Secondary Unit Substations-Secondary Below 1000
Secondary Unit Substations-Secondary Below 1000
Secondary Unit Substations-Secondary Below 1000
0-1
April 2016
Sheet 14 001
ii
Transformer Product Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-2
Transformer Cooling Classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-3 1
Transformer Fluids Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-4
National Electrical Code (NFPA 70 NEC) Requirements. . . . . . . . . . . . 14.0-5
Product Overview
2
DOE 2016 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-9
Types of Distribution Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-10 3
Cable Terminal Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-11
Type MVS Load Interrupter Switchgear . . . . . . . . . . . . . . . . . . . . . . . . 14.0-11 4
Metal-Enclosed Switchgear Assembly, Type MSB . . . . . . . . . . . . . . . . 14.0-11
Liquid-Filled Substation Transformers . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-12 5
VPI/VPE Dry-Type Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-19
Cast Coil Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-21
RESIBLOC Epoxy Cast Resin Transformers. . . . . . . . . . . . . . . . . . . . . . 14.0-23
6
Magnum DS Low Voltage Metal-Enclosed Switchgear . . . . . . . . . . . . 14.0-25
Pow-R-Line C Switchboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-25 7
Secondary Unit Substation Plug-and-Play . . . . . . . . . . . . . . . . . . . . . . 14.0-26
TC-100 Temp Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-27 8
Layout Dimensions
Composite Floor Plans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-28
9
Substation with Air Terminal Chamber (ATC). . . . . . . . . . . . . . . . . . . . 14.0-32
Primary Switching Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-34
Transformers and Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-35
10
Outdoor Secondary Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-39
Technical Data 11
Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-41
Primary Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-42 12
Secondary Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.0-47
Specifications
13
See Eatons Product Specification Guide, available on CD or on the Web.
CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010
Section 16311 Section 26 11 16.11 14
15
16
17
18
19
20
MVS Primary Switch and DSII Low Voltage Metal-Enclosed Switchgear
21
11 Secondary
Unit Substation
34.5 kV 600 V 300 kVA
3750 kVA
14 Mineral OilTypical
outdoor installation.
Transformer is part
of a close-coupled
Complies with
ANSI C57.12.00
(provides secondary assembly that may and C57.12.90,
SiliconeApplied
system voltage) include both primary CSA88
12 where flammability
is a concern.
and secondary
UL, FM
equipment.
available
Envirotemp FR3
High short-circuit
Specified where Seismic Zone 4
13 flammability, clean-up
strength.
certification
and life extension are Sealed tank design
a concern. is impervious to the
14 environment.
Smaller footprint,
greater efficiency,
15 nonpolluting to
the environment
when filled with
Envirotemp FR3
16
17
18
19
20
21
14
15
16
17
18
19
20
21
17
18
19
20
21
15
16
17
18
19
20
21
Indoor installations using less- The installation of less-flammable with an automatic fire extinguishing
i flammable liquid-insulated liquid insulated transformers indoors system and liquid containment or
transformers must comply with without a vault in a Type I or II non- the transformer must be installed
NEC Article 450.23 part A, which combustible building where no complying with NEC 450.26.
ii defines the requirements for three combustible materials are stored
types of indoor transformer installa- requires that: NEC Article 450.28, modification
tions as detailed in Table 14.0-7: of transformers, requires that when
1 A liquid confinement area modifications are made to transformers
Type I or II (non-combustible) be provided in existing installations that change
building with no combustible The transformer be filled with a the transformer type, the transformers
2 materials stored in area listed less-flammable insulating must be marked to show the type
Combustible building or liquid with a minimum 300 C of insulating liquid installed and the
combustibles stored in area fire point installations must comply with current
3 Rating greater than 35 kV The installation complies with the
requirements of the NEC. Examples of
listing requirements (either UL or changes include replacing a complete
FM) of the liquid in the transformer transformer (retrofitting) or replace-
4 ment of the liquid only (retrofilling).
Liquid containment can be offered as Askarel (PCB) and conventional mineral
a transformer accessory for indoor oil-filled transformers are frequently
5 installations by the transformer retrofitted or retrofilled using less-
manufacturer. If the installation cannot flammable liquids. NEC 110.34 sets
comply with the liquid listing require- minimum clear work space dimensions
6 ments, it must either be provided around transformers.
Table 14.0-7. NEC Article 450 Requirements
7 Installation
Type
NEC
Requirements
Indoor Installations
8 Transformer rated m35 kV, installed in a non-combustible building Less-flammable fluid filled with liquid confinement, and equipped
with no combustible materials stored in area. and installed per either of the following listing requirements 1:
Underwriters Laboratories Classification
9 FM Global
Less-flammable fluid filled with liquid confinement and
auto extinguishment
10 Vault per NEC 450, Part III 1
Dry-type transformer
Transformer rated m35 kV, installed in a combustible building or in a Less-flammable fluid filled with liquid confinement and
11 building with combustible materials stored in area. auto extinguishment 1
Vault per NEC 450, Part III 1
Dry-type transformer in accordance with NEC 450.21 (B)
17
18
19
20
21
20
21
The primary circuit shall have Transformers shall be capable of Transformers with greater than
i overcurrent protection that limits maintaining rated basic lightning 100 gal (380 L) of non-approved
the let-through current (I2t) to a impulse insulation level (BIL) at a fluids:
specified maximum value as listed minimum tilt of 1.5 from vertical 3-hour fire-rated construction.
ii in Table 14.0-10 and in Section 2.3.5
If multiple transformers are
of the FM approval Standard 3990. Transformers will be supplied with
appropriate pressure withstand, present, also provide one of
Current-limiting fusing and its
1 pressure relief and other devices noted the following:
functional equivalents are designed
to interrupt a high current internal above when FM Approval is specified. 3-hour fire-rated subdivisions
fault before the tank withstand The required overcurrent protection for each transformer, or
2 pressure level is reached. If protec- may be supplied integral to the trans-
Automatic sprinklers, FM
tion is designed to vent gas during former or via switchgear feeding the
approved foam-water or
operation, such as with expulsion transformer as noted above depending
3 how it is specified by the user. FM approved water mist
fuses, this protection shall be
protection per Section 2.2.3
located outside the transformer Additional FM Global Requirements
tank. Certain exceptions apply Applying to All Indoor Transformers (Non-approved fluids generally applies
4 and permit expulsion fusing to be to mineral oil.)
mounted in the tank if in series and Indoor installation requirements,
properly coordinated with current according to FM loss prevention data Table 14.0-9. FM and UL Pressure Relief
5 limiting fusing (LPD) 5-4, consist of requirements for Device Required Ratings
all transformer types and likely would kVA Rating Flow Rate
The transformer shall have an apply to those who are FM insured or SCFM at 15PSI
additional nameplate with the FM Three- Single-
6 approval mark with the following
those choosing FM Approval as their Phase Phase (103 kPa)
means to comply with the listing
data: tank pressure rating, fuse part restrictions of NEC 450.23 for less- 112.5 37.5 35
number, pressure relief device part
7 number, and requirements particular
flammable insulated transformers. 150
300
50
100
50
100
to the type of installation Transformer If transformers cannot be located out- 1000 333 350
manufacturers instructed to design doors, provide a detached dedicated 2000 667 700
8 and build transformers per the UL building or room with location and 10,000 3333 5000
Classification Mark (refer to UL construction safeguards as noted in
Classification Mark in 17.0-5) the Figure 14.0-1 and Figure 14.0-9. Note: For kVA ratings not listed, use next
9 utilized less-flammable fluid should highest rating in table.
be designed accordingly. If primary Arrange transformer rooms for direct
access only from outdoors or install Table 14.0-10. FM and UL Maximum I2t
overcurrent protection is specified
10 as integral to the transformer, trans- transformer(s) in a detached building Let-Through Required Ratings
former manufacturers should also of the following construction: kVA Rating Current Other
Limiting Protection
11 comply. Otherwise, meeting FM Dry-type, gas-insulated and Three- Single-
Fusing
Approval requirements will be the Phase Phase
FM approved or equivalent
responsibility of the user. less-flammable liquid insulated 45 15 500,000 700,000
12 For grounded wye secondary wind- transformers: 75 25 500,000 800,000
ings of 150 V or more and rated at Liquid containment 112.5 37.5 550,000 900,000
1000 or more nominal amperes, a 150 50 600,000 1,000,000
Noncombustible building
13 notification tag shall be provided by
construction
225 75 650,000 1,200,000
the manufacturer, secured to the low 300 100 750,000 1,400,000
voltage neutral bushing, advising Non-FM Approved transformers 500 167 900,000 1,900,000
750 250 1,100,000 2,200,000
14 that the transformer installation with FM Approved transformer
requires ground fault relay protec- fluids: 1000 333 1,250,000 3,400,000
tion prior to energization (if not 1500 500 1,500,000 4,500,000
Liquid containment
2000 667 1,750,000 6,000,000
15 installed at time of manufacturing) 1-hour fire-rated construction if 2500 833 2,000,000 7,500,000
Indoor units greater than 500 kVA no fire protection is provided, or 3000 1000 2,250,000 9,000,000
and outdoor units greater than 3750 1250 2,500,000 11,000,000
16 Noncombustible construction if
2500 kVA shall be equipped with 5000 1667 3,000,000 14,000,000
fire protection (automatic sprin-
alarm contacts on the pressure relief 7500 2500 3,000,000 14,000,000
klers, FM Approved foam-water
device. Transformer above 2500 kVA 10,000 3333 3,000,000 14,000,000
17 in all locations shall be equipped
sprinklers, or FM Approved water
mist) is also provided
with a rapid rise relay Note: For kVA ratings not listed, use next
Transformers with no more than lowest rating in table.
Three-phase pad-mounted and
18 substation transformers shall be 100 gal (380 L) of non-approved
equipped with an oil level gauge. fluids: 1-hour fire-rated construction
Additionally, all transformers rated
19 750 kVA or higher shall be equipped
with a liquid temperature indicator
and pressure-vacuum gauge
20
21
DOE 2016 Requirements Table 14.0-12. High Voltage 15 kV and Below. Low Voltage 600 V and
Below. Copper Conductor Windings. Losses in Watts. Three-Phase i
This information details the minimum efficiencies required Dry-Type Unit Substation Transformers 1
of distribution transformers rated 2500 kVA and below, VPI, 15 kV Primary 150C Temp. Rise
as defined by the Department of Energy (DOE) Federal kVA No Load Loss Total 4695 kV BIL
ii
Regulation for Distribution Transformers. Load at 100% Losses Total Losses at
(Watts) Load and at 100% 50% Load and
This federal regulation requires all transformers rated 170 C Ref. Load and 75C Ref. Temp. 1
2500 kVA and below with a primary voltage of 35,000 V and Temp. 170 C per DOE (Watts)
below, and a low voltage of 600 V and below to meet the (Watts) (Watts)
efficiency levels as stated below. This regulation affects all 300 2 950 3450 4400 1806 2
transformers in scope manufactured as of January 1, 2016. 500 2 1300 5650 6950 2551
This regulation affects all applicable transformers installed in 750 2 1600 8600 10,200 3329
the U.S., regardless of domestic or foreign manufacturing. 1000 2 1850 10,700 12,550 4032 3
1500 2 2700 11,850 14,550 5287
Note: There are transformers exempt from DOE efficiency 2000 2 2950 16,900 19,850 6441
requirements. Contact Eaton with any questions.
2500 2 4500 14,500 19,000 7419 4
3000 6200 26,100 32,300 N/A
Table 14.0-11. DOE 2016 Transformer Efficiencies Three-Phase 3750 7100 33,400 40,500 N/A
Liquid Filled Transformers
Three-Phase Efficiency No-Load Load Loss Total Total
5000 13,000 40,000 53,000 N/A 5
7500 18,500 45,000 63,500 N/A
kVA at 50% (Watts) at 100% Losses Losses at 10,000 23,500 55,000 78,500 N/A
Load (Watts) at 100% 50% Load
(Watts) (Watts)
1
2
Losses offered are typical only, not guaranteed. 6
Units must typically meet the new DOE efficiency guideline levels with
300 99.27 609 1977 2586 1103 noted losses complying with such.
500 99.35 903 2932 3835 1636
750 99.4 1250 4057 5307 2264 Table 14.0-13. High Voltage 15 kV and Below. Low Voltage 600 V and 7
1000 99.43 1582 5136 6718 2866 Below. Copper Conductor Windings. Losses in Watts. Three-Phase
1500 99.48 2164 7025 9189 3920 Dry-Type Unit Substation Transformers 3
2000 99.51 2718 8824 11,542 4924 Cast, 15 kV Primary 115 C Temp. Rise 8
2500 99.53 3258 10,578 13,836 5903
kVA No Load Loss Total 4695 kV BIL
Load at 100% Losses Total Losses at
(Watts) Load and at 100% 50% Load and 9
135 C Ref. Load and 75 C Ref. Temp.
Temp. 135 C per DOE (Watts)
(Watts) (Watts) 10
300 4 950 3400 4350 1806
500 4 1350 4450 5800 2551
750 4 2050 4700 6750 3329 11
1000 4 2350 7200 9550 4032
1500 4 2900 12,200 15,100 5287
2000 4 3150 13,200 16,350 6441 12
2500 4 4350 16,150 20,500 7419
3000 7200 20,000 27,200 N/A
3750 8600 21,000 29,600 N/A 13
5000 13,500 30,000 43,500 N/A
7500 20,000 35,000 55,000 N/A
3
10,000 22,500 45,000 67,500 N/A 14
Losses offered are typical only, not guaranteed.
4 Units must typically meet the new DOE efficiency guideline levels with
noted losses complying with such. 15
16
17
18
19
20
21
l l
ii
l l
1
Selector Loop
l l
2
l
l
3
l
i Liquid-Filled Substation Design and Technology Note: Envirotemp FR3 fluid-filled trans-
formers are a potential cost, footprint and/
Transformers Liquid-filled transformers are custom or weight reducing option. This design is
designed and manufactured. Coils are available due to the insulation life extending
ii Application Description of the rectangular design. Primary
windings are comprised of wire
properties that Envirotemp FR3 provides.
Insulation life of an Envirotemp FR3 fluid-
Eatons liquid-filled substation conductors, either aluminum or filled transformer operating at a 75 C
transformers are custom-designed average winding rise is expected to double
1 power transformers suitable for both
copper. Secondary windings are either
the insulation life of a mineral oil-filled
full height sheet conductors or wire transformer operating at 65 C average
indoor and outdoor applications. conductor dependent on the voltage winding rise. This design is recognized
2 The transformers are of the sealed and kVA rating. The layer-to-layer in IEEE C57.154 and is available as a UL
tank design and suitable for use insulation is coated with a diamond Listed transformer. Contact Eaton for
in coordinated unit substation in pattern of B-stage epoxy adhesive, more information.
3 most any type of application and which cures during processing to
Material used for cores is non-aging,
environment. Typical applications form a high-strength bond. This bond
restrains the windings during opera- cold rolled, high permeability, grain-
of liquid-filled transformers are:
4 tion and under short-circuit stresses. oriented silicone steel or amorphous
Utility substations metal. Cores are rigidly braced to
Liquid-filled transformers are suitable reduce sound levels and losses in
Pulp and paper mills for use up to 65 C average winding
5 Steel mills rise (75 C average winding rise with
the finished product.
Chemical plants/refineries Envirotemp FR3 fluid) over a maxi- The core and coil assembly is immersed
mum ambient temperature of 40 C, in either mineral oil, silicone or
6 General industry
not to exceed 30 C average for any environmentally friendly fluids
Commercial buildings
24-hour period. The transformer may and is contained in a sealed tank.
be specified as 55 C rise, in which
7 Benefits case the transformer has a self-cooled
Flat, tubular or panel radiators may be
Custom-design flexibility to meet mounted on the front and back of the
(OA) overload capability of 112%
special customer needs and tank. The liquid circulates through the
(55/65 C rise) or 122% (55/75 C rise)
8 applications such as retrofitting without loss of life.
tank and radiators by means of natural
existing liquid-filled and dry convection, and effectively cools the
transformers core and coil assembly.
9 Computerized loss-evaluated
designs for specific customer
10 load and evaluation criteria
Standard Features
11 High short-circuit strength
IEEE short-time overload capability
Impervious to the environment
12 through sealed design
Lowest first cost and cost of
13 ownership to cast/dry designs
Available as mineral oil-filled or
with less-flammable liquids, such
14 as silicone or Envirotemp FR3
an environmentally friendly fluid
15
16
17
18
19
20
21
LIQUID
TEMPERATURE
4
GAUGE
For easy
monitoring of 5
oil temperature.
Available with LOW VOLTAGE
BUSHINGS
multiple alarm
contacts. Sidewall- 6
mounted
low voltage
DE-ENERGIZED
TAP CHANGER
molded epoxy 7
or porcelain
Tap changer bushings with
is externally NEMA spades.
operable. 8
THROAT
FULL
LENGTH
Allows
connection
9
CABINET to low
voltage gear.
10
CONTROL
BOX
Weather- 11
resistant,
dust-proof,
COOLING
NEMA-rated
RADIATORS
12
control box
for controls
and alarm
contacts. 13
14
GROUND PADS
Non-corrosive, stainless
steel or copper faced 15
ground pads on the front
and rear.
BASE
16
Suitable for skidding,
rolling and jacking.
DRAIN FILTERING VALVE
17
The combination drain and
filtering valve contains a fluid
sampling device. 18
Liquid-Filled Substation Transformer
19
20
21
12
13
14
15
16
17
18
19
20
21
17
18
19
20
VFI Primary with Secondary Cable VFI with Secondary Unit Substation VFI End View with Secondary 21
Connections and Containment Pan Cable Connections
Triplex Indoor Power Center Base ratings of 7502500 kVA Optional substation transformer
i Installation and removal of either dry- Three-phase, 50 or 60 Hz accessories:
type or liquid-filled transformers can be distribution substation transformers Air terminal chambers
Primary voltage through 15 kV Control boxes
ii difficult when encountering a size and
weight constrained entry. An Eaton Secondary voltage through 600 V Gauges (with or without
Triplex Indoor Power Center (IPC) Envirotemp FR3 fluid contacts)
1 offers a modular designed efficient
Temperature rise options: 55 C, Rapid rise relays
liquid-filled transformer that may be
55 C to 65 C, 65 C, 55 C to 75 C, Removable radiators
installed even when access is limited by
75 C
2 a freight elevator or doorway. A Triplex
FM approved
Containment pans
IPC is a three-phase transformer
UL Listed/Classified Removable castors
assembly consisting of three single-
3 phase Envirotemp FR3 fluid-filled Infrared viewing windows
transformers connected into one Air insulated bus for
complete assembly built according interconnections
4 to applicable D.O.E. (Department of
Energy), ANSI/IEEE, UL, FM and NEMA
standards and customer supplied
5 specifications. The Triplex IPC shall be
constructed in the field with single-
phase transformers and partially
6 assembled factory prepackaged
modules. The core and coil construc-
tion uses the same proven methods
7 as the conventional three-phase
substation assemblies. Flawless fire
safety of Triplex IPC is attributed to
8 the use of Envirotemp FR3 fluid,
a less-flammable and biodegradable
dielectric fluid. Integrated switching
9 and protection schemes are available
with Triplex designs. Castors may be
added to further facilitate transformer
10 installation and to reduce the transmis-
sion of vibrations to the surrounding
structures. Downtime may be reduced
11 by stocking a spare single-phase
transformer for emergency situations.
12
13
14
15
16
17
18
19
20
21
19
20
21
500 +15%
6 750 863
1000 1150
1500 1725
2000 2300
7 2500 +25% 3125
3750 4688
5000 6250
8 7500 9375
10,000 12,500
12,000 +33% 16,000
9
Table 14.0-17. Three-Phase, Dual or Triple Temperature kVA Ratings 1
Three-Phase kVA Self-Cooled and Forced-Air Cooled with PEAK Triple Rated 55 C/75 C Temperature Rise
10 55 C Rise 65 C Rise 75 C Rise 55 C Rise 65 C Rise 75 C Rise
KNAN KNAN KNAN KNAN/KNAF KNAN/KNAF KNAN/KNAF
14 10,000
12,000
11,200
13,440
12,208
14,650
12,500
16,000
14,900
17,920
15,260
16,533
1 If 65 C Rise is the base rating, the 75 C slash rating will increase the kVA capacity by 12%.
15
16
17
18
19
20
21
VPI/VPE Dry-Type i
Transformers
Application Description Ventilation ii
Eatons VPI and VPE transformers Louvers
are custom-designed dry-type power
transformers, which give environmental
1
Fan Control/
protection, for both indoor and outdoor Winding
applications. The transformers are
explosion-resistant, fire-resistant,
Temperature
Indicator
2
non-polluting to the environment, and Core-Coil
Removable Assembly
ideally suitable for use in coordinated
unit substations. Typical applications Panel 3
of VPI/VPE transformers are:
Schools, hospitals, shopping centers 4
High-rise buildings
Industrial environments
5
Benefits
Custom-design flexibility to meet Fan Motor and Blades
6
special customer needs and
Dry-Type Substation Transformer
applications
Computerized loss-evaluated Design and Technology
7
designs for specific customer load
and evaluation criteria The dry-type transformers are custom Taps are provided on the central section
Environmental protection
designed and manufactured with coils of the HV coil face. Taps are accessed by 8
insulated with a 220 C, Class H, removing enclosure panels, and taps are
Low maintenance insulation system. Environmental changed by moving the flexible bolted
High short-circuit strength protection is provided by vacuum links from one connecting point to the 9
IEEE short-time overload capability pressure impregnation with polyester other. To simplify these changes, the
Aluminum or copper windings resin (VPI). Enhanced environmental connection points are clearly identified.
Available in NEMA 1, 2 and
protection is available through the use 10
of silicone resin encapsulation (VPE). Material used for cores is non-aging,
3R enclosures cold rolled, high permeability, grain-
Both systems are superior to the
Economical conventional dry-type technology oriented silicone steel. Cores are con- 11
known as Dip and Bake. Transformers structed with step lap mitered joints and
Ratings with Class H insulation are suitable for are rigidly braced to reduce sound levels
112.53750 kVA use up to 150 C average rise over a and losses in the finished product. 12
Primary voltages: 600 V 35 kV maximum ambient temperature of To reduce the transfer of noise to the
40 C, not to exceed 30 C average for case, the core is mounted on neoprene
Primary BIL: up to 150 kV
any 24-hour period. Other temperature rubber vibration dampeners. The core
13
Secondary voltages: 120 V 15 kV rise options are 80 C and 115 C, which is electrically grounded by means of
Secondary BIL: up to 75 kV allow the transformer to be overloaded a flexible ground braid.
Temperature rise: 80/115/150 C up to 150 C rise. 14
The enclosure has removable panels
for access to taps and for core and coil
inspection. The complete case can be 15
removed and knocked down to reduce
size and weight for rigging into tight
locations. 16
17
18
19
20
21
10
11
12
13
14
15
16
17
18
19
20
21
21
10
11
12
13
14
15
16
17
18
19
20
21
21
10
11
12
13
14
15
16
17
18
19
20
21
ii
8
Magnum DS Switchgear with Power Circuit Breaker Pow-R-Line C 9
Product Description Construction Details
Eatons Magnum DS switchgear has a 50-year history of 6000 A main bus maximum 10
power circuit breaker and switchgear development that has Front and rear accessmain section front and/or
set industry standards for quality, reliability, maintainability side accessible
and extended operating life. Magnum DS switchgear is an Feeder devices panel mounted
11
assembled metal enclosure that houses drawout power Sections rear aligned, or front and rear aligned
circuit breakers and typically includes control and metering
devices. Low voltage switchgear is applied at 600 V and less.
Not designed for mounting against a wall, self-supporting 12
and requires code clearance at the rear
20
21
11 24VDC CONTROL
+
-
7
8
7
8
24+
24-
7
8
7
8
+
-
24VDC CONTROL
5310
9 9 9 9
MV 52 AUX b 5311 MV 52 AUX b
10 10 10 10
3CB18
11 11 11 11
12 LV 52 MAIN AUX b
12
13
12
13
3CB19 12
13
12
13 F1
LV 52 MAIN AUX b
ALARM FROM XFMR TO MSB 14 14 ALARM FROM XFMR TO MSB 240/120VAC TO XFMR FROM LVA 14 14 Y 240/120VAC TO XFMR FROM LVA
15 15 15 15 F2
16 16 16 16 A
TB619
17
18
17
18
B
SH/COM
RS-485 MODBUS TO PXG600A
19 19 19 19
MV 52 REMOTE OPEN TB620 MV 52 REMOTE OPEN
20 20 20 20
21 21 TB621 21 21
MV 52 REMOTE CLOSE MV 52 REMOTE CLOSE
14 ETR4000 TRIP
22
23
22
23
TB622
TB623
TB624
22
23
22
23
ETR4000 TRIP
24 24 24 24
15
16 CT WIRING TO RUN DIRECT BETWEEN MSB AND SWGR. NO TERMINAL BLOCKS IN XFMR.
STBB2
B2CG
B2C1
ETR-4000 B2C2 (3) CTS MOUNTED IN LVA TO ETR-4000
17 B2C3
STBB1
B1C1
B1G1
B1C2
18 DT 520MV B1G2
B1C3
(3) CTS MOUNTED IN LVA TO DT 520MV
B1G3
MVCG
20
Figure 14.0-8. Plug-and-Play Diagram
21
TC-100 Transformer Form C contacts are provided for Features and Benefits
i
notification of alarm conditions. A
Temperature Controller for red LED illuminates to indicate that the Control
Dry-Type Transformers alarm is actuated. An internal audible Thermocouple inputs (E or K type
ii
alarm also sounds when the unit goes thermocouples)
into alarm condition. This audible
Automatic correlation throughout
buzzer can be silenced without cancel-
entire temperature range to 1
ing the alarm. The alarm and trip relays
compensate for thermocouple
can be configured as a fail-safe relay
non-linearity
(normally energized when the unit is
powered up). For example, if the alarm Programmable on and off set points 2
relay was configured as a fail-safe; if Alarm relay for remote monitoring
supply control power to the TC-100 is Trip relay for remote monitoring
interrupted, the alarm relay changes Two fan power relays
3
state for notification of this condition.
Fan failure detection to start a
The alarm circuit is also used for
notification of an open or a missing
backup fan or alarm 4
thermocouple. If a thermocouple were Fan exerciser (cycle time and
to open, the alarm relay operates and duration) to reduce fan wear
the corresponding channel will read - Fans can be operated automatically 5
on the LED display. It is important to or manually
note that a failed thermocouple
TC-100
will not cause the device to trip the Metering 6
transformer offline. Average temperature
(all three windings)
General Description Form C contacts are provided to trip 7
Maximum instantaneous
The TC-100 Transformer Temperature the transformer offline if any of the temperature (all three windings)
Controller monitors up to three venti- winding temperatures exceed the trip
Maximum temperature memory
lated dry-type transformer windings setting. A red LED indicates that the
per winding
8
and one ambient temperature. The trip relay has actuated.
TC-100 operates relays by comparing Fans hours of operation
A test function is provided to: test the Winding 1, Winding 2, Winding 3 9
the highest winding temperature to
digital display and all of the LEDs; and ambient temperature
stored set point temperatures and
simulate over-temperature conditions;
displays four thermocouple inputs,
and check the internal temperature of Monitoring 10
as well as the stored maximum
the monitor. Trending
temperature and its associated wind-
ing. The unit provides fans, alarm and A 420 mA analog signal is provided Fan failure
trip output relays. Up to two fans can for remote indication or for use with Fan wear 11
be controlled via the TC-100. Each fan SCADA systems. Alarm log
operating contact is fuse protected.
A yellow LED indicates that fans are The TC-100 has built-in monitoring Trip log 12
on. A fan exerciser turns the fans on functions and logging functions to Test mode
automatically at periodic intervals to help you shed some light on the Detect failed sensors
prevent fan motor seizing (on-time unknowns of the operation of your
Self-diagnostics
13
and interval is programmable). transformer. Temperature trending lets
you understand the hour of the day Communications
that the transformer runs hotter, and USB port in the front 14
modify its loading to extend the life of
Modbus-RTU communications
your transformer; logging information
lets you restore the operation of your Programming and monitoring 15
system faster, by letting you correlate software (the unit can be completely
tripping and alarming events to the programmed through the front of
overall conditions of your system; the unit) 16
and fan wear information can be 420 mA output for integration with
used to perform preventive mainte- SCADA systems
nance to increase the uptime in 17
your transformers. Hardware
One trip relay (Form C)
One alarm relay (Form C) 18
Two power fan relays (1 NO each)
Two digital inputs 19
420 mA output for integration with
SCADA systems
Local Alarm 95 db 20
Available in semi-flush or hinge
panel-mounting versions
21
Rear
ii
D1F D2F
4
5
WP W1 WTX W2 WS
6 Front
16 Magnum DS and SB switchgear (rear access) 22.00 (558.8) 45.00 (1143.0) 20.1
Pow-R-Line C switchboard (front access) 20.00 (508.0) 24.00 (609.6) 21.1 (All)
Pow-R-Line C switchboard (rear access) 20.00 (508.0) 24.00 (609.6) 21.2 (All)
17 Pow-R-Line i switchboard (rear access) 20.00 (508.0) 24.00 (609.6) 21.3 (All)
18
19
20
21
Dimensions for estimating purposes only.
Transition Section/Throat
1
Primary Equipment
D1R
DTX DS
Section/Throat
DP
2
Transition
CL
of Transformer
3
D1F
5
Door
WP W TX W2 WS Swing
W1
6
Walk-in Aisle (if used)
7
Figure 14.0-10. Liquid-Filled, Outdoor EnclosureTop View
1 Radiator position and number of radiators will vary based on design.
8
Table 14.0-20. Primary Equipment Dimension References Legend:
Primary Dimensions Reference MVC = Medium Voltage Motor Control,
Equipment Page(s) Type AMPGARD 9
MVS = Medium Voltage Metal-Enclosed
Transformer WTX, DTX Page 14.0-35 Switches, Type MVS
MVS
ME
WP, DP
WP, DP
Page 14.0-34
Page 14.0-34
ME = Medium Voltage Metal-Enclosed 10
Breakers, Type MEB, MSB
MC WP, DP Tab 5
MC = Medium Voltage Metal-Clad Breaker
Air Terminal Chamber (ATC) or Transition Section/ThroatDimensions in Inches (mm) Assemblies, Type VacClad-W
Voltage Primary Three-Phase, Three-Wire or Three-Phase Four-Wire
11
kV Equipment
W1 D1F D1R
19
20
21
Dimensions for estimating purposes only.
ii 1 1
1
DP
DTX DS
2 Primary Equipment Transition Transformer Transition Secondary Equipment
Section Section
(Optional) (Optional)
3
4 Front
WP W1 WTX W2 WS
5
Figure 14.0-11. Ventilated Dry-Type, RESIBLOC and Cast Coil, IndoorTop View
1
6 Transition section may only be required for connection to existing transformers or rear alignment.
Contact Eaton for details.
13
14
15
16
17
18
19
20
21
Dimensions for estimating purposes only.
1 1 ii
DP DTX DS
2
Transformer Secondary Equipment
3
Front 5
WP W1 WTX W2 WS
6
Figure 14.0-12. Ventilated Dry-Type, RESIBLOC and Cast Coil, OutdoorTop View
1 Transition section may only be required for connection to existing transformers or rear alignment. Contact Eaton for details.
7
Table 14.0-24. Primary Equipment Dimension References Legend:
Primary
Equipment
Dimensions Reference
Page(s)
MVC = Medium Voltage Motor Control,
Type AMPGARD
8
MVS = Medium Voltage Metal-Enclosed
Transformer WTX, DTX Pages 14.0-37 and 14.0-38 Switches, Type MVS
MVS W P , DP Page 14.0-34 ME = Medium Voltage Metal-Enclosed 9
ME W P , DP Page 14.0-34 Breakers, Type MEB, MSB
MC W P , DP Tab 5
MC = Medium Voltage Metal-Clad Breaker
Air Terminal Chamber (ATC) or Transition Section/ThroatDimensions in Inches (mm) Assemblies, Type VacClad-W 10
Primary W1
Equipment 5 kV 15 kV 27 kV 38 kV
11
MVS 5.00 (127.0) 5.00 (127.0) 1 1
ME 5.00 (127.0) 5.00 (127.0) N/A N/A
1 1
1
MC 16.00 (406.4) 16.00 (406.4)
12
Contact Eaton.
16
17
18
19
20
21
Dimensions for estimating purposes only.
1 Transformer
D2 R
2 D1R
CL
of Transformer
4
D1F
W1 W TX W2
7
Figure 14.0-13. Liquid-Filled Indoor/Outdoor Using Air Terminal ChambersTop View
8 1 Radiator position and number of radiators will vary based on design.
Table 14.0-26. Primary ATC or Transition Section Table 14.0-27. Secondary ATC or Transition Section
9 Dimensions in Inches (mm) Dimensions in Inches (mm)
Voltage Three-Phase, Three-Wire or Three-Phase, Four-Wire Voltage W2 DS
10 kV W1 DP V
14
15
16
17
18
19
20
21
Dimensions for estimating purposes only.
Front
6
W1 WTX W2
7
Figure 14.0-14. Dry-Type Indoor/Outdoor Using Air Terminal ChambersTop View
Table 14.0-28. Primary ATC or Transition Section Table 14.0-29. Secondary ATC or Transition Section
8
Dimensions in Inches (mm) Dimensions in Inches (mm)
Voltage Three-Phase, Three-Wire or Three-Phase, Four-Wire Voltage W2 DS 9
kV W1 DP V
5 or 15
27
18.00 (457.2)
24.00 (609.6)
DTX
DTX
All 18.00 (457.2) DTX
10
38 36.00 (914.4) DTX Note: Minimum ATC widths by kVA are listed in the table above.
The width of any ATC can be expanded to allow for the installation
Note: Minimum ATC widths by kVA are listed in the table above. of additional conduits. When calculating the area of the conduit 11
The width of any ATC can be expanded to allow for the installation opening, allow for a 3.00-inch (76.2 mm) lip around the entire
of additional conduits. When calculating the area of the conduit perimeter of the ATC.
opening, allow for a 3.00-inch (76.2 mm) lip around the entire 12
perimeter of the ATC.
13
14
15
16
17
18
19
20
21
Dimensions for estimating purposes only.
5 Sectional- 5 64 108.00 (2743.2) 55.30 (1404.6) 62.00 (1574.8) 90.40 (2296.2) 95.50 (2425.7) 10.00 (254.0) 8.00 (203.2)
izing 15 64 108.00 (2743.2) 55.30 (1404.6) 62.00 (1574.8) 90.40 (2296.2) 95.50 (2425.7) 10.00 (254.0) 8.00 (203.2)
loop feed 27 60 144.00 (3657.6) 80.00 (2032.0) 3 80.00 (2032.0) 3 127.00 (3225.8) 4 135.00 (3429.0) 5 16.00 (406.4) 8.00 (203.2)
6 switches 38 30 144.00 (3657.6) 80.00 (2032.0) 3 80.00 (2032.0) 3 127.00 (3225.8) 4 135.00 (3429.0) 5 16.00 (406.4) 8.00 (203.2)
1 A transition section is required when any MVS switchgear assembly is connected to a liquid-filled transformer and when any MSB switchgear
assembly is connected to any kind of transformer. When a 5 or 15 kV MVS switchgear assembly is connected to a dry-type or cast coil transformer,
7 no transition section is required when installed indoors, but a 5.00-inch (127.0 mm) throat is required when installed outdoors.
2 Where disconnect fuses are used, add 6.00 inches (152.4 mm) to section width, 5 and 15 kV only.
3 When height of 101.50 inches (2578.1 mm) is used with fuses identified in footnote 4, the depth increases to 100.00 inches (2540.0 mm).
8 4 Height is 101.50 inches (2578.1 mm) for 27 kV MVS switchgear without fuses or with Cooper type NX fuses, and 38 kV MVS switchgear without
fuses or with GE type EJO-1 fuses.
5 Height is 110.00 inches (2794.0 mm) for 27 kV MVS switchgear without fuses or with Cooper type NX fuses, and 38 kV MVS switchgear without
fuses or with GE type EJO-1 fuses.
9 6 Can be 62.00 inches (1574.8 mm) deep if incoming cable enters from below.
Single 5 64 42.00 (1066.8) 70.00 (1778.0) 90.40 (2296.2) 95.50 (2425.7) 10.00 (254.0) 8.00 (203.2)
15 64 42.00 (1066.8) 70.00 (1778.0) 90.40 (2296.2) 95.50 (2425.7) 10.00 (254.0) 8.00 (203.2)
12 52
Duplex 5 64 78.00 (1981.2) 70.00 (1778.0) 90.40 (2296.2) 95.50 (2425.7) 10.00 (254.0) 8.00 (203.2)
13 l
52
15 64 78.00 (1981.2) 70.00 (1778.0) 90.40 (2296.2) 95.50 (2425.7) 10.00 (254.0) 8.00 (203.2)
14 Sectionalizing
loop feed
5
15
64
64
114.00 (2895.6)
114.00 (2895.6)
70.00 (1778.0)
70.00 (1778.0)
90.40 (2296.2)
90.40 (2296.2)
95.50 (2425.7)
95.50 (2425.7)
10.00 (254.0)
10.00 (254.0)
8.00 (203.2)
8.00 (203.2)
switches 52
15 7 A transition section is required when any MVS switchgear assembly is connected to a liquid-filled transformer and when any MSB switchgear
assembly is connected to any kind of transformer. When a 5 or 15 kV MVS switchgear assembly is connected to a dry-type or cast coil transformer,
no transition section is required when installed indoors, but a 5.00-inch (127.0 mm) throat is required when installed outdoors.
16
WC WC WC WC WC WC WC WC WC WC
Table 14.0-32. Approximate Weights in Lb (kg)
6.6
6.6 (167.6) (167.6) 6.6 (167.6) Description Indoor Outdoor
17 CC CC CC
5 or 15 kV Class
MSB section 1600 (726) 1900 (863)
MVS section 1500 (681) 1800 (817)
18 (non-fused)
DP Fuses (3) add 200 (91) 200 (91)
Transition section 300 (136)
19 Outdoor throat 1200 (544)
25.8 or 38 kV Class
MVS section 2000 (908) 2400 (1090)
20 WP WP WP
(non-fused)
Fuses (3) add 300 (136) 300 (136)
Single or Duplex Sectionalized Loop Feed Transition section 1100 (499)
SelectorPlan View Plan View Plan View Outdoor throat 1200 (544)
21 Figure 14.0-15. Primary Equipment Floor Plan Dimensions for estimating purposes only.
Liquid-Filled Transformers i
Table 14.0-33. Oil-Filled Standard Design, 60 Hz, HV Delta, LV at 600 V Class (30 kV BIL) Indoor or Outdoor Application
kVA HV, kV HV BIL, kV Dimensions in Inches (mm) Weight Liquid
HTX WTX DTX Lb (kg) Gallons (Liters) ii
Oil-Filled 55, 65 and 75 C Rise
300 5 or 15 60 or 95 74.05 (1880.9) 65.50 (1663.7) 53.50 (1358.9) 4800 (2177) 330 (1249) 1
500 5 or 15 60 or 95 74.05 (1880.9) 67.50 (1714.5) 57.50 (1460.5) 5800 (2631) 330 (1249)
750 5 or 15 60 or 95 74.05 (1880.9) 71.50 (1816.1) 59.50 (1511.3) 6800 (3084) 370 (1401)
25 or 35 125 or 150 74.05 (1880.9) 78.00 (1981.2) 66.50 (1689.1) 8500 (3856) 460 (1741) 2
1000 5 or 15 60 or 95 82.05 (2084.1) 75.50 (1917.7) 59.50 (1511.3) 8400 (3810) 440 (1666)
25 or 35 125 or 150 82.05 (2084.1) 82.00 (2082.8) 66.50 (1689.1) 9400 (4264) 480 (1817)
1500 5 or 15 60 or 95 82.05 (2084.1) 79.10 (2009.1) 84.70 (2151.4) 10,800 (4899) 480 (1817)
3
25 or 35 125 or 150 82.05 (2084.1) 91.60 (2326.6) 91.70 (2329.2) 12500 (5670) 600 (2271)
2000 5 or 15 60 or 95 82.05 (2084.1) 81.10 (2060.0) 94.10 (2390.1) 13,000 (5897) 500 (1893)
25 or 35 125 or 150 82.05 (2084.1) 93.60 (2377.4) 97.10 (2466.3) 15,000 (6804) 620 (2347) 4
2500 5 or 15 60 or 95 82.05 (2084.1) 89.10 (2263.1) 94.10 (2390.1) 15,500 (7031) 560 (2120)
25 or 35 125 or 150 82.05 (2084.1) 103.60 (2631.4) 98.10 (2491.7) 18,800 (8528) 730 (2763)
3000 25 or 35 125 or 150 92.25 (2343.2) 89.60 (2275.8) 119.90 (3045.5) 19,000 (8618) 750 (2839)
5
3750 25 or 35 125 or 150 106.50 (2705.1) 97.60 (2479.0) 119.90 (3045.5) 23,000 (10,433) 980 (3710)
5000 5 or 15 60 or 95 85.00 (2159.0) 98.00 (2489.2) 105.00 (2667.0) 25,000 (11,340) 960 (3634) 6
Plan Elevation 7
CLof Bushing
8
HTX
DTX CL
9
10
WTX
11
Figure 14.0-16. Liquid-Filled, Indoor and Outdoor
1 = 55.00 inches (1397.0 mm) for all ratings through 15 kV primary,
600 V secondary. 12
13
14
15
16
17
18
19
20
WTX
11
Figure 14.0-17. Liquid-Filled, Indoor and Outdoor
12 1 = 55.00 inches (1397.0 mm) for all ratings through 15 kV primary,
600 V secondary.
13
14
15
16
17
18
19
20
Table 14.0-37. High Voltage 15 kV and Below. Low Voltage 600 V and 13
Below. Copper Conductor Windings. Losses in Watts. Three-Phase
Dry-Type Unit Substation Transformers 3
VPI, 15 kV Primary 150 C Temp. Rise 14
kVA No Load Loss Total 4695 kV BIL
Load at 100% Losses Total Losses at
(Watts) Load and at 100% 50% Load and 15
170 C Ref. Load and 75 C Ref. Temp.
Temp. 170 C per DOE (Watts)
H
TX (Watts) (Watts) 16
300 4 950 3450 4400 1806
500 4 1300 5650 6950 2551
750 4 1600 8600 10,200 3329 17
1000 4 1850 10,700 12,550 4032
1500 4 2700 11,850 14,550 5287
2000 4 2950 16,900 19,850 6441 18
2500 4 4500 14,500 19,000 7419
3000 6200 26,100 32,300 N/A
W
D
TX
3750 7100 33,400 40,500 N/A 19
TX 3 Losses offered are typical only, not guaranteed.
4 Units must typically meet the new DOE efficiency guideline levels with
noted losses complying with such. 20
Figure 14.0-18. Indoor Ventilated Enclosure (NEMA 1 Construction)
Table 14.0-39. High Voltage 15 kV and Below. Low Voltage 600 V and
13 Below. Copper Conductor Windings. Losses in Watts. Three-Phase
Dry-Type Unit Substation Transformers. 3
14 Cast, 15 kV Primary 115 C Temp. Rise
kVA No Load Loss Total 4695 kV BIL
Load at 100% Losses Total Losses at
(Watts) Load and at 100% 50% Load and
15 135 C Ref. Load and 75 C Ref. Temp.
H Temp. 135 C per DOE (Watts)
TX (Watts) (Watts)
16 300 4 950 3400 4350 1806
500 4 1350 4450 5800 2551
750 4 2050 4700 6750 3329
17 1000 4 2350 7200 9550 4032
1500 4 2900 12,200 15,100 5287
2000 4 3150 13,200 16,350 6441
18 2500 4 4350 16,150 20,500 7419
3000 7200 20,000 27,200 N/A
D 3750 8600 21,000 29,600 N/A
TX
19 W
TX 5000 13,500 30,000 43,500 N/A
7500 20,000 35,000 55,000 N/A
10,000 22,500 45,000 67,500 N/A
20 Figure 14.0-19. Indoor Ventilated Enclosure (NEMA 1 Construction) 3 Losses offered are typical only, not guaranteed.
4 Units must typically meet the new DOE efficiency guideline levels with
noted losses complying with such.
21
Dimensions and weights for estimating purposes only.
12.13
i
(308.1) Structure
Roof Width 109.13
2.50 3.21 25.00 25.00 45.66 Rear of Base 'C' to Floor
(63.5) (81.5) (635.0) (635.0) (1159.8) 5.03
(127.8)
B Rear of
Inner Structure
1.05
(26.7)
(2771.9)
ii
3.06 Control Wire 2.00 15.68 14.07
26.94 Maximum Opening (50.8) 30.00 (398.3) (357.4)
(77.7) 25.25
Opening Opening Unit C
(684.3) 4.25 x 3.50
(108.0 x 88.9)
(762.0) A A (641.4)
1
3.06 30.81 47.83 B 1.05
(77.7) Opening Bottom (1214.9) (26.7)
Section B-B
40.94 Conduit 44.00 C
Opening
(1039.9)
(782.6)
Maximum
Space
3.93
Control Wire
Opening
Unit
(1117.6)
Structure
2
Opening
(99.8) 4.25 x 3.50 Top View A Width 'B' 'C'
(108.0 x 88.9) 22.00 16.99 11.00
3.06 Bus Duct (558.8) (431.6) (279.4)
(77.7) 18.94
Opening
(481.1)
Maximum
Opening
22.00
Unit
(558.8)
Chimney
& Cover
30.00
(762.0)
24.99
(634.8)
15.00
(381.0)
3
1.05 1.05 38.00 32.99 19.00
Lifting Angle 1.50 (26.7) (26.7) (965.2) (838.0) (482.6)
(38.1) 'B'
Foundation
Tie Down Section A-A
44.00
(1117.6)
38.99
(990.4)
22.00
(558.8) 4
(for Seismic Only) 50.00 44.99 25.00
Floor Plan (1270.0) (1142.8) (635.0)
5
22-inch Width = 21.40 (543.56) to Rear Frame
30-inch Width = 29.40 (746.76) to Rear Frame
'A' 38-inch Width = 37.40 (949.96) to Rear Frame
O.S. of
50-inch Width = 49.40 (1254.76) to Rear Frame
55-inch Width = 54.40 (1381.76) to Rear Frame
6
119.98 Outdoor
Overall Depth End Sheet
(3047.5) Outdoor
See Section A-A Above for
Bus Duct Orientation Info.
15.68 Bus Opening
(398.3) (from Base)
Roof
Sheet
36.00
(914.4) 16.96
7
1.00 21.50 14.50 (430.8) 'A'
0.61 (25.4) (546.1) (368.30)
2.30
(15.5)
(58.4)
28.59 30.21 29.97 26.57 C
8
(From Base) (Opening (761.2) (674.9)
(726.2) Width)
109.13 C
(2771.9) 5.75 (767.3) 111.48 72.00 C
105.06 C
(146.1)
5.75
(146.1) Overall
Height
Throat
Opening
& TXF
(Switchgear
Depth)
See
Top View
9
(2668.5) (1828.8) Above
(2831.6)
C Switchgear Throat
33.45 (Shipped Disassembled)
*51.79
(1315.5) (Door Width)
(849.6)
10
A 1.00 4.00 A 33.45 33.45
(25.4) Door Swing 42.00 Door Swing
(101.6)
26.00
(660.4) 117.08
(849.6) (Aisle Width)
(1066.8)
(849.6) 39.66
(1007.4) 11
(Base)
(2973.8)
Front of
Side View Top View Outdoor
Base
12
Switchgear
Structure Lb (kg) 14
Throat
End trims (one set per lineup) 1500 (681)
(Shipped 22-inch (558.8 mm) wide breaker structure 2600 (1180)
Disassembled)
19.70
30-inch (762.0 mm) wide breaker structure
44-inch (1117.6 mm) wide breaker structure
2700 (1226)
5200 (2361)
15
(500.4)
45.00
22-inch (558.8 mm) wide auxiliary structure 2300 (1044)
22-inch (558.8 mm) wide transition structure 2500 (1135)
(1143.0)
41.38 38-inch (965.2 mm) wide utility structure 2700 (1226)
16
(1051.1)
50-inch (1270.0 mm) wide utility structure 3200 (1453)
8.00
Transformer throat 150 (68)
1.00
(25.4) 16.00
(203.2)
17
(406.4) 44.00 30.00
21.50 22.00
(1117.6) (762.0)
(546.1) (558.8) 5.00
38.50 Unit Widths
(977.9) (Overall Shipping Width)
(127.0) 18
Front View
9255C25 19
Figure 14.0-20. Outdoor Walk-in Enclosure Magnum DS Switchgear and Magnum SB SwitchboardsDimensions in Inches (mm)
1 46.63 inches (1184.4 mm) = 55.00-inch (1397.0 mm) throat (44.00-inch [1117.6 mm] wide transition box). 20
52.63 inches (1336.8 mm) = 61.00-inch (1549.4 mm) throat (44.00-inch [1117.6 mm] wide transition box).
2 18.70 inches (475.0 mm) = 44.00-inch [1117.6 mm] wide transition box.
3 0.50-inch (12.7 mm) hardware recommended in all tie down locations.
21
i EnclosuresPow-R-Line C
Table 14.0-40. Enclosure
4.50
17.37 Dimensions in Inches (mm)
ii 2.15 (54.6)
(114.3)
(441.2) 1.25
Switchboard Non-Walk-in
(31.8)
Indoor Structure Enclosure
Depth Depth
1
2.13 48.00 (1219.2) 61.00 (1549.4)
(54.0) Dimension A
20.00
2 5.00
(127.0)
(508.0)
02500 kVA transformer 55.00 (1397.0)
90.70
22.00 25015000 kVA transformer 61.00 (1549.4)
(2303.8) (558.8)
1 Standard busway entry/exit location,
3 44.00 36.00-inch (914.4 mm) deep minimum.
A (1117.6) 2 20.00-inch (508.0 mm) wide structure always
To Front of required when throat connecting to other
4 Floor PRL C Inner
Structure
equipment. Standard transformer throat
connection, 48.00-inch (1219.2 mm) deep
structure only.
5 Structure 20-inch
(508.0)
12.81 Swbd. Struc.
Depth
Width (325.4)
Transition Enclosure Depth
Structure Width
6
Figure 14.0-21. Front or Rear AccessNon-Walk-in with Flat RoofDimensions in Inches (mm)
9 5.00
(127.0)
(54.0) 20.00
(508.0)
48.00 (1219.2)
54.00 (1371.6)
61.00 (1549.4)
67.00 (1701.8)
66.00 (1676.4) 79.00 (2006.6)
92.95
22.00
Dimension A
10 (2360.9) (558.8)
02500 kVA transformer 55.00 (1397.0)
44.00
A (1117.6) 25015000 kVA transformer 61.00 (1549.4)
11 To
Floor
Front of
PRL C Inner
3 20.00-inch (508.0 mm) wide structure always
Structure required when throat connecting to other
equipment. Standard transformer throat
12 Swbd. Struc.
connection, 48.00-inch (1219.2 mm) deep
structure minimum.
0.13 (3.2) Structure 20-inch 0.13 (3.2) 12.81
(508.0) (325.4) Depth
End Trim Width End Trim
Transition Enclosure Depth
13
Figure 14.0-22. Front AccessNon-Walk-in with Sloped RoofDimensions in Inches (mm)
14 Table 14.0-42. Enclosure
20.5 Dimensions in Inches (mm)
4.50 (520.7)
2.31 (58.7)
(114.3) Switchboard Non-Walk-in
15 Indoor Structure Enclosure
Depth Depth
Rear of
Enclosure
16 2.13
(54.0)
25.00
(635.0)
48.00 (1219.2)
54.00 (1371.6)
65.00 (1651.0)
71.00 (1803.4)
5.00
(127.0)
66.00 (1676.4) 83.00 (2108.2)
96.25
17 92.95
(2360.9)
22.00
(558.8)
(2444.8) Dimension A
02500 kVA transformer 55.00 (1397.0)
Top of
44.00 Bus Duct 25015000 kVA transformer 61.00 (1549.4)
(1117.6)
18 A
to
Front of
PRL C Inner Rear of
Chimney Cap
4 Standard transformer throat connection,
Floor Structure PRL C Inner 48.00 inches (1219.2 mm) deep only.
Structure 20.00-inch (508.0 mm) wide structure
19 always required when throat connecting
to other equipment.
Structure 20-inch 0.125 (3.2) Swbd. Struc. 4.19 5
Depth (106.3)
Non-walk-in dimension12.81 inches
Width (508.0) End Trim
Enclosure Depth (325.4 mm).
20 Transition
6 Standard busway entry/exit location.
Table 14.0-43. Suggested Minimum Ratings (kV) for Metal Oxide Surge Arresters Located in Metal-Enclosed Switchgear
System Nominal System Line-to-Line Voltage (kV)
i
Grounding 2.4 4.16 4.8 7.2 12.0 12.47 13.2 13.8 14.4 22.9 24.9 34.5
Solidly grounded 3 6 6 6 12 12 12 12 12 12 24 30 ii
system
Low resistance 3 6 6 6 12 12 12 12 12 21 24 30
grounded system 1
High resistance 6 6 9 12 18 18 21 21 24 36 39 54
or ungrounded system
2
Note: Arrester rating is based on a 55C maximum ambient temperature in the enclosure.
Table 14.0-45. Suggested Current Limiting Fuse Current Ratings for Self-Cooled 2.415.5 kV
i Transformer Applications
(Check Compliance of Fuses to FM Requirements if Installation Must Comply with FM)
System 2.4 4.16 4.8 7.2 12.0 13.2 13.8 14.4 Per-
ii Nominal kV cent
Fuses Max- 2.75 5.5 5.5 8.3 15.5 15.5 15.5 15.5 Impe-
imum kV dance
1 Transformer Full Fuse Full Fuse Full Fuse Full Fuse Full Fuse Full Fuse Full Fuse Full Fuse
(% Z)
kVA Rating Load Rating Load Rating Load Rating Load Rating Load Rating Load Rating Load Rating Load Rating
Self-Cooled Current Amps E Current Amps E Current Amps E Current Amps E Current Amps E Current Amps E Current Amps E Current Amps E
2 Amps Amps Amps Amps Amps Amps Amps Amps
112.5 27.1 40E 15.6 25E 13.5 20E 9.0 15E 5.4 10E 4.9 10E 4.7 10E 4.5 10E 2.25
150 36.1 50E 20.8 30E 18.0 25E 12.0 20E 7.2 10E 6.6 10E 6.3 10E 6.0 10E 3.0
3 225 54.1 80E 31.2 50E 27.1 50E 18.0 25E 10.8 15E 9.8 15E 9.4 15E 9.0 15E 3.0
300 72.2 100E 41.6 80E 36.1 65E 24.1 40E 14.4 20E 13.1 20E 12.6 20E 12.0 20E 5.0
500 120.3 175E 69.4 125E 60.1 100E 40.1 65E 24.1 40E 21.9 30E 20.9 30E 20.0 30E 5.0
4 750 180.4 250E 104.1 150E 90.2 150E 60.1 100E 36.1 65E 32.8 65E 31.4 65E 30.1 65E 5.75
1000 240.6 350E 138.8 200E 120.3 175E 80.2 125E 48.1 80E 43.7 80E 41.8 80E 40.1 80E 5.75
1500 360.8 600E 1 208.2 300E 180.4 250E 120.3 175E 72.2 100E 65.6 100E 62.8 100E 60.1 100E 5.75
5 2000 481.1 750E 1 277.6 400E 240.6 350E 160.4 250E 96.2 150E 87.5 125E 83.7 125E 80.2 125E 5.75
2500 601.4 1100E 1 347.0 600E 300.7 400E 200.5 300E 120.3 175E 109.3 150E 104.6 150E 100.2 150E 5.75
1 Fuse ratings represent the smallest fuse possible that will withstand transformer inrush (12 x
6 FLA for 0.1 second and 25 x FLA for 0.01 second)
and be able to handle temporary overloads (133% of FLA).
7 Table 14.0-46. Suggested Minimum RBA Expulsion Fuse Current Ratings for Self-Cooled 2.415.5
kV Power Transformer Applications 2
8 System
Nominal kV
2.4 4.16 4.8 7.2 12.0 13.2 13.8 14.4 Per-
cent
Fuses Max- 8.3 8.3 8.3 8.3 15.5 15.5 15.5 15.5 Impe-
imum kV dance
9 Transformer Full Fuse Full Fuse Full Fuse Full Fuse Full Fuse Full Fuse Full Fuse Full Fuse
(% Z)
kVA Rating Load Rating Load Rating Load Rating Load Rating Load Rating Load Rating Load Rating Load Rating
Self-Cooled Current Amps E Current Amps E Current Amps E Current Amps E Current Amps E Current Amps E Current Amps E Current Amps E
10 Amps Amps Amps Amps Amps Amps Amps Amps
Three-Phase Transformers
11 112.5
150
27
36
40E
50E
16
21
25E
30E
14
18
20E
25E
9
12
15E
20E
5
7
10E
10E
5
7
7E
10E
5
6
7E
10E
5
6
7E
10E
2.25
3.0
225 54 80E 31 50E 27 40E 18 25E 11 15E 10 15E 9 15E 9 15E 3.0
300 72 100E 42 65E 36 50E 24 40E 14 20E 13 20E 13 20E 12 20E 5.0
12 500 120 200E 69 100E 60 100E 40 65E 24 40E 22 30E 21 30E 20 30E 5.0
750 180 250E 104 150E 90 125E 60 100E 36 50E 33 50E 31 50E 30 50E 5.75
1000 241 400E 139 200E 120 200E 80 125E 48 80E 44 65E 42 65E 40 65E 5.75
13 1500 361 540E 3 208 300E 180 250E 120 200E 72 100E 66 100E 63 100E 60 65E 5.75
2000 481 720E 4 278 400E 241 400E 160 250E 96 150E 87 125E 84 125E 80 125E 5.75
2500 601 347 540E 3 301 450E 5 200 300E 120 200E 109 150E 105 150E 100 150E 5.75
14 3750 180 250E 164 250E 157 250E 150 250E
2 Fuse ratings represent the smallest fuse possible that will withstand transformer inrush (12XFLA
for 0.1 second and 25XFLA for .01 second) and be able to handle temporary overloads (133% of
15 3
FLA).
Two 300 E-Ampere fuse refills used in parallel with 10% derating factor.
4 Two 400 E-Ampere fuse refills used in parallel with 10% derating factor.
16 5 Two 250 E-Ampere fuse refills used in parallel with 10% derating factor.
Table 14.0-47. Suggested Minimum RBA Expulsion Fuse Current Ratings for Self-Cooled 25.838.0
17 kV Power Transformer Applications
System Nominal kV 22.9 23.9 24.9 34.5
Fuses Maximum kV 25.8 25.8 25.8 38.0
18 Transformer Full Load Fuse Full Load Fuse Full Load Fuse Full Load Fuse
kVA Rating Current Rating Current Rating Current Rating Current Rating
Self-Cooled Amps Amps E Amps Amps E Amps Amps E Amps Amps E
19 Three-Phase Transformers
750 19 30E 18 25E 17 25E 13 20E
1000 25 40E 24 40E 23 40E 17 25E
20 1500 38 65E 36 50E 34 50E 25 40E
2000 50 80E 48 80E 46 65E 33 50E
2500 63 100E 60 100E 58 80E 42 65E
21 3750 95 150E 91 150E 87 125E 63 100E
Table 14.0-48. Type MVS Primary Switch, Standard Ratings Transformer Technical Data
Rated Impulse Rated Current Rated Fault-Close i
Maximum Withstand, Continuous and and Momentary Transformer Standards
Voltage, kV kV (BIL) Load Break, Amperes Current, kA Asym. Dimensions and weights as listed in
5 60 600 40 the tables are based on the following: ii
5 60 600 64
5 60 1200 40 Standard base kVA ratings:
5 60 1200 64
30050075010001500 1
15 95 600 40 2000250030003750
15 95 1200 40 Three-phase, 60 Hz, two windings
15 95 600 64 Standard temperature rise
2
15 95 1200 64 (see tables) above ambient air
27 125 600 40
temperature of 40 C (104 F)
27 125 600 64 maximum and 30 C (86 F)
3
38 150 600 40
average in any 24-hour period
Table 14.0-49. Available Vacuum Breaker Ratings, MSB Switchgear Maximum altitude of 3300 ft 4
1
(1006 m) above sea level for full
Rated Control Spring Charge Motor Close or Trip Voltage Range
Voltage Amperes
rating
Run Amperes Time Seconds Close Trip
VPI altitude derating is 0.3% per 5
48 Vdc 4.0 5 5.2 3856 2856 100 m on the AA rating and 0.5%
125 Vdc 3.0 5 3.6 100140 70140 per 100 m on the FA rating
250 Vdc 2.0 5 1.8 200280 140180
Liquid-filled transformer derating 6
120 Vac 3.0 5 3.6 104127 104127 is 0.4% per 100 m above 1000 m
240 Vac 2.0 5 1.8 208254 208254
Standard high voltages:
1 Inrush current is four times running amperes.
2400416048006900720012000
7
1247013200138002080022900
34500, delta connected only 8
Standard high voltage taps:
Two approximately 2-1/2% full
capacity above and two below 9
rated voltage
Standard low voltages (no taps):
208Y/120 (2000 kVA maximum) 10
240 delta (2000 kVA maximum)
480 delta (all ratings)
480Y/277 (all ratings) 11
Note: 600Y and 600 delta also available.
21
Table 14.0-50. Liquid-Filled Transformer Continuous kVA for Different Base Temperature Rise Ratings
i Temperature Rise, C, Transformer Base, kVA Continuous kVA Multiplier
Base Rating, OA 65 C OA 55 C FA 65 C FA
Table 14.0-51. Dry-Type (Conventional VPE and VPI) Transformer Continuous kVA for Different Base Temperature Rise Ratings
2 Temperature Rise, C, Continuous kVA Multiplier
Base Rating, AA 80 C AA 115 C AA 150 C AA 80 C FA 115 C FA 150 C FA
500 +15%
750 863
9 1000 1150
1500 1725
2000 2300
10 2500 +25% 3125
3750 4688
5000 6250
11 7500
10,000
9375
12,500
12,000 +33% 16,000
12 Table 14.0-54. Three-Phase, Dual or Triple Temperature kVA Ratings 1
Three-Phase kVA Self-Cooled and Forced-Air Cooled with PEAK Triple Rated 55 C/75 C Temperature Rise
13 55 C Rise 65 C Rise 75 C Rise 55 C Rise 65 C Rise 75 C Rise
KNAN KNAN KNAN KNAN/KNAF KNAN/KNAF KNAN/KNAF
18
19
20
21
300
5%
50,000
100,000
834 14,900 1700
15,700
16,600
17,400
722 12,90
13,60
2900 15,800
16,500
361 6,400
6,800
1400 7,800
8,200
289 5,200
5,500
1200 6,400
6,700
2
150,000 16,000 17,700 13,90 16,800 6,900 8,300 5,600 6,800
250,000 16,300 18,000 14,10 17,000 7,000 8,400 5,600 6,800
500,000 16,500 18,200 14,300 17,200 7,100 8,500 5,700 6,900 3
Unlimited 16,700 18,400 14,400 17,300 7,200 8,600 5,800 7,000
500 50,000 1388 21,300 2800 25,900 1203 20,000 4800 24,800 601 10,000 2400 12,400 481 8,000 1900 9,900
5% 100,000 25,200 28,000 21,900 26,700 10,900 13,300 8,700 10,600 4
150,000 26,000 28,800 22,500 27,300 11,300 13,700 9,000 10,900
250,000 26,700 29,500 23,100 27,900 11,600 14,000 9,300 11,200
500,000 27,200 30,000 23,600 28,400 11,800 14,200 9,400 11,300
Unlimited 27,800 30,600 24,100 28,900 12,000 14,400 9,600 11,500
5
750 50,000 2080 28,700 4200 32,900 1804 24,900 7200 32,100 902 12,400 3600 16,000 722 10,000 2900 12,900
5.75% 100,000 32,000 36,200 27,800 35,000 13,900 17,500 11,100 14,000
150,000 33,300 37,500 28,900 36,100 14,400 18,000 11,600 14,500 6
250,000 34,400 38,600 29,800 37,000 14,900 18,500 11,900 14,800
500,000 35,200 39,400 30,600 37,800 15,300 18,900 12,200 15,100
Unlimited 36,200 40,400 31,400 38,600 15,700 19,300 12,600 15,500 7
1000 50,000 2776 35,900 5600 41,500 2406 31,000 6900 40,600 1203 15,500 4800 20,300 962 12,400 3900 16,300
5.75% 100,000 41,200 46,800 35,600 45,200 17,800 22,600 14,300 18,200
150,000
250,000
43,300
45,200
48,900
50,800
37,500
39,100
47,100
48,700
18,700
19,600
23,500
24,400
15,000
15,600
18,900
19,500
8
500,000 46,700 52,300 40,400 50,000 20,200 25,000 16,200 20,100
Unlimited 48,300 53,900 41,800 51,400 20,900 25,700 16,700 20,600
1500 50,000 4164 47,600 8300 55,900 3609 41,200 14,400 55,600 1804 20,600 7200 27,800 1444 16,500 5800 22,300 9
5.75% 100,000 57,500 65,800 49,800 64,200 24,900 32,100 20,000 25,800
150,000 61,800 70,100 53,500 57,900 26,700 33,900 21,400 27,200
250,000 65,600 73,900 56,800 71,200 28,400 35,600 22,700 28,500 10
500,000 68,800 77,100 59,600 74,000 29,800 37,000 23,900 29,700
Unlimited 72,500 80,800 62,800 77,200 31,400 38,600 25,100 30,900
2000
5.75%
50,000
100,000
2406 24,700
31,000
9600 34,300 1924
40,600
19,700
24,800
7800 27,500
32,600
11
150,000 34,000 43,600 27,200 35,000
250,000 36,700 46,300 29,400 37,200
500,000 39,100 48,700 31,300 39,100 12
Unlimited 41,800 51,400 33,500 41,300
2500 50,000 3008 28,000 12,000 40,000 2405 22,400 9600 32,000
5.75% 100,000 36,500 48,500 29,200 38,800 13
150,000 40,500 52,500 32,400 42,000
250,000 44,600 56,600 35,600 45,200
500,000
Unlimited
48,100
52,300
60,100
64,300
38,500
41,800
48,100
51,400
14
3000 50,000 3609 30,700 14,000 44,700 2886 24,600 11,500 36,100
5.75% 100,000 41,200 55,200 33,000 44,500
150,000 46,600 60,600 37,300 48,800 15
250,000 51,900 65,900 41,500 53,000
500,000 56,800 70,800 45,500 57,000
Unlimited 62,800 76,800 50,200 61,700 16
3750 50,000 4511 34,000 18,000 52,000 3608 27,200 14,400 41,600
5.75% 100,000 47,500 65,500 38,000 52,400
150,000
250,000
54,700
62,200
72,700
80,200
43,700
49,800
58,100
64,200
17
500,000 69,400 87,400 55,500 69,900
Unlimited 78,500 96,500 62,800 77,200
1 Short-circuit capacity values shown correspond to kVA and impedances shown in this table. For impedances other than these, short-circuit
18
currents are inversely proportional to impedance.
2 The motors short-circuit current contributions are computed on the basis of motor characteristics that will give four times normal current.
For 208 V, 50% motor load is assumed while for other voltages 100% motor load is assumed. For other percentages, the motor short-circuit 19
current will be in direct proportion.
20
21
Table 14.0-56. IEEE Standard Insulation LevelskV BIL Table 14.0-60. Transformer kVA Ratings, Three-Phase
i High- Transformer In addition to their self-cooled (AA or OA) kVA ratings,
Voltage Eatons standard secondary unit substation transformers
Liquid-Filled Ventilated Dry Cast Coil
Rating of liquid-filled and ventilated dry-types are designed for
ii HV LV 1 HV LV 1 HV LV 1
continuous operation at the following supplementary
2400 45 30 20 10 20 10 self-cooled and fan-cooled (FA) kVA ratings:
4160 60 30 30 10 30 10
1 4800 60 30 30 10 30 10 Liquid-Filled
6900 75 30 45 10 45 10 65 C Rise 55/65 C Rise
7200 75 30 45 10 45 10 OA FA OA 55 C OA 65 C FA 55 C FA 65 C
2 12,000 95 30 60 10 60 10
300 N/A 300 336 N/A N/A
12,470 95 30 60 10 60 10
500 N/A 500 560 N/A N/A
13,200 95 30 60 10 60 10
750 862 750 840 862 966
3 13,800 95 30 60 10 60 10
1000 1150 1000 1120 1150 1288
22,900 125 30 110 10 110 10
1500 1725 1500 1680 1725 1932
34,400 150 30 150 10 150 10
2000 2300 2000 2240 2300 2576
4 1 600 V maximum.
2500 3125 2500 2800 3125 3500
Note: Increased BIL option is available. 3000 3750 3000 3360 3750 4200
3750 4690 3750 4200 4690 5250
5 Table 14.0-57. Standard Guaranteed Sound LevelsDecibels Ventilated Dry-Type
Maximum Liquid-Filled Ventilated Dry and Cast 150 C Rise 115/150 C Rise
Base kVA Transformer Coil Transformer
AA FA AA 115 C AA 150 C FA 150 C
6 (Self-Cooled) OA FA AA FA
300 400 300 345 450
300 55 55 67 500 667 500 575 750
7 500
750
56
58
67
67
60
64
67
67
750 1000 750 863 1125
1000 1333 1000 1150 1500
1000 58 67 64 67 1500 2000 1500 1725 2250
1500 60 67 65 68
8 2000 61 67 66 69
2000 2667 2000 2300 3000
2500 3333 2500 2875 3750
2500 62 67 68 71
3000 63 67 68 71 80/115 C Rise 80/150 C Rise
9 3750 64 67 70 73
AA 80 C AA 115 C FA 115 C AA 80 C AA 150 C FA 150 C
21
Secondary Equipment i
For information on secondary
equipment for use in unit substations,
refer to the following tabs of the ii
Consulting Application Guide:
Tab 20Low Voltage Metal-Enclosed 1
Drawout Switchgear
Tab 21Low Voltage
Switchboards
2
Tab 26Power Circuit Breakers
and Insulated-Case Circuit Breakers 3
Tab 27Molded-Case Circuit Breakers
and Enclosures 4
10
11
12
13
14
15
16
17
18
19
20
21
ii
10
11
12
13
14
15
16
17
18
19
20
21