Gondola
Gondola
Gondola
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
A
C
= tan-1 (640/960)
= 34 degree F3cos F1
F3 = P/sin(34)
= 9.84 kN P
F1 = F3 x cos(34)
= 8.16 kN
Consider Point B F2
= tan-1 (640/960)
= 34 degree Tcos10o F3sin(90o -)
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Consider Member A
D= 80 mm Zx = 13.6 cm3
B= 40 mm Zy = 9 cm3
t= 3 mm Sx = 17.1 cm3
Ix = 54.2 cm4 Sy = 10.4 cm3
Iy = 18 cm4 J= 43.8 cm4
rx = 2.84 cm C= 15.3 cm3
ry = 1.63 cm
A= 6.74 cm2
Mass 5.29 kg/m
Check Compression
LEX/ry= 59 LEX/rx= 34
=> l= 59
=> pc= 240 MPa (Curve a )
A x pc = Pc= 162 kN (>13.264kN) OK!
Consider Member B
D= 80 mm Zx = 13.6 cm3
B= 40 mm Zy = 9 cm3
t= 3 mm Sx = 17.1 cm3
Ix = 54.2 cm4 Sy = 10.4 cm3
Iy = 18 cm4 J= 43.8 cm4
rx = 2.84 cm C= 15.3 cm3
ry = 1.63 cm
A= 6.74 cm2
Mass 5.29 kg/m
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Check Compression
LEX/ry= 39 LEX/rx= 23
=> l= 39
=> pc= 261 MPa (Curve a )
A x pc = Pc= 176 kN (>11.184kN) OK!
According to gondola supplier's drawing, 8mm dia. wire will be adopted as suspension wire for this gondola system.
Minimum Breaking Tension of wire, TB,min = 44 kN (According to Mill Cert. provided by Gondola Supplier)
According to gondola supplier's dwg, 4 nos. of Hilti HST-M12 anchor bolt bill be adopted per joint between the steel frame and existing beam.
4nos of anchor bolt per joint is satisfied, detail please see next page.
Project : Project No. :
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Loading Estimation
F1 = 11.98 kN
F2 = 6.99 kN
F3 = 9.97 kN
T = 8.42 kN
Design Wind Load = 2.86 kPa
Assume 600mm H x150mm thk. R.C. beam for fixing the outrifgger,
K = M /( fcubd2)
= 9.52kNm/(25*600*(150-35)^2)
= 0.048
< 0.156
Therefore, z = 141.5 mm
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Checking to existing Beam (600x150) for connecting tie back wire (Method A)
Loading Estimation
T T
150 mm 150 mm
4800 mm
T = 8.42 kN
Design Wind Load = 2.86 kPa
Assume 600mm H x150mm thk. R.C. beam for fixing the tie back wire.
K = M /( fcubd2)
= 3.46/(25*600*(150-35)^2)
= 0.014
< 0.156
Therefore, z = 142.5 mm
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Checking to existing Column (500x150) for connecting tie back wire (Method A)
Loading Estimation
LL, Life Load Tramsmitted form Beam
2500 mm 2200 mm
Assume 500mm x150mm thk. R.C. column for fixing the tie back wire,
K = M /( fcubd2)
= 54.2/(25*150*(500-35)^2)
= 0.004
< 0.156
Therefore, z = 475 mm
Project : Project No. :
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Checking to existing Column (500x150) for connecting tie back wire (Method B)
Loading Estimation
WL, Wind Load Transmitted from Beam
300 mm
T
2500 mm
1900 mm
T = 8.42 kN
WL = 2.86kPa x4.8m x0.6m
= 8.24 kN
Design Wind Load = 2.86 kPa
Assume 500mm x150mm thk. R.C. column for fixing the tie back wire,
K = M /( fcubd2)
= 47.39/(20*150*(500-35)^2)
= 0.004
< 0.156
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Therefore, z = 475 mm
Loading Estimation
WL, Wind Load transmitted from Beam
300 mm
T
2500 mm
1900 mm
T = 8.42 kN
T1 = T2(sin(22)/sin(36))
= 0.64T2
0.64T2cos(36) +T2cos(22) = T
T2 = T /(0.64cos(36)+cos(22))
= 5.83 kN Dominate
T1 = 3.73 kN
Assume 500mm x150mm thk. R.C. wall for fixing the tie back wire
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Mx /h' = 60.77
My /b' = 93.48
K = M /( fcubd2)
= 18.14/(25*150*(500-35)^2)
= 0.004
< 0.156
Checking to existing Column(500x150) for connecting tie back wire (Method C) (Cont')
Therefore, z = 142.5 mm
Checking to existing Column(500x150) for connecting tie back wire (Diagonal Connection) Cont'
Calc'n No.:
Tel : Part of structure : Sheet No.: Rev. No.:
Fax :
E-mail : Drawing : Prepared by : Checked by : Date :
Rev. No.:
Date :
Remark
g = 9.8 N/kg
Project No. :
Rev. No.:
Date :
Remark
Project No. :
Rev. No.:
Date :
Remark
Project No. :
Rev. No.:
Date :
Remark
Project No. :
Rev. No.:
Date :
Remark
Project No. :
Rev. No.:
Date :
Remark
Project No. :
Rev. No.:
Date :
Remark
Project No. :
Rev. No.:
Date :
Remark
Dominate
Project No. :
Rev. No.:
Date :
Remark
Project No. :
Rev. No.:
Date :
Remark