Transformer Sizing

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 2

CALCULATION COVER SHEET

CLIENT: Zakum Development Company (ZADCO) PAGE COUNT LAST PAGE No.
PROJECT: Zirku Island Power Upgrade FEED SUMMARY SUMMARY
CALCULATION TITLE: TOTAL CALC BODY PAGES: 11 11
TOTAL ATTACH. PAGES: 10
POWER TRANSFORMER SIZING
TOTAL PAGES: 21

CALCULATION NUMBER
PROJECT or W.O. NO. DISCIPLINE CODE SEQUENCE NO. REV NO.
P8374-CN - 421-E - 0039 - A

REVISION HISTORY
REV REV DATE PREPARER REVIEWER/CHECKER CONFIRMATION
NO. PRINTED NAME PRINTED NAME REVISION DESCRIPTION REQUIRED
AND SIGNATURE AND SIGNATURE YES NO

A SM TRS ISSUED FOR CLIENT COMMENTS (IFCC) X

###

Page 1 of 2
10) DEFINITION

Max ambient Tmax= 50 Deg C.


Min ambient Tmin= 9 Deg C
Generator Min MW output at max temp Pgmin= 20.2 MW
Generator Max MW op at min temp Pgmax = 24 MW
Lagging Power factor at Generator terminal when the Cos lag = 0.8
generator is generating its rated power output

Leading Power factor at Generator terminal, PF lead Cos lead = 0.95

Transformer impedance, in PU ONAN base Zt= 12%

Transformer impedance X/R ratio Txr= 27


Transformer impedance tolerance Ztol= 10%
Generator Auxiliary active load Pl= 0.323 MW
Generator Auxiliary reactive load Ql= 0.198 MVAr
Generator min lagging reactive power output at max Qglagmin= 15.15 MVAr
temperature
Generator min leading reactive power output at max Qgldmin = 6.64 MVAr
temperature
Generator maximum lagging reactive power output at min Qglagmax= 18 MVAr
temperature
Generator max leading reactive power output at min Qgldmax = 7.89 MVAr
temperature

ONAF rating multiplier times ONAN rating MF= 1 Since transformer is desired to be of
only ONAN rating.

Transformer capacity multiplier at Tmax site ambient Cpu1= 0.625 An additional 50C Margin has been
temperature based on 1.5% reduction in capacity per C included in determining Cpu1 and Cpu2
temperature above 30 C as per Table 4 IEEE Std C57.91- as per IEEE C57.91-1995 (Clause 6.4)
1995
Transformer capacity multiplier at Tmin site ambient Cpu2= 1.16
temperature based on 1% increase in capacity per C
temperature below 30 C as per Table 4 IEEE Std C57.91-
1995

Transformer Resistance, in PU ONAN base Rt= 0.44% =Zt/SQRT(1+Txr^2)

Transformer reactance, in PU ONAN base Xt= ### =SQRT(Zt^2-Rt^2)

Required transformer ONAN capacity (at 30 deg C ambient) Kone


to evacuate generator active and reactive generation at
maximum ambient temperature and generator lagging
power factor operation

Required transformer ONAN capacity (at 30 deg C ambient) Ktwo


to evacuate generator active and reactive generation at
maximum ambient temperature and generator leading
power factor operation

Required transformer ONAN capacity (at 30 deg C ambient) Kthree


to evacuate generator active and reactive generation at
minimum ambient temperature and generator lagging
power factor operation.

Required transformer ONAN capacity (at 30 deg C ambient) Kfour


to evacuate generator active and reactive generation at
minimum ambient temperature and generator leading
power factor operation

Page 2 of 2

You might also like