Fact Sheet CabD 3000 en PDF
Fact Sheet CabD 3000 en PDF
Fact Sheet CabD 3000 en PDF
CabD 3000
Power system
Description
CabD is Deltas robust indoor cabinet developed for expandable telecom power systems. The number 3000 defines
the maximum current carrying capacity of single cabinet bus bars. Total load current in parallel configurations may be
from 1000 A to over 10000 A.
A complete system includes high efficiency rectifiers, AC and DC connections, battery connection and the
advanced ORION controller. The system is typically organized in bulk power concept. The rectifiers are housed in a
rectifier cabinet including the AC inputs. The battery connections locate in specific cabinet and load connections in
distribution cabinet. Optionally the rectifiers, battery connection and even one load distribution row are possible to be
configured in a single cabinet.
The multi cabinet CabD 3000 power system is easy to define with a table-based technical configuration file. Finally,
Delta factory configures the cabinets to be individually packed for delivery.
Delta is known for quality and product reliability in this solution that has been combined to optimize the total cost
of ownership.
Main features
Scalable power system up to 144 kW per
cabinet and max 768 kW parallel
Truly modular building blocks
Mirroring the system built for top entry or
bottom entry for cabling
High efficiency rectifiers up to 95 %
Enhanced monitoring and controlling with
ORION controller
Applications
Central offices
Mobile telephone switching offices
Data centers
3791701000
CabD 3000
Power system
Technical specifications
DPS 6000B-48-12 CabD DPS 6000B-48-24 DPS 4000B-48-18 CabD DPS 4000B-48-36
Rectifier section
1500 CabD 3000 1500 CabD 3000
Rectifier module DPR 6000B-48 DPR 6000B-48 DPR 4000B-48 DPR 4000B-48
Efficiency 95 % 95 % 95 % 95 %
Install power (max.
72 kW 144 kW 72 kW 144 kW
per cabinet)
320 (*) - 528 VRMS L-L, 320 - 528 VRMS L-L, 184 - 300 VRMS L-N, 184 - 300 VRMS L-N,
Input voltage range (* linear power derating below (* linear power derating below (* linear power derating below (* linear power derating below
until 266 VRMS L-L (4500 W) ) until 266 VRMS L-L (4500 W) ) until 88 VRMS L-L (1500 W) ) until 88 VRMS L-L (1500 W) )
Input current (3 48 ARMS (per rectifier shelf) 48 ARMS (per rectifier shelf) 48 ARMS (per rectifier shelf) 48 ARMS (per rectifier shelf)
phase) 144 ARMS (per cabinet) 288 ARMS (per cabinet) 144 ARMS (per cabinet) 288 ARMS (per cabinet)
Input fuse (recom.) 3 x (3 x 50 A) 6 x (3 x 50 A) 3 x (3 x 50 A) 6 x (3 x 50 A)
Internal OVP, Inbuilt fuses Internal OVP, Inbuilt fuses Internal OVP, Inbuilt fuses Internal OVP, Inbuilt fuses
Input protection
High input voltage High input voltage High input voltage High input voltage
Inbuilt fuses (all poles) Inbuilt fuses (all poles) Inbuilt fuses (both poles) Inbuilt fuses (both poles)
Output protection High voltage High voltage High voltage High voltage
Over-temperature protection Over-temperature prot. Over-temperature prot. Over-temperature prot.
www.deltapowersolutions.com
FS_CabD_3000_en.docx / Rev. 03 / RP