TPC AC - DC Ground Detector Fault Detector
TPC AC - DC Ground Detector Fault Detector
TPC AC - DC Ground Detector Fault Detector
FAULT DETECTOR
REVISION HISTORY
Rev. Description ERO/ECN #
A Initial Release 058713
B Correct section number. C31851
Table of Contents
TPC AC/DC GROUND FAULT DETECTOR ASSEMBLY P/N # C18H0000 .........................4-3
APPLICATION ...................................................................................................................................4-3
TERMINAL BLOCK - INPUT AND OUTPUTS .....................................................................4-3
INPUT TERMINALS............................................................................................................4-3
OUTPUT TERMINALS .......................................................................................................4-3
BLOCK DIAGRAM SCHEMATIC ....................................................................................................4-3
THEORY OF OPERATION..............................................................................................................4-3
TESTING ............................................................................................................................................4-4
AC GROUND TEST..................................................................................................................4-4
DC GROUND TEST..................................................................................................................4-4
Table of Figures
THERE ARE NO FIGURES IN THIS SECTION
Error! No table of contents entries found.
Table of Tables
THERE ARE NO TABLES IN THIS SECTION
Error! No table of contents entries found.
On a dead short on any phase, all the Should show a ground on A phase
current passes through the shorted ground (Light should go dark).
and no current passes through that phase
resistor thus the light will not illuminate. Push Ground Test Pushbutton all
lights should come bright
Additionally, this neutral point is connected
to the actual ground through a bridge This function is to test for burnt out
rectifier. Whenever the neutral point has lights.
potential on it, the bridge rectifier will build
some DC potential across the relay to Do this on all three phases.
energize the relay coil and actuate the relay
contacts. DC GROUND TEST
A ground indication of one of the 3 phases Verify that there is no ground on any
can be alarmed or displayed by use of the particular motor you assigned to, for this
relay contacts. test.
Similarly on the detection of a DC ground Install a small gauge jumper (22 awg
on either of the DC BUS paths the relay wire) from + side of bus to ground.
picks up. Resistor R4 can be adjusted to
give full deflection on the desired amount of Throttle up the SCR a little bit.
DC ground.
DC ground meter should show 100%
TESTING deflection to one side.
If the lights are 220 VAC then there should Adjust the potentiometer on the back of
be approximately 130 VAC applied to them the meter to obtain this reading.
normally (no ground). Lights should be
about bright. If they are 120 VAC lights This can be repeated on the - side of
then there should be about 70Vac applied the bus and the meter should read
to them normally (no ground). Lights should 100% Deflection in the opposite
be about bright. These readings should direction.
be same for all 3 lights and can be adjusted