782 e
782 e
782 e
W2
DRIESCHER - Air-Insulated
36kV
Medium-Voltage Switchgears
Type W 24 - 901121
Rated voltage 24 kV
Rated current up to 1250 A
W 24
ELEKTROTECHNISCHE WERKE
FRITZ DRIESCHER & SHNE GMBH
D-85366 MOOSBURG TEL. +49 87 61 6 81-0 FAX +49 87 61 68 12 30
http://www.driescher.com [email protected]
782
DRIESCHER - 24 kV Switchgears
in compliance with EN 62271-200
12 Production program
2
782
General
The metal-enclosed, air-insulated medium-voltage The switch panels of Type W 24 - 901121 measure
switchgears, Type W 24 can be universally applied: 900 mm in width, 1100 mm in depth and 2100 mm
in height.
They range from the compact ring cable switchgears
up to complex power distribution switchgears. They are available as individual panels or as a swit-
Tailored to meet the needs of networks of public chgear unit, the equipment and panel sequence of
utilities and power supply companies in industry which can be selected by the customer.
and municipal buildings.
These medium-voltage switchgears meet the specific The switch panels are type-tested in compliance with
requirements put by the user in full and ensure a DIN VDE 0671, Part 200 including Pehla directive
satisfactory power distribution. no. 4.
Operating Conditions
The switch panels of Type W 24 are installed in clo- For installations above an altitude of 1000 m the
sed electrical operating areas which are only to be rated insulating level of the switchgear must be cor-
entered by skilled personnel and appropriately rected accordingly. The switch panels are designed
instructed persons. for use under normal operating conditions in compli-
The equipment can be used at an altitude of up to ance with the standard EN 62271-1.
1000 m above sea level.
Technical Standards
The design of the air-insulated switch panels corre- switchgear equipment is designed in compliance with
sponds to the specifications of the EN 62271-200. EN 62271-1.
The resistance to accidental arcs of the switch panels The degree of protection of the switch panels corre-
has been determined at 16, 20, 25 and 31.5 kA; 1 s, sponds to IP 3X.
by and independent testing institute. The installed
Technical Data
Rated voltage Ur 24 kV Rated short-circuit duration tk 1 s
Rated lightning impulse withstand voltage Up 125 kV Rated frequency fr 50 Hz
Rated short-time withstand voltage Ud 50 kV
Technical data for the installed Rated (operating) current Rated short-time current Rated peak current
switchgear equipment Ir Ik Ip
3
782
Benefits
Flexibility
Variability Reliability
Safe and reliable through the high quality of our
products
Economical based on continuous further development
development
Economical
Advanced
Compact dimensions Customer-oriented
Easy handling
Minimum amount of maintenance
Design
The air-insulated medium-voltage switch panels of Switch panels equipped with switch-disconnectors
Type W 24 - 901121 are metal-encapsulated. can optionally be fitted with an earthing switch.
The switch panel frame is made of a screwed, hot- In circuit-breaker panel, Type WL 24, there is also
galvanized composite structure. an integrated bus disconnector in addition to the
The front of the switch panels has a single-wing door circuit breaker.
of steel plate with the door hinge optionally on the It is also possible to equip these panels with a set of
right or left. A window of compound glass is inserted current and voltage transformers as well as with an
in the door. earthing switch.
The cover in front of the bus bar area is either screwed
The relay boxes extend over the entire width of the
on or designed as a door for the relay box positioned
switch panels. These measure 265 mm in depth and
behind it.
are available in 3 different heights (455, 635 and 815
Each switch panel has a screwed on rear panel of
mm, see Page 11).
galvanized sheet metal.
Connecting cables are conducted into the switch The optional interlocking features of the devices
panels from below and are mounted on cross rails practically rule out any incorrect operation.
which can be adjusted in two dimensions. All installed switchgear equipment can be operated
The doors and covers of the switchgear are painted manually or via motor-operated mechanism with clo-
in structural paint (available in different colours sed panel door.
according to the customer's request).
Special measuring panels equipped with current and
voltage transformers complete the program.
Equipment Earthing switches or spherical fixed points are avai-
lable for earthing and short-circuiting.
The switch panels of Type W 24 are available in the An insulating protective barrier can be inserted when
following versions: the panel door is closed.
It is possible to install corresponding surge voltage
Cable switch panel Type WK 24
protectors in the panel, if required.
Transformer feeder panel Type WT 24
Measuring switch panel Type WM 24
All switch panels are designed with central locking
Bus sectionalizer panel Type W 24
and double-bit key.
Circuit-breaker panel Type WL 24
There are additional locking features available using
The switch panels are optionally designed with a bus profile cylinders or padlocks, if required.
bar compartment which is either open or closed at
the side.
Pressure relief can be in upward or downward direc-
tion.
4
Air-Insulated Medium-Voltage Switch Panels 24 kV
Type W 24 - 901121
Cable panel Transformer feeder Measuring panel Bus sectionalizer panel Bus sectionalizer Circuit-breaker panel Circuit-breaker bus
Switch Panel Type (WK) panel (WT) (WM) (W) /Measuring panel (WL) sectionalizer panel
W 24 - 901121 Fig. Bild 2,3 Fig. 11,12,13 Fig. 7,8,9,10 Fig. 4 (WM) Fig. 5,6 Fig. 14,17 (WL) Fig. 15,16
*
*
Disconnecting switch - - -
Switch-disconnector /
H 22 EA/EK H 22 SEA - H 22 EK/EA/SEA H 27 EK/EA/SEA V24 F/KUF V24 F/KUF
Circuit breaker
**
Earthing switch
Current transformer -
Voltage transformer - -
*
5
782
782
Switch Panels Type W 24 - 901121
Rated voltage 24 kV
3
3 Bus terminal
4 Switch-disconnector H 22
5 5 Insulating protective barrier *
6 Switch-disconnector H 27
4
7 Current transformer
8 Voltage transformer
9 Vakuuc circuit-breaker
10
10 Position indicator and actuation of
load-break switch
13
11
Position indicator and actuation of
disconnecting switch
12 Position indicator and actuation of
12
earthing switch
16 13 Earthing switch
14 Disconnecting switch
15 HV-HBC fuse
Fig. 2: 24 kV Cable panel with
switch-disconnector H 22
16 Cable terminal
* The insulating protective barrier can be inserted with switched off switchgear
6
782
Switch Panels Type W 24 - 901121
1 1
3 3
5
4
14
5
11
10 10
4
13
12
14
13
16
11
Fig. 3: 24 kV Cable panel with disconnecting Fig. 4: 24 kV Bus sectionalizer panel with
switch and switch-disconnector H 22 fuse switch-disconnector H 22 SEA
6
6
8
13
15
8
13 7
7
782
Switch Panels Type W 24 - 901121
1
1
3 3
7 7
8 8
1
1
3 3
13
7
12
8 8
13
8
782
Switch Panels Type W 24 - 901121
1 1
3 3
5
5
14
4
11
10 6
10
15
12
12
13
13
16
16
Fig. 11: 24 kV Transformer feeder panel with Fig. 12: 24 kV Transformer feeder panel with
switch-disconnector H 22 SEA switch-disconnector H 27 SuT
15
10
12
12
16
Fig. 13: 24 kV Transformer feeder panel with switch-disconnector H22 SEA as well as current and voltage transformer
9
782
Switch Panels Type WL 24 - 901121
1
2
2
3
3
5
5
11
14
14
11
9
9
7
13
12
Fig. 14: Circuit-breaker panel in mobile Fig. 15: Circuit-breaker bus sectionalizer panel
stationary-mounted design in mobile stationary-mounted design
Auxiliary truck
Fig. 16:
Circuit-breaker bus sectionalizer panel in mobile stationary-mounted design
10
782
Relay Boxes Type W 24 - 901121
Auxiliary Equipment
Insulating protective barrier in compliance with DIN Addtional locking systems with profile cylinder and
VDE 0682 Part 552 lockable operating mechanisms
Panel illumination Short-circuit indicator
Capacitive voltage testing system in compliance Floor coverings
with (E) DIN VDE 0682 Part 415
Weights
Type Designation Weight approx. kg Drawing-no.
11
Our range of products includes:
MFT
Medium-voltage systems
Single-bus and duplicate-bus switchgear
Non-withdrawable, withdrawable, and truck-type units
24 kV
Compact switchgear assemblies
Custom-made models
Industrial systems
Medium-voltage switchgear
Indoor switches, disconnectors, and earthing switches (single and triple pole)
Indoor circuit breakers (vacuum)
Outdoor switches (low oil content and vacuum)
High-voltage high-breaking-capacity fuses
Low-voltage systems
Open-framework design
Enclosed break devices (up to 6.300 A)
Cable and fixed-station distribution cabinets
Low-voltage switchgear
31,5 kA
Switch disconnectors
Switch and fuse blocks
Low-voltage high-breaking-capacity fuses
Driving gear
Hand-operated and motor-operated mechanisms
Indoor and outdoor driving gear
Accessories
Dimensions, weights , diagrams and descriptions in the list are non-binding. Subject to change without notice.
ELEKTROTECHNISCHE WERKE
FRITZ DRIESCHER & SHNE GMBH
D-85366 MOOSBURG TEL. +49 87 61 6 81-0 FAX +49 87 61 68 12 30
http://www.driescher.com [email protected]