Transformer Sizing
Transformer Sizing
Transformer Sizing
CLIENT: Zakum Development Company (ZADCO) PAGE COUNT LAST PAGE No.
PROJECT: Zirku Island Power Upgrade FEED SUMMARY SUMMARY
CALCULATION TITLE: TOTAL CALC BODY PAGES: 11 11
TOTAL ATTACH. PAGES: 10
POWER TRANSFORMER SIZING
TOTAL PAGES: 21
CALCULATION NUMBER
PROJECT or W.O. NO. DISCIPLINE CODE SEQUENCE NO. REV NO.
P8374-CN - 421-E - 0039 - A
REVISION HISTORY
REV REV DATE PREPARER REVIEWER/CHECKER CONFIRMATION
NO. PRINTED NAME PRINTED NAME REVISION DESCRIPTION REQUIRED
AND SIGNATURE AND SIGNATURE YES NO
###
Page 1 of 2
10) DEFINITION
ONAF rating multiplier times ONAN rating MF= 1 Since transformer is desired to be of
only ONAN rating.
Transformer capacity multiplier at Tmax site ambient Cpu1= 0.625 An additional 50C Margin has been
temperature based on 1.5% reduction in capacity per C included in determining Cpu1 and Cpu2
temperature above 30 C as per Table 4 IEEE Std C57.91- as per IEEE C57.91-1995 (Clause 6.4)
1995
Transformer capacity multiplier at Tmin site ambient Cpu2= 1.16
temperature based on 1% increase in capacity per C
temperature below 30 C as per Table 4 IEEE Std C57.91-
1995
Page 2 of 2