Getting Started Manual: Allen-Bradley
Getting Started Manual: Allen-Bradley
Getting Started Manual: Allen-Bradley
DriveTools32
Getting Started
Version 1.xx
Getting Started
Using RSLinx Lite
Version 1.7
Manual
Important User Because of the variety of uses for the products described in this publica-
Information tion, those responsible for the application and use of this control equip-
ment must satisfy themselves that all necessary steps have been taken to
assure that each application and use meets all performance and safety
requirements, including any applicable laws, regulations, codes and stan-
dards.
Throughout this manual we use notes to make you aware of safety con-
siderations:
Identify a hazard.
Avoid the hazard.
Recognize the consequences.
Important: Identifies information that is critical for successful applica-
tion and understanding of the product.
Summary of Changes
Summary of Changes
Overview Chapter 1
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
What Hardware Do I Need to Run DriveTools32 and RSLinx?. . . . . . . . . . . . 1-1
Using DriveTools32 with an Allen-Bradley
SCANport-Compatible Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Using DriveTools32 with a 1336T (FORCE) Drive . . . . . . . . . . . . . . . . . . . 1-4
Using DriveTools32 with a 1395 Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Example Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
DriveTools32 and Database Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Installing DriveTools32 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Installing RSLinx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
Starting RSLinx and DriveTools32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
Setting Up a Chapter 6
ControlNet Direct Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Communications What is a ControlNet Communications System? . . . . . . . . . . . . . . . . . . . . . . 6-1
System Checking Your Hardware Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Configuring RSLinx for ControlNet Direct Communications . . . . . . . . . . . . . . 6-2
Configuring the Communication Driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Testing the Configured Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Mapping the Configured Driver(s) to the KTPort Value. . . . . . . . . . . . . . . . 6-4
Setting the Communication Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Connecting to the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Using the WHO Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
SCANport- Appendix A
Compatible Appendix Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
Products Supported Supported SCANport-Compatible Database Files . . . . . . . . . . . . . . . . . . . . .A-1
by DriveTools32 DriveTools32 and Database Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-2
Notes:
Preface
Read this preface to become familiar with the rest of the manual. This preface
covers the following topics:
Who Should Use Use this manual if you are responsible for using the DriveTools32 software to
This Manual? program, monitor, and troubleshoot Allen-Bradley AC and DC digital drive
products. You should be familiar with programming Allen-Bradley digital drives
and have basic personal computer and Windows operation skills and knowledge,
such as starting applications, navigating between applications, using menus and
dialogs, and accessing your Windows help system.
DriveManager32 Easily create and edit drive data tables that are used to configure the
drive for your application. DriveManager32 also provides several
methods of displaying drive diagnostic information.
DriveMonitor32 Graphically monitor a drive and/or PLC controller data points when
connected to a Data Highway Plus (DH+) network. You can easily
display live data values in a graphic format.
DrivePanel32 Use the programming and control functions available with a Human
Interface Module (HIM) from your terminal screen. DrivePanel32
includes several additional programming and control features that are
not available with a HIM.
DriveTrending32 Program the internal drive trending functions when supported by the
drive.
DriveBlockEditor32 Create and monitor function block programs that run internally on drives
that support function blocks.
What Is RSLinx? RSLinx provides the necessary communications drivers which enable
DriveTools32 to communicate with Allen-Bradley drive products using a variety
of different networks as well as direct serial connection.
Before you can start DriveTools32 applications, you must either load RSLinx
Lite (version 1.7), which is shipped with DriveTools32, or you must already
have RSLinx running and properly configured on your PC.
Purpose of this This manual is designed to get you started using DriveTools32 software. You
Manual will learn how to set up and properly configure RSLinx for your system and how
to connect to your drive from a DriveTools32 application.
The DriveTools32 software family contains online help designed to let you
understand and use this product.
Important: You should read this manual and be familiar with your drive system
before you install and set up your DriveTools32 software.
Preface Describes the purpose, background, and scope of this manual as well as an overview
of this product.
2 Setting Up an RS-232 Point-to- Provides information for properly configuring RSLinx for an RS-232 point-to-point
Point Serial Communications serial communications system as well as the steps for connecting to the drive from
System for a SCANport Product within DriveTools32 applications.
3 Setting Up an RS-232 Point-to- Provides information for disabling RSLinx and properly configuring DriveTools32 for a
Point Serial Communications 1395 RS-232 point-to-point serial communications system as well as the steps for
System for a 1395 Drive connecting to the drive from within DriveTools32 applications.
4 Setting Up DH+ Direct Provides information for properly configuring RSLinx for DH+ Direct communications
Communications Systems systems as well as the steps for connecting to the drive from within DriveTools32
applications.
5 Setting Up a DH+ to RIO Block Provides information for properly configuring RSLinx for a DH+ to RIO Block Transfer
Transfer Pass Thru Pass Thru communications system as well as the steps for connecting to the drive
Communications System from within DriveTools32 applications.
6 Setting Up a ControlNet Direct Provides information for properly configuring RSLinx for a ControlNet Direct
Communications System communications system as well as the steps for connecting to the drive from within
DriveTools32 applications.
7 Setting Up an Allen-Bradley Provides information for properly configuring RSLinx for an A-B Ethernet to RIO Pass
Ethernet to RIO Block Transfer Thru communications system as well as the steps for connecting to the drive from
Pass Thru Communications within DriveTools32 applications.
System
8 Using RSLinx Gateways Provides information for properly configuring RSLinx for RSLinx gateways as well as
the steps for connecting to the drive from within DriveTools32 applications.
Related Documentation
See the online help files for individual application information. All
documentation for Drive Tools32 is currently in the online help.
Terms and For a complete listing of Allen-Bradley terminology, including terms and
Abbreviations abbreviations used in this manual, refer to the Allen-Bradley Industrial
Automation Glossary.
Conventions Used The following conventions are used throughout this manual:
in this Manual
Bulleted lists provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical information.
Italic type is used for chapter names.
Bold type is used for names of dialog boxes, dialog box fields, menus,
menu options, and buttons.
When RSLinx is referred to in this manual, you may use either the RSLinx
Lite (version 1.7) shipped with DriveTools32 or RSLinx (version 1.7).
Important: This type of paragraph contains tips or notes that have been added to
call attention to useful information.
Rockwell Rockwell Automation offers support services worldwide, with over 75 sales/
Automation support offices, over 500 authorized distributors, over 250 authorized systems
Support integrators located through the United States alone, and Rockwell Automation
representatives in every major country in the world.
Notes:
What Hardware Do DriveTools32 and RSLinx allow for flexibility when it comes to connecting to
I Need to Run drive products. The hardware you need depends on your drive and your drive
DriveTools32 and system. This section provides information about some of the more common
configurations.
RSLinx?
Important: DriveMonitor32 cannot use RIO Block Transfer Pass Thru
communications or 1395 Serial communications.
Before determining the configuration that you want to use, you should have a
basic understanding of the different communication types that DriveTools32
supports:
DH+ Direct 4
ControlNet Direct 6
RSLinx Gateway 8
To use this You need this And this hardware For installation,
communication type: hardware on the PC-side: refer to:
on the drive-side:
To use this You need this And this hardware For installation,
communication type: hardware on the PC-side: refer to:
on the drive-side:
Point-to-Point
RS232 Serial Connection
RS232/RS422
1395 Protocol
RS232 1395
1300-ITSSC
RS422
Figure 1.2
RS-232 Point-to-Point Communications for a SCANport-Compatible Product
Point-to Point
Serial Connection
RS232/DF1 RS232
DF1 Point-to-Point
Protocol
RS232
DF1
RS232 GD2
GM2
SCANport GK2
SCANport
SCANport
Product Important: For a list of SCANport products,
refer to Appendix A.
Figure 1.3
DH+ Direct and RIO Block Transfer Pass Thru Networks
Multi-Point PLC-5
Serial Connection KT, KL,
DH+ PCMK RS232
1770-KF2
DH+ RS232 DF1
DH+
DH+
RIO
Or Or
RIO GD1
GM1
SCANport GK1
SCANport SCANport
Figure 1.4
ControlNet Direct Communications Network
PLC-5 (C)
ControlNet
Connection KTC,
KTC(X)
ControlNet
ControlNet
Fiber CNet
Repeater
Module
1786-RPA 1786-RPFM
ControlNet
Adapter
1336T
(FORCE)
Figure 1.5
Allen-Bradley Ethernet to RIO Block Transfer Pass Thru Communications System
PLC-5 (E)
Ethernet Connection Ethernet
TCP/IP
Ethernet
Ethernet
RIO
Or Or ENet RIO BT
Pass Thru
RIO GD1
GM1
SCANport GK1
SCANport SCANport
Figure 1.6
RSLinx Gateway Ethernet to DH+ RIO Block Transfer Pass Thru Connection
Gateway PLC-5
Connection Server
Client
DH+ Ethernet
DH+
RIO
Or Or RIO BT
Pass Thru
RIO GD1
GM1
SCANport GK1
SCANport SCANport
DriveTools32 and DriveTools32 uses a unique database file for each drive product so that you can
Database Files configure each drive individually. DriveTools32 ships with many of the database
files it will need (refer to Appendix A).
If you connect to a drive for which DriveTools32 does not have a database file,
you will be prompted to upload a new database. Click OK and DriveTools32
uploads a database which you can then configure.
Click: To:
Next Indicate that all Windows programs are closed and you are ready to begin the
installation.
Cancel 1. Quit the setup program. The setup script prompts you to make sure
that you really want to cancel the setup script.
2. Close any programs you have running.
3. Go back to step 2.
Do not accept the terms of agreement No. The set up procedure will
close.
5. After carefully reading the information in the readme.txt file, click the
appropriate button.
To: Click:
6. In the Registration dialog box, enter your name, company, and the
DriveTools32 serial number, and then click Next.
Important: The serial number is located on the DriveTools32 box.
To: Click:
Install DriveTools32 in a different directory Browse and use the menu structure to locate the
directory
The default setup procedure. We recommend that you use this Typical (Recommended)
option as it sets up DriveTools32 in the most typically used
configuration.
Enable the security system. You will need to log in to the system Yes
later using the default user name of ADMIN and the default
password of PASS.
Change information Back. You can continue using the Back button until you reach the
information that you wish to change.
Installing RSLinx After you install DriveTools32, the RSLinx InstallShield wizard program
appears automatically. You must have RSLinx installed and properly configured
before you can use DriveTools32.
Important: If you already have RSLinx (version 1.7) installed on your PC, do
not install RSLinx Lite. Click Cancel and then Exit Setup.
If you need to install RSLinx Lite, follow the instructions in the InstallShield
wizard.
Starting RSLinx To start RSLinx, click Start, Programs, Rockwell Software, RSLinx, and
and DriveTools32 then RSLinx.
RS232 GD2/GM2/GK2
DF1 Point-to Point
Protocol RS232
RS232 SCANport
SCANport
DF1
SCANport
Product
For this type of configuration, you can have any drive, except a 1395. For
information on setting up an RS-232 point-to-point serial communications
system for a 1395 drive, refer to Chapter 3.
Checking Your Before configuring RSLinx for an RS-232 point-to-point serial communications
Hardware and running DriveTools32, you should check your hardware installation. You
Installation should:
In most cases, you should use the factory-set defaults. If you decide to
change the default settings, note the new settings because you will use them
later.
For any change to take effect, you must remove and then re-apply power to your
communications module.
Configuring To use RSLinx for an RS-232 point-to-point serial communications system, you
RSLinx for RS-232 need to:
Point-to-Point
1. Configure the communication driver.
Serial
Communications 2. Test the configured driver.
3. Map the configured driver(s) to the KTPort Value.
Important: In the Station Number field, you must enter the station number that
matches the GD2 modules address.
5. Click OK.
If you have more than one configured driver, double-click on the driver you
just configured to view the communication between the node(s) on the
network.
3. Use the drop box for the field to map the configured driver to the port.
4. Click OK or Apply.
Setting the You need to provide DriveTools32 with some information that it needs to
Communication establish a connection between your PC and your drive. To do this, you need to:
Information
1. Start the DriveManager32 application.
2. From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.
7. In the Enter Comm Port Baud Rate field, enter the baud rate that your
communications module and port are using. You can choose 2400, 4800,
9600, or 19200 baud.
8. If applicable, select 1336T Two Word Header (used ONLY for 1336T
version 0.10).
9. Click OK.
3. Click OK.
After a short pause, either the DriveManager32 screen with the drive parameters
appears, or you are prompted to create a database.
Using the WHO The WHO button is located on the ScanPort Network Connect to Drive dialog
Button box to help you determine the station number for your drive. When you click the
WHO button, the WHOs Active dialog box scans the SCANport list and
displays the devices that are currently active. The following is an example of a
WHOs Active dialog box.
To select a device:
When you are using serial communications, the WHOs Active dialog box takes
a few moments to complete the scan.
The main window displayed in the WHOs Active dialog box shows the
information read from the network WHO command. The information consists of
the following:
Station # The network station number for each device on the network.
Device Type The type of device that is associated with the network station number.
Station Name The textual description contained in the device at the network station number.
SCAN
Click SCAN to rescan the network to read station information.
KT Port x
Lets you select an alternate RSLinx KT:0 communication driver. For
RS-232 serial communications, this setting must match your RSLinx DF1
port settings.
Notes:
RS232 1300-ITSSC
RS232
1395 Protocol RS232 Serial port
RS422
1395
Checking Your Before running DriveTools32, check to make sure that all cable connections
Hardware between the drive and the PC are secure. Specifically, you should check that the
Installation following cables are firmly plugged in:
The cable between the 1395 drive and the 1300-ITSSC communications
module.
The cable between the 1300-ITSSC communications module and your PC.
Disabling RSLinx Before starting DriveTools32, you must make sure RSLinx is disabled for the
communications port you intend to use. To disable it, follow these instructions:
1. Start RSLinx.
2. From the Communications menu, select Configure drivers. The
Configure Drivers dialog box appears.
Setting the To provide DriveTools32 with some information that it needs to establish a
Communication connection between your PC and your drive, you need to:
Information
1. Start DriveManager32.
2. From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.
6. In the Enter Comm Port Baud Rate field, enter the baud rate that your
communications port uses. You can choose either 2400 or 4800 baud.
7. In the DTR Pulse Delay (0 to calculate automatically) field, enter 0.
Important: If your PCs transmission is too fast for the 1300-ITSSC adapter,
you will have to increase the value for DTR Pulse Delay. Start at 1000 and
increase the value by increments of 500 until communications work.
9. Click OK.
2. Click OK.
After a short pause, either the DriveManager32 screen with the drive
parameters appears, or you are prompted to create a database.
What is a DH+ A Data Highway Plus (DH+) system lets your PC communicate directly with
Direct drives that are connected to the DH+ network using either an internal PC card
Communications (such as a 1784-KT, -KL, or -PCMK) or an external RS232 or DH+ converter
module (such as a 1770-KF2). Figure 4.1 shows an example of a DH+ direct
System? communication system.
Figure 4.1
DH+ Direct Network
Multi-Point
Serial Connection KT, KL,
DH+ Or RS232
PCMK 1770-KF2
DH+ RS232 DF1
DH+
DH+
Or
SCANport
1336T 1395
(FORCE)
Checking Your Before configuring RSLinx and running DriveTools32, you should check:
Hardware
Installation All the cable connections between the drive and the PC are secure.
Equipment is powered up.
Configuring To use RSLinx for a DH+ communications system, you need to:
RSLinx for DH+
Direct 1. Configure the communication driver.
Communications 2. Test the configured driver.
3. Map the configured driver(s) to the KTPort Value.
4. In the Value field, select the correct DH+ device for your configuration.
5. In the Property box, change any fields as required to match the settings
needed for your DH+ interface card.
6. Click OK.
If you have more than one configured driver, double-click on the driver you
just configured to view the communication between the node(s) on the
network.
3. Use the drop box for the field to map the configured driver to the port.
4. Click OK or Apply.
Setting the You need to provide DriveTools32 with some information that it needs to
Communication establish a connection between your PC and your drive. To do this, you need to:
Information for
1. Start DriveManager32.
DH+ Direct
2. From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.
6. If applicable, select 1336T Two Word Head (used ONLY for 1336T
version 0.10).
7. Click OK.
Configuring To use RSLinx for DF1 (KF2) to DH+ communications system, you need to:
RSLinx for DF1
(KF2) to DH+ 1. Configure the communication driver.
Communications 2. Test the configured driver.
3. Map the configured driver(s) to the KTPort Value.
Important: In the Station Number field, you must enter the station number that
matches the GD2 modules address.
5. Click OK.
If you have more than one configured driver, double-click on the driver you
just configured to view the communication between the node(s) on the
network.
3. Use the drop box for the field to map the configured driver to the port.
4. Click OK or Apply.
Setting the You need to provide DriveTools32 with some information that it needs to
Communication establish a connection between your PC and your drive. To do this, you need to:
Information for
1. Start DriveManager32.
DF1(KF2) to DH+
2. From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.
6. In the Enter Serial Port Com # field, enter the number of the PC serial
communications port that is being used.
7. In the Enter Comm Port Baud Rate field, enter the baud rate that your
communications module and port are using. You can choose 2400, 4800,
9600, or 19200 baud.
8. If applicable, select 1336T Two Word Head (used ONLY for 1336T
version 0.10).
9. Click OK.
2. Enter the DH+ station number. The DH+ station number is the DH+ address
for the drive. Valid station numbers are octal values between 0 and 77.
Important: You can use the WHO button to determine the station number. The
WHO button is covered in further detail below.
3. Click OK.
After a short pause, either the DriveManager32 screen with the drive parameters
appears, or you are prompted to create a database.
Using the WHO The WHO button is located on the DH+ Network Connect to Drive dialog box
Button to help you determine the station number for your drive. When you click WHO,
the WHOs Active dialog box scans the DH+ Network and displays the devices
that are currently active. The following is an example of a WHOs Active dialog
box.
To select a device:
The main window displayed in the WHOs Active dialog box shows the
information read from the network WHO command. The information consists of
the following:
Station # The network station number for each device on the network.
Device Type The type of device that is associated with the network station number.
Station Name The textual description contained in the device at the network station number.
The Bulletin 1395 drive does not support a network station name. Therefore, the
name shown on the network map is the same for all 1395 drives.
SCAN
Click on the SCAN button to rescan the network to read station
information.
KT Port x
The KT Port radio buttons let you change the currently selected DH+
network KT card from within the WHOs Active dialog box. When you
change the KT port definition, the dialog rescans the network based on the
new setting.
What is a DH+ to A Data Highway Plus (DH+) to RIO Block Transfer Pass Thru communications
RIO Block Transfer system lets your PC communicate with drive products using the PLC-5 RIO
Pass Thru Block Transfer Pass Thru mechanism.
Communications Important: A DH+ to RIO Block Transfer Pass Thru communications system
System? also works with an SLC-500 family processor using a Series B 1747-SN RIO
scanner in slot 1.
The RIO Block Transfer Pass Thru mechanism requires that a drive be
connected to a PLC-5 as an RIO device on the PLCs RIO network. You can
connect a drive as an RIO device using several different hardware options
depending on the drive type. These options include:
To communicate with a drive over RIO, you need to set the drives RIO adapter
up so that it appears to be an adapter to a PLC RIO scanner. To do this, you need
to specify the rack and group number where the drive is to appear on the RIO
network. You will do this during the Connecting to the Drive step. You should
refer to the documentation for your drive and the communications module for
information on configuring the drive as an RIO device.
Figure 5.1 shows an example of a DH+ to RIO Block Transfer Pass Thru
communications system.
Figure 5.1
DH+ to RIO Block Transfer Pass Thru Network
Multi-Point PLC-5
Serial Connection KT, KL,
DH+ PCMK
DH+
DH+
RIO
Or Or
Important: In your communications
RIO GD1 module, Switch 1 of SW3 must be On to
GM1
SCANport GK1 enable block transfer.
SCANport SCANport
Important: For RIO Block Transfer Pass Thru communications to work, the
PLC to which the drive is connected must be in RUN mode. If the PLC is not in
RUN mode, pass thru messages cannot be delivered to the connected drive
product.
Checking Your Before configuring RSLinx and running DriveTools32, you should check:
Hardware
Installation All cable connections between the drive and PC are secure.
If you are using a 1203-GD1, 1203-GK1, or 1336-GM1 communications
module, Switch 1 of SW3 must be On to enable block transfer.
Power is applied to the drive.
Configuring To use RSLinx for a DH+ communications system, you need to:
RSLinx for DH+ to
RIO Block Transfer 1. Configure the communication driver.
Pass Thru 2. Test the configured driver.
Communications 3. Map the configured driver(s) to the KTPort Value.
4. In the Value field, select the correct DH+ device for your configuration.
5. In the Property box, change any fields as required to match the settings
needed for your DH+ interface card.
6. Click OK.
If you have more than one configured driver, double-click on the driver you
just configured to view the communication between the node(s) on the
network.
3. Use the fields drop box to map the configured driver to the port.
4. Click OK or Apply.
Important: When using RIO Block Transfer Pass Thru for drive
communications from the PC, you cannot use Block Transfer messages in the
PLC program for this drive.
Setting the To provide the DriveTools32 with information that it needs to establish a
Communication connection between your PC and your drive, you need to:
Information
1. Start DriveManager32.
2. From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.
6. If applicable, select 1336T Two Word Header (used ONLY for 1336T
version 0.10).
7. Click OK. A window displaying information about RIO Block Transfer
Pass Thru communications appears.
8. Read the information and click OK.
2. In the Enter PLC (SLC) DH+ Station field, enter the DH+ station number.
The DH+ station number is the DH+ address of the PLC-5 that has the drive
connected to its RIO channel.
Valid station numbers are octal values between 0 and 77. If you are using a
1395 drive with a Multi-Comm board or a 1336 FORCE drive with a PLC
Communications Adapter Board, the station number is set on the
communications board.
Important: You can use the WHO button to determine the station number. The
WHO button is explained in further detail below.
4. In the Enter Drive Rack # field, enter the RIO rack number associated with
this drive.
The rack number is specified in octal and is set in the communication
hardware module for the drive.
5. In the Enter Starting Group # field, enter the RIO starting group number
associated with this drive.
The RIO starting group number is set in the communication hardware
module for the drive. Valid numbers are 0, 2, 4, and 6.
Using the WHO The WHO button is located on the RIO Pass Through Network Connect to
Button Drive dialog box to help you determine the DH+ station number for the PLC to
which the drive is connected. When you click WHO, the WHOs Active dialog
box scans the DH+ network and displays the devices that are currently active.
The following is an example of a WHOs Active dialog box.
To select a device:
When you are using DH+ communications, the WHOs Active dialog box
quickly completes the scan.
The main window displayed in the WHOs Active dialog box shows the
information read from the network WHO command. The information consists of
the following:
Station # The network station number for each device on the network.
Device Type The type of device that is associated with the network station number.
Station Name The textual description contained in the device at the network station number.
The Bulletin 1395 drive does not support a network station name. Therefore, the
name shown on the network map is the same for all 1395 drives.
SCAN
Click on the SCAN button to rescan the network to read station
information.
KT Port x
The KT Port radio buttons let you change the currently selected DH+
network KT card from within the WHOs Active dialog box. When you
change the KT port definition, the dialog rescans the network based on the
new setting.
Notes:
ControlNet
ControlNet
Fiber CNet
Repeater
Module
1786-RPA 1786-RPFM
ControlNet
Adapter
1336T
(FORCE)
Checking Your Before setting up RSLinx and running DriveTools32, you should check your
Hardware hardware installation. You should:
Installation
Have a ControlNet interface device. For example, a 1784-KTC(X) board is
installed correctly in your PC.
Check to make sure all cable connections between the drive and PC are
secure.
Have a ControlNet Repeater Adapter and ControlNet Fiber Module
connecting the network to your drive.
Configuring To use RSLinx for a ControlNet direct communications system, you need to:
RSLinx for
ControlNet Direct 1. Configure the communication driver.
Communications 2. Test the configured driver.
3. Map the configured driver(s) to the KTPort Value.
If you have more than one configured driver, double-click on the driver you
just configured to view the communication between the node(s) on the
network.
3. Use the drop box for the field to map the configured driver to the port.
4. Click OK or Apply.
Setting the To provide the DriveTools32 with information that it needs to establish a
Communication connection between your PC and your drive, you need to:
Information
1. Start DriveManager32.
2. From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.
6. If applicable, select 1336T Two Word Header (use ONLY for 1336T
version 0.10).
7. Click OK.
2. In the Enter ControlNet Station field, enter the ControlNet station number
for the 1336 FORCE drive.
Valid station numbers are decimal values between 0 and 99. The station
number is set on the PLC Communications Adapter board on the 1336
FORCE. For more information, consult the 1336-GT3EN user manual.
Important: You can use the WHO button to determine the station number. The
WHO button is covered in further detail below.
3. Click OK.
After a short pause, either the DriveManager32 screen with the drive parameters
appears, or you are prompted to create a database.
Using the WHO The WHO button is located on the ControlNet Network Connect to Drive
Button dialog box to help you determine the station number for your drive. When you
click WHO, the WHOs Active dialog box scans the network and displays the
devices that are currently active. The following is an example of a WHOs
Active dialog box.
To select a device:
When you are using ControlNet communications, the WHOs Active dialog
box quickly completes the scan.
The main window displayed in the WHOs Active dialog box shows the
information read from the network WHO command. The information consists of
the following:
Station # The network station number for each device on the network.
Device Type The type of device that is associated with the network station number.
Station Name The textual description contained in the device at the network station number.
The Bulletin 1395 drive does not support a network station name. Therefore, the
name shown on the network map is the same for all 1395 drives.
SCAN
Click SCAN to rescan the network to read station information.
KT Port x
The KT Port radio buttons let you change the currently selected ControlNet
network KT card from within the WHOs Active dialog box. When you
change the KT port definition, the dialog rescans the network based on the
new setting.
What is an Ethernet is a local area network (LAN) that provides non-deterministic data
Ethernet transport. The following is an example of this type of configuration.
Communications
Important: An Ethernet communications system cannot and should not be used
System? for controlling a device.
Figure 7.1
Allen-Bradley Ethernet Communications System
PLC-5 (E)
Ethernet Connection Ethernet
TCP/IP
Ethernet
Ethernet
RIO
Or Or ENet RIO BT
Pass Thru
RIO GD1
GM1
SCANport GK1
SCANport SCANport
Important: For RIO Block Transfer Pass Thru communications to work, the
PLC to which the drive is connected must be in RUN mode. If the PLC is not in
RUN mode, pass thru messages cannot be delivered to the connected drive
product.
Checking Your Before setting up RSLinx and running DriveTools32, you should check your
Hardware hardware installation. You should:
Installation
Have an Ethernet card running TCP/IP correctly installed.
Check that all cable connections between the computer and drive are secure.
Configuring To use RSLinx for a serial communications system, you need to:
RSLinx for
Ethernet to RIO 1. Configure the communication driver.
Block Transfer 2. Test the configured driver.
Pass Thru
Communications Configuring the Communication Driver
To configure the communication driver, you need to:
4. In the Driver Station field, enter a unique station number for your PC on
the Ethernet. Valid numbers are from 0 to 63.
5. In the IP Address or hostname field, enter the IP address.
Remember the IP address. You will enter it again in the Communications
Setup dialog box.
If you have more than one configured driver, double-click on the driver you
just configured to view the communication between the node(s) on the
network.
Setting the You need to provide DriveTools32 with some information that it needs to
Communication establish a connection between your PC and your drive. To do this, you need to:
Information
1. Start DriverManager32.
2. From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.
6. If applicable, select 1336T Two Word Header (Use ONLY for 1336T
version 0.10).
7. Click OK. A window displaying information about RIO Block Transfer
Pass Thru communications appears.
8. Read it and click OK.
2. In the Enter Drive Rack # field, enter the RIO rack number associated with
this drive.
The rack number is specified in octal and is set in the communication
adapter for the drive.
3. In the Enter Starting Group # field, enter the RIO starting group number
associated with this drive.
The RIO starting group number is set in the communication adapter for the
drive. Valid starting group numbers are 0, 2, 4, and 6.
Figure 8.1
RSLinx Gateway to DH+ and to DH+ RIO Block Transfer Pass Thru Connection
Server Client
Gateway PLC-5
Connection RSLinx Ethernet
TCP/IP TCP/IP
DH+ Ethernet
DH+
RIO
Or Or RIO BT
Pass Thru
RIO GD1
GM1
SCANport GK1
SCANport SCANport
Checking Your Before setting up RSLinx and running DriveTools32, you should check your
Hardware hardware installation. You should:
Installation
Have an Ethernet card running TCP/IP correctly installed in your PC.
Check that you are logged on to your local area network.
To start DriveTools32 applications, click Start, Programs, DriveTools32 and
then the DriveTools32 application (e.g., DriveManager32).
Configuring To use RSLinx for an RSLinx Gateway communications system, you need to:
RSLinx for RSLinx
Gateways 1. Configure the communication driver.
2. Test the configured driver.
3. Map the configured driver(s) to the KTPort Value.
4. From the Server Name list, select the server to which you want to connect.
A list of Remote drive names appears.
5. From the Remote driver name list, select the DH+ driver to which you
want to connect.
6. Click OK.
If you have more than one configured driver, double-click on the driver you
just configured to view the communication between the node(s) on the
network.
3. Use the drop box for the field to map the configured driver to the port.
4. Click OK or Apply.
Setting the To provide DriveTools32 with information that it needs to establish a connection
Communication between your PC and your drive, you need to:
Information
1. Start DriveManager32.
2. From the Options menu, select Communication Setup. The
Communication Setup dialog box appears.
6. If applicable, select 1336T Two Word Header (used ONLY for 1336T
version 0.10).
7. Click OK. A window displaying information on RIO Pass Thru
communications may appear.
8. Click OK.
Important: You can use the WHO button to determine the station number. The
WHO button is covered in further detail below.
3. Click OK.
After a short pause, either the DriveManager32 screen with the drive parameters
appears, or you are prompted to create a database.
Using the WHO The WHO button is located on the Gateway DH+ Network Connect to Drive
Button dialog box to help you determine the station number for your drive. When you
click WHO, the WHOs Active dialog box scans the SCANport list and
displays the devices that are currently active. The following is an example of a
WHOs Active dialog box.
To select a device:
The main window displayed in the WHOs Active dialog box shows the
information read from the network WHO command. The information consists of
the following:
Station # The network station number for each device on the network.
Device Type The type of device that is associated with the network station number.
Station Name The textual description contained in the device at the network station number.
The Bulletin 1395 drive does not support a network station name. Therefore, the
name shown on the network map is the same for all 1395 drives.
SCAN
Click on the SCAN button to rescan the network to read station
information.
KT Port x
The KT Port radio buttons let you change the currently selected DH+
network KT card from within the WHOs Active dialog box. When you
change the KT port definition, the dialog rescans the network based on the
new setting.
Supported The following table lists the most common SCANport products.
SCANport-
Compatible Bulletin Number Product Sub-Directory
Database Files 1305 AC Micro Drive 1305 AC Micro Drive D_1305N
2364F RGU DC Bus Regen Front End 2364F RGU DC Bus Regen Front End D_2364F
DriveTools32 and DriveTools32 uses a unique database file for each drive product so that you can
Database Files configure each drive individually. DriveTools32 ships with many of the database
files it will need (refer to the table above).
If you connect to a drive for which DriveTools32 does not have a database file,
you will be prompted to upload a new database file.
Click Yes and DriveTools32 uploads a database which you can then configure.
When the upload is complete, DriveTools32 prompts you.
Click OK.
Windows, WindowsNT, and Microsoft are either registered trademarks or trademarks of Microsoft Corporation.
Publication 9303-5.13 March 1998 185856
Copyright 1998 Allen-Bradley Company, Inc. Printed in USA