FIELD FRESH, LUDHIANA
Design of Rafter Bracing
Length of Building = 105.00 m
Width of Building = 40.00 m
Bay Spacing = 7.0 m C/C
End Wall Spacing = 6.0 m C/C
Clear Height = 7.55 m
Eaves Height = 9.00 m
Brick Wall Height = 7.55 m
Wind Pressure = 115.00 kg/m2
Wind Coeff on Roof = 1.14
Wind Coeff on Wall = 0.90
Slope = 10 (1:10)
Number of Joints = 8 nos
Number of Sets = 4 nos
### Total Gable Wind Force = 115 x 0.9 x [0.5 x (40/2)x(40/(2x10)) + (40 / 2)x( 9 - 7.55 ) ]
= 5071.50 Kg
Considering connection of Gable Columns with Gable Rafter as fixed,
= 0.625 * 5071.50 = 3169.7 Kg is transferred in base of gable columns
and the rest of force which is 1901.8 Kg is transferred into rafter bracing.
Force per Joint = 1901.81 = 237.7 Kg
8
### Maximum force in Rafter = 22.80 T
Maximum moment in Rafter = 101.10 T-m
Lever Arm = 1262 mm = 1.26 m
Total force = (22.8 + 101.1/1.26) x 1000 x 0.075 = 7727.9 Kg
Force per Joint = 7728 = 966.0 Kg
8
### Frictional Drag for Rafter Bracing Joint = 105 x (40/2)x0.025x115x1.14
8x4
= 222.0 Kg
Total Force Per Joint = 237.7 + 966.0 + 221.97 = 1425.68 Kg
= 1.42 T
Force in Bracing F = R / Cos Q
Length of the Diagonal = 9.21 m
Cos Q = 0.76
Force in Bracing F = 1.42 / 0.76
F = 1.86 Tons
ASSUME: Angle 65x65x6
WT= 5.91 Kg/m
Area = 7.44 cm2
MI = 29.10 cm4
Z = 6.20 cm3
r = 29.1 / 7.44 = 1.98 cm
Eff Length ( l ) = 0.75 x 9.21 / 2
= 3.45 m
Slenderness Ratio = l / r = 174.63 < 250 [SAFE]
Permissible Stress in Axial Compression (As Per IS : 800 Table - 5.1)
Pac = 35 N/mm2
= 357 kg/cm2
Safe Load on Tube = 357 x 7.44 / 1000
= 2.7 Tons
Total Load Per Bracing = 1.42 Tons < 2.7 Tons [SAFE]
PROVIDE RAFTER BRACING SECTION = 65x65x6 Angle
Design of Column Bracing
### Force per Joint of Column Bracing = Force per Joint of Rafter Bracing
2
= 118.9 kgs
### Frictional Drag for Column Bracing Joint = 105 x 7.55 x0.025x115x0.9
4
= 512.8 kgs
### Reaction From Rafter Bracing = 1425.67 kgs
Total Force per Joint = 1425.67 + 512.81 - 118.86
= 1819.62 kgs
Force in Bracing F = R / Cos Q
Length of the Diagonal = 10.29 m
Cos Q = 0.68
Force in Bracing F = 1819.62 / 0.68
= 2675.91 kgs
F = 2.67 Tons
ASSUME: Angle 75x75x6
WT= 6.93 Kg/m
Area = 8.66 cm2
MI = 45.70 cm4
Z = 8.40 cm3
r = 45.7 / 8.66 = 2.30 cm
Eff Length ( l ) = 0.75 x 10.29 / 2
= 3.86 m
Slenderness Ratio = l / r = 167.98 < 250 [SAFE]
Permissible Stress in Axial Compression (As Per IS : 800 Table - 5.1)
Pac = 38 N/mm2
= 387.6 kg/cm2
Safe Load on Tube = 387.6 x 8.66 / 1000
= 3.4 Tons
Total Load Per Bracing = 2.67 Tons < 3.4 Tons [SAFE]
PROVIDE COLUMN BRACING SECTION = 75x75x6 Angle