This site inspection test report summarizes the inspection and testing of binary inputs for an ACCS-type REC670 relay used in a 13.8kV capacitor switching scheme. The inspection included checking the relay's general information, mechanical components, and visual connections. Binary input testing involved verifying 16 inputs on each of 8 slots for various circuit breaker and protection functions. All binary inputs were found to be functioning correctly.

Uploaded by

m kh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
329 views8 pages

Accs

This site inspection test report summarizes the inspection and testing of binary inputs for an ACCS-type REC670 relay used in a 13.8kV capacitor switching scheme. The inspection included checking the relay's general information, mechanical components, and visual connections. Binary input testing involved verifying 16 inputs on each of 8 slots for various circuit breaker and protection functions. All binary inputs were found to be functioning correctly.

Uploaded by

m kh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 8

SITE INSPECTION TEST REPORT

380 /132/13.8kV SUBSTATION -9016


ACCS TYPE REC670 RELAY
Client: SEC-COA Contractor:
Site location: Contractor
Panel Ref/Bay: ACCS / 13.8kV AUTONo:
CAPACITOR SWITCHING SCHEME
PANEL

ACCS FUNCTION AND FINAL SETTING TEST

1. GENERAL DATA AND INFORMATION

Designation : Aux. Voltage : 125 V DC


Manufacturer : ABB Software :
Type : REC670 Serial no :

2. MECHANICAL CHECK AND VISUAL INSPECTION:

ITE
DESCRIPTION CHECKED
M
1 Inspect for any physical damage or defects.
2 Verify connections as per approved drawings.
3 Check case earthing
4 Watchdog contacts checked
5 Operational single line diagram in BCU

Tested by: Witnessed by:


P a g e : 1 of 9
Name : Name: Date :
Signature: Signature:
SITE INSPECTION TEST REPORT
380 /132/13.8kV SUBSTATION -9016
ACCS TYPE REC670 RELAY
Client: SEC-COA Contractor:
Site location: Contractor
Panel Ref/Bay: ACCS / 13.8kV AUTONo:
CAPACITOR SWITCHING SCHEME
PANEL

4.0 . BINARY INPUTS: (BIM)


SLOT NO : P3

Binary Relay
Function Duty Result
Inputs terminals
BI 01 X31:1&2 13.8Kv incomer-1 CB OPEN Yes N/A
BI 02 X31:3&4 13.8Kv incomer-1 CB CLOSED Yes N/A
BI 03 X31:5&6 13.8Kv incomer-1 CB TEST Yes N/A
BI 04 X31:7&8 13.8Kv incomer-1 CB SERVICE Yes N/A
BI 05 X31:9&10 SPARE Yes N/A
BI 06 X31:11&12 SPARE Yes N/A
BI 07 X31:13&14 13.8Kv incomer-2 CB OPEN Yes N/A
BI 08 X31:15&16 13.8Kv incomer-2 CB CLOSED Yes N/A
BI 09 X32:1&2 13.8Kv incomer-2 CB TEST Yes N/A
BI 10 X32:3&4 13.8Kv incomer-2 CB SERVICE Yes N/A
BI 11 X32:5&6 SPARE Yes N/A
BI 12 X32:7&8 SPARE Yes N/A
BI 13 X32:9&10 13.8Kv incomer-3 CB OPEN Yes N/A
BI 14 X32:11&12 13.8Kv incomer-3 CB CLOSED Yes N/A
BI 15 X32:13&14 13.8Kv incomer-3 CB TEST Yes N/A
BI 16 X32:15&16 13.8Kv incomer-3 CB SERVICE Yes N/A
SLOT NO :P5

Binary Relay
Function Duty Result
Inputs terminals
BI 01 X51:1&2 SPARE Yes N/A
BI 02 X51:3&4 SPARE Yes N/A
BI 03 X51:5&6 13.8Kv BUS TIE-1 CB OPEN Yes N/A
BI 04 X51:7&8 13.8Kv BUS TIE-1 CB CLOSED Yes N/A
BI 05 X51:9&10 13.8Kv BUS TIE-1 CB TEST Yes N/A
BI 06 X51:11&12 13.8Kv BUS TIE-1 CB SERVICE Yes N/A
BI 07 X51:13&14 SPARE Yes N/A
BI 08 X51:15&16 SPARE Yes N/A
BI 09 X52:1&2 13.8Kv BUS TIE-2 CB OPEN Yes N/A
BI 10 X52:3&4 13.8Kv BUS TIE-2 CB CLOSED Yes N/A
BI 11 X52:5&6 13.8Kv BUS TIE-2 CB TEST Yes N/A
BI 12 X52:7&8 13.8Kv BUS TIE-2 CB SERVICE Yes N/A
BI 13 X52:9&10 SPARE Yes N/A
BI 14 X52:11&12 SPARE Yes N/A
BI 15 X52:13&14 13.8KV CAP BANK-1 CB OPEN Yes N/A
BI 16 X52:15&16 13.8KV CAP BANK-1 CB CLOSED Yes N/A
SLOT NO : P6
Tested by: Witnessed by:
P a g e : 2 of 9
Name : Name: Date :
Signature: Signature:
SITE INSPECTION TEST REPORT
380 /132/13.8kV SUBSTATION -9016
ACCS TYPE REC670 RELAY
Client: SEC-COA Contractor:
Site location: Contractor
Panel Ref/Bay: ACCS / 13.8kV AUTONo:
CAPACITOR SWITCHING SCHEME
PANEL

Binary Relay
Function Duty Result
Inputs terminals
BI 01 X61:1&2 13.8KV CAP BANK-1 CB TEST Yes N/A
BI 02 X61:3&4 13.8KV CAP BANK-1 CB SERIVICE Yes N/A
BI 03 X61:5&6 SPARE Yes N/A
BI 04 X61:7&8 SPARE Yes N/A
BI 05 X61:9&10 13.8KV CAP BANK-2 CB OPEN Yes N/A
BI 06 X61:11&12 13.8KV CAP BANK-2 CB CLOSED Yes N/A
BI 07 X61:13&14 13.8KV CAP BANK-2 CB TEST Yes N/A
BI 08 X61:15&16 13.8KV CAP BANK-2 CB SERIVICE Yes N/A
BI 09 X62:1&2 SPARE Yes N/A
BI 10 X62:3&4 SPARE Yes N/A
BI 11 X62:5&6 13.8KV CAP BANK-3 CB OPEN Yes N/A
BI 12 X62:7&8 13.8KV CAP BANK-3 CB CLOSED Yes N/A
BI 13 X62:9&10 13.8KV CAP BANK-3 CB TEST Yes N/A
BI 14 X62:11&12 13.8KV CAP BANK-3 CB SERIVICE Yes N/A
BI 15 X62:13&14 SPARE Yes N/A
BI 16 X62:15&16 SPARE Yes N/A
SLOT NO: P7

Binary Relay
Function Duty Result
Inputs terminals
BI 01 X71:1&2 GT-1 HV CB CLOSED Yes N/A
BI 02 X71:3&4 GT-1 VT MCB FAIL Yes N/A
BI 03 X71:5&6 GT-2 HV CB CLOSED Yes N/A
BI 04 X71:7&8 GT-2 VT MCB FAIL Yes N/A
BI 05 X71:9&10 GT-3 HV CB CLOSED Yes N/A
BI 06 X71:11&12 GT-3 VT MCB FAIL Yes N/A
BI 07 X71:13&14 A2 RELAY FAULTY Yes N/A
BI 08 X71:15&16 CAP-1 PROT TRIP Yes N/A
BI 09 X72:1&2 CAP-2 PROT TRIP Yes N/A
BI 10 X72:3&4 CAP-3 PROT TRIP Yes N/A
BI 11 X72:5&6 13.8KV BUS-A PROT TRIP Yes N/A
BI 12 X72:7&8 13.8KV BUS-A PROT TRIP Yes N/A
BI 13 X72:9&10 13.8KV BUS-A PROT TRIP Yes N/A
BI 14 X72:11&12 BLOCK ON SWITCHING BUS-A Yes N/A
BI 15 X72:13&14 BLOCK ON SWITCHING BUS-B Yes N/A
BI 16 X72:15&16 BLOCK ON SWITCHING BUS-C Yes N/A
SLOT NO: P8

Tested by: Witnessed by:


P a g e : 3 of 9
Name : Name: Date :
Signature: Signature:
SITE INSPECTION TEST REPORT
380 /132/13.8kV SUBSTATION -9016
ACCS TYPE REC670 RELAY
Client: SEC-COA Contractor:
Site location: Contractor
Panel Ref/Bay: ACCS / 13.8kV AUTONo:
CAPACITOR SWITCHING SCHEME
PANEL
Binary Relay 1
Function Duty Result
Inputs terminals
BI 01 X81:1&2 C1 U/OV BLOCK Yes N/A
BI 02 X81:3&4 C2 U/OV BLOCK Yes N/A
BI 03 X81:5&6 C3 U/OV BLOCK Yes N/A
BI 04 X81:7&8 ACCS REMOTE Yes N/A
BI 05 X81:9&10 ACCS LOCAL Yes N/A
BI 06 X81:11&12 ACCS AUTO Yes N/A
BI 07 X81:13&14 ACCS MANUAL Yes N/A
BI 08 X81:15&16 ACCS ON Yes N/A
BI 09 X82:1&2 ACCS OFF Yes N/A
BI 10 X82:3&4 ACCS TEST ON Yes N/A
BI 11 X82:5&6 ACCS TEST OFF Yes N/A
BI 12 X82:7&8 CB1 MANUAL ON Yes N/A
BI 13 X82:9&10 CB1 MANUAL OFF Yes N/A
BI 14 X82:11&12 CB2 MANUAL OFF Yes N/A
BI 15 X82:13&14 CB2 MANUAL ON Yes N/A
BI 16 X82:15&16 CB3 MANUAL OFF Yes N/A
BINARY OUTPUTS (BOM)
SLOT NO:P4

Binary Relay
Function Duty Result
Inputs terminals
BO01 X41:2&1 CAP .BANK-1 CLOSE CMND Yes N/A
BO02 X41:2&3 CAP .BANK-1 OPEN CMND Yes N/A
BO03 X41:5&4 CAP .BANK-2 CLOSE CMND Yes N/A
BO 04 X41:5&6 CAP .BANK-2 OPEN CMND Yes N/A
BO 05 X41:8&7 CAP .BANK-3 CLOSE CMND Yes N/A
BO 06 X41:8&9 CAP .BANK-3 OPEN CMND Yes N/A
BO 07 X41:11&10 SPARE Yes N/A
BO 08 X41:11&12 SPARE Yes N/A
BO 09 X41:14&13 SPARE Yes N/A
BO 10 X41:14&15 SPARE Yes N/A
BO 11 X41:17&16 SPARE Yes N/A
BO 12 X41:17&18 SPARE Yes N/A
BO 13 X42:2&1 SPARE Yes N/A
BO 14 X42:2&3 SPARE Yes N/A
BO 15 X42:5&4 SPARE Yes N/A
BO 16 X42:5&6 SPARE Yes N/A
BO17 X42:8&7 SPARE Yes N/A
BO18 X42:8&9 SPARE Yes N/A
BO19 X42:11&10 SPARE Yes N/A
BO20 X42:11&12 SPARE Yes N/A
BO21 X42:14&13 SPARE Yes N/A
Tested
BO22
by:X42:14&15 SPARE
Witnessed by: Page
Yes
:
4 of
N/A
9
Name
BO23: X42:17&16 SPARE Name:
Date :
Yes N/A
Signature: X42:17&18
BO24 SPARE Signature: Yes N/A
SITE INSPECTION TEST REPORT
380 /132/13.8kV SUBSTATION -9016
ACCS TYPE REC670 RELAY
Client: SEC-COA Contractor:
Site location: Contractor
Panel Ref/Bay: ACCS / 13.8kV AUTONo:
CAPACITOR SWITCHING SCHEME
PANEL
FUNCTIONAL CHECK :
Case: 1 INCOMER-1 (INDEPENDANT)

Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over clo ope ope open ope o-c open open
9Mvar se n n n 5min
Under clo ope ope open ope c-o open open
mvar se n n n 5min
1 Mvar

Case: 2 INCOMER-2 (INDEPENDANT)

Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over ope clos ope open ope ope o-c open
9 Mvar n e n n n 5min
Under ope clos ope open ope ope c-o open
mvar n e n n n 5min
1 Mvar

Case: 3 INCOMER-3 (INDEPENDANT)

Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over ope ope clos open ope ope open o-c
9 Mvar n n e n n 5min
Under ope ope clos open ope ope open c-o
mvar n n e n n 5min
1 Mvar

Tested by: Witnessed by:


P a g e : 5 of 9
Name : Name: Date :
Signature: Signature:
SITE INSPECTION TEST REPORT
380 /132/13.8kV SUBSTATION -9016
ACCS TYPE REC670 RELAY
Client: SEC-COA Contractor:
Site location: Contractor
Panel Ref/Bay: ACCS / 13.8kV AUTONo:
CAPACITOR SWITCHING SCHEME
PANEL
Case: 4 INCOMER 1&2 PARALLEL

Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over clo clos ope close ope o-c o-c open
10,11 se e n n 5mi 10mi
Mvar n n
Under clo clos ope close ope c-o c-o open
mvar se e n n 10m 5
2,3 Mvar in min

Case: 5 INCOMER 2&3 PARALLEL

Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over ope clos clos open clos ope o-c o-c
10,11 n e e e n 5min 10mi
Mvar n
Under ope clos clos open clos ope c-o c-o
mvar n e e e n 10mi 5
2,3 Mvar n min

Case: 6 INCOMER 1&3 PARALLEL

Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over clo ope clos close clos o-c open o-c
10,11 se n e e 5mi 10mi
Mvar n n
Under clo ope clos close clos c-o open c-o
mvar se n e e 10m 5
2,3 Mvar in min

Tested by: Witnessed by:


P a g e : 6 of 9
Name : Name: Date :
Signature: Signature:
SITE INSPECTION TEST REPORT
380 /132/13.8kV SUBSTATION -9016
ACCS TYPE REC670 RELAY
Client: SEC-COA Contractor:
Site location: Contractor
Panel Ref/Bay: ACCS / 13.8kV AUTONo:
CAPACITOR SWITCHING SCHEME
PANEL

Case: 7 INCOMER 1,2, IN PARALLEL BC-1&2 CLOSED


Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over clo clos ope close clos o-c o-c open
10,11 se e n e 5mi 10mi
Mvar n n
Under clo clos ope close clos c-o c-o open
mvar se e n e 10m 5
2,3 Mvar in min

CASE: 8

INCOMER 2&3 CLOSED BC-1 &2 CLOSED


Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over ope clos clos close clos ope o-c o-c
10,11 n e e e n 5min 10mi
Mvar n
Under ope clos clos close clos ope c-o c-o
mvar n e e e n 10 5
2,3 Mvar min min

CASE:9

INCOMER 1&3 CLOSED BC-1 &2 CLOSED


Starting Qt1 Qt2 Qt3 Qbus Qbu Qc1 Qc2 Qc3 pass
status 1 s2
Mvar over clo ope clos close clos o-c ope o-c
10,11 se n e e 5min n 10mi
Mvar n
Under clo ope clos close clos c-o ope c-o
mvar se n e e 10 n 5
2,3 Mvar min min

Tested by: Witnessed by:


P a g e : 7 of 9
Name : Name: Date :
Signature: Signature:
SITE INSPECTION TEST REPORT
380 /132/13.8kV SUBSTATION -9016
ACCS TYPE REC670 RELAY
Client: SEC-COA Contractor:
Site location: Contractor
Panel Ref/Bay: ACCS / 13.8kV AUTONo:
CAPACITOR SWITCHING SCHEME
PANEL

LABELS :

QT1 : INCOMER 1(H11)

QT2 : INCOMER 2(H12)

QT3 : INCOMER 3(H40)

QB1 : BUS TIE -1(H120)

QB2 : BUS TIE-2(H320)

QC1 : CAPACITOR FEEDER 1(H01)

QC2 : CAPACITOR FEEDER 2(H24)

QC3 : CAPACITOR FEEDER 3(H48)

Tested by: Witnessed by: