector of the selected phase current is in the range
> 90 of the measurement relation.
3-137 Example of formation of phase current stage direction decision with a single-pole fault in A-G, an inductive system, and a clockwise rotary
field
3-138 Enable for the direction determination function of the phase current stages
After direction determination is enabled, one of the following two signals is generated,
depending on the measurement decision:
A blocking signal for the first DTOC phase current stage is formed if one of the following
conditions is met:
" The direction for tI> is set on forward, and the short-circuit direction determination
function identifies a fault in the backward direction.
" The direction for tI> is set on backward, and the short-circuit direction determination
function identifies a fault in the forward direction.
A blocking signal for the second DTOC phase current stage is formed if one of the
following conditions is met:
" The direction for tI> is set on forward, and the short-circuit direction determination
function identifies a fault in the backward direction.
" The direction for tI> is set on backward, and the short-circuit direction determination
function identifies a fault in the forward direction.
A blocking signal for the IDMT phase current stage is formed if one of the following
conditions is met:
" The direction for tIref,P> is set on forward, and the short-circuit direction determination
function identifies a fault in the backward direction.
" The direction for tIref,P> is set on backward, and the short-circuit direction
determination function identifies a fault in the forward direction.
If there is no enable for direction determination (in the case of m.c.b. trip, for example),
the user may specify at S C D D : T r i p b i a s P S x whether stages set to forward shall
be operated with trip bias.
3-140 Formation of the blocking signals for the phase current stage
The reference quantity is the vector of the neutral displacement voltage. The
characteristic angle specifies the measuring position relative to the reference quantity.
The measuring position is defined as the bisector of the forward direction zone. The
forward direction applies if the vector of the residual current is in the range of 90 of
the measuring position.
The backward direction applies if the vector of the residual current is in the range > 90
of the measuring position.
In the following example the system neutral has been grounded with a relatively low
resistance. When there is a single-pole fault in A-G and a fault in the forward direction,
the residual current will then assume a position approximately like the one shown in
Figure 3-141. With a set characteristic angle of N = - 45, a direction decision in the
forward direction is issued.
3-142 Enable for the direction determination function of the residual current stages
After direction determination is enabled, one of the following two signals is generated,
depending on the measurement decision:
A blocking signal for the first DTOC residual current stage is formed if one of the
following conditions is met:
" The direction for tIN> is set on forward, and the short-circuit direction determination
function identifies a fault in the backward direction.
" The direction for tIN> is set on backward, and the short-circuit direction determination
function identifies a fault in the forward direction.
A blocking signal for the IDMT residual current stage is formed if one of the following
conditions is met:
" The direction for tIN>> is set on forward, and the short-circuit direction determination
function identifies a fault in the backward direction.
" The direction for tIN>> is set on backward, and the short-circuit direction determination
function identifies a fault in the forward direction.
A blocking signal for the IDMT residual current stage is formed if one of the following
conditions is met:
" The direction for tIref,P> is set on forward, and the short-circuit direction determination
function detects a fault in the backward direction.
" The direction for tIref,N> is set on backward, and the short-circuit direction
determination function identifies a fault in the forward direction.
If there is no enable for direction determination (in the case of m.c.b. trip, for example),
the user may specify at S C D D : T r i p b i a s P S x ) whether stages set to forward
shall be operated with trip bias. In the event of phase current starting, the trip bias can
be suppressed in the residual current stage by making the appropriate setting at
S C D D : B l o c k . b i a s G P S x.
3-144 Formation of the blocking signals for the residual current stage
Signaling logic
The signals for fault direction that are generated by the direction determination functions
of the phase current and residual current stages are combined into one common
function.
3-145 Fault signals of phase current stage or residual current stages, forward or backward
To ensure rapid clearing with manual closing, the manual close signal must be issued
not only to the circuit breaker but also to the P139 at the same time. If there is no close
request from the ARC and if no HSR cycle of an external auto-reclosure control is
running, an adjustable timer stage is started with the manual close command. By setting
a parameter, the user can choose which of the time-overcurrent protection starting
decisions will generate a trip signal while the timer stage is elapsing:
An internal blocking signal is generated with the starting signal for the timer stage. This
signal prevents the ARC from being activated when a manual close causes switching on
to a fault.
Protective signaling
Protective signaling is used together with short-circuit direction determination in power
systems with single-side infeed and a subsequent parallel line configuration (line
section). Selective instantaneous clearing of the line section affected by the fault is
initiated by this function, while the IDMT or DTOC tripping times are bypassed.
Disabling or enabling
protective signaling
The function can be disabled or enabled from the integrated local control panel or
through binary signal inputs.
! It must be activated.
! There is no external block
! There is no transmission fault.
Forming the
communication link
To form the communication link it is necessary to connect either the break contact or the
make contact of the transmitting relay, depending on the transmitting relay mode
selected (Transm. relay make contact or Transm. relay break contact), to the
P S I G : R e c e i v e E X T input of the remote station by means of pilot wires (see
Installation and Connection and Figure 3-148). With both operating modes, a receive
signal (DC loop closed) is present in both protection devices in the idle state.
3-148 Protective signaling using pilot wires, selected mode of operation: transmission relay break contact
no no no no
no no no yes
no yes no no
no yes no yes
yes no no yes
After the loop has reclosed and provided that both a general starting condition and a
status signal through the P S I G : R e c e i v e E X T input of a closed loop are present,
then the signal P S I G : T r i p b y P S I G is generated without delay. The loop recloses
after dropout of the general starting condition and after a delay equal to the release time
that can be set at P S I G : R e l e a s e t . s e n d . P S x .
If protective signaling is not ready, the DC loop will be open if Transm. relay make
contact has been selected as operating mode for the transmitting relay or closed if
Transm. relay break contact has been selected.
Protective signaling
monitoring and loop check
The pilot wires are monitored for interruptions. If, in fault-free operation (i.e., in the
absence of a general starting condition), no signal is received through the loop for a
period longer than the set release time of the transmitting relay + 600 ms, then the signal
P S I G : T e l e c o m . f a u l t y is issued (see Figure 3-150). A communication
malfunction or failure leads to a protective signaling block.
To check the loop, the communications link can be opened from the local control panel
by using the function P S I G : T e s t t e l e c o m . U S E R .
Under certain conditions the automatic reclosure control function (ARC) will cause a line
section to be cleared and then, when the dead time has elapsed, automatic reclosure of
the line section will occur.
Figure 3-151 shows an example for the usual sequence of a failed high-speed reclosure
followed by a subsequent successful time-delay reclosure.
ARC blocking
Under certain conditions the ARC will be blocked and the signal A R C : B l o c k e d will
be issued, provided that one of the following conditions is met:
When all blocking conditions have been removed, the blocking time is started. When the
blocking time has elapsed, ARC blocking is canceled.
Tripping times
When protection functions operating with auto-reclosure control are started, the tripping
times (HSR or TDR) are started together with the operative time. If the tripping time has
elapsed during an active ARC cycle while the operative time is still running, a trip signal
is issued. The HSR or TDR trip time having caused the trip signal also determines which
dead time (HSR or TDR) is to be triggered. Once the dead time commences, all tripping
times already triggered and the operative time will be terminated.
The beginning of the following starts or input signals trigger the tripping times provided
that the starting conditions are met and the respective tripping times are not "blocked". If
short-circuit direction determination (SCDD) is enabled, then some of the starting signals
are directional:
! General starting
! DTOC starting I> (directional)
! DTOC starting I>> (directional)
! DTOC Starting I>>>
! DTOC starting IN> (directional)
! DTOC starting IN>> (directional)
! DTOC Starting IN>>>
! IDMT starting IkIref,P> (directional)
! IDMT starting IkIref,N> (directional)
! IDMT starting IkIref,neg>
! Start by programmable logic
! Ground fault direction determination by steady-state values (GFDSS) has operated
and detected one of the following faults:
" GFDSS starting fault 'forward/LS'
" GFDSS starting Y(N)>
" GFDSS starting fault 'forward/LS' or GFDSS starting Y(N)>
If - in the operating mode "HSR/TDR permitted" - only one of the starting conditions
listed above applies, then the first trip signal is always generated by the HSR trip time
stage, regardless of the duration of the HSR or TDR tripping time setting. HSR precedes
TDR. If more than one starting is present then the trip signal will be issued after the
HSR tripping time that has elapsed first. As an exception, a TDR will be triggered first
after having elapsed first, if the associated HSR tripping time is set to "Blocked".
If the trip signal has been generated by a TDR tripping time stage, then no HSR will be
initiated within the same ARC cycle.
The ARC trip signal must be included in the m out of n selection of the trip commands.
The TDR tripping time stages are blocked or reset either by the set value "Blocked" or by
one of the following conditions:
ARC cycle
An ARC cycle begins, provided that the starting condition is met, with the presence of a
relevant starting option (DTOC/IDMT starting, starting via programmable logic, GFDSS,
or start of a test HSR), as long as the signal AR C : R e a d y is present at this time. As
the ARC cycle proceeds, the signal AR C : R e a d y is no longer taken into account.
An ARC cycle is running if the ARC is not blocked and one of the following conditions is
met:
Example of programmable
logic in the ARC
This example (see Figure 3-163) illustrates the possible interconnection and the binary
signal output for starting the tripping time stage via a binary signal input.
By using the programmable logic a binary signal input with serial operate delay and an
AND element is implemented. The function AR C : Bl o c k i n g tr i p "NOT" has been
assigned to the second input on this AND element. The output from the AND element
must be included in the configuration of the m out of n selection for the general trip
command. The tripping time can be started by the output signal
ARC: Start by logic.
For this example the following list parameters need to be set from the local control panel
(see the section on Setting a List Parameter in the chapter entitled Local Control).
List Parameter
LOGIC: Fct.assignm. OR e.g. LOGIC: Input 4 EXT
output 1 (address 034 003)
(address 030 000)
LOGIC: Fct.assignm. OR LOGIC: Output 1 (t)
output 2 (address 042 033)
AND NOT ARC: Blocking trip
(address 042 000)
In general, any equation within the programmable logic function can be used to start the
ARC tripping time.
One of the options offered by the programmable logic is the triggering of the ARC by an
external protection device.
While the ASC function is enabled, reclosure requires a close enable by the ASC
function, which implements a check of the synchronism conditions.
If the starting conditions are met then any ARC-relevant protection startings will trigger
an ARC cycle. The starts trigger the associated tripping time stages and the operative
time. If an HSR tripping time is running during the operative time then the signal
A R C : T r i p s i g n a l is issued and this signal can lead to a trip command if the function
assignment for the trip commands is configured appropriately. With the release of the
starting, the operative time is terminated and the HSR dead time begins. If there is no
starting during the dead time, a reclosure command is issued once the dead time has
elapsed. The reclaim time is started simultaneously. If there is no starting during the
reclaim time, the signal ARC: R e c l o s u r e s u c c e s s fu l is issued and the ARC cycle is
terminated once the reclaim time has elapsed.
If the HSR does not succeed and another starting occurs then a TDR is started if at least
one TDR is permitted. If TDR after HSR is not permitted then the current reclaim time
will be the last reclaim time of the ARC cycle. If the last reclaim time has elapsed and
another starting occurs then the tripping time stages are no longer started. Instead the
signal AR C : Bl o c k i n g tr i p is set to a logic value of 0 and a trip by other protection
functions is enabled. If a trip signal occurs during the last reclaim time then it will be
regarded as a final trip. The ARC cycle is completed after the last reclaim time has
elapsed.
If the operative time has elapsed before the starting drops out, the last reclaim time will
be started directly and the blocking of protection trip signals is cancelled.
During the dead time, the P139 keeps checking whether any ARC-relevant startings
occur. If this is the case, the last reclaim time is started and the blocking of protection
trip signals is cancelled.
While the ASC function is enabled, the procedures described in the following section
"Joint Operation of the ARC and ASC Functions" are also applicable.
3-165 HSR signal sequence (example shown is with ASC disabled see also next section "Joint Operation of the ARC and ASC Functions")
Figure 3-166 shows the joint operation of the ARC and ASC functions, illustrated for a
high-speed reclosure (HSR).
If the starting conditions are met then any ARC-relevant protection startings will trigger
an ARC cycle. The startings set off the associated tripping time stages and the
operative time. If a HSR tripping time is running during the operative time then the signal
A R C : T r i p s i g n a l is issued and this signal can lead to a trip command if the function
assignment for the trip commands is configured appropriately. With the release of the
starting, the operative time is terminated and the HSR dead time begins. After the dead
time has elapsed, a close request is sent to the ASC. The ASC checks to determine
whether reclosure is possible. If a positive decision is reached during the ASC operative
time, then there is a close enable, and the close command is issued.
If the ASC is disabled or deactivated, or if its decisions are to be ignored, then a close
command is issued immediately and the reclaim time is started. If there is no starting
during the reclaim time, the signal ARC: R e c l o s u r e s u c c e s s fu l is issued and the
ARC cycle is terminated once the reclaim time has elapsed.
If the ASC function decides against a reclosure then the reclaim time is started and the
ARC cycle is completed after the reclaim time has elapsed.
Test HSR
A test HSR can only be triggered when the ARC is ready to operate and if the operating
mode has been set to "Test HSR only permit.". In this operating mode, the blocking of
the trip signals from the DTOC, IDMT and other protection functions is cancelled so that
any system fault can be properly cleared.
Once a test HSR has been triggered, a trip signal of defined duration is issued. The
subsequent sequence corresponds to a successful HSR (open and reclose command
when the HSR dead time has elapsed). Once the close command pulse time has
elapsed, further triggering during the reclaim time does not result in a further HSR.
A test HSR can be triggered either from the local control panel or via a binary signal
input and adds an increment to the A R C : N u m b e r H S R counter.
Each Test HSR request that does not result in a test HSR generates the signal
ARC: Reject test HSR.
Multiple reclosures using TDRs are possible if the operating mode is set accordingly. A
TDR may occur after a HSR if reclosure has occurred as the result of the HSR or if the
operating mode set for the ARC allows only TDRs. This is only possible if the setting
fo r A R C : N o . o f p e r m i t . T D R P S x (number of permitted TDRs) is not zero.
If the starting conditions are met then any ARC-relevant protection startings will trigger
the associated tripping times. The operative time is started simultaneously. If a TDR
tripping time is running during the operative time then the signal A R C : T r i p s i g n a l
is issued and this signal can lead to a trip command if the function assignment for the trip
commands is configured appropriately. With the release of the starting, the operative
time is terminated and the TDR dead time begins. If there is no starting during the dead
time, a reclosure command is issued once the dead time has elapsed. The reclaim
time is started simultaneously. If no further TDR is permitted during the current ARC
cycle then this will be the last reclaim time. If the last reclaim time has elapsed and
another starting occurs then the tripping time stages are no longer started. Instead the
signal A R C : B l o c k i n g t r i p is set to a logic value of 0 and a final trip by other
protection functions is enabled. If a trip signal occurs during the last reclaim time then it
will be regarded as a final trip. The ARC cycle is completed after the last reclaim time
has elapsed. If there is no starting during the last reclaim time, the signal
A R C : R e c l o s u r e s u c c e s s f u l will be issued.
If there is a new starting during the reclaim time and at least one TDR is still permitted
then the reclaim time is terminated and another trip is issued when the tripping time has
elapsed. Once the dead time has elapsed, a further reclosure command is issued.
If the operative time has elapsed before the starting drops out, the last reclaim time will
be started directly and the blocking of protection trip signals is cancelled.
During the dead time, the P139 keeps checking whether any ARC-relevant startings
occur. If this is the case, the last reclaim time is started and the blocking of protection
trip signals is cancelled.
While the ASC function is enabled, the procedures described in the previous section
"Joint Operation of the ARC and ASC Functions" are also applicable.
3-168 Signal sequence of a failed HSR followed by a failed TDR and then by a final successful TDR (example shown is with ASC disabled)
The automatic synchronism check (ASC) function allows the device to verify that before
a close or reclose command is issued synchronism exists between network sections that
are to be synchronized (paralleled) or whether one of the network sections is de-
energized. In order to check for synchronism, two voltages generally the voltages on
the line and busbar sides are compared for differences in frequency, angle, and
voltage. Connecting the reference voltage transformer will determine which of the
network sections will provide the reference voltage (e.g. the line side or the busbar side).
At the P139 the measurement loop must be set to correspond to the reference voltage
connection (A S C : M e a s u r e m e n t l o o p P S x ) so that the correct measuring
voltage is selected for the comparison. In the connection example shown in the section
entitled 'Conditioning the Measured Variables', the busbar voltage VA-B is the reference
voltage.
No
Yes
ASC: Enable
PSx
ASC: Enabled
No
Yes
Address
Address
ASC: Enabled
don't execute
execute
don't execute
execute
The user can also specify separately for high-speed reclosures (HSR) and time-delay
reclosures (TDR) whether reclosure will be carried out with or without a check.
Close request
The ASC function can be triggered by ARC, from the integrated local control panel, via
an appropriately configured binary signal input (A S C : C l o s e r e q u e s t E X T ), or via
a close request from the control functions. Close requests from the local control panel,
the binary signal input or the control functions are only accepted if no ARC cycle is
running.
The ASC operative time is started with the close request. If the close enable is issued
before the ASC operative time has elapsing, the close command is issued. Otherwise
an A S C : C l o s e r e j e c t i o n signal is generated for 100 ms.
! Voltage-checked
! Synchronism-checked
! Voltage/synchronism-checked
Voltage-checked
The synchronism-checked close enable can be bypassed using the voltage-checked
close enable, without affecting the former. For this purpose the three phase-to-ground
voltages and the reference voltage Vref are monitored to determine whether they exceed
or fall below the set threshold values (A S C : V > v o l t . c h e c k and A S C : V <
v o l t . c h e c k ). Depending on the operating mode selected for the voltage check, all
three phase-to-ground voltages need to exceed or fall below the set value in order to
meet the condition for voltage-checked closing. If the conditions corresponding to the
set operating mode for the voltage-checked synchronism check are met, then the close
enable is issued after the set minimum time has elapsed (A S C : t m i n v o l t . c h e c k ).
The following operating modes for voltage checking can be selected separately for each
parameter subset:
ASC: Enabled
ASC: Active
VA G
VB G
VC G
V V
ASC: Op.mode ASC: V> volt. ASC: V< volt. ASC: tmin volt.
volt.chk.PSx check PSx check PSx check PSX
set
set
set
set
19Z5233A_EN
Synchronism-checked
Before a close enable is issued, the ASC checks the voltages for synchronism.
Synchronism is recognized if the following conditions are met simultaneously:
! The three phase voltage and the reference voltage must exceed the set threshold
value (A S C : V > s y n c . c h e c k . ) . When with a three phase voltage the setting of
M A I N : N e u t r a l - p o i n t t r e a t . is "Low-imped. grounding" both the phase-to-
ground and the phase-to-phase voltages are checked. If the setting is
"Isol./res.w.start.(or w/o st.)PG" only the phase-to-phase voltages are checked.
! The difference in magnitude between measuring voltage and reference voltage must
not exceed the set threshold value (A S C : D e l t a V m a x ).
! The frequency difference between measuring voltage and reference voltage must not
exceed the set threshold value (A S C : D e l t a f m a x ).
! The angle difference between measuring voltage and reference voltage must not
exceed the set threshold value (A S C : D e l t a p h i m a x ). The set offset angle
(A S C : P h i o f f s e t ) is taken into account in these comparisons.
If these conditions are met for at least the set time (A S C : t m i n s y n c . c h e c k ), then
a close enable is issued. The ASC operating time for determination of differences in
voltage, angle, and frequency is approximately 100 ms.
The voltage magnitude difference, angle difference, and frequency difference are stored
as measured synchronism data at the time the close request is issued. In the event of
another close request, they are automatically overwritten by the new data.
Voltage/synchronism-
checked
If this setting has been selected, then the close enable is issued if the conditions for
voltage- or synchronism-checked closing are met.
The ASC cycle and the operating time are started by the test close request. The
network synchronism is checked during the whole operating time and A S C : C l o s e
e n a b l e is set accordingly. If at the end of the operate time no network synchronism is
registered, a 100 ms signal A S C : C l o s e r e j e c t i o n is issued.
2
ASC: >
Operative time PSx
set
set
set
set
19Z5230A_EN
3-179 Integrating the ASC function into the control and monitoring of switchgear units
Outside of the ASC cycle the measured values have the status of "not measured".
ASC: Transm.cycle,
meas.v.
101 212
ASC: Cycle
running
038 019
ASC: Voltage
Vref
004 087
ASC: Angle
difference
004 089
ASC: Frequ.
difference
004 090
19Z5231A_EN
ASC counters
The following ASC signals are counted:
! Number of reclosures after a close request from the integrated local control panel or
through a binary signal input.
! Number of close requests
! Number of close rejections
The counters can be reset individually (at the address at which they are displayed) or as
a group.
Ground fault direction is determined by evaluating the neutral displacement voltage and
the residual current using the steady-state power evaluation method or, alternatively, the
admittance evaluation method. As an alternative, it is also possible to detect ground
faults (without direction determination in this case) using a steady-state evaluation
method based solely on current (steady-state current evaluation). In that case only the
filtered residual current is used as the ground fault criterion.
The functional sequence of ground fault direction determination can be influenced by the
auto-reclosing control function.
3-182 Enabling, disabling and readiness of ground fault direction determination using steady-state values (GFDSS)
In order to detect the ground fault direction, ground fault direction determination by
steady-state power evaluation requires the neutral-point displacement voltage and the
residual current. The frequency given by the setting f/fnom is filtered from these quantities
using Fourier analysis. Three periods are used for analysis if the setting selected for the
timer stage G F D S S : t V N G > is greater than or equal to 60 ms. This means that
typical ripple control frequencies are suppressed in addition to all integer-frequency
harmonics. If the timer stage has been set for values less than 60 ms, only one period is
used for filtering purposes.
Measurement is enabled after timer stage tVNG> has elapsed; this stage is started by
the trigger VNG>. The sign of either active power G F D S S : O p e r . m o d e G F
( p o w . ) cos phi circuit or reactive power G F D S S : O p e r . m o d e G F ( p o w . )
sin phi circuit is used for direction determination, depending on the operating mode
selected cos phi circuit or sin phi circuit. Connection of the measuring circuits is taken
into account by the setting G F D S S : M e a s u r i n g d i r e c t i o n . With the standard
connection, a decision for LS is reached in the case of a ground fault on the line side
and BS in the case of a ground fault on the busbar side.
cos circuit
The direction decision is not enabled until the active component of the residual current
exceeds the set value and the phase displacement between residual current and neutral
displacement current is smaller than the set sector angle. The sector angle makes it
possible to extend the dead zone to take into account the expected phase-angle errors
of the measured variables. These settings make it possible to achieve the characteristic
shown in Figure 3-185.
The trip signal of the GFDSS function for the forward direction is blocked by the auto-
reclosing control function (ARC) if the ARC is able to form a trip command.
3-185 Characteristic of ground fault direction determination by steady-state power evaluation, operating mode cos
sin circuit
The direction decision is enabled if the reactive component of the residual current has
exceeded the set threshold operate value. These settings make it possible to achieve
the characteristic shown in Figure 3-186.
The trip signal of the GFDSS function for the forward direction is blocked by the auto-
reclosing control function (ARC) if the ARC is able to form a trip command.
3-186 Characteristic of ground fault direction determination by steady-state power evaluation, operating mode sin
The frequency given by the setting f/fnom is filtered from the residual current using Fourier
analysis. Three periods are used for steady-state current evaluation. If the current
exceeds the set threshold value, then a ground fault signal is issued after the set operate
delay has elapsed.
In order to detect the ground fault direction, ground fault direction determination in the
admittance evaluation mode requires the neutral-point displacement voltage and the
residual current. The frequency given by the setting f/fnom is filtered from these quantities
using Fourier analysis.
Measurement is enabled after timer stage tVNG> has elapsed; this stage is started by
the trigger VNG>. The sign of either active power G F D S S : O p e r . m o d e G F
( p o w . ) cos phi circuit or reactive power G F D S S : O p e r . m o d e G F ( p o w . )
sin phi circuit is used for direction determination, depending on the operating mode
selected cos phi circuit or sin phi circuit. Connection of the measuring circuits is taken
into account by the setting G F D S S : M e a s u r i n g d i r e c t i o n . With the standard
connection, a decision for LS is reached in the case of a ground fault on the line side
and BS in the case of a ground fault on the busbar side. The setting G F D SS:
C o r r e c t i o n a n g l e is provided to compensate for phase-angle errors of the system
transformers.
cos circuit
The direction decision is enabled if the conductance G(N) in the residual current loop
has exceeded the set threshold operate value. This setting makes it possible to achieve
the characteristic shown in Figure 3-191.
The trip signal of the GFDSS function for the forward direction is blocked by the auto-
reclosing control function (ARC) if the ARC is able to form a trip command.
3-191 Characteristic of ground fault direction determination by steady-state admittance evaluation, operating mode cos
sin circuit
The direction decision is enabled if the susceptance B(N) in the residual current loop has
exceeded the set threshold operate value. This setting makes it possible to achieve the
characteristic shown in Figure 3-192.
The trip signal of the GFDSS function for the forward direction is blocked by the auto-
reclosing control function (ARC) if the ARC is able to form a trip command.
3-192 Characteristic of ground fault direction determination by steady-state admittance evaluation, operating mode sin
Non-directional ground
fault determination
In the admittance evaluation mode, the non-directional ground fault determination
function can serve as backup protection in case, for example, the active component G(E)
is too small for directional determination.
The admittance in the residual current loop is used in the evaluation. If the admittance
exceeds the set threshold value, then a ground fault signal is issued after the set operate
delay has elapsed.
The trip signal of the non-directional ground fault determination is blocked by the auto-
reclosing control function (ARC) if the ARC is able to form a trip command.
The number of ground faults and direction decisions is counted. The counters can be
reset either individually or as a group.
Ground fault direction is determined by evaluating the neutral displacement voltage and
the residual current using the transient ground fault measurement method.
Readiness of transient
ground fault direction
determination
A readiness signal is issued if the following conditions are satisfied:
3-195 Enabling, disabling, and readiness of transient ground fault direction determination
Determination of ground
fault direction
Determination of the ground fault direction can only take place if the TGFD function is
ready.
Higher frequency components are filtered out of the two measured variables residual
current and neutral displacement voltage. The amplitudes of the harmonic components
of residual current and neutral displacement voltage and the fundamental component of
the neutral displacement voltage are monitored by settable triggers. For the
determination of ground fault direction, the P139 separately evaluates the trigger
decisions of harmonic component monitoring for the positive and negative half-cycles.
The respective sign of the harmonic component of the neutral displacement voltage is
determined immediately after the harmonic component of the current has exceeded the
positive or negative operate value. For the directional decision, the trigger decisions of
current and voltage are compared, and the connection of the measuring circuits is the
determining factor for the evaluation. The connection of the measuring circuits is taken
into account by the setting TGFD: M e a s u r e m . d i r e c t i o n . With the standard
connection, a decision for LS is reached in the case of a ground fault on the line side
and BS in the case of a ground fault on the busbar side. The directional decision is
enabled once the set operate delay has elapsed. The set operate delay follows the
harmonic component monitoring stage of the neutral displacement voltage.
Furthermore, a timer stage is started when a current trigger operates. Once this timer
stage has elapsed, transient ground fault direction determination can then detect another
transient ground fault. A new ground fault can be detected after the set operate delay of
+ 40 ms has elapsed.
The direction decisions are output for the duration of the set storage time. If the storage
time is set to 0s, the direction decisions are output until the fundamental component of
the neutral displacement voltage no longer exceeds the set threshold T G F D : VN G > .
A motor protection function is implemented in the P139. This motor protection function is
designed especially for protection of directly switched, high-voltage asynchronous
motors with thermally critical rotors. Optimized protection functions are available for this
application:
The definite-time overcurrent protection stages and the unbalance protection function,
which are necessary for comprehensive motor protection, are described in this chapter in
the sections on DTOC protection and unbalance protection (I2>), respectively.
Starting conditions
The overcurrent stage I kIref,P> serves as the starting stage for the overload protection
function. The maximum value of the three phase currents is evaluated. The reference
quantity for operate value and tripping time is the set reference current Iref,P. The current
stage operates when I kIref,P> is exceeded.
The output signal of the overcurrent stage IkIref,P> is the starting signal.
Recognition of operating
state
In order to control the overload protection function, i.e., for optimized thermal tracking,
the P139 is equipped with an operating state recognition function. The possible
operating states of a directly switched asynchronous motor are detected by way of
different trigger stages, as follows:
" 0 %:
A value of 0 % represents the cold state of the protected object, i.e., after the
protected object has cooled down to ambient temperature.
" 20 %:
A value of 20 % represents the minimum load of the overload memory with the
protected object at operating temperature or after initial startup. A running machine is
always considered as being at operating temperature.
" 40 %:
A value of 40 % temporarily represents the minimum load of the overload memory
after two consecutive startups of the protected object.
" 60 %:
A value of 60 % temporarily represents the minimum load of the overload memory
after three consecutive startups of the protected object.
" 100 %:
As soon as the overload memory reaches a value of 100 % (trip threshold), an
overload protection trip is issued. The hysteresis for a defined release of the trip
signal is 1 %.
The overload memory mapping process that results in a replica of the actual thermal
conditions in the protected object includes the following operations:
m0
# Machine stopped: t = machine.stopped ln
m( t)
Startup frequency
monitoring
A startup counter in count down circuit configuration is included in the P139 for startup
frequency monitoring. Depending on the setting M P: Pe r m . N o . s t.- u p s PSx, the
permissible number of consecutive startups is either three from cold or two from warm
or two from cold or one from warm. The counter reading at any given time indicates the
number of consecutive startups that are still permitted. The startup counter is controlled
as follows (see Figure 3-205):
" The permissible number of consecutive startups is limited to two from cold or one
from warm (MP: Perm. No. st.-ups PSx).
" For the permissible startup time tStUp (M P: St.- u p ti m e tStU p PSx), a higher
value is set than for the maximum permissible blocking time tE from operating
temperature (M P: Bl o c k i n g ti m e tE PSx). These two setting values are only
relevant for this particular application; if both settings are identical, they have no
effect on the protective function and the heavy starting logic is not active.
If this logic function has been activated, then the two timer stages tE and tStUp are started
at the time when the onset of a startup is detected, corrected by the discrimination time
tIStUp>. Once the set time tE has elapsed, the logic function checks to see whether the
machine is actually running. The presence of an external signal from an overspeed
monitor, for example serves as the criterion for a running machine.
If a running machine is detected once the set time tE has elapsed, then the overload
memory charge is automatically frozen and tracking is only restarted after the set startup
time tStUp has elapsed. If a locked rotor state is detected after the set time tE has
elapsed, the overload memory is automatically set to a value of 100 %, which leads to an
immediate trip decision.
Tripping time
characteristics
The P139 user can choose between the following two tripping time characteristics:
36
" Reciprocally squared t = (1 m 0 ) t 6Iref
(I Iref ) 2
(I Iref ) 2
( )
" Logarithmic: t = 1 m 0 t 6Iref 36 ln
(I Iref ) 2 1
where m0 in each case signifies the pre-charging of the overload memory at time t = 0.
With reference to the basic physical model (two-body model), the logarithmic
characteristic in the overload range also takes into account heat transfer to the coolant,
but this heat transfer becomes less significant as the overcurrent increases. At I = 6Iref,
for example, the tripping time increase is only about 1.4 % and is thus below the
specified accuracy of the protection device. In the low overcurrent range, selection of
the logarithmic characteristic guarantees significantly higher tripping times than selection
of the reciprocally squared characteristic (see Figure 3-206) since in the overload range
the reciprocally squared characteristic always disregards heat transfer to the cooling
medium. The possibility of choosing between two different tripping time characteristics
takes into account the fact that the user or the application may require a more restrictive
or less restrictive type of protection. For currents in excess of 10 Iref, the tripping times
are limited in the direction of lower values.
The equation for determining the setting value t6Iref can be derived from the above
equations for tripping time t. For this purpose the startup current Istartup and the
maximum permissible blocking time from cold tblock,cold for the asynchronous motor must
be known. Setting the overload protection function on the basis of the cold tripping time
where m0 = 0 % (cold curve) is permitted since the conditions for a machine at
operating temperature are automatically taken into account. The conditional equations
for the setting value t6Iref are therefore the following:
(Istartup )
2
Iref
" For the reciprocally squared characteristic we set: t 6IB = t block,cold
36
1
" For the logarithmic characteristic we set: t 6IB = t block,cold
(Istartup )
2
Iref
36 ln
(Istartup )
2
Iref 1
10000
A
1000
B
C
100
D
E
t in s 10
F
0,1
1 2 3 4 5 6 7 8 9 10 11
I / Iref
A = logarithmic characteristic D = reciprocally squared
(at t6Iref=100s) characteristic (at t6Iref=10s)
3-207 Tripping characteristic of motor protection (at I/Iref 2.5 we have m=0.2, at I/Iref > 2.5 we have m=0)
Plausibility conditions
A number of plausibility conditions need to be observed in order to ensure that the
protected object is given optimum protection and that unintended tripping is prevented.
" If the permissible number of consecutive startups is set for the sequence 'three from
cold or two from warm' and if this set permissible number of consecutive startups is
also intended to be used up during operation, then the heating during startup in the
overload memory (OL_DA: Heat. dur. start-up) must not exceed 60 %. If the
calculation is based on a constant startup current (O L _ D A : S t a r t - u p c u r r e n t )
over the entire startup period, then we obtain the plausibility condition tstartup
0.6tblock,cold. However, since the startup current decreases during the course of the
startup time (O L _ D A: T i m e ta k e n f. s ta r tu p ), thereby causing rate of memory
charging to decrease as well, one can therefore assume that there is a corresponding
extra margin, for all practical purposes.
" The setting value for the overload protection function is determined on the basis of
the stated maximum permissible blocking time from the cold state tblock,cold.
However, when a machine at operating temperature is connected, a protective trip
during the tE period must be guaranteed. Therefore, it is always necessary to check
the plausibility condition tblock,cold 1.25tE and make sure the condition is met.
Initialization or plausibility
check of the thermal
replica
Under the following conditions, the P139 will not be able to track the thermal replica of
the protected object, and re-initialization of the thermal replica will be triggered :
1000
100
t in s 10
0.1
1 2 3 4 5 6 7 8 9 10
I / Iref
MP protection: set reciprocally squared characteristic, t6Iref = 1 s
THERM protection: set time constant 1 = 300 s, trip limit value = 100 %
S8Z50F3A
3-208 Tripping characteristic of motor protection with operating mode With THERM (cold characteristic)
Startup counter
The motor startups are counted. The counter can be reset either individually or with
others as a group.
The low load protection function makes it possible to monitor the load torque of a motor
drive for a minimum level. If the operating state recognition function detects a running
machine and the maximum r.m.s. phase current falls below the set operate value for a
set time, then an appropriate signal is generated. The signal needs to be configured to a
separate output relay, since it cannot be linked directly to either the general starting
signal or the trip command.
Motors that are operated in areas subject to explosion hazards must not reach a
temperature in the case of overload or blocking that would be critical for the existing air-
gas mixture.
The P139 is suitable for this type of application, which requires increased-safety
protection (Type e), but the device must be installed outside the hazardous area.
Using this function, Thermal Overload Protection can be implemented. The Thermal
Overload Protection function can be operated together with the Motor Protection
function.
Disabling or enabling
Thermal Overload
Protection
The power thermal overload function can be disabled or enabled from the local control
panel. Moreover, enabling can be carried out separately for each parameter set.
Tripping characteristics
The maximum r.m.s. phase current is used to track a first-order thermal replica as
specified in IEC 255-8. The following parameters will govern the tripping parameters:
2
I
P
t = ln Iref
2
I c c,max
trip 1
Iref max c,max
Figure 3-214 shows the tripping characteristics for P = 0 % and with a measured
coolant temperature c identical to the maximum permissible coolant temperature.
The setting for the operating mode selects an absolute or relative replica. If the setting
is for Absolute replica, the P139 will operate with a fixed trip threshold trip of 100 %.
trip / %
10000
200
1000
110
/min
50
100
200
110
10 1000
50
t/min 200
1
110
50 30
0.1
0.01 1
0 1 2 3 4 5 6 7 8 9 10 11
0.00
I/Iref
D5Z50BE
3-214 Tripping characteristic of Thermal Overload Protection (tripping characteristics apply to P = 0 % and with a measured coolant
temperature c identical to the setting for the maximum permissible coolant temperature c,max)
To permit coolant temperature acquisition, one of the analog modules Y must be fitted
either the analog (I/O) module Y with a 20 mA current input and the PT100 input or the
temperature p/c board (the RTD module) with the temperature sensor inputs T1 to T9. If
neither module is available in the P139 then the setting T H E R M : C o o l a n t t e m p .
P S x is used in the calculation of the tripping time. The setting T H E R M : S e l e c t
m e a s . i n p u t P S x will determine which of these 11 inputs ("PT100", 20 mA, T1 to T9)
will influence the thermal replica.
One of the following signals is issued when an open circuit to a sensor has ocurred on
one of these analog inputs (see function description for 'Measured data input'):
The open circuit signal from the function group MEASI is forwarded to the Thermal
Overload Protection function.
Example for a setting without back-up temperature sensor and a configuration without measuring
card for temperature
Select.
meas.inputPSx
with CTA
Without
input
++
CTA error
MEASI Open circ.
SFMON: CTA error
MEASI Overload
input
MEASI Open circ.
inp.
CTA error
EXT
Bl. f. CTA
fault PSx
Block. by
CTA error
No
Yes
19Z5220A_EN
3-215 Monitoring the coolant temperature acquisition with an analog module (I/O) if the
parameter T H E R M : S e l . b a c k u p t h . P S x is set to 'Without'.
If the the temperature p/c board (the RTD module) is installed in addition to the analog
(I/O) module y one of the temperature sensors T1 to T9 may be selected by setting
T H E R M : S e l e c t m e a s . i n p u t P S x . Depending on the setting one of these open
circuit signals will be processed:
If one of the analog inputs (PT100, 20mA, T1 to T9) was selected as a backup by setting
T H E R M : S e l . b a c k u p t h . P S x the coolant temperature acquisition will continue
to operate with the selected backup sensor input when an open circuit to the main
sensor input has occurred. Only after the selected backup sensor has also become
defective the coolant temperature can no longer be measured and the signal T H E R M :
C T A f a u l t is issued.
THERM: Select
meas.inputPSx
*
With CTA
4: T2
MEASI:Open circ.
T2
040 194
THERM:CTA error
EXT
038 062
Bl. f. CTA
fault PSx
Block. by
CTA error
No
Yes
19Z5221A_EN
3-216 Monitoring the coolant temperature acquisition with main and backup sensors
Warning
A warning signal can be set in accordance with the set operate value T H E R M : R e l .
O / T w a r n i n g P S x Additionally, a pre-trip time limit can be set, when the time left
until tripping falls below this pre-trip limit, a warning will be issued.
If the current falls below the default threshold of 0.1 Iref, the buffer is discharged with the
set time constant T H E R M : T i m . c o n s t . 2 , < I b l P S x . The thermal replica may be
reset from an appropriately configured binary signal input. Resetting is possible even
when Thermal Overload Protection is disabled. Thermal Overload Protection can be
blocked via an appropriately configured binary signal input.
Enabling or disabling
unbalance protection
Unbalance protection can be disabled or enabled from the local control panel.
Moreover, enabling can be carried out separately for each parameter set.
Operation
The presence or absence of unbalance is assessed on the basis of the negative-
sequence system current. The negative-sequence current is monitored to determine
whether it exceeds the set thresholds. After the set operate delay periods have elapsed,
a signal is issued. The following stages are available for the negative-sequence current:
The unbalance protection signals can be configured to separate output relays. These
signals cannot be linked to the general starting signal but can be configured to the trip
command.
The time-voltage protection function evaluates the fundamental component of the phase
voltages and of the neutral displacement voltage as well as the positive-sequence
voltage and negative-sequence voltage obtained from the fundamental components of
the three phase-to-ground voltages.
Disabling or enabling
V<> protection
V<> protection can be disabled or enabled from the local control panel. Moreover,
enabling can be carried out separately for each parameter set.
If the decisions of undervoltage monitoring are to be included in the trip commands, then
it is recommended that transient signals be used. Otherwise the trip command would
always be present when the system voltage was disconnected, and thus it would not be
possible to reclose the circuit breaker.
If the decisions of undervoltage monitoring are to be included in the trip commands, then
it is recommended that transient signals be used. Otherwise the trip command would
always be present when the system voltage was disconnected, and thus it would not be
possible to reclose the circuit breaker.
The P139 monitors the selected voltage to determine whether it exceeds or falls below
set frequencies. The frequency is determined from the difference in time between the
zero crossings of the voltage (voltage zeroes). The over-/underfrequency protection
function has four stages. The operation of over-/underfrequency protection will be
explained below using the first stage as an example.
Disabling or enabling
over-/underfrequency
protection
Over-/underfrequency protection can be disabled or enabled from the local control panel.
Moreover, enabling can be done separately for each parameter subset.
! Frequency monitoring
! Frequency monitoring combined with differential frequency gradient monitoring (df/dt)
! Frequency monitoring combined with mean frequency gradient monitoring (f/t)
Frequency monitoring
Depending on the setting, the P139 monitors the frequency to determine whether it
exceeds or falls below set thresholds. If an operate threshold in excess of the set
nominal frequency is set, the P139 checks to determine whether the frequency exceeds
the operate threshold. If an operate threshold below the set nominal frequency is set,
the P139 checks to determine whether the frequency falls below the operate threshold.
If it exceeds or falls below the set threshold, a set timer stage is started. The timer stage
can be blocked by way of an appropriately configured binary signal input.
Frequency monitoring
combined with differential
frequency gradient
monitoring (df/dt)
In this operating mode of the over-/ underfrequency protection function, the frequency is
also checked to determine whether the set frequency gradient is reached (in addition to
being monitored for exceeding or falling below the set threshold). Monitoring for
overfrequency is combined with monitoring for a frequency increase; monitoring for
underfrequency is combined with monitoring for a frequency decrease. If both operate
conditions are satisfied, a set timer stage is started. The timer stage can be blocked by
way of an appropriately configured binary signal input.
Frequency monitoring
combined with mean
frequency gradient
monitoring (f/t)
The frequency gradient can differ for system disturbances in individual substations and
may vary over time due to power swings. Therefore it makes sense to take the mean
value of the frequency gradient into account for load-shedding systems.
Monitoring the mean value of the frequency gradient is started with the starting of
frequency monitoring. If the frequency decreases by the set value f within the set
time t, then the t/f monitoring function operates instantaneously and generates a trip
signal. If a frequency change does not lead to an operate decision of the monitoring
function, then the t/f monitoring function will be blocked until the underfrequency
monitoring function drops out. The trip signal can be blocked by way of an appropriately
configured binary signal input.
The power directional protection function determines the active and reactive power from
the fundamental currents and voltages. The sign of the active or the reactive power,
respectively, is evaluated for direction determination
Disabling or enabling
P<> protection
The power directional protection function can be disabled or enabled from the local
control panel. Moreover, enabling can be carried out separately for each parameter set.
Power determination
The P139 determines the active and reactive power from the three phase and the phase-
to-ground voltages. If the measuring-circuit monitoring function detects malfunctioning in
the voltage measuring circuit, power determination will be blocked.
Power monitoring
The P139 checks the determined power values to detect whether they exceed or fall
below set thresholds. The triggers are followed by timer stages that can be blocked via
appropriately configured binary signal inputs.
If the decisions of power monitoring are to be included in the trip commands when
values have fallen below set thresholds, then it is recommended that transient signals be
used. Otherwise, the trip command would always be present when the system voltage
was disconnected, and thus it would not be possible to close the circuit breaker again.
When the active power exceeds the set thresholds, a starting results. The starting signal
is followed by the set operate and resetting delays.
P<>: Operate
delay P> PSx
P<>: Release
P<>: Blocking delay P> PSx
tP> EXT
035 082
P<>: Diseng.
ratio P> PSx
P<>: Starting
P>
035 086
P<>: Operate
delay P>>PSx
P<>: Release
delay P>>PSx
P<>: Blocking
tP>> EXT
035 083
P<>: Diseng.
ratio P>>PSx
P<>: Starting
P>>
035 089
19Z5271A_EN
3-238 The direction-dependent trip signal of the active power protection function when set thresholds are exceeded
When the reactive power exceeds the set thresholds, a starting results. The starting
signal is followed by the set operate and resetting delays.
P<>: Operate
delay Q> PSx
P<>: Release
P<>: Blocking delay Q> PSx
tQ> EXT
035 084
P<>: Diseng.
ratio Q> PSx
P<>: Starting
Q>
035 092
P<>: Operate
delay Q>>PSx
P<>: Release
delay Q>>PSx
P<>: Blocking
tQ>> EXT
035 085
P<>: Diseng.
ratio Q>>PSx
P<>: Starting
Q>>
035 095
3-240 The direction-dependent trip signal of the reactive power protection function when set thresholds are exceeded
When the active power falls below the set thresholds, a starting results. The starting
signal is followed by the set operate and resetting delays.
P<>: Blocking
tP< EXT
035 050
P<>: P<
PSx P<>: Operate
delay P< PSx
Setting blocked
P<>: Starting
P<
035 054
P<>: Fault
P<>: Blocking P<
tP<< EXT 035 057
035 051
Setting blocked
P<>: Starting
P<<
035 060
P<>: Fault
P<<
035 063
P<>: tP<
abgel. Wischer
035 056
P<>: tP<<
elapsed trans.
035 062
P<>: tP</tP<<
elaps.trans
035 178
Parameter P<>: P<< P<>: Diseng. P<>: Operate P<>: Release P<>: tTransient
PSx ratio P<<PSx delay P<<PSx delay P<<PSx pulse PSx
set 1 017 234 017 238 017 242 017 246 018 246
set 2 017 235 017 239 017 243 017 247 018 247
set 3 017 236 017 240 017 244 017 248 018 248
set 4 017 237 017 241 017 245 017 249 018 249
19Z5272A_EN
3-241 Active power monitoring when values fall below set thresholds
P<>: Starting
P<
035 054
Appar. power S
> 0,010 Snom
Direction
forward
backward
&
& >1
& trans.
035 059
&
P<>: Starting
P<<
035 060
Direction
forward
backward
non-directional
P<>: Signal P<<
delayed
035 061
&
P<>: Trip signal
& P<<
& >1 035 064
&
P<>: tP<<
elapsed trans.
&
035 062
P<>: Trip sig.
& >1 & P<< trans.
035 065
P<>: Direction P<>: Direction
Parameter
P< PSx P<< PSx &
set 1 017 230 017 250
set 2 017 231 017 251
set 3 017 232 017 252
set 4 017 233 017 253
19Z5273A_EN
3-242 The direction-dependent trip signal of the active power protection function when values fall below set thresholds
1
P<>: Starting
P<
035 054
P<>: Operate
delay P< PSx
*
P<>: Release
delay P< PSx
* 2
P<>: Signal
P< delayed
035 055
P<>: tP<
elapsed trans.
035 056 3
P<>: Fault
P<
035 057
P<>: Operate
1 delay P< PSx *
P<>: Release
2 delay P< PSx *
P<>: tTransient
3 pulse PSx *
19Z5278A_EN
3-243 Performance of the transient signal and the fault signal issued by the active power monitoring
When the reactive power falls below the set thresholds, a starting results. The starting
signal is followed by the set operate and resetting delays.
P<>: Blocking
tQ< EXT
035 052
P<>: Q<
PSx P<>: Operate
delay Q< PSx
Setting blocked
P<>: Starting
Q<
035 066
P<>: Fault
Q<
P<>: Blocking 035 069
tQ<< EXT
035 053
P<>: Q<<
PSx P<>: Operate
delay Q<<PSx
Setting blocked
P<>: Starting
Q<<
035 010
P<>: Fault
Q<<
035 049
P<>: tQ<
elapsed trans.
035 068
P<>: tQ<<
elapsed trans.
035 016
P<>: tQ</tQ<<
elapsed trans.
035 179
Parameter P<>: Q<< P<>: Diseng. P<>: Operate P<>: Release P<>: tTransient
PSx ratio Q<<PSx delay Q<<PSx delay Q<<PSx pulse PSx
set 1 018 085 018 095 018 213 018 236 018 246
set 2 018 086 018 096 018 214 018 237 018 247
set 3 018 087 018 097 018 215 018 238 018 248
set 4 018 088 018 098 018 216 018 239 018 249
19Z5276A_EN
3-244 Reactive power monitoring when values fall below set thresholds
P<>: Starting
Q<
035 066
Appar. power
S > 0,010 Snom
Direction
forward
backward
&
& >1
& trans.
035 156
&
P<>: Starting
Q<<
035 010
Direction
forward
backward
non-directional
P<>: Signal Q<<
delayed
035 011
&
P<>: Trip signal
& Q<<
& >1 035 176
&
19Z5277A_EN
3-245 The direction-dependent trip signal of the reactive power protection function when values fall below set thresholds
1
P<>: Starting
Q<
035 066
P<>: Operate
delay Q< PSx
*
P<>: Release
delay Q< PSx
* 2
P<>: Signal
Q< delayed
035 067
P<>: tQ<
elapsed trans.
035 068 3
P<>: Fault
Q<
035 069
P<>: Operate
1 delay Q< PSx *
P<>: Release
2 delay Q< PSx *
P<>: tTransient
3 pulse PSx *
19Z5279A_EN
3-246 Performance of the transient signal and the fault signal issued by the reactive power monitoring
P<>: Starting
P>
035 086
P<>: Starting
P>>
035 089 P<>: Direction P
>1 & forw.
P<>: Starting 035 181
P<
035 054
P<>: Starting
P<<
035 060
P<>: Direction P
& backw.
035 191
19Z5274A_EN
P<>: Direction Q
& forw.
035 193
P<>: Starting
Q>
035 092
P<>: Starting
Q>> P<>: Direction Q
035 095 >1 & backw.
035 194
P<>: Starting
Q<
035 066
P<>: Starting
Q<<
035 010
19Z5275A_EN
An adjustable timer stage for monitoring circuit breaker action is started with the general
trip signal 1. This timer stage is also triggered if, in the presence of a general starting
signal, a trip decision from an external protection device is acquired through a signal
input. The general trip signal 2 of the P139 is not used to trigger circuit breaker failure
protection. If the fault still persists when the timer stage elapses, the CB failure signal is
issued.
The input of a trip on starting signal via an appropriately configured binary signal input
generates an undelayed trip signal, provided a general starting signal is present.
Monitoring of the reference voltage has been added to the measuring-circuit monitoring
function.
The P139 monitors the phase currents and voltages for balance during healthy system
operation. If either unbalance or the lack of measuring voltage is detected, action is
taken to prevent the unit from malfunctioning.
Current monitoring
Current monitoring is only enabled if the following conditions are met simultaneously:
IP,max IP,min
I diff >
IP,max
where IP,max is the highest of the three phase currents and IP,min is the lowest; Idiff> is the
set operate value M C M O N : I d i f f > . In order to suppress short-term transients, the
measuring stage Idiff> is followed by a set operate-delayed timer stage M C M O N :
Operate delay.
If connection is to two current transformers only (phase ANC connection only) evaluation
of current IB can be disabled by an appropriate selection for the operating mode.
Voltage monitoring
Voltage monitoring is only enabled if the following conditions are met simultaneously:
In addition to these conditions, either a minimum current having the default threshold
setting of I > 0.05 Inom or the closed position of the circuit breaker contacts can be used
as enabling criteria. If at least one of the phase-to-phase voltages falls below the set
trigger value M C M O N : V m i n < for the period of the operate-delayed timer stage
M C M O N : O p e r a t e d e l a y , then the M C M O N : U n d e r v o l t a g e signal is issued.
Phase-sequence
monitoring
Phase-sequence monitoring is only enabled if the following conditions are met
simultaneously:
"Fuse Failure" monitoring must be able to discriminate between a short circuit in the
three-phase network being monitored and a reference voltage missing because of a
short circuit or an open circuit in the secondary circuits of the reference voltage.
A short circuit or an open circuit in the secondary circuits of the reference voltage is
present when the following conditions are met:
If any of the measured values exceeds or falls below the corresponding upper or lower
limit values, then a signal is issued after the associated time period has elapsed.
3-255 Limit Value Monitoring of maximum and minimum phase-to-phase voltage and maximum and minimum phase-to-ground voltage
LIMIT: General
enable USER
014 010
LIMIT:
Enabled
040 074
0: no
MAIN: Device 1: yes
on-line LIMIT: Vref> LIMIT: tVref>
003 030
042 144 042 148
1: yes (= on)
LIMIT: tVref>
elapsed
042 152
LIMIT: tVref>>
Vref elapsed
042 153
LIMIT: tVref<
elapsed
042 154
LIMIT: tVref<<
abgelaufen
042 155
19Z5215A_EN
LIMIT Starting
MAIN: Protection
active
MEASI: Temperature LIMIT
elapsed
LIMIT Starting
LIMIT LIMIT
LIMIT
elapsed
LIMIT Starting
LIMIT LIMIT
LIMIT
elapsed
LIMIT Starting
LIMIT LIMIT
LIMIT
elapsed
19Z5212A_EN
LIMIT: Starting
T1>
040 200
LIMIT Enabled LIMIT: T1> LIMIT: tT1>
LIMIT: Starting
T1>>
040 201
LIMIT: T1>> LIMIT: tT1>>
LIMIT: tT1>>
elapsed
040 203
LIMIT: Starting
T1<
040 204
LIMIT: T1< LIMIT: tT1<
040 206
LIMIT: Starting
T1<<
040 205
LIMIT: T1<< LIMIT: tT1<<
040 207
19Z5213A_EN
3-260 Monitoring the measured temperature value T1 as an example for measured temperature values T1 to T9
Backup sensors
When an open circuit has occurred the 2-out-of-3-logic available with the Limit Value
Monitoring function will revert to backup sensors.
The selection of such backup sensors for the Limit Value Monitoring function is made in
the function group M E A S I .
For this purpose the temperature sensors connected to the temperature p/c board (RTD
module) are divided into three groups:
If the backup temperature sensor from group 2 also fails it will be replaced by the
corresponding sensor from group 3, under the assumption that
M E A S I : B a c k u p T e m p S e n s o r P S x is set to Group 1 2/3.
Main sensor Backup sensor from group 2 Backup sensor from group 3
With setting: With setting:
Group 1 -2 Group 1 2/3
or
Group 1 -2/3
T1 T4 T7
T2 T5 T8
T3 T6 T9
Should temperature sensor T1 fail, with the setting Group 1 2/3, it will replaced by T4.
Should temperature sensor T4 also fail it will replaced by T7.
2-out-of-3 monitoring
Limit values resulting from temperature values measured by main sensors (from
group 1) or their corresponding backup sensors are processed by the '2-out-of-3' Limit
Value Monitoring function, L I M I T : 2 o u t o f 3 w i t h T 1 , 2 , 3 . This is displayed in the
following figure.
19Z5210A_EN
3-261 Using backup sensors ("B a c k u p T e m p S e n s o r " ) with the '2-out-of-3' Limit Value Monitoring function
All functions associated with temperature sensors operate in a parallel mode. In this
way the '2-out-of-3' Limit Value Monitoring function, L I M I T : 2 o u t o f 3 w i t h T 4 , 5 , 6
may use temperature sensors from group 2 even though these backup sensors are
configured to group 1.
19Z5211A_EN
3-262 Limit Value Monitoring function '2-out-of-3' for temperature sensors T4 to T6 and T7 to T9. If M E A S I : B a c k u p T e m p S e n s o r P S x
is set to 'Without' this scheme will also apply to temperature sensors T1 to T4.
Application example
A motor protection application is shown in the figure below with temperature sensors T1
to T9 connected to the temperature p/c board (RTD module) and a "PT 100" resistance
thermometer connected to the analog (I/O) module Y.
! On the stator there are three temperature sensors as the main sensors (group 1: T1,
T2, T3) and three backup sensors (group 2: T4, T5, T6) used by the '2-out-of-3' Limit
Value Monitoring function
! One temperature sensor on each of the bearings is used for individual Limit Value
signaling
! One main and one backup sensor inside the coolant are used by the thermal replica
in the Thermal Overload protection
RTD
RTD
RTD
RTD
RTD
RTD
RTD
RTD
Stator
RTD
RTD
Rotor
Bearing Bearing
19B5236A_EN
3-263 Temperature measurements on a motor to be used with the Limit Value Monitoring function (L I M I T ) and the Thermal Overload protection
(THERM)
Programmable (or user-configurable) logic enables the user to link binary signals within
a framework of Boolean equations.
Logical operations can be controlled through the binary signal inputs in different ways.
The binary input signals L O G I C : I n p u t n E X T (n = 1 to 16) have an updating
function, whereas the input signals L O G I C : S e t n E X T (n = 1 to 8) are stored. The
logic can only be controlled from the binary signal inputs that are configured for
L O G I C : S e t n E X T if the corresponding reset input (L O G I C : R e s e t n E X T )
has also been configured for a binary signal input. If only one or neither of the two
functions is configured, then this is interpreted as Logic externally set. If the input
signals of the two binary signal inputs are implausible (such as when they both have a
logic value of 1), then the last plausible state remains stored in memory.
3-264 Control of logic operations via setting parameters or stored input signals
3-265 Setting options for programmable logic (shown here for output 1)
The output signal of one equation can be processed as the input signal for another
higher-order equation, and this makes it possible to have a sequence of nested Boolean
equations. The equations are processed in the sequence defined by the order of each
equation so that the end result of a sequence of nested Boolean equations is given by
the highest-order equation.
The output signal of each equation is fed to a separate timer stage that has two timer
elements and a choice of operating modes. This offers the possibility of assigning a
freely configurable time characteristic to the output signal of each Boolean equation. In
the Minimum time operating mode, the setting of timer stage t2 has no effect. Figures
3-266 to 3-270 show the time characteristics for the various timer stage operating
modes.
Note: If the unit is set to off-line, the equations are not processed and all outputs are
set to a logic value of '0'.
The P139 is designed to control up to 6 switchgear units. The Bay Panel type defines
the layout of a bay with its switchgear units.
When a Bay Panel type is selected, the binary inputs for switchgear status signals and
the output relays for control commands are configured automatically if M A I N : A u t o -
a s s i g n m e n t I / O is set to 'Yes'. If set to 'No', the user will need to carry out this
configuration. The list of Bay Panel types in the Appendix shows which binary inputs
and output relays have been assigned signals or commands for control of switchgear
units in the case of automatic configuration.
Setting options for the P139 and the different possibilities to integrate a switchgear unit
into the functional sequence of the P139 (processing of status signals only or controlling
and signaling) will be explained below, using one switchgear unit as an example.
Function group DEV01 will be used throughout in this example. If a signal is identified in
the function diagrams by function group C O M M 1 : with a blank address [--- ---], it will
indicate that it is a signal to or from the communication interface and that it has not been
assigned an address. Signals listed in the function diagrams as signal 1 to signal n
are specified in the configuration tables of the Address List.
The status signals Open and Closed are assigned to binary signal inputs. The signals
conditioned by debouncing and chatter suppression (see: Main Functions of the P139)
are used for further processing. If no logic value of '1' is present at any of the two binary
signal inputs, the running time monitoring function is started. For the duration of the
running time or until the switchgear unit is back to a defined position - either Open or
Closed - the signal Intermediate position is issued.
The signal Faulty position is issued if the switchgear unit does not return to the Open
or Closed position once the running time monitoring and the delay time set in M AIN :
D e l a y M a n . O p . S u p e r v . have elapsed. If D E V 0 1 : S t a t . i n d . i n t e r m . p o s . is
set to 'Yes', a delay time of 5 s is started. Once this time period has elapsed and there is
no status signal for the position, the state actually present at the binary inputs will be
signaled.
Switch truck
For switchgear units mounted on switch trucks with switch truck plugs, it is possible to
configure a single-pole signal as the status signal from the switch truck plug. If such a
configuration has been assigned, the status signal for the position of the associated
switchgear unit is set to Open while the input has a logic value of '1'.
Enabling switching
commands
Before a switching command is executed, the P139 checks the interlocking conditions
defined in the interlocking logic to determine whether a switching command is permitted
or not. Bay interlock conditions for operation with or without the station interlock function
can be defined. The assignment of an output relay from the interlocking logic to a
switching command determines the interlocking conditions that define, for example, the
conditions for the 'Open' command for operation without the station interlock function.
3-274 Assignment of the equations of the interlocking logic to the switching commands; enabling of switching commands by the bay interlock
function
If there is to be a check on the bay interlock and the station interlock function, the bay
interlock will be checked first. If bay interlocking issues a switching enable, a switching
request will be sent to the substation control level. At substation control level, there will
then be a check - taking into account the station interlock functions as to whether
switching is permitted or not. If the substation control level also issues an enabling
command, the switching operation is carried out provided that the enable from the bay
interlock is still present. Optionally, the Open or Close switching operation can be
carried out without checking the station interlock function conditions. In this case, the
bay interlock conditions defined for operation without station interlock functions will be
considered.
Linking protection
commands to switching
commands
For circuit breakers, the Open command can be linked to the protection trip signals.
The 'Close' command can also be linked to the close command of the protection
functions. The Bay Panel type defines which of the switchgear units are circuit breakers.
The trip (open) or close commands of the protection functions are executed directly
without a check of the interlocking conditions.
Issue of switching
commands
Depending on the operating mode (set at D E V x x : O p e r . m o d e c m d . ) set for
commands, switching commands are issued for the set timer durations or according to
time control.
When the automatic synchronism check (ASC) is active and the parameter
A S C : S y s t e m i n t e g r a t . P S x is set to 'automatic synchr. control' a 'Close' request
will automatically issue a 'Close' command for the circuit breaker after a close enable'
was issued by the ASC.
If the contacts on the switchgear unit have not reached either their Open or Closed
position after the set time period for running time monitoring has elapsed the signal
'Faulty position' is issued. If D E V 0 1 : S t a t . i n d . i n t e r m . p o s . is set to 'Yes', a
delay time of 5 s is started. Once this time period has elapsed and there is no status
signal for the position, the state actually present at the binary inputs will be signaled.
Switch truck
For switchgear units mounted on switch trucks with switch truck plugs, it is possible to
configure a single-pole status signal from the switch truck plug. If such a configuration
has been assigned, the status signal for the position of the associated switchgear unit is
set to Open while the input has a logic value of '1'.
DEV01: Close
command
210 029 1
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
4
1 10 ms
19Z5201A_EN
3-279 Sequence for time control of switching commands without external termination control
DEV01: Close
command
210 029
1
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
DEV01:Inp.asg.
end Close
210 016
1 10 ms
3 DEV01: Latching time 210 005
19Z5202A_EN
3-280 Sequence for time control of switching commands with external termination control
If a Bay Panel type with direct motor control is selected, a binary input for the status
signal of the motor relay and one output relay each to trigger the motor relay and the
shunt windings will have to be configured. In the example illustrated in Figure 3-281, the
single-pole command C M D _ 1 : C o m m a n d C 0 1 2 is defined for control of the motor
relay, the single-pole command C M D _ 1 : C o m m a n d C 0 1 1 is defined for control of
the shunt windings and the single-pole signal S I G _ 1 : S i g n a l S 0 1 2 (debounced
and conditioned by chatter suppression) is defined for the status signal of the motor
relay.
After triggering the motor relay, a set monitoring time period is started during which the
status signal must be issued by the motor relay. If the status signal is not received
during this time period the 'Close' command issued to the output relays, configured to
control the motor relay and the shunt windings, is terminated. In addition a signal is
transferred to the substation control level.
If the status signal from the motor relay is issued during the monitoring time period, the
running time monitoring of the motor relay is started simultaneously with this status
signal. Monitoring of the switching command is then the same as with
electromechanically operated switchgear units.
CMD_1: Command
C011
200 051
DEV01: Close
command
210 029
1 2
CMD_1: Command
C012
200 056 2
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
4
1 10 ms
19Z5203A_EN
3-282 Sequence of time monitoring for direct motor control without external termination
DEV01: Close
command
210 029
1 2
CMD_1: Command
C012
200 056 2
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
DEV01: Inp.
asg.end Close
210 016
1 10 ms
19Z5204A_EN
3-283 Sequence of time monitoring for direct motor control with external termination
The switching commands to the controllable switchgear units of the bay are not enabled
until the interlock conditions have been checked. The interlocks are defined in the form
of Boolean equations in the interlocking logic function.
The choice of the bay type automatically defines the bay interlock conditions (or
equations) for the Open and Close operations of the individual switchgear units in the
bay. Different conditions are defined for the bay interlock equations for operation with or
without station interlock (see the section entitled List of Bay Types in the Appendix).
These automatically defined interlock conditions - determined by the choice of bay type -
can be modified by the users at any time to fit their station requirements. For the bay
interlock, the following signals acquired by the P139 are linked by logic operations:
A maximum of 32 equations with 32 equation elements each are available for definition
of the interlock conditions. The Boolean equations need to be defined without the use of
brackets. The following rule applies to the operators: NOT before AND before OR.
The output signal of one equation can be processed as the input signal for another
higher-order equation, and this makes it possible to have a sequence of nested Boolean
equations.
Commands can be sent to the P139 through the communication interface. If the P139
receives the command, then the appropriately configured output relay is triggered and a
signal is issued - provided that remote control has been enabled.
The user may select the operating mode for any single-pole command. The following
settings are possible:
! Long command
! Short command
! Persistent command
If the user selects either a long or a short command, then the output relay is only
triggered for the time period set at M A I N : C m d . d u r . l o n g c m d . or
MAIN: Cmd. dur. short cmd.
The following figure shows the setting options and the functional sequence for command
C001. Equivalent considerations apply to all other single-pole commands.
3-285 Functional sequence for single-pole commands, illustrated for command C001
Binary, single-pole signals from the station can be transmitted by the P139 to the control
station through appropriately configured binary signal inputs.
The input signal is conditioned by debouncing and chatter suppression (see: 'Main
Functions of the P139). The conditioned signal is then available as S I G _ 1 : L o g i c
signal xxx.
! Without function:
! Start/end signal
! Transient signal
If the setting is Without function, then no telegram is sent when there is a state change at
the binary input. If the setting is Start/end signal then a telegram is sent each time there
is a state change. The requirement for sending the 'start' signal is that the logic '1' signal
be available for the set minimum time. If the setting is Transient signal, telegrams are
only sent if there is a state change from logic '0' to logic '1'.
The following figure shows the setting options and the functional sequence for signal
S001. Equivalent considerations apply to all other single-pole signals.
3-286 Functional sequence for single-pole signals, illustrated for signal S001
The P139 has one binary counter which counts the positive edges at an appropriately
configured binary signal input. The signal to be counted can be debounced.
Debouncing
The first positive pulse edge of the signal to be counted starts a timer stage running for
the duration of the set debouncing time. Each positive pulse edge during the
debouncing time retriggers the timer stage. If the signal is stable until the set
debouncing time has elapsed, it is counted.
If the signal has not changed its state from the occurrence of the first pulse edge to the
elapsing of the set debouncing time, it is not counted.
Counting function
The debounced signal is counted by a 16 bit counter. Each counter can be set to a
specific count from the local control panel and through the serial interfaces (preload
function). The count (counter reading) can be displayed on the LCD display and output
via the PC and communication interfaces.
4 Design
The P139 is available in different design types and with different combinations of
modules.
Regardless of design, the P139 like all other device types in the MiCOM Px30
system is equipped with the standard local control panel. The local control panel is
covered with a tough film so that the specified degree of protection will be
maintained. In addition to the essential control and display elements, a parallel
display consisting of a total of 17 LED indicators is also incorporated into the local
control panel. The meaning of the various LED indications is shown in plain text on a
label strip.
The PC interface (9-pin D-Sub female connector) is located under the lower covering
flap of the local control panel.
4.1 Designs
Both versions are connected in the same way via plug-in threaded terminal blocks.
The threaded terminal blocks in the surface-mounted case are accessible from the
front of the device after loosening the four crosshead screws on the sides (see
Figure 4-1 !), taking off the local control panel and hanging it in the slots in the left
side panel (see Figure 4-1 "). The P139 in the flush-mounted case is connected at
the back of the case.
!
The local control panel is connected to processor module P by a plug-in connecting
cable. Do not bend the connecting cable. Hang the local control panel in the slots
provided for this purpose in the left side panel.
The secondary circuit of operating current transformers must not be opened. If the
secondary circuit of an operating current transformer is opened, there is the danger
that resulting voltages may injure personnel or damage the insulation.
The threaded terminal block for current transformer connection is not a shorting block
for devices with pin-terminal connection. Therefore always short-circuit the current
transformer before loosening the threaded terminals.
4-1 Surface-mounted case, removal of local control panel (example for 40T case)
4-3 Dimensional drawing for flush-mounted case 40 T, flush-mount method 1 (without the angle brackets and frame)
(dimensions in mm)
4-4 Dimensional drawing for flush-mounted case 40 T, flush-mount method 2 (using the angle brackets and frame) (dimensions in mm)
4-5 Dimensional drawing for flush-mounted case 84 T, flush-mount method 1 (without the angle brackets and frame)
(dimensions in mm)
4-6 Dimensional drawing for flush-mounted case 84 T, flush-mount method 2 (using the angle brackets and frame) (dimensions in mm)
4.2 Modules
The P139 is constructed of hardware modules that are standard throughout the
system. The following table gives an overview of the modules relevant for the P139
(*: modules that are not shown in the location diagrams, #: optional, $: standard
equipment, %: depending on order).
<2>
-X31 *
-X32 *
<2>
*
-X33
<2>
*
-X34
Alternative module
(see order information)
Per order
Communic. module
Transformer module
19Y5201A_EN
Location diagram of the NCIT and RTD modules: see end of this chapter.
<2>
-X31 *
-X32 *
<2>
*
-X33
<2>
*
-X34
Alternative module
(see order inform.)
Per Order
Communic. module
Transformer module
19Y5203A_EN
4-8 Location diagram P139 in case 40 T, transformer module: ring terminal connection, other modules: pin terminal connection
<2>
-X31 *
-X32 *
<2>
-X121
-X141
-X161
-X181
-X201
*
-X041
-X33
<2>
*
-X34
Alternative module
(see order inform.)
Per Order
Communic. module
Transformer module
19Y5202A_EN
Location diagram of the NCIT and RTD modules: see end of this chapter.
01 04 05
-X044
-X054
-X045
-X055
-X046
-X056
Type
T
*
01 04 05
: Alternative module
*
(see order inform.)
P439_NCIT _01a_EN
01 03
-X81
-X82
-X83
Type
Y
*
01 03
: Alternative module
*
(see order information)
P139_RTD_01a_EN
All P139 overcurrent and control devices are packaged separately into dedicated cartons
and shipped with outer packaging. Use special care when opening cartons and
unpacking devices, and do not use force. In addition, make sure to remove supporting
documents and the type identification label supplied with each individual device from the
inside carton.
The design revision level of each module included in the device when shipped can be
determined from the list of components (assembly list). This list of components should
be filed carefully.
If the P139 needs to be shipped, both inner and outer packaging must be used. If the
original packaging is no longer available, make sure that packaging conforms to
DIN ISO 2248 specifications for a drop height 0.8 m.
The nominal data and design type of the P139 can be determined by checking the type
identification label (see Figure 5-1). One type identification label is located under the
upper hinged cover on the front panel and a second label can be found on the inside of
the device. Another copy of the type identification label is fixed to the outside of the
P139 packaging.
The data shown on the type identification label includes the nominal auxiliary voltage VX,
and the nominal VT input voltage Vn.
The P139 design version can be determined from the order number. A breakdown of the
order number is given in Chapter 14 of this operating manual and in the supporting
documents supplied with the device.
The P139 has been designed to conform to DIN 57435 part 303. Therefore it is
important when choosing the installation location to make certain that it provides the
operating conditions as specified in above DIN norm sections 3.2 to 3.4. Several of
these important operating conditions are listed below.
Environmental Conditions
Ambient temperature: -5 C to +55 C [+23 F to +131 F]
Relative humidity: The relative humidity must not result in the formation of
either condensed water or ice in the P139.
Ambient air: The ambient air must not be significantly polluted by dust,
smoke, gases or vapors, or salt content.
Solar radiation: Direct solar radiation on the front of the device must be
avoided to ensure that the LC-Display remains readable.
Mechanical conditions
Vibration stress: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Electromagnetic conditions
Substation secondary system design must follow the best of modern practices,
especially with respect to grounding and EMC.
5.4 Installation
The dimensions and mounting dimensions for surface-mounted cases are given in
Chapter 4. When the P139 is surface-mounted on a panel, the wiring to the P139 is
normally run along the front side of the mounting plane. If the wiring is to be at the back,
an opening can be provided above or below the surface-mounted case. Figure 5-2
shows such an opening below the surface-mounted case.
5-2 Opening for running the wiring to the 40 T surface-mounted case (dimensions in mm)
Flush-mounted cases are designed for control panels. The dimensions and mounting
dimensions are given in Chapter 4. When the P139 is mounted on a cabinet door,
special sealing measures are necessary to provide the degree of protection required for
the cabinet (IP 51). Figures 5-3 to 5-6 show the required panel cutouts for both
mounting methods.
5-3 Panel cutout for the 40 T flush-mounted case, flush-mount method 1 (without the angle brackets and frame) (dimensions in mm)
5-4 Panel cutout for the 40 T flush-mounted case, flush-mount method 2 (using the angle brackets and frame) (dimensions in mm)
5-5 Panel cutout for the 84 T flush-mounted case, flush-mount method 1 (without the angle brackets and frame) (dimensions in mm)
5-6 Panel cutout for the 84 T flush-mounted case, flush-mount method 2 (using the angle brackets and frame) (dimensions in mm)
For flush-mount method 1 (without the angle brackets and frame), the procedure is as
follows:
Before the P139 can be installed into a control panel, the local control panel must be
removed. The local control panel is removed as described below:
! Remove both top and bottom hinged flaps from the device. (Lift/lower both hinged
flaps 180up/down. Hold them in the middle and bend them slightly. The side
mountings of both hinged flaps can then be disengaged.)
! Remove the M3 screws (see Figure 5-7).
! Then remove the local control panel.
!
The local control panel is connected to processor module P by a plug-in connecting
cable. Remember the connector position! Do not bend the connecting cable.
Then remove the lower M4 screws and only loosen the upper M4 screws (see Figure 5-7).
Now insert the P139 into the panel opening from the rear so that the upper M4 screws fit
into the corresponding holes. Then tighten all the M4 screws. After this, replace the
local control panel.
Note: For panels with a thickness 2 mm, replace the M3 and M4 screws with
longer screws. Longer screws are enclosed within the device packing.
5-7 Installation of a case into a control panel. Flush-mount method 1 (without the angle brackets and frame ).
Example for a device with a 40 T case.
For flush-mount method 2 (using the angle brackets and frame), the procedure is as
follows:
! Remove the screws as shown in Figure 5-8, " and mount the enclosed angle
brackets using these same screws.
! Then push the device into the control panel cutout from the front.
! Secure the device to the control panel by using the enclosed M6 screws (see Figure 5-9).
! Assemble the cover frame and snap-fasten onto the fixing screws.
5-9 Installation of a case into a control panel. Flush-mount method 2 (using the angle brackets and frame ).
Example for a device with a 40 T case.
A rack mounting kit can be used to combine a flush-mounted 40 T case with a second
sub-rack to form a 19 mounting rack (see Figure 5-10). The second sub-rack can be
another device, for example, or an empty sub-rack with a blank front panel. Fit the
19 mounting rack to a cabinet as shown in Figure 5-11.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters PE on the terminal connection diagram) is also
required for proper operation of the device. The cross-section of this ground conductor
must also conform to applicable national standards. A minimum cross section of
1.5 mm2 is required.
The grounding connection at both locations must be low-inductance, i.e. it must be kept
as short as possible.
5.6 Connection
The P139 overcurrent and control device must be connected in accordance with the
terminal connection diagram as indicated on the type identification label. The terminal
connection diagram is included in the supporting documents supplied with the device.
The terminal connection diagrams that apply to the P139 are also to be found in the
Appendix to this operating manual.
In general copper conductors with a cross section of 2.5 mm are sufficient to connect a
system current transformer to a current input on the P139. To reduce CT knee-point
voltage requirements, it may be necessary to install shorter copper conductors with a
greater cross section between the system current transformers and the current inputs on
the P139. Copper conductors having a cross section of 1.5 mm2 are adequate to
connect binary signal inputs, the output relays and the power supply input.
All connections run into the system must always have a defined potential. Connections
that are pre-wired but not used should preferably be grounded when binary inputs and
output relays are isolated. When binary inputs and output relays are connected to
common potential, the pre-wired but unused connections should be connected to the
common potential of the grouped connections.
Power supply
Before connecting the auxiliary voltage Vx for the P139 power supply, it must be
ensured that the nominal value of the auxiliary device voltage corresponds with the
nominal value of the auxiliary system voltage.
Current-measuring inputs
When connecting the system transformers, it must be ensured that the secondary
nominal currents of the system and the device correspond.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for system current transformer connection is not a shorting
block! Therefore always short-circuit the system current transformers before loosening
the threaded terminals.
The P139 is generally fitted with four current-measuring inputs. Three-pole or two-pole
connection is possible to suit the individual power system and substation.
The steady-state ground fault direction determination requires either the three
phase-to-ground voltages or, alternatively, the neutral-point displacement voltage from
the open delta winding of a voltage transformer assembly as the measured voltage. An
additional voltage transformer (T 90) is available in the P139 to connect an open delta
winding. When setting the protection function, the selected voltage needs to be taken
into account.
Figure 5-14 shows the standard connection for ground fault direction determination by
steady-state values where the voltage measuring circuit is connected to an open delta
winding. With this connection configuration, forward/LS is displayed if a ground fault
occurs on the line side. A connection with reverse orientation for the system current or
voltage transformer is possible if the appropriate setting is made (see Chapter 7).
Connection to Connection to
Holmgreen group Core balance CT
A
B BS
C
19Z5290A_EN
5-14 Connecting the steady-state ground fault direction determination function to Holmgreen-configuration and core balance transformers
Connecting protective
signaling
Either a transmission device or pilot wires are required for signal transmission,
depending on the operating mode selected. Twisted pair cores should be used as pilot
wires. Two or four cores are required. If only two cores are available, there must be an
all-or-nothing relay in each station for coupling received and transmitted signals. The
coils of the all-or-nothing relays must be designed for half the loop voltage. Figure 5-15
shows connection with two cores and Figure 5-16 connection with four cores.
The protective signaling transmitting relay can be set to either Transm. relay break
contact or Transm. relay make contact. In the first case the break contact of the
transmitting relay must be wired, and in the second case the make contact must be
wired. The figures show the connection for the setting Transm. relay break contact.
Connecting a resistance
thermometer
A resistance thermometer can be connected if the device is fitted with analog module Y.
This analog I/O module input is designed to connect a PT 100 resistance thermometer.
The PT 100 should be connected using the 3-wire method (see Figure 5-17). No supply
conductor compensation is required in this case.
The polarity for connected binary inputs is to be found in the terminal connection
diagrams (see supporting documents supplied with the device or in the Appendix). This
is to be understood as a recommendation only. Connection to binary inputs can be
made as desired.
Connection of switchgear
units having direct motor
control
In the case of bay types having direct motor control, one binary input is configured for
the status signal and one output relay is configured for triggering and resetting the motor
relay. Configuration of appropriate output relays to trigger the armature and shunt
windings of motors on load disconnect switches, isolating links or grounding switches is
in accordance with the List of Bay Types (see Appendix). A connection example for a
direct motor control is shown in Figure 5-18.
PC interface
The PC interface is provided so that personnel can operate the device from a personal
computer (PC).
!
The PC interface is not designed as a permanent connection. Consequently, the female
connector does not have the extra insulation from circuits connected to the system that
is required per VDE 0106 Part 101.
Communication interface
The selection and assembly of a properly cut fiber-optic connecting cable requires
special knowledge and expertise and is therefore not covered in this operating manual.
!
The fiber-optic interface may only be connected or disconnected when the supply
voltage for the device is shut off.
A RS485 data transmission link between a master and several slave devices can be
established by using the optional communication interface. The communication master
could be, for instance, a central control station. Devices linked to the communication
master, e.g. P139, are set-up as slave devices.
The RS 485 interface available on the P139 was designed so that data transfer in a full
duplex transmission mode is possible using a 4-wire data link between devices. Data
transfer between devices using the RS 485 interface is set up only for a half duplex
transmission mode. To connect the RS485 communication interface the following must
be observed:
! Only twisted pair shielded cables must be used, that are common in
telecommunication installations.
! At least one symmetrical twisted pair of wires is necessary.
! Conductor insulation and shielding must only be removed from the core in the
immediate vicinity of the terminal strips and connected according to national
standards.
! All shielding must be connected to an effective protective ground surface at both
ends.
! Unused conductors must all be grounded at one end.
P139
P139
P139
P139
! Control of switchgear
! Readout and modification of settings
! Readout of cyclically updated measured operating data and logic status signals
! Readout of operating data logs and of monitoring signal logs
! Readout of event logs after overload situations, ground faults, or short circuits in the
power system
! Device resetting and triggering of additional control functions used in testing and
commissioning
Control is also possible through the PC interface. This requires a suitable PC and a
specific operating program.
Trip
Alarm
Out of Service
C
Healthy G
Edit Mode
O I L/R
Display levels
All data relevant for operation and all device settings is displayed on two levels. Data
such as the switching status or the measured operating values is displayed at the panel
level and provides an up-to-date overview of the status of the bay. The menu tree level
below the panel level allows the user to select all data points (settings, signals,
measured variables, etc.) and to change them, if appropriate. To access a selected
event recording from either the panel level or from any other point in the menu tree,
press the READ key .
G
Current A prim. CB closed sig. EXT
Q8 Bay interlock. act. 416 A End
MAIN: Current B prim. 21.04.98
Locked Subst. interl. act. 415 A 05:21:32.331 DEV01
Remote Current C prim.
1088 A 417 A
Switch.device closed
Curr. IP,max prim. Start
Display panels
The following display panels are available with the P139:
! Bay Panel
! Signal Panel
! Measured Value Panels, which are called up according to system conditions
! Event Panel
The Bay Panel displays the up-to-date switching status of the selected bay as a one line
diagram. If user-defined bay types are applied, resulting information may be sub-divided
into up to eight images. A maximum of 28 physical and logic binary status may be
configured to one Signal Panel and, depending on the operating mode, acknowledged.
Selected measured values are displayed on the Measured Value Panels. Only the
Measured Value Panels relevant for the particular design version of the given device and
its associated range of functions are actually available. The Event Panel displays the
most recent events, each with a time tag, such as the opening of a switchgear unit.
! ENTER Key
Panel Level:
By pressing the ENTER key at the Panel level, the user can go to the first menu tree
level.
Menu Tree Level:
To enter the input mode, press the ENTER key. Press the ENTER key a second time
to accept the changes as entered and leave the input mode. The LED indicator
labeled EDIT MODE signals that the input mode is active.
! CLEAR Key C
Press the CLEAR key to reset the LED indicators and clear all measured event data.
The records in the recording memories are not affected by this action.
Panel Level:
Bay Panel:
If the CLEAR key is pressed while selecting a switchgear unit on the Bay Panel then
the selection of the switchgear unit is canceled. The LED indicators are not reset in
this procedure.
Signal Panel:
A selected flashing signal may be acknowledged individually by pressing the CLEAR
key. This acknowledgement will switch the flashing signal to a static status but will
not cause the LED indicators to reset or clear measured event data.
Menu Tree Level:
Input mode:
When the CLEAR key is pressed all changes entered are rejected and the input
mode is exited.
! READ Key
Press the READ key to access a selected event recording from either the Panel level
or from any other point in the menu tree.
! Local/Remote Key L/R
The local/remote key is effective in the Bay Panel except where a binary signal input
has been configured for this function. The local/remote key is the transfer switch
between remote and local control (setting RL), or between remote&local and local
control (setting R&L L). If the local/remote key is set to (RL), the transfer from
remote to local control can only take place if the L/R password has been entered first.
The transfer from local to remote control does not require any password entry.
! Page Key
Panel Level:
Pressing the page key shows the next panel.
Menu Tree Level:
When the page key is pressed the Menu Tree Level is exited and the Bay Panel is
accessed.
! Selection Key
Bay Panel:
The Selection key is effective only in the Bay Panel and only if local control is
activated. If local control has been selected, pressing the Selection key selects the
switchgear unit to be controlled. The selected external device will be marked by an
asterisk (*) as long as no external device names are displayed. Otherwise the
external device name will flash and will be displayed in the status line.
Signal Panel:
The Selection key is used to select a flashing signal (not yet acknowledged) and will
also automatically switch to pages that might be available. When the last flashing
signal has been reached pressing the Selection key again will start with the first
flashing signal.
! OPEN Key O
The OPEN key is effective in the Bay Panel only. Pressing the OPEN key controls
the selected switchgear unit taking into account the interlock equation to assume
the open status.
! CLOSE Key I
The CLOSE key is effective in the Bay Panel only. Pressing the CLOSE key controls
the selected switchgear unit taking into account the interlock equation to assume
the closed status.
The following presentation of the individual control steps shows which displays can be
changed in each case by pressing keys. A small black square to the right of the enter
key indicates that the LED indicator labeled EDIT MODE is illuminated. An underscored
external device name in the Bay Panel indicates a selected switchgear unit. The
examples used here are not necessarily valid for the device type described in this
manual; they merely serve to illustrate the control principles involved.
After start-up of the device, the display is at the Panel Level. The Bay Panel is
displayed.
device. SS1
SS2
Note: Q1 Q2
When the device is delivered, it is set for a
dummy bay without switchgear units.
Q0
Therefore only the name of the device appears
on the Bay Panel. The display shown in the Q9
Note: Q0
It is important to press the up key first and
Q9
release it last in order to avoid unintentional
resetting of stored data. Q8
Locked
Remote
1088 A
Curr. IP,max prim.
After the set return time has elapsed (setting in menu tree: "Par/Conf/LOC"), the display
will switch automatically to the Bay Panel.
If none of the control keys is pressed, the display illumination will switch off once the set
return time illumination (setting in menu tree: "Par/Conf/LOC") has elapsed. Pressing
any of the control keys will turn the display illumination on again. In this case the control
action that is normally triggered by that key will not be executed. Reactivation of the
display illumination is also possible by using a binary input.
If continuous display illumination is required, the function return time illumination is set
to blocked.
At Panel Level, the user can move from one Panel type to another by pressing the Page
key (in one direction only) or the left/right keys (in both directions).
Information displayed on
the Bay Panel
Figure 6-3 shows an example of a Bay Panel. The top line shows the device type on the
left and the current time of day on the right. Together with a customized Bay Panel type
with more than one Bay Panel image the top line will include an image marker in the
center. The image markers run from "Image A" (first image) to "Image H" (eighth image).
The Bay Panel shown below in one-line diagram representation is a function of the set
Bay Panel type. The symbols shown in the following table are used to represent the
switchgear units and other external devices as well as the status of switchgear units.
The user can switch between character sets 1, 2, and 3. Character set 3 is identical to
character set 1 in as-delivered condition but can be replaced by a user-defined character
set by using a special ancillary tool. The symbols of character set 2 are used in the
following description.
The fourth line from the bottom shows (in abbreviated form) whether a bay interlock is
active. The third line from the bottom indicates whether remote or local control is
permitted. In the example shown here, remote control is activated. The two lines at the
bottom contain measured value data. The arrows to the right of the measured value
data indicate that additional measured values can be called up by pressing the up or
down keys.
X YYY 10:33:22
SS1
SS2
Q1 Q2
Q0
Q9
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
Closed
In-motion, Faulty
Closed
In-motion, Faulty
Closed
In-motion, Faulty
Closed
In-motion, Faulty
Closed
SS1
10:33:22
displayed. Remote
1088 A
Curr. IP,max prim.
SS1
10:33:25
Q9
Q8
Locked
Remote
1000 A
Curr. IA prim.
Controlling switchgear
units
Switchgear units can be controlled from the local control panel, provided that the unit has
been set for 'local control'. If the local/remote key is set to switch between remote and
local control (RL), then the switch from 'remote' to 'local' operation requires a
password. When more than one Bay Panel image is used only joint 'local/remote'
switching is available.
The following example is based on the (RL) setting for the local/remote key and the
factory-set L/R password. If the password has been changed by the user (see the
section entitled 'Changing the Password'), the following description will apply
accordingly.
SS1
SS2
Q1 Q2
Q0
Q9
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
Up XX YYY 10:33:33
The display will change as shown in the
column on the right.
*
SS1
If the correct password has been entered, the SS2
Bay Panel will re-appear. The third line from Q1 Q2
the bottom will display Local.
If an invalid password has been entered, the Q0
Q8
Locked
Local
1088 A
Curr. IP,max prim.
SS1
10:33:22
Q0
Q9
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
SS1
10:33:28
SS1
10:33:28
Q0
Q9
Q8
Locked
Local
1088 A
Curr. IP,max prim.
SS1
10:33:33
Q8
Locked
Local
1088 A
Curr. IP,max prim.
Q1 Q2
Q0
Q9
Q8
Locked
Local
1088 A
Curr. IP,max prim.
Q9
Q8
Locked
Local
1088 A
Curr. IP,max prim.
SS1
10:33:38
Q0
Q9
Q8
Locked
Remote
1088 A
Curr. IP,max prim.
The Signal Panel is used to display the up to 28 different physical and logical binary
states that the device has available. The top line in the display shows the panel
designation 'Signals' and the current time of day. The following empty line separates the
heading from actual signals. This gives display capacity of up to seven signals to one
Signal Panel. Additional pages are created when more than seven signals have been
configured. As with all other panels, switching between pages is carried out
automatically, after the parameter panel hold-time (LOC: H o l d - t i m e f o r P a n e l s )
has elapsed, or manually by pressing the up/down keys.
Each signal consists of two lines. The first line shows a status marker (square)
and the associated function group. The second line shows the full text for this signal.
Automatic activation
When automatic activation of the Signal Panel is set (L O C : A u t . a c t i v . S i g n . P a n e l )
each status change of signals, configured to a panel, is automatically switched from the
Bay Panel image or the Operation Panel/Event Panel (depending on the actual
selection) to the Signal Panel. Depending on the range of functions available in the
device, the displays of Overload Panels, Ground Fault Panels or Fault Panels have a
higher priority and will be shown when an event has occurred. Using the Page key will
make the display jump to the other panels at any time.
Each status change of signals, configured to a panel of the Bay Panel image can be set
to call for user attention either by having the status marker or both signal lines flash
when a new event has occurred. The switching control will then automatically switch to
the page, which includes the first signal that has experienced a status change. After
pressing the Selection key this flashing signal is selected on the current page (signal
preceded by a flashing cursor >). The next flashing signal can be called up by pressing
the Selection key again. At this point it may occur that the display will automatically
jump to the next page. When the last flashing signal has been reached pressing the
Selection key again will start with the first flashing signal.
transient signals will lead to a flashing signal. The status change is generally shown as
"storing" i.e. the flashing signal will remain until it has been acknowledged.
Acknowledging flashing
signals
Acknowledging a flashing signal that has been selected will occur by pressing the
CLEAR key C . This will not reset illuminated LED indicators but will only acknowledge
the display. The flashing will stop when the CLEAR key is pressed and a static status
display will appear. Then the display will automatically jump to the next flashing signal.
This will enable the user to acknowledge any flashing signals by multiple pressing of the
CLEAR key. As long as the Selection key is pressed and no resetting has occurred the
current page will be continuously displayed (no automatic switching to the next page).
The selection will remain active until the time set in L O C : R e t u r n t i m e s e l e c t has
elapsed. When the time has elapsed the display will jump to the next page. During an
active selection the user may at any time jump to the next or the previous page by
pressing the 'up or 'down' keys (similar to the Measured Value Panel and the Event
Panel).
As long as at least one status change signal in the Signal Panel has not been
acknowledged, L O C : C h g . S i g . P a n e l s t a t . will show the status change of the
Signal Panel as a static signal. This signal is made available in the selection tables for
the function groups LED, OUTP, LOGIC, PC, COMM1 and COMM2.
Description Display
0 The uppermost line of the display shows the Meas. values 16:57:33
The Event Panel shows the signals relevant for operation, each with the complete time
tag (date and time of day). A maximum of three signals are displayed. The Event Panel
is based on entries in the operating data memory (menu tree: "Opdat/Rec/OP_RC").
08:10:59.688 MAIN
Blockade/Strung
End
The menu tree begins with the device type at the top and then branches out below into
the three main folders entitled Parameters, Operation, and Events, which form the first
folder level. Below the first folder level are two more folder levels, so that the entire
folder structure consists of three main branches and a maximum of three folder levels.
At the bottom of each branch of folders, below the folder levels, are the various function
groups in which the individual data points are combined.
PX yyy
Unit
type
Oper/
Folder Cyclic measurements
plane 2
Oper/Cycl/
Folder Meas. operating data
plane 3
Oper/Cycl/Data/
Function MAIN
groups
Oper/Cycl/Data/MAIN
Data Date
points 01.01.99 dd.mm.yy
The display on the local control panel can be switched between address mode and plain
text mode. In the address mode the display shows setting parameters, signals, and
measured values in numerically coded form, that is, as addresses. In plain text mode
the setting parameters, signals, and measured values are displayed in the form of plain
text descriptions. In either case, control is guided by the menu tree. The active branch
of the menu tree, as well as the headings of the panels are displayed in plain text in both
modes. Also the text on the Bay Panel is always displayed in plain text mode. In the
following examples, the display is shown in only plain text mode.
Although it is possible to select any data point in the menu tree and read the associated
value by pressing the keys, it is not possible to switch directly to the input mode. This
safeguard prevents unintended changes in the settings.
There are two ways to enter the input mode.
Global change-enabling
function
! To activate the global change-enabling function, set the Param. change enabl.
parameter to Yes (menu tree: Oper/CtrlTest/LOC).
The change can only be made after the password has been entered. Thereafter, all
further changes with the exception of specially protected control actions (see the
section entitled Password-Protected Control Actions) are enabled without entering
the password.
Selective change-enabling
function
! Password input prior to any parameter change.
Right Oper/CtrlTest/LOC
Param. change enabl.
No
*
Up Oper/CtrlTest/LOC
Param. change enabl.
No
*
Down Oper/CtrlTest/LOC
Param. change enabl.
The display will change as shown in the No
column on the right. *
The same procedure applies to any parameter change unless the global change-
enabling function has been activated. This method is recommended for a single
parameter change only. If several settings are to be changed, then the global change-
enabling function is preferable. In the following examples, the global change-enabling
function has been activated.
Automatic return
The automatic return function prevents the change-enabling function from remaining
activated after a change of settings has been completed. Once the set return time
(menu tree Par/Conf/LOC) has elapsed, the change-enabling function is automatically
deactivated, and the display switches to a Measured Value Panel corresponding to the
current system condition. The return time is restarted when any of the control keys is
pressed.
Forced return
The return described above can be forced from the local control panel either by pressing
the Page key or by pressing the up key and then holding it down while pressing the
CLEAR key.
Note: It is important to press the up key first and release it last in order to avoid
unintentional deletion of stored data.
Even when the change-enabling function is activated, not all parameters can be
changed. For some settings it is also necessary to switch the device to offline. (menu
tree: Par/Func/Glob/MAIN, device on-line). Such settings include the configuration
parameters, by means of which the device interfaces can be adapted to the system. The
following entries in the Change column of the address list (see appendix) indicate
whether values can be changed or not:
! "on": The value can be changed even when the device is switched to online.
! "off": The value can only be changed when the device is switched to offline.
! "-": The value can be read out but cannot be changed.
The device is factory-set so that the device is switched to offline.
If all the conditions for a value change are satisfied (see above), the desired setting can
be entered.
Using list parameters, the user is able to select several elements from a list in order to
perform tasks such as defining a trip command or defining the measured values that will
be displayed on Measured Value Panels. The maximum possible number m that can
be selected out of the total number n of the set is given in the address list in the
Remarks column. As a rule, the selected elements are linked by an OR operator.
Other operators (NOT, OR, AND, NOT OR and NOT AND) are available in the LOGIC
function group for linking the selected list items. In this way binary signals and binary
input signals can be processed in a Boolean equation tailored to meet user
requirements. For the DNP 3.0 communication protocol, the user defines the class of a
parameter instead of assigning operators. The definition of a trip command shall be
used here as an example to illustrate the setting of a list parameter.
After a memory is entered, the memory can be read out at the entry point. It is not
necessary to activate the change-enabling function or even to switch the device to
offline. Inadvertent clearing of a memory at the entry point is not possible.
Not all of these event memories are present in each unit. A given unit may contain only
some of them or even none at all, depending on the device type.
1 Press the down key to enter the monitoring Mon. signal record.
01.01.97 13:33 SFMON
signal memory. The oldest entry is displayed. Checksum error param
3 Press the left key to display the previous Mon. signal record.
01.01.97 13:33 SFMON
entry. Checksum error param
6.5.7 Resetting
All information memories including the event memories and the monitoring signal
memory and also the LED indicators can be reset manually. In addition, the LED
indicators are automatically cleared and initialized at the onset of a new fault provided
that the appropriate operating mode has been selected so that they always indicate the
latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which is
always possible in the standard control mode. This action also triggers an LED indicator
test and an LCD display test. The event memories are not affected by this action, so that
inadvertent deletion of the records associated with the reset signal pattern is reliably
prevented.
Because of the ring structure of the event memories, the data for eight consecutive
events are updated automatically so that manual resetting should not be necessary, in
principle. If the event memories need to be cleared completely, however, as would be
the case after functional testing, this can be done after selecting the appropriate
parameter. The resetting procedure will now be illustrated using the fault memory as an
example. In this example the global change-enabling function has already been
activated.
Certain actions from the local control panel (such as a manual trip command for testing
purposes) can only be carried out by entering a password. This setup is designed to
prevent accidental output and applies even when the global change-enabling function
has been activated.
right Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*
up Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*
down Oper/CtrlTest/MAIN
Man. trip cmd USER
The display will change as shown in the Don't execute
column on the right. *
The password consists of a combination of keys that must be entered sequentially within
a specific time interval. The left,right, up and down keys may be used to define the
password and represent the numbers 1, 2, 3 and 4, respectively:
1 2
The password can be changed by the user at any time. The procedure for this change is
described below. The starting point is the factory-set password.
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
**
Par/Conf/LOC
Password
**
**
Operation from the local control panel without password protection is also possible. To
select this option, immediately press the ENTER key a second time in steps 4 and 6
without entering anything else. This will configure the local control panel without
password protection, and no control actions involving changes will be possible until the
global change-enabling function has been activated (see the section entitled Change-
Enabling Function).
If the configured password has been forgotten, it can be called up on the LCD display as
described below. The procedure involves turning the device off and then on again.
Par/Conf/LOC
Password L/R
********
*
Par/Conf/LOC
Password L/R
********
*
Par/Conf/LOC
Password L/R
********
*
Par/Conf/LOC
Password L/R
**
Par/Conf/LOC
Password L/R
**
**
7 Settings
7.1 Parameter
The P139 must be adjusted to the system and to the protected equipment by appropriate
settings. This section gives instructions for determining the settings, which are located in
the folder titled Parameters in the menu tree. The sequence in which the settings are
listed and described in this chapter corresponds to their sequence in the menu tree. The
'Address List' in the Appendix lists all parameters, along with setting ranges and
incrementation or selection tables.
The units are supplied with a factory-set configuration of settings that in most cases
correspond to the default settings given in the Address List. If the factory settings differ
from the default settings, then this is indicated below at the appropriate points.
The default settings given in the Address List are activated after a cold restart. The
P139 is blocked in that case. All settings must be re-entered after a cold restart.
The device identification settings are used to record the ordering information and the
design version of the P139. They have no effect on the device functions. These settings
should only be changed if the design version of the P139 is modified.
Identification of the change level of the texts of the data model. This display
cannot be altered.
DVICE: Text vers.data model 002 121
Using the text replacement tool provided by the operating program, the
user can change the parameter descriptors (plain text designations) and
load them into the device. These customized data models contain an
identifier defined by the user while preparing the data model. This identifier
is displayed at this point in the menu tree. Standard data models have the
identifier 0 (factory-set default).
DVICE: F number 002 124
The F number is the serial number of the device. This display cannot be
altered.
DVICE: Order No. 000 001
Order number of the device. The user cannot alter this number.
Index letter specifying the version of the module fitted in the respective slot.
Set your numerically coded user data here for your records.
DVICE: Device ID 000 035
The password to be used for changing settings from the local control panel
can be defined here. Further information on changing the password is
given in Chapter 6.
LOC: Password L/R 221 040
The password to be used for changing settings from the local control panel
can be defined here. Further information on changing the password is
given in Chapter 6.
LOC: Displ. ext.dev.desig 221 032 Fig: 3-2
This setting defines whether the control site local or remote shall be
displayed on the Bay Panel.
LOC: Displ. interl. stat. 221 071 Fig: 3-2
Note:
Character set 3 is identical to character set 1 in the factory default setting,
but can be replaced by an user-defined character set, by applying an
accessory tool to the operating program.
This setting determines whether the switching (using either the L/R key or
the key switch) is between local and remote control (LR) or between
local+remote and local control (R&LL).
LOC: Assignment read key 080 110
Selection of the event log that will be displayed when the READ key is
pressed.
LOC: Fct. Operation Panel 053 007 Fig: 3-4
Note:
Measured values to be displayed in bar chart form must also be selected for
display as numerical measured values. However, not all measured values
that can be displayed in numerical form can also be displayed in bar chart
form! In such cases, a dummy or placeholder must be included in the
selection list for the bar chart display at the same point at which a measured
value that cannot be displayed in bar chart form appears in the selection list
for numerical measured values.
Example:
Deactivation of the bar chart display or definition of the orientation of the bar
chart to display measured values on the Bay Panel.
LOC: Scal. bar display I 221 044 Fig: 3-2
Setting the time period for which a panel is displayed, before the unit
switches to the next panel. This setting is only relevant if more values are
selected than can be shown on the LC-Display.
If the user does not press a key on the local control panel during this set
time period, the change-enabling function is deactivated and the Bay Panel
is called up.
LOC: Return time select. 221 030 Fig: 3-2
If the user does not press a key on the local control panel during this set
time period, then the selection of a switchgear unit is canceled.
LOC: Return time illumin. 003 023
If the user does not press a key on the local control panel during this set
time period, then the backlighting of the LCD display is switched off, and
any switchgear selection that might have been made is canceled.
Set the same parity that is set at the interface of the PC connected to the
P139.
PC: Spontan. sig. enable 003 187 Fig: 3-9
Enable for the cyclic transmission of measured values via the PC interface.
PC: Cycl. data ILS tel. 003 185 Fig: 3-9
The active power value is transmitted via the PC interface if it differs by the
set delta quantity from the last measured value transmitted.
PC: Delta f 003 057 Fig: 3-9
All measured values are transmitted again via the PC interface after this
time period has elapsed provided that transmission has not been triggered
by the other delta conditions.
PC: Time-out 003 188 Fig: 3-9
Setting the time to elapse after the last telegram exchange via the PC
interface before activating the second communication channel of
communication module A.
Enabling additional settings that are relevant for the protocol based on
IEC 870-5-101.
COMM1: Addit. ILS enable 003 217 Fig: 3-10
Enabling additional settings that are relevant for the ILS protocol.
COMM1: MODBUS enable 003 220 Fig: 3-10
Select the communication protocol that shall be used for the communication
interface.
COMM1: -103 prot. variant 003 178 Fig: 3-11
The user may select either the AREVA D or the VDEW variant of the 103
protocol.
The user may select either the AREVA D or the VDEW variant of the
MODBUS protocol.
Note: This setting is hidden unless the MODBUS protocol is enabled.
COMM1: Line idle state 003 165 Fig: 3-11,
3-12,3-13,
Setting the line idle state indication. 3-14,3-15,
3-16
In the DNP 3.0 protocol, a 16-bit address is used to identify devices. The
address that can be set here is the higher-order octet, whereas the address
set at C O M M 1 : O c t e t c o m m . a d d r e s s is the lower-order octet of
the DNP address.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Test monitor on 003 166 Fig: 3-11,
3-12,3-13,
Setting specifying whether data shall be recorded for service activities. 3-14,3-15,
3-16
Setting the transmission direction. Normally this value will be set to '1' at
the control center and to '0' at the substation.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
COMM1: Time-out interval 003 228 Fig: 3-12
Setting the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
COMM1: Reg.asg. selec. cmds 003 210 Fig: 3-14
Number of bits that must pass between the receipt of the 'request' and the
start of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Phys. Char. Timeout 003 242 Fig: 3-15
Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Confirm. Mode 003 243 Fig: 3-15
Setting the time period within which the master must acknowledge at the
link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Number of repetitions that are carried out on the link layer if errors have
occurred during transmission (such as failure to acknowledge).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl.Confirm.Timeout 003 246 Fig: 3-15
Setting the time period within which the master must acknowledge at the
application layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl. Need Time Del. 003 247 Fig: 3-15
Time interval within which the slave cyclically requests time synchronization
from the master.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin. inputs 003 232 Fig: 3-15
Selection of data points and data classes for object 1 binary inputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin.outputs 003 233 Fig: 3-15
Selection of data points and data classes for object 10 binary outputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin. count. 003 234 Fig: 3-15
Selection of data points and data classes for object 20 binary counters.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. analog inp. 003 235 Fig: 3-15
Selection of data points and data classes for object 30 analog inputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. analog outp 003 236 Fig: 3-15
Selection of data points and data classes for object 40 analog outputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Cycle time at the conclusion of which the selected measured values are
again transmitted.
Note: This setting is hidden unless the COURIER protocol is enabled.
Set the same parity that is set at the interface of the control system
connected to the P139.
COMM2: Dead time monitoring 103 176 Fig: 3-18
The time between two polling calls from the communication master must be
less than the time set here.
COMM2: Octet comm. address 103 072 Fig: 3-18
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Name of manufacturer 103 161 Fig: 3-18
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Spontan. sig. enable 103 177 Fig: 3-18
All measured values are transmitted again via the communication interface
after this time period has elapsed provided that transmission has not been
triggered by the other delta conditions.
Adjustment of the baud rate for telegram transmission via the teleprotection
interface (InterMiCOM interface) so as to meet the requirements of the
transmission carrier.
COMM3: Source address 120 031
This timer triggers the alarm signals CO MM 3 : Com mu nic a ti ons fau l t
and SFM ON : Co mm un ic .fa ul t CO MM 3 and sets the received signals
to their user-defined default values. Time-out occurs when the set time has
elapsed since the most recent 100% valid telegram was received.
COMM3: Sig.asg. comm.fault 120 034
Using this setting, the alarm signal can be configured (assigned) to the
corresponding PSIG input signal.
COMM3: Time-out link fail. 120 035 Fig: 3-21
Binary inputs
The P139 has opto coupler inputs for processing binary signals from the substation. The
number and connection schemes for the available binary inputs are shown in the
terminal connection diagrams. The Address List in the Appendix gives information about
the configuration options for all binary inputs.
The P139 identifies the fitted modules during startup. If a given binary I/O module is not
fitted or has fewer binary signal inputs than the maximum number possible at this slot,
then the configuration addresses for the missing binary signal inputs are automatically
hidden in the menu tree.
When configuring binary inputs one should keep in mind the fact that the same function
can be assigned to several signal inputs. Thus one function can be activated from
several control points having different signal voltages.
The configuration in slots A and B and the configuration for the binary inputs U C01 to
U C08 will be changed with the selection of a new bay type. (Whether automatic
configuration occurs, is defined by the setting at M A I N : A u t o - a s s i g n m e n t I / O .)
Depending on the connection type chosen for the P139 pin type or ring type cable
socket terminals the symbolic slots A, B and C refer to the following slots:
Symbolic slot Pin type cable socket Ring type cable socket
terminals terminals
A 06 12
B 07 14
C 08 16
The configuration of binary inputs for each bay type in the case of auto-assignment is
given in the List of Bay Types in the Appendix.
Note: Before selecting a new bay type, make sure that the binary inputs at slots A
and B as well as the binary inputs U C01 to U C08 are configured for
functions from the DEVxx function groups only. Otherwise there will be an
error message, and the new bay type will not be activated.
Note: Before selecting a new bay type, make sure that all binary inputs specified in
the List of Bay types for the selected bay type are actually available in the
device. Otherwise there will be an error message, and the new bay type will
not be activated.
In order to ensure that the device will recognize the input signals, the triggering signals
must persist for at least 30 ms.
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active high mode) or absence (active low mode) of a voltage
shall be interpreted as the logic 1 signal.
Setting the minimum current that must flow in order for the P139 to display a
measured value > 0 (zero suppression).
MEASI: IDC< open circuit 037 191 Fig: 3-27
If the input current falls below the set threshold, the P139 will issue an open
circuit signal.
MEASI: IDC 1 037 150 Fig: 3-27
Setting the input current that will correspond to a linearized value that has
been set accordingly.
Setting the linearized current that will correspond to an input current that
has been set accordingly.
MEASI: Scaled val. IDC,lin1 037 192 Fig: 3-28
Binary outputs
The P139 has output relays for the output of binary signals. The number and connection
schemes for the available output relays are shown in the terminal connection diagrams.
The Address List in the Appendix gives information about the configuration options for all
binary outputs.
The P139 identifies the installed modules during startup. If a given binary I/O module is
not fitted or has fewer output relays than the maximum number possible at this slot, then
the configuration addresses for the missing output relays are automatically hidden in the
menu tree.
The contact data for the all-or-nothing relays permits them to be used either as
command relays or as signal relays. It is important to note that the contact rating of the
binary modules (X) varies (see chapter Technical Data). One signal can also be
assigned simultaneously to several output relays for the purpose of contact
multiplication.
Selecting a new bay type can change the configuration for slots A and B! (Whether
automatic configuration occurs, is defined in the setting M A I N : A u t o - a s s i g n m e n t
I / O .) .Depending on the connection type chosen for the P139 pin type or ring type
cable socket terminals the symbolic slots A and B correspond to the following slots:
Symbolic slot Pin type cable socket Ring type cable socket
terminals terminals
A 06 12
B 07 14
The configuration of output relays for each bay type in the case of auto-assignment is
given in the List of Bay Types in the Appendix.
Note: Before selecting a new bay type, make sure that the output relays at slots A
and B are configured for functions from the DEVxx function groups only.
Otherwise there will be an error message, and the new bay type will not be
activated.
Note: Before selecting a new bay type, make sure that all output relays specified in
the List of Bay types for the selected bay type are actually available in the
device. Otherwise there will be an error message, and the new bay type will
not be activated.
An operating mode can be defined for each output relay. Depending on the selected
operating mode, the output relay will operate in either an energize-on-signal (ES) mode
or a normally-energized (NE) mode and in either a latching or non-latching mode. For
output relays operating in latching mode, the operating mode setting also determines
when latching will be canceled.
Setting the time period for transmission of the selected measured value in
BCD-coded form.
MEASO: Scaled min. val. BCD 037 140 Fig: 3-38
MEASO: Scaled max. val. BCD 037 141 Fig: 3-38
MEASO: BCD-Out min. value 037 142 Fig: 3-38
MEASO: BCD-Out max. value 037 143 Fig: 3-38
Setting the time period for output of the selected measured value.
MEASO: Scaled min. val. A-1 037 104 Fig: 3-40
with:
Mx,min. ... Mx,max. : measured values to be issued
MEASO: Output value 1 037 120 Fig: 3-40
LED indicators
The P139 has a total of 17 LED indicators for parallel display of binary signals. The
Address List in the Appendix gives information about the configuration options for all
LED indicators. LED indicator H 1 is not configurable. It is labeled HEALTHY and
signals the operational readiness of the device (supply voltage present). LED indicators
H 2 and H 3 are also not configurable. H 2 is labeled OUT OF SERVICE and signals a
blocking or malfunction; H 3 is labeled ALARM and signals a warning alarm. LED
indicator H 17 indicates that the user is in the EDIT MODE.
The factory setting for LED indicator H 4 is shown in the terminal connection drawings
included in the documentation or the appendix.
The layout of the LED indicators is shown in the dimensional drawings in chapter 4.
An operating mode can be defined for each LED indicator. Depending on the set
operating mode, the LED indicator will operate in either energize-on-signal (ES) mode
('open-circuit principle') or normally-energized (NE) mode ('closed-circuit principle') and
in either latching or non-latching mode. For LED indicators operating in latching mode,
the operating mode setting also determines when latching will be canceled.
If a customized bay type has been loaded, its bay type No. will be
displayed. If no customized bay type has been loaded, the number '0' will
be displayed.
The user specifies the channel on which each physical variable is recorded.
Canceling a protection
or control function
The user can adapt the device to the requirements of a particular high-voltage system by
including the relevant protection or control functions in the device configuration and
canceling all others (removing them from the device configuration).
The following conditions must be met before canceling a protection or control function:
determination using Canceling function group GFDSS or including it in the configuration. If the
steady-state values function group is cancelled from the configuration, then all associated
settings and signals are hidden.
direction determination Canceling function group TGFD or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'low
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN2.
DEV01: Inform. No., signal 210 035
7.1.3.1 Global
Communication interface 1 COMM1: Command block. USER 003 172 Fig: 3-10
Communication interface 2 COMM2: Command block. USER 103 172 Fig: 3-18
When the test mode user is activated, signals or measured data for PC and
communication interfaces are labeled 'test mode'.
MAIN: Nominal frequ. fnom 010 030 Fig: 3-196,
3-234
Setting the nominal frequency of the protected system.
MAIN: Rotary field 010 049 Fig: 3-116,
3-131,3-139,
Setting the rotary field direction, either clockwise or anticlockwise. 3-220,3-225,
3-252
MAIN: Inom C.T. prim. 010 001 Fig: 3-47,
3-107
Setting the primary nominal current of the main current transformers for
measurement of phase currents.
Setting the primary nominal current of the main current transformer for
measurement of residual current.
MAIN: Vnom V.T. prim. 010 002 Fig: 3-51,
3-107
Setting the primary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
MAIN: VNG,nom V.T. prim. 010 027 Fig: 3-52
Setting the primary nominal current of the NCIT for measurement of residual
current.
MAIN: Vnom prim. NCIT 010 038
Setting the primary nominal voltage of the NCIT for measurement of phase-
to-ground and phase-to-phase voltages.
MAIN: Ph. err. VAG,1 NCIT 010 180
Setting the phase error of the system transformer for each phase-to-ground
voltage in voltage measuring channel 1 of the NCIT.
MAIN: Ph. err. VAG,2 NCIT 010 192
Setting the phase error of the system transformer for each phase-to-ground
voltage (or for the reference voltage Vref, with ASC activated) in voltage
measuring channel 2 of the NCIT.
MAIN: Channel select. NCIT 010 187
Setting the minimum current that must be exceeded so that the measured
operating value of the residual current is displayed.
MAIN: Meas. value rel. V 011 032 Fig: 3-51
Setting the minimum voltage that must be exceeded so that the measured
operating value of the neutral-point displacement voltage is displayed.
MAIN: Meas. val. rel. Vref 011 034 Fig: 3-53
Setting the minimum voltage that must be exceeded so that the measured
operating value of the reference voltage for the automatic synchronism
check is displayed.
MAIN: Op. mode energy cnt. 010 138
Setting the time after which the delayed maximum current display shall
reach 95% of the maximum current IP,max.
Setting the number of signal changes allowed during the chatter monitoring
time before chatter suppression operates.
MAIN: Cmd. dur.long cmd. 221 230 Fig: 3-277,
3-285
Setting the command duration for a long command.
MAIN: Cmd. dur. short cmd. 221 231 Fig: 3-277,
3-285
Setting the command duration for a short command.
MAIN: Inp.asg.interl.deact 221 007 Fig: 3-78
Definition of the binary signal used to switch from remote control to local
control.
MAIN: Auto-assignment I/O 221 065 Fig: 3-45
When a bay type is selected the binary inputs and outputs, required to
control switchgear, are automatically configured with function assignments.
MAIN: Electrical control 221 061 Fig: 3-273
This setting determines whether the binary inputs, that are configured to
control switchgear, will be active with remote control or local control
MAIN: Delay Man.Op.Superv. 221 079
After the delay time period, to be set in this window, has elapsed (with the
signal "Sw. dev. interm. pos." already present and the status signal
continuously absent), the actual switchgear status signal, as obtained from
the respective binary inputs, will be issued. (See also "Processing status
signals from manually operated switchgear")
MAIN: W. ext. cmd. termin. 221 063 Fig: 3-281
This setting determines if bay types, defined for direct motor control, can be
used together with external termination contacts to directly influence the
control process of motor driven switchgear.
MAIN: Inp.assign. tripping 221 010 Fig: 3-77
Selection of the protection function trip command that will be used to form
the CB trip signal.
Definition of the binary signal used by the P139 to signal the 'CB open'
position signal.
MAIN: Sig. asg. CB closed 021 020 Fig: 3-66
Definition of the binary signal used by the P139 to signal the 'CB closed'
position signal.
MAIN: Inp.asg.CB tr.en.ext 221 050 Fig: 3-77
Definition of the binary signal used to carry the CB trip signal of an external
device.
MAIN: Inp.asg. mult.sig. 1 221 051 Fig: 3-68
Parameter subset selection PSS: Control via USER 003 100 Fig: 3-86
The setting of this timer stage is relevant only if parameter subset selection
is carried out via binary signal inputs. Any voltage-free pause that may
occur during selection is bridged. If, after this time period has elapsed, no
binary signal input has yet been set, then the parameter subset selected
from the local control panel shall apply.
Fault data acquisition FT_DA: Line length 010 005 Fig: 3-108
This setting defines the distance in km that the fault locator interprets as
100 % when calculating the line distance to a fault.
FT_DA: Line reactance 010 012 Fig: 3-108
This setting defines the reactance X that the fault locator interprets as
100 % when calculating the line distance to a fault.
Z 0 Z pos
kG =
3 Z pos
Z 0 : zero-sequence impedance
Z pos : positive-sequence impedance
X 0 X pos X pos
k G angle = arc tan arc tan
R0 Rpos Rpos
If the calculated value cannot be set exactly, then a next smaller value
should be set.
FT_DA: Abs. value kG 012 037 Fig: 3-106
Z 0 Z pos
kG =
3 Z pos
Z 0 : zero-sequence impedance
Z pos : positive-sequence impedance
kG =
( X 0 X pos )2 + (R0 Rpos )2
3 Rpos 2 + X pos 2
If the calculated value cannot be set exactly, then a next smaller value
should be set.
FT_DA: Start data acquisit. 010 011 Fig: 3-105
This setting determines at what point during a fault the acquisition of fault
data should take place.
FT_DA: Output fault locat. 010 032 Fig: 3-105
Fault recording FT_RC: Fct. assig. trigger 003 085 Fig: 3-110
This setting defines the signals that will trigger fault recording and fault data
acquisition.
FT_RC: I> 017 065 Fig: 3-110
This setting defines the threshold value of the phase currents that will
trigger fault recording and fault data acquisition.
FT_RC: Pre-fault time 003 078 Fig: 3-112
Setting the time during which data will be recorded before a fault occurs
(pre-fault recording time).
FT_RC: Post-fault time 003 079 Fig: 3-112
Setting the time during which data will be recorded after the end of a fault
(post-fault recording time).
FT_RC: Max. recording time 003 075 Fig: 3-112
Setting the maximum recording time per fault. This includes pre-fault and
post-fault recording times.
Setting the hold time of the "dynamic parameters". After switching to the
"dynamic" thresholds, the latter will remain active in place of the "normal"
thresholds during this period.
MAIN: Syst.IN enabled USER 018 008 Fig: 3-60
This setting defines whether a blocking of the residual current stages should
take place for single-pole or multi-pole phase current startings.
MAIN: Gen. starting mode 017 027 Fig: 3-72
This setting defines whether the triggering of the residual current stages IN>,
Iref,N>, IN>> or Iref>>> as well as the negative-sequence current stage Iref,neg>
should result in the formation of the general starting signal. If the setting is
'W/o start. IN, Ineg' then the associated time delays tIN>, tIref,N>, tIN>>, tIN>>>,
tIref,neg> are automatically excluded from the formation of the trip command.
MAIN: Op. mode rush restr. 017 097 Fig: 3-62
Definite-time overcurrent DTOC: General enable USER 022 075 Fig: 3-113
protection Enable/disable the definite-time overcurrent protection function.
Inverse-time overcurrent IDMT: General enable USER 017 096 Fig: 3-124
protection Enable/disable the inverse-time overcurrent protection function.
Short-circuit direction SCDD: General enable USER 017 070 Fig: 3-136
determination Enable/disable the short-circuit direction determination.
Switch on to fault protection SOTF: General enable USER 011 068 Fig: 3-146
This setting for the operating mode defines that, during the timer period, the
general starting signal will lead to a Trip command ("Trip with starting") or
that the measuring distance of impedance zone 1 will be extended by
D I S T : k z e H S R zone extension factor ("Trip with overreach").
SOTF: Manual close timer 011 060 Fig: 3-146
Protective signaling PSIG: General enable USER 015 004 Fig: 3-147
Auto-reclosing control ARC: General enable USER 015 060 Fig: 3-153
Automatic synchronism check ASC: General enable USER 018 000 Fig: 3-171
Ground fault direction GFDSS: General enable USER 016 060 Fig: 3-182
determination using Enable/disable the ground fault direction determination by steady-state
steady-state values values.
GFDSS: Operating mode 016 090 Fig: 3-182
Setting of the sector angle for measurement in the line side direction.
Setting the sector angle for measurement in the direction of the busbar side.
Setting the operate value of the admittance for the non-directional ground
fault determination (in the admittance evaluation mode).
GFDSS: Correction angle 016 110 Fig: 3-190
Setting the operate delay value of the admittance for the non-directional
ground fault determination (in the admittance evaluation mode).
GFDSS: Release delay Y(N)> 016 115 Fig: 3-194
Setting the release delay value of the admittance for the non-directional
ground fault determination (in the admittance evaluation mode).
Transient ground fault TGFD: General enable USER 016 040 Fig: 3-196
direction determination Enable/disable the transient ground fault direction determination.
TGFD: Evaluation VNG 016 048
Setting the signal buffer time for transient ground fault direction
determination.
Motor protection MP: General enable USER 017 059 Fig: 3-203
Thermal overload protection THERM: General enable USER 022 050 Fig: 3-213
Unbalance protection I2>: General enable USER 018 090 Fig: 3-219
Time-voltage protection V<>: General enable USER 023 030 Fig: 3-221
Setting the evaluation time. The operate conditions must be met for the
duration of the set evaluation time so that a signal is issued.
f<>: Undervolt. block. V< 018 200 Fig: 3-232
Setting the threshold of undervoltage blocking. If the voltage falls below this
threshold, the over-/underfrequency protection function will be blocked.
Power directional protection P<>: General enable USER 014 220 Fig: 3-235
Circuit breaker failure CBF: General enable USER 022 080 Fig: 3-249
protection Enable/disable the circuit breaker failure protection function.
CBF: tCBF 011 067 Fig: 3-249
Setting the operate delay at the conclusion of which the Circuit breaker
failure signal is issued.
Measuring-circuit monitoring MCMON: General enable USER 014 001 Fig: 3-251
Setting the operate value for the voltage trigger Vmin< of measuring circuit
monitoring.
MCMON: Operate delay 017 023 Fig: 3-251
Setting the time delay for "Fuse Failure" monitoring of the reference voltage
Vref.
Limit value monitoring LIMIT: General enable USER 014 010 Fig: 3-254
Setting the operate value of the first overcurrent stage for limit value
monitoring.
LIMIT: I>> 014 020 Fig: 3-254
Setting the operate value of the second overcurrent stage for limit value
monitoring.
LIMIT: tI> 014 031 Fig: 3-254
Setting the operate delay of the first overcurrent stage for limit value
monitoring.
LIMIT: tI>> 014 032 Fig: 3-254
Setting the operate delay of the second overcurrent stage for limit value
monitoring.
LIMIT: I< 014 021 Fig: 3-254
Setting the operate value of the first undercurrent stage for limit value
monitoring.
LIMIT: I<< 014 022 Fig: 3-254
Setting the operate value of the second undercurrent stage for limit value
monitoring.
Setting the operate delay of the first undercurrent stage for limit value
monitoring.
LIMIT: tI<< 014 034 Fig: 3-254
Setting the operate delay of the second undercurrent stage for limit value
monitoring.
LIMIT: VPG> 014 023 Fig: 3-255
Setting the operate value of overvoltage stage VPG> for limit value
monitoring.
LIMIT: VPG>> 014 024 Fig: 3-255
Setting the operate value of overvoltage stage VPG>> for limit value
monitoring.
LIMIT: tVPG> 014 035 Fig: 3-255
Setting the operate delay of overvoltage stage VPG> for limit value
monitoring.
LIMIT: tVPG>> 014 036 Fig: 3-255
Setting the operate delay of overvoltage stage VPG>> for limit value
monitoring.
LIMIT: VPG< 014 025 Fig: 3-255
Setting the operate value of undervoltage stage VPG< for limit value
monitoring.
LIMIT: VPG<< 014 026 Fig: 3-255
Setting the operate value of undervoltage stage VPG<< for limit value
monitoring.
LIMIT: tVPG< 014 037 Fig: 3-255
Setting the operate delay of undervoltage stage VPG< for limit value
monitoring.
LIMIT: tVPG<< 014 038 Fig: 3-255
Setting the operate delay of undervoltage stage VPG<< for limit value
monitoring.
LIMIT: VPP> 014 027 Fig: 3-255
Setting the operate value of overvoltage stage VPP> for limit value
monitoring.
LIMIT: VPP>> 014 028 Fig: 3-255
Setting the operate value of overvoltage stage VPP>> for limit value
monitoring.
LIMIT: tVPP> 014 039 Fig: 3-255
Setting the operate delay of overvoltage stage VPP> for limit value
monitoring.
LIMIT: tVPP>> 014 040 Fig: 3-255
Setting the operate delay of overvoltage stage VPP>> for limit value
monitoring.
LIMIT: VPP< 014 029 Fig: 3-255
Setting the operate value of undervoltage stage VPP< for limit value
monitoring.
Setting the operate value of undervoltage stage VPP<< for limit value
monitoring.
LIMIT: tVPP< 014 041 Fig: 3-255
Setting the operate delay of undervoltage stage VPP< for limit value
monitoring.
LIMIT: tVPP<< 014 042 Fig: 3-255
Setting the operate delay of undervoltage stage VPP<< for limit value
monitoring.
LIMIT: VNG> 014 043 Fig: 3-256
Setting the operate value of overvoltage stage VNG> for limit value
monitoring.
LIMIT: VNG>> 014 044 Fig: 3-256
Setting the operate value of overvoltage stage VNG>> for limit value
monitoring.
LIMIT: tVNG> 014 045 Fig: 3-256
Setting the operate delay of overvoltage stage VNG> for limit value
monitoring.
LIMIT: tVNG>> 014 046 Fig: 3-256
Setting the operate delay of overvoltage stage VNG>> for limit value
monitoring.
LIMIT: Vref> 042 144 Fig: 3-258
Setting the operate value of overvoltage stage Vref> for limit value monitoring.
(Relevant only with circuit board 5V, i.e. ordering option Vnom = 50 to 130 V {5 poles}
for ASC).
LIMIT: Vref>> 042 145 Fig: 3-258
Setting the operate value of overvoltage stage Vref>> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref> 042 148 Fig: 3-258
Setting the operate delay of overvoltage stage Vref> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref>> 042 149 Fig: 3-258
Setting the operate delay of overvoltage stage Vref>> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: Vref< 042 146 Fig: 3-258
Setting the operate value of undervoltage stage Vref< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: Vref<< 042 147 Fig: 3-258
Setting the operate value of undervoltage stage Vref<< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref< 042 150 Fig: 3-258
Setting the operate delay of overvoltage stage Vref< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref<< 042 151 Fig: 3-258
Setting the operate delay of overvoltage stage Vref<< for limit value
monitoring. (Relevant only with circuit board 5V).
Setting the operate value IDC,lin> for monitoring the linearized direct
current.
LIMIT: IDC,lin>> 014 111 Fig: 3-257
Setting the operate value IDC,lin>> for monitoring the linearized direct
current.
LIMIT: tIDC,lin> 014 112 Fig: 3-257
Setting the operate value IDC,lin< for monitoring the linearized direct
current.
LIMIT: IDC,lin<< 014 115 Fig: 3-257
Setting the operate value IDC,lin<< for monitoring the linearized direct
current.
LIMIT: tIDC,lin< 014 116 Fig: 3-257
These settings define the static input conditions for the logic function.
LOGIC: Fct.assignm. outp. 1 030 000 Fig: 3-163,
3-265
LOGIC: Fct.assignm. outp. 2 030 004 Fig: 3-163
LOGIC: Fct.assignm. outp. 3 030 008
These settings define the operating modes for the output timer stages.
These settings assign the function of a binary input signal to the output of
the logic equation.
These settings assign the function of a binary input signal to the output of
the logic equation.
Group assignment for the debouncing time and the chatter suppression.
The logic '1' signal must be available for this minimum time setting so that a
telegram can be sent in the "Start/end signal" mode.
Binary counts COUNT: General enable USER 217 000 Fig: 3-288
Setting the cycle time for the periodic transmission of the counts.
Measured data input MEASI: BackupTempSensor PSx 004 243 004 244 004 245 004 246 Fig: 3-261
Definite-time overcurrent DTOC: Enabled PSx 072 098 073 098 074 098 075 098 Fig: 3-113
protection This setting defines the parameter subset in which definite-time overcurrent
protection is enabled.
DTOC: I> PSx 017 000 073 007 074 007 075 007 Fig: 3-114
Setting the operate value of the first overcurrent stage (phase current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: I> dynamic PSx 017 080 073 032 074 032 075 032 Fig: 3-114
Setting the operate value of the first overcurrent stage in dynamic mode
(phase current stage). This operate value is effective only while the timer
stage M AIN: H ol d- time d yn . par am . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: I>> PSx 017 001 073 008 074 008 075 008 Fig: 3-114
Setting the operate value of the second overcurrent stage (phase current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: I>> dynamic PSx 017 084 073 033 074 033 075 033 Fig: 3-114
Setting the operate value of the second overcurrent stage (phase current
stage).This operate value is effective only while the timer stage MAIN :
Ho ld - ti me d yn . pa ram. is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: I>>> PSx 017 002 073 009 074 009 075 009 Fig: 3-114
Setting the operate value of the third overcurrent stage (phase current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: I>>> dynamic PSx 017 085 073 034 074 034 075 034 Fig: 3-114
Setting the operate value of the third overcurrent stage in dynamic mode
(phase current stage). This operate value is effective only while the timer
stage M AIN: H ol d- time d yn . par am . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: tI> PSx 017 004 073 019 074 019 075 019 Fig: 3-114
DTOC: tI>>> PSx 017 007 073 021 074 021 075 021 Fig: 3-114
Setting the operate value of the first overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: IN> dynamic PSx 017 081 073 035 074 035 075 035 Fig: 3-119
Setting the operate value of the dynamic first overcurrent stage (residual
current stage). This operate value is effective only while the timer stage
M A IN : H o ld - t i me d y n . p ar a m . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: IN>> PSx 017 009 073 016 074 016 075 016 Fig: 3-119
Setting the operate value of the second overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: IN>> dynamic PSx 017 086 073 036 074 036 075 036 Fig: 3-119
Setting the operate value of the second overcurrent stage in dynamic mode
(residual current stage). This operate value is effective only while the timer
stage M AIN: H ol d- time d yn . par am . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: IN>>> PSx 017 018 073 017 074 017 075 017 Fig: 3-119
Setting the operate value of the third overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: IN>>> dynamic PSx 017 087 073 037 074 037 075 037 Fig: 3-119
Setting the operate value of the dynamic third overcurrent stage (residual
current stage). This operate value is effective only while the timer stage
M A IN : H o ld - t i me d y n . p ar a m . is elapsing.
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Technical Data).
DTOC: tIN> PSx 017 008 073 027 074 027 075 027 Fig: 3-119
Setting the operate delay of the first overcurrent stage (residual current
stage).
DTOC: tIN>> PSx 017 010 073 028 074 028 075 028 Fig: 3-119
Setting the operate delay of the second overcurrent stage (residual current
stage).
DTOC: tIN>>> PSx 017 019 073 029 074 029 075 029 Fig: 3-119
Setting the operate delay of the third overcurrent stage (residual current
stage).
DTOC: Puls.prol.IN>,intPSx 017 055 073 042 074 042 075 042 Fig: 3-119
Setting the pulse prolongation time of the hold-time logic for intermittent
ground faults.
DTOC: tIN,interm. PSx 017 056 073 038 074 038 075 038 Fig: 3-119
Setting the tripping time of the hold-time logic for intermittent ground faults.
DTOC: Hold-t. tIN>,intmPSx 017 057 073 039 074 039 075 039 Fig: 3-119
Inverse-time overcurrent IDMT: Enabled PSx 072 070 073 070 074 070 075 070 Fig: 3-124
protection This setting defines the parameter subset in which IDMT protection is
enabled.
IDMT: Iref,P PSx 072 050 073 050 074 050 075 050 Fig: 3-129
IDMT: Iref,P dynamic PSx 072 003 073 003 074 003 075 003 Fig: 3-129
Setting the reference current in dynamic mode (phase current system). This
operate value is effective only while the timer stage M AIN : Ho ld -ti me
d yn . pa ram. is elapsing.
IDMT: Character.type P PSx 072 056 073 056 074 056 075 056 Fig: 3-129
Setting the factor kt,P of the starting characteristic (phase current system).
IDMT: Min. trip time P PSx 072 077 073 077 074 077 075 077 Fig: 3-129
Setting the minimum trip time (phase current system). As a rule, this value
should be set as for the first DTOC stage (I>).
IDMT: Hold time P PSx 072 071 073 071 074 071 075 071 Fig: 3-129
Setting the holding time for intermittent short circuits (phase current
system).
IDMT: Release P PSx 072 059 073 059 074 059 075 059 Fig: 3-129
IDMT: Characteristic N PSx 072 058 073 058 074 058 075 058 Fig: 3-133
Setting the factor kt,N of the starting characteristic (residual current system).
IDMT: Min. trip time N PSx 072 079 073 079 074 079 075 079 Fig: 3-133
Setting the minimum trip time (residual current system). As a rule, this
value should be set as for the first DTOC stage (IN>).
IDMT: Hold time N PSx 072 073 073 073 074 073 075 073 Fig: 3-133
Setting the holding time for intermittent short circuits (residual current
system).
IDMT: Release N PSx 072 061 073 061 074 061 075 061 Fig: 3-133
Short-circuit direction SCDD: Enabled PSx 076 235 077 235 078 235 079 235 Fig: 3-136
determination This setting defines the parameter subset in which short-circuit direction
determination is enabled.
SCDD: Trip bias PSx 017 074 077 236 078 236 079 236 Fig: 3-140
This setting for the measuring direction determines whether a tI> trip signal
in the DTOC phase current stage will be issued for forward, backward or
non-directional fault decisions. If the ARC is enabled and has been set
accordingly then a starting will trigger the associated ARC tripping time.
SCDD: Direction tI>> PSx 017 072 077 238 078 238 079 238 Fig: 3-140
This setting for the measuring direction determines whether a tI>> trip signal
in the DTOC phase current stage will be issued for forward, backward or
non-directional fault decisions. If the ARC is enabled and has been set
accordingly then a starting will trigger the associated ARC tripping time.
SCDD: Direct. tIref,P> PSx 017 066 077 239 078 239 079 239 Fig: 3-140
This setting for the measuring direction determines whether a tIref,P> trip
signal in the IDMT phase current stage will be issued for forward, backward
or non-directional fault decisions. If the ARC is enabled and has been set
accordingly then a starting will trigger the associated ARC tripping time.
SCDD: Direction tIN> PSx 017 073 077 240 078 240 079 240 Fig: 3-144
This setting for the measuring direction determines whether a tIN> trip
signal in the DTOC residual current stage will be issued for forward,
backward or non-directional fault decisions. If the ARC is enabled and has
been set accordingly then a starting will trigger the associated ARC tripping
time.
SCDD: Direction tIN>> PSx 017 075 077 241 078 241 079 241 Fig: 3-144
This setting for the measuring direction determines whether a tIN>> trip
signal in the DTOC residual current stage will be issued for forward,
backward or non-directional fault decisions. If the ARC is enabled and has
been set accordingly then a starting will trigger the associated ARC tripping
time.
SCDD: Direct. tIref,N> PSx 017 067 077 242 078 242 079 242 Fig: 3-144
This setting for the measuring direction determines whether a tIref,N> trip
signal in the IDMT residual current stage will be issued for forward,
backward or non-directional fault decisions. If the ARC is enabled and has
been set accordingly then a starting will trigger the associated ARC tripping
time.
SCDD: Charact. angle G PSx 017 076 077 243 078 243 079 243 Fig: 3-143
Setting the operate value VNG>. This setting value is an enabling criterion
of the base point release of short-circuit direction determination.
In choosing this setting, the set nominal voltage M AIN : VNG ,nom V.T .
sec . should be taken into account.
SCDD: Block. bias G PSx 017 078 077 245 078 245 079 245 Fig: 3-144
This setting defines whether the trip bias of the residual current stage
should be blocked in the event of a phase current starting.
Protective signaling PSIG: Enabled PSx 015 014 015 015 015 016 015 017 Fig: 3-147
Auto-reclosing control ARC: Enabled PSx 015 046 015 047 015 048 015 049 Fig: 3-153
This setting defines whether the CB closed position will be scanned or not.
If the setting is 'With', a binary signal input must be configured accordingly.
ARC: Operating mode PSx 015 051 024 025 024 085 025 045 Fig: 3-152
The operating mode setting defines which of the following reclosure types is
permitted.
" TDR only
" HSR or TDR
" Test HSR only
ARC: Operative time PSx 015 066 024 035 024 095 025 055 Fig: 3-164,
3-166
Setting the operative time 1.
ARC: HSR trip.time GS PSx 015 038 024 100 024 150 025 100 Fig: 3-160
Setting the HSR tripping time and start via a general starting condition.
ARC: HSR trip.time I> PSx 015 072 024 040 025 000 025 060 Fig: 3-156,
3-166
Setting the HSR tripping time and start via a phase current starting in the
first DTOC overcurrent stage.
ARC: HSR trip.time I>>PSx 015 074 024 101 024 151 025 101 Fig: 3-156
Setting the HSR tripping time and start via a phase current starting in the
second DTOC overcurrent stage.
ARC: HSRtrip.time I>>>PSx 014 096 024 102 024 152 025 102 Fig: 3-156
Setting the HSR tripping time and start via a phase current starting in the
third DTOC overcurrent stage.
ARC: HSR trip.time IN>PSx 015 076 024 103 024 153 025 103 Fig: 3-156
Setting the HSR tripping time and start via a residual current starting in the
first DTOC overcurrent stage.
ARC: HSRtrip.time IN>>PSx 015 031 024 104 024 154 025 104 Fig: 3-156
Setting the HSR tripping time and start via a residual current starting in the
second DTOC overcurrent stage.
ARC: HSRtrip.t. IN>>> PSx 014 098 024 105 024 155 025 105 Fig: 3-156
Setting the HSR tripping time and start via a residual current starting in the
third DTOC overcurrent stage.
ARC: HSRtrip.t. kIref>PSx 015 094 024 106 024 156 025 106 Fig: 3-158
Setting the HSR tripping time and start via a starting in the IDMT phase
current system.
ARC: HSRtrip.t.kINref>PSx 015 096 024 107 024 157 025 107 Fig: 3-158
Setting the HSR tripping time and start via a starting in the IDMT residual
current system.
ARC: HSRtrip.t. Ineg> PSx 015 034 024 108 024 158 025 108 Fig: 3-158
Setting the HSR tripping time and start via a starting in the IDMT negative-
sequence current system.
ARC: HSR trip t.GFDSS PSx 015 078 024 109 024 159 025 109 Fig: 3-159
Setting the HSR tripping time and start via ground fault direction
determination using steady-state values.
ARC: HSRtrip.t. LOGIC PSx 015 098 024 110 024 160 025 110 Fig: 3-161
Setting the HSR tripping time and start via programmable logic.
ARC: HSR block.f. I>>>PSx 015 080 024 111 024 161 025 111 Fig: 3-162
Setting the TDR tripping time and start via a general starting condition.
ARC: TDR trip.time I> PSx 015 073 024 041 025 001 025 061 Fig: 3-157
Setting the TDR tripping time and start via a phase current starting in the
first DTOC overcurrent stage.
ARC: TDR trip.time I>>PSx 015 075 024 113 024 163 025 113 Fig: 3-157
Setting the TDR tripping time and start via a phase current starting in the
second DTOC overcurrent stage.
ARC: TDRtrip.time I>>>PSx 014 097 024 114 024 164 025 114 Fig: 3-157
Setting the TDR tripping time and start via a phase current starting in the
third DTOC overcurrent stage.
ARC: TDR trip.time IN>PSx 015 077 024 115 024 165 025 115 Fig: 3-157
Setting the TDR tripping time and start via a residual current starting in the
first DTOC overcurrent stage.
ARC: TDRtrip.time IN>>PSx 015 032 024 116 024 166 025 116 Fig: 3-157
Setting the TDR tripping time and start via a residual current starting in the
second DTOC overcurrent stage.
ARC: TDRtrip.t. IN>>> PSx 014 099 024 117 024 167 025 117 Fig: 3-157
Setting the TDR tripping time and start via a residual current starting in the
third DTOC overcurrent stage.
ARC: TDRtrip.t. kIref>PSx 015 095 024 118 024 168 025 118 Fig: 3-158
Setting the TDR tripping time and start via a starting in the IDMT phase
current system.
ARC: TDRtrip.t.kINref>PSx 015 097 024 119 024 169 025 119 Fig: 3-158
Setting the TDR tripping time and start via a starting in the IDMT residual
current system.
ARC: TDRtrip.t. Ineg> PSx 015 035 024 120 024 170 025 120 Fig: 3-158
Setting the TDR tripping time and start via a starting in the IDMT negative-
sequence current system.
ARC: TDR trip t.GFDSS PSx 015 079 024 121 024 171 025 121 Fig: 3-159
Setting the TDR tripping time and start via ground fault direction
determination using steady-state values.
ARC: TDRtrip.t. LOGIC PSx 015 099 024 122 024 172 025 122 Fig: 3-161
Setting the TDR tripping time and start via programmable logic.
ARC: TDR dead time PSx 015 057 024 031 024 091 025 051 Fig: 3-164
Setting the time that will elapse before the ARC will be ready again after
blocking by a binary signal input.
Automatic synchronism check ASC: Enabled PSx 018 020 018 021 018 022 018 023 Fig: 3-171
This setting defines the function group DEVxx that will control the circuit
breaker.
ASC: System integrat. PSx 037 135 037 136 037 137 037 138 Fig: 3-179
This setting defines whether ASC will operate in the mode automatic
synchron. check or automatic synchr. control.
ASC: Active for HSR PSx 018 001 077 030 078 030 079 030 Fig: 3-172
This setting defines whether reclosing after a three-pole HSR will occur only
after being enabled by ASC.
ASC: Active for TDR PSx 018 002 077 031 078 031 079 031 Fig: 3-172
This setting defines whether reclosing after a three-pole TDR will occur only
after being enabled by ASC.
ASC: Clos.rej.w.block PSx 018 003 077 032 078 032 079 032 Fig: 3-172
Criteria for a close enable are defined by setting the operating mode.
ASC: Op.mode volt.chk.PSx 018 029 018 030 018 031 018 032 Fig: 3-175
This setting defines the logic linking of trigger decisions for a voltage
controlled close enable.
ASC: V> volt.check PSx 026 017 077 043 078 043 079 043 Fig: 3-175
Setting the voltage threshold that the phase-to-ground voltages and the
reference voltage must exceed so that they are recognized as "Voltage
showing".
ASC: V< volt. check PSx 018 017 077 040 078 040 079 040 Fig: 3-175
Setting the voltage threshold that the phase-to-ground voltages and the
reference voltage must fall below so that they are recognized as "Voltage
showing".
Setting the operate delay value to define the minimum time period during
which synchronism conditions must be met so that the close enable of the
ASC is effected.
Motor protection MP: Enabled PSx 024 148 024 147 024 197 025 147 Fig: 3-203
Pnom
I nom , motor =
3 U nom cos
The reference current is the nominal motor current as projected onto the
transformer secondary side and is thus calculated as follows:
I ref I nom , motor Tnom
=
I nom ,( relay ) I nom,( relay )
Example:
Motor and System Data:
Nominal motor voltage Vnom: 10 Kv
Efficiency : 96.6 %
MP: Factor kP PSx 017 040 024 132 024 182 025 132 Fig: 3-204
I therm, motor
k=
I nom , motor
Example:
Motor Data:
Setting the operate delay for the operational status determination 'machine
starting up'. Usually, the default setting can be retained.
MP: Character.type P PSx 017 029 024 135 024 185 025 135 Fig: 3-209
MP: t6Iref PSx 017 041 024 136 024 186 025 136 Fig: 3-209
This Setting the overload tripping time t6Iref is determined from the cold
machine data, using Iref = Inom,motor.
I ref = I nom , motor
Based on the setting value thus determined, the tripping time for a warm
machine is now defined as follows.
For the reciprocally squared characteristic we set:
36
t = (1 0.2 ) t6 I ref 2
I startup
I
nom , motor
18 s at Vnom
MP: Tau after st.-up PSx 018 042 024 137 024 187 025 137 Fig: 3-209
Setting the heat dispersion time constant after startup. Usually, the default
setting can be retained.
MP: Tau mach.running PSx 017 088 024 138 024 188 025 138 Fig: 3-209
MP: Tau mach.stopped PSx 017 089 024 139 024 189 025 139 Fig: 3-209
This setting defines whether motor protection will be operated together with
thermal overload protection (THERM).
MP: St.-up time tStUpPSx 017 043 024 143 024 193 025 143 Fig: 3-209
MP: Blocking time tE PSx 017 044 024 144 024 194 025 144 Fig: 3-209
Setting the operate value of the minimum current stage of the underload
protection function of motor protection.
MP: tI< PSx 017 050 024 146 024 196 025 146 Fig: 3-212
Setting the operate delay of the minimum current stage of the underload
protection function of motor protection.
Thermal overload protection THERM: Enabled PSx 072 175 073 175 074 175 075 175 Fig: 3-213
Selecting the backup temperature sensor for the parameter subset PSx.
THERM: Iref PSx 072 179 073 179 074 179 075 179 Fig: 3-217
Setting the thermal time constants of the protected object with current flow
(Ibl: base line current).
THERM: Tim.const.2,<Ibl PSx 072 188 073 188 074 188 075 188 Fig: 3-217
Setting the thermal time constants of the protected object without current
flow (Ibl: base line current).
Note:
This setting option is only relevant when machines are running. In all other
cases, time constant 2 must be set equal to time constant 1.
THERM: Max.perm.obj.tmp.PSx 072 182 073 182 074 182 075 182 Fig: 3-217
Setting the coolant temperature to be used for calculation of the trip time if
coolant temperature is not measured.
THERM: Bl. f. CTA fault PSx 072 178 073 178 074 178 075 178 Fig: 3-215,
3-216
This setting specifies whether the thermal overload protection function will
be blocked in the event of faulty coolant temperature acquisition.
THERM: Rel. O/T warning PSx 072 184 073 184 074 184 075 184 Fig: 3-217
A warning will be given in advance of the trip. The time difference between
the warning time and the trip time is set here.
Unbalance protection I2>: Enabled PSx 018 220 018 221 018 222 018 223 Fig: 3-219
Time-voltage protection V<>: Enabled PSx 076 246 077 246 078 246 079 246 Fig: 3-221
Setting the operate delay of overvoltage stage V> when all three trigger
stages are activated.
V<>: tV>> PSx 076 006 077 006 078 006 079 006 Fig: 3-223
V<>: tV< 3-pole PSx 076 028 077 028 078 028 079 028 Fig: 3-224
Setting the operate delay of undervoltage stage V< when all three trigger
stages are activated.
V<>: tV<< PSx 076 010 077 010 078 010 079 010 Fig: 3-224
Setting the time limit of the signals generated by the undervoltage stages.
V<>: Hyst. V<> meas. PSx 076 048 077 048 078 048 079 048 Fig: 3-223
V<>: Hyst. V<> deduc. PSx 076 049 077 049 078 049 079 049 Fig: 3-226
Setting the hysteresis of the trigger stages for monitoring derived voltages
such as Vneg and VNG.
Over-/underfrequency f<>: Enabled PSx 018 196 018 197 018 198 018 199 Fig: 3-230
protection This setting defines the parameter subset in which over-/underfrequency
protection is enabled.
f<>: Oper. mode f1 PSx 018 120 018 121 018 122 018 123 Fig: 3-234
f<>: Oper. mode f2 PSx 018 144 018 145 018 146 018 147
f<>: Oper. mode f3 PSx 018 168 018 169 018 170 018 171
f<>: Oper. mode f4 PSx 018 192 018 193 018 194 018 195
f<>: f3 PSx 018 148 018 149 018 150 018 151
f<>: f4 PSx 018 172 018 173 018 174 018 175
f<>: tf3 PSx 018 152 018 153 018 154 018 155
f<>: tf4 PSx 018 176 018 177 018 178 018 179
f<>: df3/dt PSx 018 156 018 157 018 158 018 159
f<>: df4/dt PSx 018 180 018 181 018 182 018 183
f<>: Delta f3 PSx 018 160 018 161 018 162 018 163
f<>: Delta f4 PSx 018 184 018 185 018 186 018 187
f<>: Delta t1 PSx 018 116 018 117 018 118 018 119 Fig: 3-234
f<>: Delta t2 PSx 018 140 018 141 018 142 018 143
f<>: Delta t3 PSx 018 164 018 165 018 166 018 167
f<>: Delta t4 PSx 018 188 018 189 018 190 018 191
Power directional protection P<>: Enabled PSx 014 252 014 253 014 254 014 255 Fig: 3-235
This setting of the measuring direction determines whether a P> trip signal
will be issued for forward, backward or non-directional fault decisions.
P<>: Diseng. ratio P> PSx 017 124 017 125 017 126 017 127 Fig: 3-237
Setting the disengaging ratio of the operate value P> for the active power.
P<>: P>> PSx 017 140 017 141 017 142 017 143 Fig: 3-237
This setting of the measuring direction determines whether a P>> trip signal
will be issued for forward, backward or non-directional fault decisions.
P<>: Diseng. ratio P>>PSx 017 144 017 145 017 146 017 147 Fig: 3-237
Setting the disengaging ratio of the operate value P>> for the active power.
P<>: Q> PSx 017 160 017 161 017 162 017 163 Fig: 3-239
This setting of the measuring direction determines whether a Q> trip signal
will be issued for forward, backward or non-directional fault decisions.
P<>: Diseng. ratio Q> PSx 017 164 017 165 017 166 017 167 Fig: 3-239
Setting the disengaging ratio of the operate value Q> of the reactive power.
P<>: Q>> PSx 017 180 017 181 017 182 017 183 Fig: 3-239
This setting of the measuring direction determines whether a Q>> trip signal
will be issued for forward, backward or non-directional fault decisions.
P<>: Diseng. ratio Q>>PSx 017 184 017 185 017 186 017 187 Fig: 3-239
Setting the disengaging ratio of the operate value Q>> of the reactive
power.
P<>: P< PSx 017 030 017 031 017 032 017 033 Fig: 3-241
This setting of the measuring direction determines whether a P< trip signal
will be issued for forward, backward or non-directional fault decisions.
P<>: Diseng. ratio P< PSx 017 034 017 035 017 036 017 037 Fig: 3-241
Setting the disengaging ratio of the operate value P< for the active power.
P<>: P<< PSx 017 234 017 235 017 236 017 237 Fig: 3-241
This setting of the measuring direction determines whether a P<< trip signal
will be issued for forward, backward or non-directional fault decisions.
P<>: Diseng.ratio P<< PSx 017 238 017 239 017 240 017 241 Fig: 3-241
Setting the disengaging ratio of the operate value P<< for the active power.
P<>: Q< PSx 018 035 018 036 018 037 018 038 Fig: 3-244
P<>: Release delay Q< PSx 018 056 018 057 018 058 018 059 Fig: 3-244,
3-246
Setting the release delay of stage Q<.
P<>: Direction Q< PSx 018 081 018 082 018 083 018 084 Fig: 3-245
This setting of the measuring direction determines whether a Q< trip signal
will be issued for forward, backward or non-directional fault decisions.
P<>: Diseng. ratio Q< PSx 018 044 018 045 018 046 018 047 Fig: 3-244
Setting the disengaging ratio of the operate value Q< of the reactive power.
P<>: Q<< PSx 018 085 018 086 018 087 018 088 Fig: 3-244
This setting of the measuring direction determines whether a Q<< trip signal
will be issued for forward, backward or non-directional fault decisions.
P<>: Diseng.ratio Q<< PSx 018 095 018 096 018 097 018 098 Fig: 3-244
Setting the disengaging ratio of the operate value Q<< of the reactive
power.
P<>: tTransient pulse PSx 018 246 018 247 018 248 018 249 Fig: 3-241,
3-243,3-244,
Setting the time limit of the signals generated by the stages P<, P<<, Q< 3-246
and Q<< after the respective operate delay has elapsed.
7.1.3.4 Control
Selecting the bay interlocking function from the local control panel.
MAIN: SI active USER 221 002 Fig: 3-78
Selecting the station interlocking function from the local control panel.
MAIN: Inp.asg. fct.block.1 221 014 Fig: 3-63
MAIN: Inp.asg. fct.block.2 221 022 Fig: 3-63
Setting the permissible motor drive operations within the time interval
defined at M A I N : M o n . t i m e m o t . d r i v e s .
MAIN: Mon.time mot.drives 221 026 Fig: 3-80
External devices 01 to 10 DEV01: Designat. ext. dev. 210 000 Fig: 3-2
DEV02: Designat. ext. dev. 210 050
Note: This setting is only active if the external device designations are
displayed on the Bay Panel.
Assigning the external device to one of eight groups for debouncing and
chatter suppression.
DEV01: Interm. pos. suppr. 210 012 Fig: 3-272,
This setting determines whether the actual status will be signaled with a 5 s
delay after the 'Faulty position' signal is issued.
DEV01: Oper. mode cmd. 210 024 Fig: 3-277
DEV02: Oper. mode cmd. 210 074
Select the operating mode of the command from long command, short
command or time control.
DEV01: Inp.asg. sw.tr. plug 210 014 Fig: 3-272,
3-278
DEV02: Inp.asg. sw.tr. plug 210 064
This setting specifies whether the circuit breaker will be opened by general
trip command 1 of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as circuit breakers. This definition is included in the bay type
definitions.
DEV01: With gen. trip cmd.2 210 022 Fig: 3-276
This setting specifies whether the circuit breaker will be opened by general
trip command 2 of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as circuit breakers. This definition is included in the bay type
definitions.
DEV01: With close cmd./prot 210 023 Fig: 3-276
This setting specifies whether the circuit breaker will be closed by the "close
command" of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as circuit breakers. This definition is included in the bay type
definitions.
This setting defines the binary signal that will be used as the control signal
to move the switchgear unit to the open position.
Note: Only signals that are defined in the DEVxx function groups can
be selected.
DEV01: Inp.asg.el.ctr.close 210 020 Fig: 3-273
This setting defines the binary signal that will be used as the control signal
to move the switchgear unit to the 'Closed' position.
Note: Only signals that are defined in the DEVxx function groups can
be selected.
DEV01: Inp. asg. end Open 210 015 Fig: 3-281
DEV02: Inp. asg. end Open 210 065
This setting defines the binary signal that will be used to terminate the
'Open' command.
Note: This setting is only visible (active) for bay types that are defined
for 'direct motor control.
This setting defines the binary signal that will be used to terminate the
'Close' command.
Note: This setting is only visible (active) for bay types that are defined
for 'direct motor control.
DEV01: Open w/o stat.interl 210 025 Fig: 3-275
DEV02: Open w/o stat.interl 210 075
This setting defines which output will issue the 'Open' enable to the
interlocking logic when there is 'bay interlock with substation interlock'.
Note:
The interlock conditions for bay interlock with station interlock are included
in the bay type definitions (see List of Bay Types in the Appendix). If the
interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
DEV01: Fct.assig.BIwSI clos 210 040 Fig: 3-274
DEV02: Fct.assig.BIwSI clos 210 090
This setting defines which output will issue the 'Close' enable to the
interlocking logic when there is 'bay interlock with substation interlock'.
Note:
The interlock conditions for bay interlock with station interlock are included
in the bay type definitions (see List of Bay Types in the Appendix). If the
interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
This setting defines which output will issue the 'Open' enable to the
interlocking logic when there is 'bay interlock without substation interlock'.
Note:
The interlock conditions for bay interlock with station interlock are included
in the bay type definitions (see List of Bay Types in the Appendix). If the
interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
DEV01: Fct.asg.BI w/o SI cl 210 042 Fig: 3-274
This setting defines which output will issue the 'Close' enable to the
interlocking logic when there is 'bay interlock without substation interlock'.
Note:
The interlock conditions for bay interlock with station interlock are included
in the bay type definitions (see List of Bay Types in the Appendix). If the
interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
7.2.1 General
The P139 was subjected to risk analysis based on the DIN V 19 250 standard of May
1994 (on basic safety considerations for measuring and protection relays) as well as
DIN V 19 251 of February 1995 (on measuring and protection relays, specifications and
measures for their fail-safe functioning) and owing to a lack of more specific standards
also based on DIN V VDE 0801 (on computers in safety systems).
Based on this risk analysis involving the examination of extensive measures for
prevention and management of malfunction, the P139 has been classified in
specifications class 3. According to NAMUR NE 31 (NAMUR: German committee on
standards for measuring and control engineering), specifications class 3 corresponds to
risk area 1. For this risk area, a protection device of single-channel design with alarm
signal and/or normally-energized arrangement (closed-circuit principle) will normally
suffice. IIn special cases, a requirement for a higher specifications class can be met by
a customized 1 out of 2 or 2 out of 3 circuit.
By connection and configuration of the output relay M AIN : Blocke d /fau l ty , the
increased-safety machine can be switched off immediately or, alternatively, an alarm
signal can be given for delayed switch-off based on an assessment of the operational
conditions by trained staff.
For the P139 to operate in a restrictive safety-oriented mode under all operational
conditions, the output relays must be operated in a normally-energized arrangement
('closed-circuit principle'). In this arrangement, the relevant output relay is energized
during normal operation and drops out in the event of an activation of the associated
function or in the event of a malfunction.
1
See the Chapter on Local Control for notes on the folders.
7-108 P139-304-405/-406/-407-605 // AFSV.12.09450.D / P139/EN M/B33
7 Settings
(continued)
During device startup and during P139 operation, cyclic self-monitoring tests are run. In
the event of a positive test result, a specified monitoring signal will be issued and stored
in a non-volatile memory the monitoring signal memory (see Chapter
Troubleshooting). A listing of all possible entries in this monitoring signal memory is
given in the address list (see Appendix). Monitoring signals prompted by a serious
hardware or software fault in the unit are always entered in the monitoring signal
memory. The entry of monitoring signals of lesser significance into the monitoring signal
memory is optional. The user can select this option by setting an 'm out of n' parameter.
The blocking of the protection device is governed by similar principles, that is, signals
prompted by a serious hardware or software fault in the unit always lead to a blocking of
the protection unit. The assignment of signals of lesser significance to the signal
M AIN : Blocke d /fau l ty by an m out of n parameter (M AIN : F c t . a s s i g n m .
F a u l t ) is optional.
For safety-oriented operation, the Warning can be configured onto an output relay as in
the following example.
The P139 generates a large number of signals, processes binary input signals, and
acquires measured data during fault-free operation of the protected object as well as
fault-related data. A number of counters are available for statistical purposes. This
information can be read out from the integrated local control panel.
All this information can be found in the Operation and Events folders in the menu tree.
8.1 Operation
While the hold time is running, the loop back test results can be checked by
reading out these values.
Measured data input MEASI: Current IDC 004 134 Fig: 3-27
Measured data output MEASO: Current A-1 005 100 Fig: 3-40
MEASO: Current A-2 005 099
Date display.
Note: The date can also be set here.
MAIN: Time of day 003 091 Fig: 3-82
Display of the updated value for the residual current as a primary quantity.
MAIN: Volt. VPG,max prim. 008 042 Fig: 3-51
Display of the updated value for phase-to-ground voltage A-G referred to Vnom.
MAIN: Voltage B-G p.u. 006 043 Fig: 3-51
Display of the updated value for phase-to-ground voltage B-G referred to Vnom.
MAIN: Voltage C-G p.u. 007 043 Fig: 3-51
Display of the updated value for phase-to-ground voltage C-G referred to Vnom.
MAIN: Volt. (VPG)/3 p.u. 005 013 Fig: 3-51
Display of the updated value for phase-to-phase voltage A-B referred to Vnom.
MAIN: Voltage B-C p.u. 006 045 Fig: 3-51
Display of the updated value for phase-to-phase voltage B-C referred to Vnom.
MAIN: Voltage C-A p.u. 007 045 Fig: 3-51
Display of the updated value for phase-to-phase voltage C-A referred to Vnom.
MAIN: Appar. power S p.u. 005 026 Fig: 3-54
Ground fault direction GFDSS: Curr. IN,act p.u. 004 045 Fig: 3-187
determination using Display of the updated value for the active component of residual current
steady-state values referred to IN,nom.
GFDSS: Curr. IN,reac p.u. 004 046 Fig: 3-187
Display of the updated value for the reactive component of residual current
referred to IN,nom.
GFDSS: Curr. IN filt. p.u. 004 047 Fig: 3-188
Display of the updated value for the harmonic content of residual current
referred to IN,nom. This display is only active when the steady-state current
evaluation mode of the GFDSS ground fault direction determination function
is enabled.
GFDSS: Admitt. Y(N) p.u. 004 191 Fig: 3-193
Thermal overload protection THERM: Status THERM replica 004 016 Fig: 3-217
! "High": Energized.
This display appears regardless of the setting for the binary signal input
mode.
This display appears regardless of the operating mode set for the output
relay.
Communication interface 1 COMM1: Command block. EXT 003 173 Fig: 3-10
COMM1: Sig./meas. block EXT 037 074 Fig: 3-11,
3-12,3-13
COMM1: Command blocking 003 174 Fig: 3-10
COMM1: Sig./meas.val.block. 037 075 Fig: 3-11,
3-12,3-13
COMM1: IEC 870-5-103 003 219 Fig: 3-11
COMM1: IEC 870-5-101 003 218 Fig: 3-12
COMM1: IEC 870-5,ILS 003 221 Fig: 3-13
COMM1: MODBUS 003 223 Fig: 3-14
COMM1: DNP3 003 230 Fig: 3-15
COMM1: COURIER 103 041 Fig: 3-16
Binary outputs OUTP: Block outp.rel. EXT 040 014 Fig: 3-32
OUTP: Reset latch. EXT 040 015 Fig: 3-32
OUTP: Outp. relays blocked 021 015 Fig: 3-32
OUTP: Latching reset 040 088 Fig: 3-32
Main function MAIN: Enable protect. EXT 003 027 Fig: 3-59
MAIN: Disable protect. EXT 003 026 Fig: 3-59
MAIN: System IN enable EXT 040 130 Fig: 3-60
MAIN: Syst. IN disable EXT 040 131 Fig: 3-60
MAIN: Test mode EXT 037 070 Fig: 3-85
MAIN: Blocking 1 EXT 040 060 Fig: 3-64
MAIN: Blocking 2 EXT 040 061 Fig: 3-64
MAIN: Reset latch.trip EXT 040 138 Fig: 3-74
MAIN: Trip cmd. block. EXT 036 045 Fig: 3-74
MAIN: M.c.b. trip V EXT 004 061 Fig: 3-172
MAIN: M.c.b. trip Vref EXT 036 086 Fig: 3-172
MAIN: Switch dyn.param.EXT 036 033 Fig: 3-61
MAIN: CB closed sig. EXT 036 051 Fig: 3-66,
3-67,3-155,
3-252,3-253
MAIN: Manual close EXT 036 047 Fig: 3-146
MAIN: Man. trip cmd. EXT 037 018 Fig: 3-75
MAIN: Man.cl.cmd.enabl.EXT 041 023 Fig: 3-67
MAIN: Man. close cmd. EXT 041 022 Fig: 3-67
MAIN: Reset indicat. EXT 065 001 Fig: 3-83
MAIN: Min-pulse clock EXT 060 060 Fig: 3-82
MAIN: Ch.1 an. NCIT on EXT 010 188
Parameter subset selection PSS: Control via user EXT 036 101 Fig: 3-86
PSS: Activate PS 1 EXT 065 002 Fig: 3-86
PSS: Activate PS 2 EXT 065 003 Fig: 3-86
PSS: Activate PS 3 EXT 065 004 Fig: 3-86
PSS: Activate PS 4 EXT 065 005 Fig: 3-86
PSS: Control via user 036 102 Fig: 3-86
PSS: Ext.sel.param.subset 003 061 Fig: 3-86
PSS: PS 1 activated ext. 036 094 Fig: 3-86
PSS: PS 2 activated ext. 036 095 Fig: 3-86
PSS: PS 3 activated ext. 036 096 Fig: 3-86
PSS: PS 4 activated ext. 036 097 Fig: 3-86
PSS: Actual param. subset 003 062 Fig: 3-86
PSS: PS 1 active 036 090 Fig: 3-86
PSS: PS 2 active 036 091 Fig: 3-86
PSS: PS 3 active 036 092 Fig: 3-86
PSS: PS 4 active 036 093 Fig: 3-86
Ground fault recording GF_RC: Record. in progress 035 005 Fig: 3-102
GF_RC: GF memory overflow 035 006 Fig: 3-103
Fault data acquisition FT_DA: Trigger EXT 036 088 Fig: 3-105
Definite-time overcurrent DTOC: Blocking tI> EXT 041 060 Fig: 3-114
protection DTOC: Blocking tI>> EXT 041 061 Fig: 3-114
DTOC: Blocking tI>>> EXT 041 062 Fig: 3-114
DTOC: Block. tIneg> EXT 036 141 Fig: 3-116
DTOC: Block. tIneg>> EXT 036 142 Fig: 3-116
DTOC: Block. tIneg>>> EXT 036 143 Fig: 3-116
DTOC: Blocking tIN> EXT 041 063 Fig: 3-119
DTOC: Blocking tIN>> EXT 041 064 Fig: 3-119
DTOC: Blocking tIN>>> EXT 041 065 Fig: 3-119
DTOC: Enabled 040 120 Fig: 3-113
DTOC: Starting I> 040 036 Fig: 3-114
DTOC: Starting I>> 040 029 Fig: 3-114
DTOC: Starting I>>> 039 075 Fig: 3-114
DTOC: Starting Ineg> 036 145 Fig: 3-71,
3-72,3-116
DTOC: Starting Ineg>> 036 146 Fig: 3-71,
3-72,3-116
DTOC: Starting Ineg>>> 036 147 Fig: 3-71,
3-72,3-116
DTOC: Starting IN> 040 077 Fig: 3-119
DTOC: Starting IN>> 040 041 Fig: 3-119
DTOC: Starting IN>>> 039 078 Fig: 3-119
DTOC: tI> elapsed 040 010 Fig: 3-114
DTOC: tI>> elapsed 040 033 Fig: 3-114
DTOC: tI>>> elapsed 040 012 Fig: 3-114
DTOC: Trip signal tI> 041 020 Fig: 3-115
DTOC: Trip signal tI>> 040 011 Fig: 3-115
DTOC: Trip signal tI>>> 040 076 Fig: 3-115
DTOC: tIneg> elapsed 036 148 Fig: 3-73,
3-116,3-117
DTOC: tIneg>> elapsed 036 149 Fig: 3-73,
3-116,3-117
DTOC: tIneg>>> elapsed 036 150 Fig: 3-73,
3-116,3-117
DTOC: Trip signal tIneg> 036 151 Fig: 3-73,
3-116,3-117
DTOC: Trip signal tIneg>> 036 152 Fig: 3-116,
3-117
DTOC: Trip signal tIneg>>> 036 153 Fig: 3-116,
3-117
DTOC: tIN> elapsed 040 013 Fig: 3-119
Inverse-time overcurrent IDMT: Block. tIref,P> EXT 040 101 Fig: 3-129
protection IDMT: Block. tIref,neg>EXT 040 102 Fig: 3-131
IDMT: Block. tIref,N> EXT 040 103 Fig: 3-133
IDMT: Enabled 040 100 Fig: 3-124
IDMT: Starting Iref,P> 040 080 Fig: 3-129
IDMT: tIref,P> elapsed 040 082 Fig: 3-129
IDMT: Trip signal tIref,P> 040 084 Fig: 3-130
IDMT: Hold time P running 040 053 Fig: 3-129
IDMT: Memory P clear 040 110 Fig: 3-129
IDMT: Starting Iref,neg> 040 107 Fig: 3-131
IDMT: tIref,neg> elapsed 040 109 Fig: 3-131
IDMT: Trip sig. tIref,neg> 040 108 Fig: 3-131
IDMT: Hold time neg runn. 040 113 Fig: 3-131
IDMT: Memory neg clear 040 111 Fig: 3-131
IDMT: Starting Iref,N> 040 081 Fig: 3-133
IDMT: tIref,N> elapsed 040 083 Fig: 3-133
IDMT: Trip signal tIref,N> 040 085 Fig: 3-134
IDMT: Hold time N running 040 054 Fig: 3-133
IDMT: Memory N clear 040 112 Fig: 3-133
Switch on to fault protection SOTF: Par. ARC running EXT 039 063 Fig: 3-146
SOTF: Enabled 040 069 Fig: 3-146
SOTF: tManual-close runn. 036 063 Fig: 3-146
SOTF: Trip signal 036 064 Fig: 3-146
Automatic synchronism check ASC: Ext./user enabled 037 092 Fig: 3-171
ASC: Enable EXT 037 049 Fig: 3-171
ASC: Disable EXT 037 061 Fig: 3-171
ASC: Blocking EXT 037 048 Fig: 3-172
ASC: Test close requ. EXT 037 064 Fig: 3-173
ASC: Enabl.close requ.EXT 037 063 Fig: 3-173
ASC: Close request EXT 037 062 Fig: 3-173
ASC: Enabled 018 024 Fig: 3-171
ASC: Blocked 038 018 Fig: 3-172
ASC: Ready 037 079 Fig: 3-172
ASC: Not ready 037 082 Fig: 3-172
ASC: Test close request 034 019 Fig: 3-173
ASC: Close request 034 018 Fig: 3-173
ASC: Cycle running 038 019 Fig: 3-177
ASC: Operat.time running 037 093 Fig: 3-177
ASC: Close enable 037 083 Fig: 3-67,
3-175
ASC: Close enable,volt.ch 037 085 Fig: 3-175
ASC: Close enable,sync.ch 037 084 Fig: 3-176
ASC: Close rejection 037 086 Fig: 3-177
Ground fault direction GFDSS: GF (curr.) eval. EXT 038 020 Fig: 3-182
determination using GFDSS: Enabled 042 096 Fig: 3-182
steady-state values GFDSS: GF (pow.) ready 038 026 Fig: 3-182
GFDSS: GF (pow.) not ready 038 027 Fig: 3-182
GFDSS: GF (curr.) evaluat. 039 071 Fig: 3-182
GFDSS: GF (curr.) ready 038 028 Fig: 3-182
GFDSS: GF (curr.) not ready 038 029 Fig: 3-182
GFDSS: Admittance ready 038 167 Fig: 3-182
GFDSS: Admittance not ready 038 168 Fig: 3-182
GFDSS: Grd. fault pow./adm. 009 037 Fig: 3-184,
3-190
GFDSS: Forward / LS 009 035 Fig: 3-187,
3-193
GFDSS: Backward / BS 009 036 Fig: 3-187,
3-193
GFDSS: Starting forward/LS 009 040 Fig: 3-187,
3-193
GFDSS: Starting backw. /BS 009 041 Fig: 3-187,
3-193
GFDSS: Trip signal forw./LS 009 031 Fig: 3-187,
3-193
GFDSS: Ground fault (curr.) 009 038 Fig: 3-188
GFDSS: Starting Y(N)> 009 074 Fig: 3-194
GFDSS: Trip Y(N)> 009 075 Fig: 3-194
GFDSS: Trip signal Y(N)> 009 072 Fig: 3-194
Transient ground fault TGFD: Blocking EXT 004 034 Fig: 3-196
direction determination TGFD: Reset signals EXT 004 140 Fig: 3-200
TGFD: Enabled 037 100 Fig: 3-196
TGFD: Ready 037 080 Fig: 3-196
TGFD: Not ready 037 081 Fig: 3-196
TGFD: Ground fault 004 033 Fig: 3-198
TGFD: Direct. determined 004 030 Fig: 3-199
TGFD: Forward / LS 004 031 Fig: 3-199
TGFD: Backward / BS 004 032 Fig: 3-199
TGFD: Signals reset 004 141 Fig: 3-200
Thermal overload protection THERM: Therm.repl.block EXT 041 074 Fig: 3-217
THERM: Reset replica EXT 038 061 Fig: 3-218
THERM: Enabled 040 068 Fig: 3-213
THERM: Reset replica 039 061 Fig: 3-218
THERM: Starting k*Iref> 041 108 Fig: 3-217
THERM: CTA error EXT 038 062 Fig: 3-215,
3-216
THERM: Warning 039 025 Fig: 3-217
THERM: Trip signal 039 020 Fig: 3-217
THERM: Buffer empty 039 112 Fig: 3-217
THERM: CTA error 039 111 Fig: 3-215,
3-216
THERM: Within pre-trip time 041 109 Fig: 3-217
THERM: Setting error,block. 039 110 Fig: 3-217
Time-voltage protection V<>: Blocking tV> EXT 041 068 Fig: 3-223
V<>: Blocking tV>> EXT 041 069 Fig: 3-223
V<>: Blocking tV< EXT 041 070 Fig: 3-224
V<>: Blocking tV<< EXT 041 071 Fig: 3-224
V<>: Blocking tVpos> EXT 041 090 Fig: 3-226
V<>: Blocking tVpos>> EXT 041 091 Fig: 3-226
V<>: Blocking tVpos< EXT 041 092 Fig: 3-226
V<>: Blocking tVpos<< EXT 041 093 Fig: 3-226
V<>: Blocking tVneg> EXT 041 094 Fig: 3-227
V<>: Blocking tVneg>> EXT 041 095 Fig: 3-227
V<>: Blocking tVNG> EXT 041 072 Fig: 3-229
V<>: Blocking tVNG>> EXT 041 073 Fig: 3-229
V<>: Enabled 040 066 Fig: 3-221
V<>: Ready 042 003 Fig: 3-221
V<>: Not ready 042 004 Fig: 3-221
V<>: Starting V>/>> A(-B) 041 031 Fig: 3-223
V<>: Starting V>/>> B(-C) 041 032 Fig: 3-223
V<>: Starting V>/>> C(-A) 041 033 Fig: 3-223
V<>: Starting V> 041 030 Fig: 3-223
V<>: Starting V> 3-pole 041 097 Fig: 3-223
V<>: Starting V>> 041 096 Fig: 3-223
V<>: tV> elapsed 041 034 Fig: 3-223
V<>: tV> 3-pole elapsed 041 098 Fig: 3-223
V<>: tV>> elapsed 041 035 Fig: 3-223
V<>: Starting V</<< A(-B) 041 038 Fig: 3-224
V<>: Starting V</<< B(-C) 041 039 Fig: 3-224
V<>: Starting V</<< C(-A) 041 040 Fig: 3-224
V<>: Starting V< 041 037 Fig: 3-224
V<>: Starting V< 3-pole 042 005 Fig: 3-224
V<>: Starting V<< 041 099 Fig: 3-224
V<>: tV< elapsed 041 041 Fig: 3-224
V<>: tV< elaps. transient 042 023 Fig: 3-224
V<>: Fault V< 041 110 Fig: 3-224
V<>: tV< 3-pole elapsed 042 006 Fig: 3-224
V<>: tV< 3p elaps. trans. 042 024 Fig: 3-224
V<>: Fault V< 3-pole 041 111 Fig: 3-224
V<>: tV<< elapsed 041 042 Fig: 3-224
V<>: tV<< elapsed trans. 042 025 Fig: 3-224
V<>: tV</<< elaps. trans. 042 007 Fig: 3-224
V<>: Fault V<< 041 112 Fig: 3-224
V<>: Starting Vpos> 042 010 Fig: 3-226
V<>: Starting Vpos>> 042 011 Fig: 3-226
V<>: tVpos> elapsed 042 012 Fig: 3-226
V<>: tVpos>> elapsed 042 013 Fig: 3-226
V<>: Starting Vpos< 042 014 Fig: 3-226
V<>: Starting Vpos<< 042 015 Fig: 3-226
V<>: tVpos< elapsed 042 016 Fig: 3-226
V<>: tVpos< elaps. trans. 042 026 Fig: 3-226
V<>: Fault Vpos< 041 113 Fig: 3-226
V<>: tVpos<< elapsed 042 017 Fig: 3-226
V<>: tVpos<< elaps.trans. 042 027 Fig: 3-226
V<>: Fault Vpos<< 041 114 Fig: 3-226
V<>: tVpos</<< elap.trans 042 018 Fig: 3-226
Power directional protection P<>: Blocking tP> EXT 035 082 Fig: 3-237
P<>: Blocking tP>> EXT 035 083 Fig: 3-237
P<>: Blocking tQ> EXT 035 084 Fig: 3-239
P<>: Blocking tQ>> EXT 035 085 Fig: 3-239
P<>: Blocking tP< EXT 035 050 Fig: 3-241
P<>: Blocking tP<< EXT 035 051 Fig: 3-241
P<>: Blocking tQ< EXT 035 052 Fig: 3-244
P<>: Blocking tQ<< EXT 035 053 Fig: 3-244
P<>: Enabled 036 250 Fig: 3-235
P<>: Starting P> 035 086 Fig: 3-237,
3-247
P<>: Starting P>> 035 089 Fig: 3-237,
3-247
P<>: Signal P> delayed 035 087 Fig: 3-237
P<>: Signal P>> delayed 035 090 Fig: 3-237
P<>: Trip signal P> 035 088 Fig: 3-238
Circuit breaker failure CBF: Starting trig. EXT 038 016 Fig: 3-249
protection CBF: Parallel trip EXT 037 019 Fig: 3-67,
3-249
CBF: Enabled 040 055 Fig: 3-249
CBF: Trip signal 040 026 Fig: 3-249
CBF: tCBF running 036 066 Fig: 3-249
CBF: CB failure 036 017 Fig: 3-249
External devices 01 to 10 DEV01: Open signal EXT 210 030 Fig: 3-272,
3-278
DEV01: Closed signal EXT 210 031 Fig: 3-272,
3-278
DEV01: Control state 210 018 Fig: 3-272,
3-278
DEV01: Switch. device open 210 036 Fig: 3-272,
3-278,3-279,
3-280,3-
282,3-283
DEV01: Switch.device closed 210 037 Fig: 3-272,
3-278,3-279,
3-280,3-282,
3-283
DEV01: Sw. dev. interm.pos. 210 038 Fig: 3-272,
3-278
DEV01: Open command 210 028 Fig: 3-277
DEV01: Close command 210 029 Fig: 3-277,
3-279,3-280,
3-282,3-283
DEV02: Open signal EXT 210 080
Single-pole signals SIG_1: Signal S001 EXT 226 004 Fig: 3-286
SIG_1: Logic signal S001 226 005 Fig: 3-286
SIG_1: Signal S002 EXT 226 012
Binary counts COUNT: Set counter 1 EXT 217 130 Fig: 3-288
COUNT: Transmit counts EXT 217 009 Fig: 3-288
COUNT: Reset EXT 217 004 Fig: 3-288
COUNT: Enabled 217 001 Fig: 3-288
COUNT: Transmit counts 217 010 Fig: 3-288
COUNT: Reset 217 005 Fig: 3-288
Setting the enable for changing values from the local control panel.
Binary outputs OUTP: Reset latch. USER 021 009 Fig: 3-32
The output relay selected for testing is triggered for the set time
(O U T P : H o l d - t i m e f o r t e s t ) .
Setting the time period for which the selected output relay is triggered
during functional testing.
Measured data output MEASO: Reset output USER 037 116 Fig: 3-36
Main function MAIN: Enable syst. IN USER 003 142 Fig: 3-60
The counters for counting close and trip commands are reset.
MAIN: Reset IP,max,stored 003 033 Fig: 3-47
The display of active and reactive energy output and input is reset.
MAIN: Man. trip cmd. USER 003 040 Fig: 3-75
A 100 ms trip command is issued from the local control panel. This setting
is password-protected (see section entitled 'Password-Protected Control
Operations' in Chapter 6).
Note:
The command is only executed if the manual trip command has been
configured as trip command 1 or 2.
A close command is issued from the local control panel for the set reclose
command time. This setting is password-protected (see section entitled
'Password-Protected Control Operations' in Chapter 6).
MAIN: Warm restart 003 039
A warm restart is carried out. The device functions as it does when the
power supply is turned on.
MAIN: Cold restart 000 085
Operating data recording OP_RC: Reset recording 100 001 Fig: 3-88
The operating data memory and the counter for operation signals are reset.
Monitoring signal recording MT_RC: Reset recording 003 008 Fig: 3-89
Ground fault recording GF_RC: Reset recording 100 000 Fig: 3-103
Fault recording is enabled from the local control panel for 500 ms.
FT_RC: Reset recording 003 006 Fig: 3-111
The auto-reclosing control function is enabled from the local control panel.
ARC: Disable USER 003 133 Fig: 3-153
The auto-reclosing control function is disabled from the local control panel.
ARC: Test HSR A-B-C USER 011 066 Fig: 3-167
Automatic synchronism check ASC: Enable USER 003 136 Fig: 3-171
A close request is issued from the integrated local control panel. This will
trigger the ASC functional operation. No close command is transmitted to
the CB if the check of the ASC is positive. Only a signal is issued.
ASC: Close request USER 018 004 Fig: 3-173
A close request is issued from the integrated local control panel. This will
trigger the ASC functional operation. A close command is transmitted to the
CB if the check of the ASC is positive.
This control action is password-protected (see section entitled 'Password-
Protected Control Operations' in Chapter 6).
Ground fault direction GFDSS: Reset counters 003 004 Fig: 3-189,3-
determination using 195
steady-state values The counters for the ground fault direction determination function using
steady-state values are reset.
Transient ground fault TGFD: Reset signals USER 003 009 Fig: 3-200
direction determination The direction decisions can be reset while the buffer time is elapsing.
TGFD: Reset counters 003 022 Fig: 3-202
The counters for the transient ground fault direction determination function
are reset.
Count transmission.
COUNT: Reset USER 217 003 Fig: 3-288
Count reset.
Operating data recording OP_RC: Operat. data record. 003 024 Fig: 3-88
Monitoring signal recording MT_RC: Mon. signal record. 003 001 Fig: 3-89
8.2 Events
Main function MAIN: No. general start. 004 000 Fig: 3-72
Number of times external devices with direct motor control are activated
during the monitoring time.
MAIN: No.overfl.act.en.out 009 090 Fig: 3-57
Counter for the number of times the measuring range of the active energy
output was exceeded.
MAIN: No.overfl.act.en.inp 009 091 Fig: 3-57
Counter for the number of times the measuring range of the active energy
input was exceeded.
MAIN: No.ov/fl.reac.en.out 009 092 Fig: 3-57
Counter for the number of times the measuring range of the reactive energy
output was exceeded.
MAIN: No.ov/fl.reac.en.inp 009 093 Fig: 3-57
Counter for the number of times the measuring range of the reactive energy
input was exceeded.
Operating data recording OP_RC: No. oper. data sig. 100 002 Fig: 3-88
Monitoring signal recording MT_RC: No. monit. signals 004 019 Fig: 3-89
Ground fault recording GF_RC: No. ground faults 004 100 Fig: 3-102
Number of faults.
FT_RC: No. system disturb. 004 010 Fig: 3-110
Auto-reclosing control ARC: Number HSR A-B-C 004 007 Fig: 3-169
Automatic synchronism check ASC: No. RC aft. man.clos 004 009 Fig: 3-181
Ground fault direction GFDSS: No. GF power/admitt. 009 002 Fig: 3-195
determination using Number of ground faults detected by steady-state power evaluation.
steady-state values
GFDSS: No. GF (curr. meas) 009 003 Fig: 3-189
Overload data acquisition OL_DA: Overload duration 004 102 Fig: 3-90
Display of the load current used by the thermal overload protection function
to calculate the tripping time.
OL_DA: Object temp. THERM 004 035 Fig: 3-92
Ground fault data acquisition GF_DA: Ground flt. duration 009 100 Fig: 3-95
Display of the ground fault duration of the most recent ground fault.
GF_DA: GF duration pow.meas 009 024 Fig: 3-96
Display of the ground fault duration of the most recent ground fault as
determined by the steady-state power evaluation feature of the ground fault
direction determination function.
Display of the active component of the residual current of the most recent
ground fault referred to IN,nom.
Note:
This display is only active when the steady-state power evaluation mode of
the GFDSS ground fault direction determination function is enabled.
GF_DA: Curr. IN,reac p.u. 009 023 Fig: 3-97
Display of the reactive component of the residual current of the most recent
ground fault referred to IN,nom.
Note:
This display is only active when the steady-state power evaluation mode of
the GFDSS ground fault direction determination function is enabled.
GF_DA: GF durat. curr.meas. 009 026 Fig: 3-98
Display of the ground fault duration of the most recent ground fault as
determined by the steady-state current evaluation feature of the ground fault
direction determination function.
GF_DA: Curr. IN filt. p.u. 009 025 Fig: 3-99
Display of the residual current component having the set filter frequency for
the most recent ground fault (referred to IN,nom).
GF_DA: GF duration admitt. 009 068 Fig: 3-100
Display of the ground fault duration of the most recent ground fault as
determined by the admittance evaluation mode of the ground fault direction
determination function.
GF_DA: Admittance Y(N) p.u. 009 065 Fig: 3-101
Fault data acquisition FT_DA: Fault duration 008 010 Fig: 3-104
Display of the fault location of the last fault (in %) referred to the setting
FT_DA: Line reactance PSx.
FT_DA: Fault location 004 022 Fig: 3-108
Display of the load impedance (in ) after the general starting condition of
time-overcurrent protection has ended. The display only appears if the fault
has been detected by the fault data acquisition function of the P139.
FT_DA: Load angle post-flt. 004 038 Fig: 3-109
Display of the load angle (in degrees) after the general starting condition of
time-overcurrent protection has ended. The display only appears if the fault
has been detected by the fault data acquisition function of the P139.
Display of the residual current referred to Inom after the general starting
condition of time-overcurrent protection has ended. The display only
appears if the fault has been detected by the fault data acquisition function
of the P139.
Automatic synchronism check ASC: Voltage Vref 004 087 Fig: 3-180
ASC: Volt. sel. meas.loop 004 088 Fig: 3-180
ASC: Volt. magnit. diff. 004 091 Fig: 3-176,
3-180
Display of the difference between amplitudes of the measurement loop
voltage and the reference voltage during a close request, referred to Vnom.
The display only appears if ASC is operating.
ASC: Angle difference 004 089 Fig: 3-176,
3-180
Display of the difference between angles (in degrees) of the measurement
loop voltage and the reference voltage during a close request. The display
only appears if ASC is operating.
ASC: Frequ. difference 004 090 Fig: 3-176,
3-180
Display of the difference between frequencies (in Hz) of the measurement
loop voltage and the reference voltage during a close request.
The display only appears if ASC is operating.
Ground fault recording GF_RC: Ground flt.record. 1 033 010 Fig: 3-103
GF_RC: Ground flt.record. 2 033 011 Fig: 3-103
GF_RC: Ground flt.record. 3 033 012 Fig: 3-103
GF_RC: Ground flt.record. 4 033 013 Fig: 3-103
GF_RC: Ground flt.record. 5 033 014 Fig: 3-103
GF_RC: Ground flt.record. 6 033 015 Fig: 3-103
GF_RC: Ground flt.record. 7 033 016 Fig: 3-103
GF_RC: Ground flt.record. 8 033 017 Fig: 3-103
9 Commissioning
The device must be reliably grounded before auxiliary voltage is turned on.
The surface-mounted case is grounded using the appropriate bolt and nut as the ground
connection. The flush-mounted case must be grounded in the area of the rear
sidepieces at the location provided. The cross-sectional area of this ground conductor
must also conform to applicable national standards. A minimum conductor cross section
of 2.5 mm2 is required.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters PE on the terminal connection diagram) is also
required for proper operation of the unit. The cross-sectional area of this ground
conductor must also conform to applicable national standards. A minimum cross section
of 1.5 mm2 is required.
Before working on the device itself or in the space where the device is connected,
always disconnect the device from the supply.
The secondary circuit of live current transformers must not be opened. If the secondary
circuit of a live current transformer is opened, there is the danger that the resulting
voltages will endanger people and damage the insulation.
The threaded terminal block for current transformer connection is not a shorting block.
Therefore always short-circuit current transformers before loosening the threaded
terminals.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
When the P139 is used for the protection of increased-safety machines, it must be
located outside of any areas that are subject to explosion hazards.
!
The fiber-optic interface may only be connected or disconnected when the supply
voltage for the unit is shut off.
!
The PC interface is not designed for permanent connection. Consequently the socket
does not have the extra insulation from circuits connected to the system that is required
per VDE 0106 Part 101.
Therefore when connecting the connecting cable make sure that you do not touch the
socket contacts.
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see chapter entitled 'Technical
Data').
Preparation
After the P139 has been installed and connected as described in Chapter 5, the
commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked again:
After the wiring work is completed, check the system to make sure it is properly isolated.
The conditions given in VDE 0100 must be satisfied.
Once all checks have been made, the power supply voltage may be turned on. After
voltage has been applied, the device starts up. During startup, various startup tests are
carried out (see section entitled Self-Monitoring in Chapter 3). The LED indicator
labeled HEALTHY (H1) and the LED indicator labeled OUT OF SERVICE (H2) will
light up. (The LED indicator H2 is coupled to the signal M A I N : B l o c k e d / f a u l t y . )
After approximately 15 s, the P139 is ready for operation. In initial, factory-set condition
or after a cold restart, the device type 'P139' and the time of day will be displayed in the
first line of the LCD display. If a bay type has already been set, the bay will be displayed
in single-pole representation.
Once the change-enabling command has been issued (see the Section Change-
Enabling Function in Chapter 6), all settings can be entered. The procedure for entering
settings from the integrated local control panel is described in Chapter 6.
After the enter key (E) is pressed to confirm the 'Type of bay' setting
parameter, the 'Initializing bay' signal is displayed for 20 s. The EDIT
MODE LED will light up. Local control actions are not possible during this
time.
If either the PC interface or the communication interface will be used for setting the P139
and reading out event records, then the following settings must first be made from the
integrated local control panel.
! Par/DvID/ folder:
" DVICE: Device password 1
" DVICE: Device password 2
! Par/Conf/ folder:
" PC: Name of manufacturer
" PC: Bay address
" PC: Device address
" PC: Baud rate
" PC: Parity bit
" COMM1: Function group COMM1
" COMM1: General enable USER
" COMM1: Name of manufacturer
" COMM1: Line idle state
" COMM1: Baud rate
" COMM1: Parity bit
" COMM1: Communicat. protocol
" COMM1: Octet comm. address
" COMM1: Octet address ASDU
! Par/Func/Glob/ folder:
" PC: Command blocking
" PC: Sig./meas.val.block
" COMM1: Command block. USER
" C O M M 1 : S i g . / m e a s . b l o c k .U S E R
Note: The settings given above apply to the IEC 60870-5-103 communication
protocol. If another protocol is being used for the communication interface,
additional settings may be necessary. See Chapter 7 for further details.
After the settings have been made, the following checks should be carried out again
before blocking is canceled:
! M A I N : D e v i c e o n - l i n e "Yes (on)"
Tests
By using the signals and displays generated by the P139, it is possible to determine
whether the P139 is correctly set and properly interconnected with the station. Signals
are signaled by output relays and LED indicators and entered into the event memory. In
addition, the signals can be checked by selecting the appropriate signal in the menu
tree.
If the user does not wish to operate the circuit breaker during the protection functions
test, the trip commands can be blocked through M A I N : T r i p c m d . b l o c k . U S E R
('Par/Func/Glob/' folder) or an appropriately configured binary signal input. If circuit
breaker testing is desired, it is possible to issue a trip command for 100 ms through
M A I N : M a n . t r i p c m d . U S E R ('Oper/CtrlTest' folder) or an appropriately
configured binary signal input. Selection of the trip command from the integrated local
control panel is password-protected (see Section Password-Protected Control Actions in
Chapter 6).
Note: The manual trip command is only executed if it has been configured for trip
command 1 or 2.
If the P139 is connected to substation control level, it is advisable to activate the test
mode via MAIN: T e s t m o d e U S E R ('Par/Func/Glob/' folder) or an appropriately
configured binary signal input. The telegrams are then identified accordingly (cause of
transmission: test mode).
This display appears regardless of the binary signal input mode selected.
!
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
When testing the time-overcurrent protection with a testing device, the measuring-circuit
monitoring function should be deactivated (M C M O N : Ge n e r a l e n a b l e U S E R ,
folder Par/Func/Gen/) since it would otherwise always operate and thus, depending on
the setting, issue fault signals.
The set rotary field needs to match the actual rotary field. In the case of a purely
resistive load, the angle N must have the following values (depending on the direction
of energy flow in either line or busbar direction):
! DTOC protection is enabled. This may be interrogated at the logic state signal
D T O C : E n a b l e d (Oper/Cycl/Log/ folder).
! The function M A I N : B l o c k t i m . s t . I N , n e g is set to No (folder Par/Func/Gen).
! The function M A I N : G e n . s t a r t i n g m o d e is set to Starting IN, Ineg (folder
Par/Func/Gen).
! The short-circuit direction determination function is disabled. S C D D : G e n e r a l
e n a b l e U S E R (folder 'Par/Func/Gen') is set to No.
By applying appropriate measuring variables, the overcurrent stages and the associated
timer stages can be tested.
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
! IDMT protection is enabled. This may be interrogated at the logic state signal
IDMT: E n a b l e d (folder Oper/Cycl/Log/).
! The function M A I N : B l o c k t i m . s t . I N , n e g is set to No (folder Par/Func/Gen).
By applying appropriate measuring variables, the overcurrent stages and the associated
time delays can be tested.
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
The trip times for the inverse-time overcurrent protection function as a function of the set
tripping characteristics are shown in the following table:
If the connection is standard in accordance with the standard schematic diagram shown
in Chapter 'Installation and Connection' and the setting of M AIN : Conn. meas. circ. IP
is Standard then the measurement of the short-circuit direction determination function
will be in line direction. The set rotary field needs to match the actual rotary field. It is
now possible to simulate the various fault types with the appropriate starting via the
DTOC or IDMT protection function by applying various shorting jumpers (such as A-G).
The trip signals of the phase current stages are now directional. The trip signals of the
phase current stages are now directional.
If the connection is standard in accordance with the standard schematic diagram shown
in Chapter 'Installation and Connection' and the setting of M AIN : C o n n . m e a s . c i r c .
IN is 'standard' then the measurement of the short-circuit direction determination
function will be in line direction. The set rotary field needs to match the actual rotary
field. It is now possible to simulate the various fault types as described under Direction
testing of the phase current stages. The trip signals of the residual current stages are
now directional.
Checking protective
signaling
The protective signaling function can only be checked if protective signaling is ready.
This can be determined via the logic state signal P S I G : R e a d y (Oper/Cycl/Log/
folder).
If protective signaling is not ready, this may be due to the following reasons:
If the conditions for testing are satisfied, it is possible to generate a send signal for test
purposes from the integrated local control panel (P S I G : T e s t t e l e c o m . U S E R ).
This pulse will be present for 1 ms and is extended for the set reset time. This pulse will
be present for 1 s and will be extended for the set reset time. The generated signal can
be checked via the logic state signal PSIG : S e n d ( t r a n s m . r e l a y ).
If the ARC function is not ready, this may be due to the following reasons:
! The ARC is being blocked. (This can be checked at the logic state signal
AR C : Bl o c k e d in folder 'Oper/Cycl/Log/'.)
! There is no signal with a logic value of 1 at the binary signal input configured for
ARC: CB drive ready EXT.
! There is no signal with a logic value of 1 at the binary signal input configured for
M AIN : C B c l o s e d s i g . E X T . The circuit breaker position signal is only
necessary if With has been set at A R C : C B c l o s . p o s . s i g . (folder
'Par/Func/Gen/').
! An ARC cycle is currently running. (This can be checked at logic state signal
A R C : C y c l e r u n n i n g in the Oper/Cycl/Log/ folder.)
A test HSR for checking can be executed from the integrated local control panel or by
triggering a binary signal input. The test HSR function first issues a trip command and
then issues a reclose command after the set dead time has elapsed.
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
In order to test the motor protection function, first clear the thermal replica. Clearing the
thermal replica is achieved by briefly disabling the protection function (M AIN : D e vi c e
o n - l i n e set to No, folder Par/Func/Glob/). The updated status of the thermal replica
can be interrogated via the operating data display M P: T h e r m . r e p l . b u ffe r M S
( folder Oper/Cycl/Data/). The trip times depend on the set tripping characteristic:
With cleared thermal replica, the test current is changed abruptly from 0 ( machine
stopped) to a value setting value M P: IStU p > PSx, folder Par/Func/Gen/
( machine running).
36
! Reciprocally squared characteristic t = (1 m 0 ) t 6Iref
(I Iref ) 2
(I Iref ) 2
! ( )
Logarithmic characteristic: t = 1 m 0 t 6Iref 36 ln
(I Iref ) 2 1
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
In order to test the thermal overload protection function, first clear the thermal replica.
Clearing the thermal replica is achieved by briefly disabling the protection function
(M A I N : D e v i c e o n - l i n e set to No, folder Par/Func/Glob/). The updated status of the
thermal replica can be interrogated via the operating data display T H ER M : T h e r m .
r e p l i c a ve r s . ( folder Oper/Cycl/Data/) The trip time can be checked:
With cleared thermal replica, the test current is changed abruptly from 0 to a value
of 0.1 Iref
2
I
P
t = ln Iref
2
I c c,max
trip 1
Iref max c,max
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
The P139 calculates the neutral-point displacement voltage from the input-side
measured variables as follows:
1
V N G = V A G + V BG + V CG
3
!
The application of analog signals to the measuring inputs must comply with the
maximum permissible rating of the measuring inputs (see Technical Data Chapter).
If allowed by system operation, a ground fault can be closed on the busbar side (BS) or
the line side (LS). The P139 must then transmit the corresponding signals. However, a
requirement for ground fault recognition in the steady-state power evaluation mode is
that the set thresholds for residual current (G F D S S : I N , a c t > / I N , r e a c > B S or
L S ) and for neutral displacement voltage (G F D S S : V N G > ) be exceeded. For steady-
state current evaluation, the requirement is that the residual current threshold
G F D S S : I N > be exceeded. In the admittance evaluation mode, the requirement is
that the set thresholds for conductance / susceptance (G F D SS: G ( N ) > / B( N ) L S
or BS) and the neutral displacement voltage (G F D S S : V N G > ) be exceeded or that
the admittance (G F D SS: Y( N ) > ) be exceeded.
Because of the danger of a double ground fault, a function test involving the closing of a
ground fault will not be possible in most cases. In these cases the current and voltage
transformers in the system can be connected so that a function test is possible without a
ground fault.
The residual current measured by the P139 and the neutral displacement voltage are
displayed as measured operating data both in primary quantities and referred to the
nominal quantities of the P139 (see the section entitled Measured Operating Data in the
Address List).
Auxiliary circuit in
resonant-grounded
systems
First the fuse in phase A of the voltage transformer is removed and the associated
secondary side is short-circuited (see Figures 9-2 and 9-3). The result is a displacement
voltage VN-G with a magnitude smaller by a factor of 3 than that of the displacement
voltage in the case of a dead fault to ground.
If the current is measured in a Holmgreen group, then the current transformer in A on the
secondary side must be disconnected and short-circuited (see Figure 9-2).
9-2 Auxiliary circuit in resonant-grounded systems with Holmgreen group, ground fault in BS direction
A pilot wire is threaded into core balance current transformers, and a current is drawn
from phase B through the wire (see Figure 9-3). The vectorial assignment of currents
and voltages is shown in the phasor diagrams included with the terminal connection
diagrams.
In the example shown below, a ground fault is simulated on the busbar side. To check a
ground fault on the line side, the current or voltage connections must be switched.
9-3 Auxiliary circuit in resonant-grounded systems with core balance current transformer, ground fault in BS direction
9-4 Auxiliary circuit in systems with isolated neutral and Holmgreen group, ground fault in LS direction
A pilot wire is threaded into core balance current transformers, and a current is drawn
from phases B and C through this wire (see Figure 9-5). The vectorial assignment of
currents and voltages is shown in the phasor diagrams included with the terminal
connection diagrams.
In the example shown below, a ground fault is simulated on the line side. To check a
ground fault on the busbar side, the current or voltage connections must be switched.
9-5 Auxiliary circuit in systems with isolated neutral and core balance current transformer, ground fault in LS direction
Local control
The switchgear unit to be controlled is selected by pressing the Selection key on the
local control panel and then controlled by pressing the Open or Close key. If the
switchgear units are to be controlled through binary signal inputs, then the appropriate
signal input must be triggered.
Remote control
The switchgear units can be controlled via the communication interface or appropriately
configured binary signal inputs.
Note: Substation interlocking is only active when there is communication with the
substation control level through the communication interface. In the event of
a communication error, the unit will switch automatically to bay interlock
without station interlock. To determine if there is a communication error,
check at M AIN : C o m m u n i c a ti o n e r r o r , Oper/Cycl/Log/ folder.
Completion of
commissioning
Before the P139 is released for operation, the user should make sure that the following
steps have been taken:
After completion of commissioning, only the green LED indicator signaling Operation
(H1) should be on.
10 Troubleshooting
This chapter describes problems that might be encountered, their causes, and possible
methods for eliminating them. It is intended as a general orientation only, and in cases
of doubt it is better to return the P139 to the manufacturer. Please follow the packaging
instructions in the section entitled Unpacking and Packing in Chapter 5 when returning
equipment to the manufacturer.
Problem:
Before checking further, disconnect the P139 from the power supply.
!
The local control panel is connected to processor module P by a plug-in connecting
cable. Make sure the connector position is correct. Do not bend the connecting cable!
" Check to make sure that fuse F1 on power supply module V is not fused.
If the fuse is defective, it should not be replaced without determining the cause of
failure. If a fuse is replaced without eliminating the problem, there is the danger
that the damage will spread.
Required Fuses:
! The P139 issues a Warning signal on LED H3. (H3 is labeled ALARM).
Identify the specific problem by reading out the monitoring signal memory (see the
section entitled Monitoring Signal Memory Readout in Chapter 6). The table below
lists possible monitoring or warning indications (provided that a configuration setting
has been entered at S F M O N : F c t . a s s i g n . w a r n i n g ) , the faulty area, the
P139 response, and the mode of the output relay configured for 'Warning' and
'Blocked/faulty'.
SFMON: Warning (LED) 036 070
Key
-: No reaction and/or no output relay triggered.
Updating: The output relay configured for 'Warning' starts only if the monitoring
signal is still present.
1)
: The 'Blocked/faulty' output relay only operates if the signal has been
configured at M A I N : F c t . a s s i g n m . f a u l t .
2)
: The 'Warning' output relay only operates if the signal has been
configured at S F M O N : F c t . a s s i g n m . w a r n i n g .
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Cold rest./SW update 093 025
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Blocking/ HW failure 090 019
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Invalid type of bay 096 122
If the user has selected a bay type that requires a P139 hardware
configuration that is not actually fitted, then this signal is generated.
The +15 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: +24V supply faulty 093 082
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Wrong module slot 1 096 100
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Defect.module slot 1 097 000
The +15 V internal supply voltage of the transient ground fault evaluation
module has dropped below a minimum value.
The -15 V internal supply voltage of the transient ground fault evaluation
module has dropped below a minimum value.
The checksum feature of the transient ground fault evaluation module has
detected a fault in the data transmission of the Dual-Port-RAM.
Fault in the program or data memory of the transient ground fault evaluation
module.
The checksum feature of analog I/O module Y has detected a fault in the
data transmission of the Dual-Port-RAM.
The checksum feature of analog module (RTD) has detected a fault in the
data transmission of the Dual-Port-RAM.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Undefined interrupt 093 012
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Exception oper.syst. 093 013
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Protection failure 090 021
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Checksum error param 090 003
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Clock sync. error 093 041
Faulty test pattern in the RAM. This can occur, for example, if the
processor module or the power supply module is removed from the bus
module (digital). This fault is only detected during device startup. After the
fault is detected, the software initializes the RAM. This means that all
records are deleted.1st device reaction / 2nd device reaction: - / -
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: -/-
Software overloaded.
Incorrect or invalid software for transient ground fault evaluation module has
been downloaded.
1st device reaction / 2nd device reaction: - / -
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: -/-
SFMON: Time-out module N 093 092
Incorrect or invalid software for analog I/O module Y has been downloaded.
Watchdog is monitoring the periodic status signal of the analog I/O module
Y. It has detected an error.
The "Fuse Failure" monitoring function has detected a fault in the voltage
measuring circuit for the reference voltage.
Since the last complete valid message was transmitted the time set at
C O M M 3 : T i m e - o u t c o m m . f a u l t has elapsed and the receive
signals are set to their user-defined default values.
A protective function has been activated that is not permitted for operation
at a system frequency of 60 Hz.
An invalid characteristic has been set for the BCD output channel of analog
I/O module Y.
An invalid characteristic has been set for one of the analog output channels
of analog I/O module Y.
An invalid characteristic has been set for the analog input channel of analog
I/O module Y.
1st device reaction / 2nd device reaction: Depends on type of fault detected.
'Warning' output relay: Yes / Yes 2)
'Blocked/faulty' output relay: -/-
SFMON: PT100 open circuit 098 024
The P139 has detected an open circuit in the connection of the resistance
thermometer "PT100" to the analog I/O module Y.
1st device reaction / 2nd device reaction: Depends on type of fault detected.
'Warning' output relay: Yes / Yes 2)
'Blocked/faulty' output relay: -/-
SFMON: PT100 T1 open circ. 098 029
The P139 has detected an open circuit in the connection of the 20 mA input.
The function was configured to a binary input on the analog I/O module Y.
This setting is not valid for this function.
11 Maintenance
The P139 is a low-maintenance device. The components used in the units are selected
to meet exacting requirements. Recalibration is not necessary.
Maintenance procedures in
the power supply area
Electrolytic capacitors are installed in the power supply area because of dimensioning
requirements. The useful life of these capacitors is significant from a maintenance
standpoint. When the equipment is operated continuously at the upper limit of the
recommended temperature range (+55C or 131F), the useful life of these components
is 80,000 hours, or more than 9 years. Under these conditions, replacement of the
electrolytic capacitors is recommended after a period of 8 to 10 years. Component drift
follows the '10-degree rule'. This means that the useful life is doubled for each 10 K
reduction in temperature. When the operating temperatures inside the devices are
lower, the required maintenance intervals are increased accordingly.
The P139 is equipped with a lithium battery for non-volatile storage of fault data and for
keeping the internal clock running in the event of failure of the auxiliary power supply.
Loss of capacity due to module-internal self-discharging amounts to less than 1% per
year over a period of availability of 10 years. Since the terminal voltage remains virtually
constant until capacity is exhausted, usefulness is maintained until a very low residual
capacity is reached. With a nominal capacity of 850 mAh and discharge currents of only
a few A during device storage or in the range of the self-discharge current during
device operation, the result is a correspondingly long service life. It is therefore
recommended that the lithium battery only be replaced after the maintenance interval
cited above.
Always turn off the power (supply voltage) before removing a hardware module.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
! Electrolytic capacitor:
on power supply module V.
! Lithium battery:
on power supply module V.
There is a danger of explosion if the electrolytic capacitor and battery are not properly
replaced. Always check to make sure that the polarity of the electrolytic capacitor and
the battery is correct.
!
The local control panel is connected to processor module P by a plug-in connecting
cable. Make sure the connector position is correct. Do not bend the connecting cable.
Note: The replaced components (electrolytic capacitor and battery) must be disposed
of in compliance with applicable national regulations.
After the maintenance procedures described above have been completed, new
commissioning tests as described in Chapter 9 must be carried out.
The P139 incorporates in its system a very extensive self-monitoring function for
hardware and software. The internal structure guarantees, for example, that
communication within the processor system will be checked on a continuing basis.
Nonetheless, there are a number of subfunctions that cannot be checked by the self-
monitoring feature without running a test from the device terminals. The respective
device-specific properties and setting parameters must be observed in such cases.
In particular, none of the control and signaling circuits that are run to the device from the
outside are checked by the self-monitoring function.
The best way to carry out a static test of the analog input circuits is to check the primary
measured operating data using the operating data measurement function or to use a
suitable testing instrument. A small measured value (such as the nominal current in
the current path) and a large measured value (such as the nominal voltage in the
voltage path) should be used to check the measuring range of the A/D converter. This
makes it possible to check the entire control range.
In addition, a dynamic test (injection test) can be used to check input performance and
the phase relation of the current transformers and the anti-aliasing filter.
This dynamic test is not absolutely necessary, since it only checks the stability of a few
less passive components. Based on reliability analysis, the statistical expectation is that
only one component in 10 years in 1000 devices will be outside the tolerance range.
Additional injection testing of every protection function, is not necessary, in our opinion,
since information processing is completely numerical and is based on the measured
analog current and voltage values. Proper operation was checked in conjunction with
type testing.
Binary inputs
The binary inputs are not checked by the self-monitoring function. However, a testing
function is integrated into the software so that the trigger state of each input can be read
out (Oper/Cycl/Phys folder). This check should be performed for each input being used
and can be done, if necessary, without disconnecting any device wiring.
Binary outputs
With respect to binary outputs, the integrated self-monitoring function includes even two-
phase triggering of the relay coils of all the all-or-nothing relays. There is no monitoring
function for the external contact circuit. In this case, the all-or-nothing relays must be
triggered by way of device functions or integrated test functions. For these testing
purposes, triggering of the output circuits is integrated into the software through a special
control function (Oper/CtrlTest/ folder).
!
Before starting testing, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Serial interfaces
The integrated self-monitoring function for the PC or communication interface also
includes the communication module. The complete communication system, including
connecting link and fiber-optic module (if applicable), is always totally monitored as long
as a link is established through the control program or the communication protocol.
12 Storage
Devices must be stored in a dry and clean environment. A temperature range of -25C
to +70C (-13F to +158F) must be maintained during storage (see the Chapter on
Technical Data). The relative humidity must be controlled so that neither condensation
nor ice formation will result.
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be recharged every 4 years. Recharge the
capacitors by connecting auxiliary voltage to the P139 for approximately 10 minutes.
The P139 is supplied with standard labeling for the LED indicators. User-specific
labeling for non-standard configurations of the LEDs can be printed on the blank label
strips packed with the device. The label strip can then be glued to the front panel area
reserved for this purpose.
The label strip can be filled in using an overhead projector pen, waterproof type.
Example: Stabilo brand pen, OH Pen 196 PS.
P139
P139 Feeder Management and Bay Control 9 0 -304 -4xx -605 -7xx -46x -9x x -9x x -8xx
Basic device:
Basic device 40TE, pin-terminal connection, 3 405
Basic device 40TE, CT/VT ring-, I/O pin-terminal connection, 5 406
Basic device 84TE, ring-terminal connection, 8 407
basic complement with 4 binary inputs and 8 output relays
and 6 binary inputs and 6 output relays
for the control of 3 switchgear units
Current transformer:
Inom = 1 A / 5 A (T1...T4) 2) (NCIT: 22.5 mV at 50 A) 9
Voltage transformer:
Without 0
Vnom = 50 ... 130 V (4-pole) 4
Vnom = 50 ... 130 V (5-pole) f. Automatic Synchronism Check 5
Language:
English (German) 4) (Without order extension No.)
Px40 English (English) 4) (On request) -800
German (English) 4) -801
French (English) 4) (On request) -802
Spanish (English) 4) (On request) -803
Polish (English) 4) (On request) -804
Russian (English) 4)
7)
(On request) -805