Load Sizing
Load Sizing
Superintending
Designation Consultant Assistant Engineer Executive Engineer
Engineer
Signature
Date
L&T CONSTRUCTION
WATER & EFFLUENT TREATMENT SBG
CLIENT: CONSULTANT :
PHED , Jaipur
PROJECT : PACKAGE 2 OF INTEGRATED TARANAGAR JHUNJHUNU
P P P
P P P
P P P
Project : PACKAGE 2 OF INTEGRATED TARANAGAR JHUNJHUNU
5 Brine Feed Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
6 Dosing Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
7 Brine dilution Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
9 Acid Recirculation Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
11 Instrumentation Load Control Room 1 0 0.90 0.85 4.00 - 4.00 4.00 5.23 5.23
12 Other Loads( Exhaust Fans,Air Conditioner Unit etc) 1 0 0.90 0.85 5.00 - 5.00 5.00 6.54 6.54
13 Axial Flow Fans Pump House 6 0 0.73 0.70 0.31 0.37 1.86 1.86 3.64 3.64
14 Electrically operated sluice Valve up to 500 mm Pump Delivery and Delivery Header 6 4 0.84 0.78 0.55 1.1 3.30 5.50 5.05 8.41
15 Auxiliary Load(For Wielding Receptacles, ceiling fans etc ) 2 1 0.90 0.80 10 10.00 20.00 30.00 27.78 41.67
2 Pump House to Wahidpura 1 1 0.95 0.90 51.86 75 51.86 103.72 60.85 121.69
Pump House to
3 1 1 0.94 0.89 42.06 55 42.06 84.12 50.17 100.34
HSC PUMP Narsinghpura
Pump House to Cluster 7A,
4 1 1 0.94 0.89 29.04 45 29.04 58.08 34.75 69.50
8 & 8A
5 Pump House to Charawas 2 1 0.96 0.90 211.75 250 423.50 635.24 490.16 735.24
6 Dewatering Pump Pump House 1 1 0.84 0.78 0.55 1.1 0.55 1.09 0.83 1.67
8 Brine Feed Pump 1 1 0.84 0.78 0.94 1.1 0.94 1.88 1.44 2.88
9 Dosing Pump 1 1 0.85 0.81 1.28 1.5 1.28 2.56 1.86 3.72
10 Brine dilution Pump 1 1 0.78 0.78 0.47 0.55 0.47 0.94 0.77 1.55
12 Air Circulation Pump 1 1 0.85 0.81 1.28 1.5 1.28 2.56 1.86 3.72
14 Instrumentation Load Control Room 1 0 0.90 0.85 4.00 - 4.00 4.00 5.23 5.23
16 Axial Flow Fans Pump House 15 0 0.73 0.70 0.33 0.37 4.95 4.95 9.69 9.69
19 EOT - 3 MT Pump House 1 0 0.88 0.81 3.33 3.7 3.33 3.33 4.66 4.66
NOTE:
Project : PACKAGE 2 OF INTEGRATED TARANAGAR JHUNJHUNU
6 Dewatering Pump Pump House 1 1 0.84 0.78 0.55 1.1 0.55 1.09 0.83 1.67
8 Brine Feed Pump 1 1 0.78 0.78 0.47 0.55 0.47 0.94 0.77 1.55
9 Dosing Pump 1 1 0.83 0.78 0.64 0.75 0.64 1.28 0.99 1.99
10 Brine dilution Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
12 Acid Recirculation Pump 1 1 0.83 0.78 0.64 0.75 0.64 1.28 0.99 1.99
14 Instrumentation Load Control Room 1 0 0.90 0.85 4.00 - 4.00 4.00 5.23 5.23
Other Loads( Exhaust Fans,Air
15 1 0 0.90 0.85 5.00 - 5.00 5.00 6.54 6.54
Conditioner Unit etc)
16 Axial Flow Fans Pump House 14 0 0.73 0.70 0.31 0.37 4.34 4.34 8.49 8.49
NOTE:
1 Kindly refer Annexure- I for Efficiency & Power Factor for the LT motors
Project : PACKAGE 2 OF INTEGRATED TARANAGAR JHUNJHUNU
3 Dewatering Pump Pump House 1 1 0.84 0.78 0.55 1.1 0.55 1.09 0.83 1.67
Dosing Pump
6 1 1 0.31 0.70 0.55 0.37 0.31 1.09 1.43 5.02
Chiller
8 1 0 1.70 0.82 0.55 2.2 1.70 0.55 1.22 0.39
9 Air Circulation Pump 1 1 0.31 0.70 0.55 0.37 0.31 1.09 1.43 5.02
11 Instrumentation Load Control Room 1 0 0.90 0.85 4.00 - 4.00 4.00 5.23 5.23
13 Axial Flow Fans Pump House 6 0 0.73 0.70 0.31 0.37 1.86 1.86 3.64 3.64
NOTE:
Project : PACKAGE 2 OF INTEGRATED TARANAGAR JHUNJHUNU
6 Brine Feed Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
7 Dosing Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
8 Brine dilution Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
10 Acid ReCirculation Pump 1 1 0.73 0.70 0.31 0.37 0.31 0.62 0.61 1.21
12 Instrumentation Load Control Room 1 0 0.90 0.85 4.00 - 4.00 4.00 5.23 5.23
14 Axial Flow Fans Pump House 8 0 0.73 0.70 0.33 0.37 2.64 2.64 5.17 5.17
NOTE:
1 Kindly refer Annexure- I for Efficiency & Power Factor for the LT motors
Project : PACKAGE 2 OF INTEGRATED TARANAGAR JHUNJHUNU
ANNEXURE - I
CROMPTON GREAVES CATALOGUE FOR ENERGY EFFICIENT MOTORS
Motor Data Based on 50 Deg. Ambient Temp, Full Load Eff. & pf , 440V at TB, 4 pole motor, 3phase
SCIM