An Overview of Protection System
An Overview of Protection System
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Generator Protection -
Introduction
Size of individual generating unit 30 MW to 500/1000
MW
Loss of even a single unit is a serious problem
Consequence : Protection systems of such generators
have also become more stringent
Required to reduce the outage period to a minimum
Achieved by rapid discriminative clearance of all fault
conditions associated with the units
Damage due to faults is none or to the minimum
59N, 27-3N,
40 Loss of field (Var flow approach) 59P Ground overvotlage
Manufacturers of
generator generally set
the typical or minimum
value. Lack of proper
co-ordination results in
generator tripping to
downstream faults.
Xd : 0.15pu to 0.25pu
Xd : 0.25pu to 0.3pu
Xd : 1pu for Hydro
2pu for Thermal.
Voltage restrained
If the voltage falls, the pickup will be at
the reduced current.
Voltage controlled
Enabled if the voltage falls below
the pre-set value.
Flux
summation
CT acts as
sensitive
differential
protection.
Example
CT ratio is 9000/5 and PT ratio 10.5 kV/110kV
Generator transformer impedance (primary side)
ZGTprimary = 0.13 x 10.52/140 = 0.1023
ZGTSecondary = 0.1023 x 9000/5 x110/10.5x103
= 1.93
Assuming that the maximum loading of the GT is 150 MVA
(worst condition loading)
Zload min on the primary side = (10.5)2/150 = 0.735
48
Copyright @ Power Research & Development Consultants Pvt. Ltd
Thank You
49
Copyright @ Power Research & Development Consultants Pvt. Ltd
Frequency Relays
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Contents
Introduction
Under Frequency Relay
dF/dT Relay
Design of Load Shedding Scheme
Example Problem
Simulation of Frequency Relay Using
MiPower
68
Copyright @ Power Research & Development Consultants Pvt. Ltd
Thank You
69
Copyright @ Power Research & Development Consultants Pvt. Ltd
Electromagnetic Transient Analysis (ETA)
& Overvoltage Studies
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Contents
Introduction
System studies
Electromagnetic Transient Analysis
Need of Overvoltage studies
Different types of Overvoltage studies
Overvoltage protection
102
Steady State Overvoltages
101 Subsynchronous resonance
Frequency Range 1
10-2
Mid term & long term Stability:
10-3 Automatic Generation Control
10-4
i R i R
1 2 1 2
i12
v1 v2
i 12(t)
[
Z0 I12(t-
v1( t)
)
]
vs(t)
G12 G23
[ ]
[ ]
[ ]
GsVs(t) GS
2(t)
-G12 G12 + G23 + G20 - G23 =
3(t)
0 - G23 G23 + G30
0 - I32(t - T) - I30(t - T)
[G ][v(t )] [i (t )] [ I history ]
where
[G ] conductance matrix
[i (t )] column vector of current sources(specified)
[ I history ] column vector of past history current sources
[v(t )] column vector of n node voltages (to be computed at instant 't')
YES
HAVE ANY SWITCH POSITIONS CHANGED?
NO
ST
IS THIS 1 STEP YES
IF NONLINEAR ELEMENTS;
FIND VECTOR [Z]
t=t+T
YES
IS t>tmax?
NO
READ OR COMPUTE SPECIFIED VOLTGAES AND CURRENTS
AND UPDATE VOLTAGES INTO [V(T)]; ADD CURRENTS INTO [ITOTAL]
STOP
FORWARD SOLUTION ON [ITOTAL] WITH UPPER PART OF TRIANGULAR MATRIX
CB Tr.line
1 2 3
G12 G23
G1s
1 2 1 2
R12= very small R12= very large
2 Creation of fault
2
3 Non linearity
f (V, I, time)
RB
Rm Lm
LB
node1
I p (t ) G12 [v1 (t ) v2 (t )] I12 (t T ) G1mv1 (t ) I1m (t T )
node 2
G12 [v2 (t ) v1 (t )] I 21 (t T ) G2 B v2 (t ) I 2 B (t T ) 0
Power
Vpo
System LA
Design issues
Protecting equipment from Insulation failures
Preventing Overheating of equipment
Avoid the Mal-operation of protective device
To find optimum location of Lightning Arrestors
To find the energy class of arrestors
Protection against high-touch voltages and
internal flashover in GIS enclosures.
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Steady state overvoltages
The highest r.m.s phase-to-phase voltage that occurs
on the system under normal operating conditions.
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Temporary Overvoltages
Oscillatory phase-to-ground or phase-to-phase
overvoltage of relatively long duration (seconds,
even minutes) at a given location and that is
undamped or only weakly damped.
Temporary overvoltages usually originate from
switching or fault clearing operations or from non-
linearities.
Temporary overvoltages are of importance when
determining stresses on equipment related to
power-frequency withstand voltage in particular
for the energy capability of MOA.
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Ferroresonance (FR) TOV
An oscillating phenomena occurring in an electric
circuit which must contain at least:
1. a non-linear inductance
2. a capacitor,
3. a voltage source (generally sinusoidal),
4. low losses.
Transients, lightning overvoltages, energizing or
deenergizing transformers or loads, occurrence or
removal of faults, etc...may initiate
ferroresonance.
The main feature of this phenomenon is that more
than one stable steady state response is possible
for the same set of the network parameters.
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Comparison of LR and FR
Its (FR) resonance possibility in a wide range of
values of Capacitances.
In case of FR, the frequency of the voltage and
current waves which may be different from that of
the sinusoidal voltage source.
The existence of several stable steady state
responses for a given configuration and values.
In case of LR the voltages and currents are linear
and they are frequency dependent.
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Examples of systems at risk
from ferroresonance.
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Ferroresonance Prediction
High permanent overvoltages of differential mode
(phase-to-phase) and/or common mode (phase-
to-earth)
High permanent over currents, high permanent
distortions of voltage and current waveforms.
Displacement of the neutral point voltage,
transformer heating (in no-load operation)
Continuous, excessively loud noise in
transformers and reactors,
Apparent untimely tripping of protection devices.
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Preventing or Damping FR
Avoid or by proper design and/or switching
operations, configurations suspectable to
ferroresonance
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Sample study results for predicting and
understanding of TOV and FR
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
1-pole 2-pole
HT side LR by opening CB2
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Voltage Current
FR existence when 2-poles opening of CB1
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Slow front overvoltages
When a circuit is energized, re-energized or
opened, transient over voltages termed as
switching surges are generated due to
associated traveling wave phenomena.
Line energisation
Transformer energisation and de-energisation
Shunt reactor switching
Shunt capacitor switching
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Line energisation
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Capacitor switching
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Shunt reactor De-energisation
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Reactor energisation
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Fast front Overvoltages
Back flashovers
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Sample study results of FFO
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Vbusbar with 1LA Vtransformer with 1LA
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Vbusbar with 1LA Vtransformer with 1LA
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Very Fast Front Overvoltages
VFFOs appear under switching conditions in GIS
or when operating vacuum circuit-breakers in
medium-voltage systems.
Pre-striking or GIS disconnector and SF6 circuit-
breaker re-ignition would produce VFFO.
VFFO in GIS can be divide into internal transient
and external transient overvoltages,
These VFFOs can be avoided by point-on-cycle
(POC) switching
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Trapped charge=0.5p.u Trapped charge=1.0p.u
VFFOs in GIS
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Overvoltage protection
Steady state overvoltages
-Transformer taps
-AVRs of Generators
-Neutral grounding of system
-Reactors
-Line reactors
-Bus reactors
-Tertiary reactors
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Overvoltage Protection for
SFO,FFO, and VFTO
-Resistor Insertion
-Controlled switching
-Shielding methods
-Lightening Arresters
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Conclusion
Based on these different overvoltage studies, we will do
the insulation coordination of system equipment and
protective device
Equipment to be protected
Voltage
Protective device
time
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Case study on Overvoltages
Insulation coordination for 400kV S/S by
conducting following overvoltage studies.
Temporary Overvoltages
Switching Overvoltages
Lightning Overvoltages
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Queries & Discussions
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Thank You
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
COMTRADE
File Analysis
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Contents
Introduction
Exploring Standard
Types of files
Difference between standard 1999 and 1991
Exercise
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Introduction
Successful implementation of AFAS requires
handling variety of recording equipments.
The data available will be mostly in proprietary
format which is a critical issue to handle.
The problem can be solved by converting it into
a standard format such as COMTRADE file
format.
Data need to be analyzed by implementing
various algorithms.
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Exploring standard
IEEE Std C37.111 is dedicated to Common
Format for Transient Data Exchange (COMTRADE)
for Power Systems.
A common format for data files and exchange
medium used for the interchange of various
types of fault, test or simulation data for
electrical power systems is defined in the
standard.
There are two versions initial came in 1991 and
revision is made in 1999.
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
IEEE Std C37.111-1999
Each COMTRADE record has set of four files
which carries a different class of information.
The four files are as follows :
Header
Conguration
Data
Information
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Header file (xxx.HDR)
The header le is an optional ASCII text le
The header le can include any information in any
order desired by the creator.
The content of file is not intended to be
manipulated by any application and it can be
Description of the power system prior to
disturbance
Name of the station
Length of the faulted line; etc..
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Configuration file (xxx.CFG)
The conguration le is an ASCII text le
intended to be read by a computer program
It contains information needed by a computer
program in order to properly interpret the data
(.DAT) le
One eld in the rst line of the conguration le
identies the year of the COMTRADE standard
revision with which the le complies (e.g. 1991,
1999, etc.)
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Configuration file (xxx.CFG)
The conguration le shall have the following information:
Station name, identication of the recording device, and
COMTRADE Standard revision year
Number and type of channels
Channel names, units, and conversion factors
Line frequency
Sample rate(s) and number of samples at each rate
Date and time of rst data point
Date and time of trigger point
Data le type
Time Stamp Multiplication Factor.
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Sample configuration file
An, ch_id, ph, ccbm, uu, a, b, skew, min, max, primary, secondary, PS
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Data file (xxx.DAT)
The data le contains the value for each input
channel for each sample in the record.
The data le contains the sample number, time
stamp, and data values of each channel for each
sample in the le.
In the event that the total storage space required
for the le set exceeds 1.44 MB, the data le may be
segmented into multiple les, each of less than 1.44
MB having file extension from .D00 to .D99, thus
allowing a maximum of 100 data les.
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Data file (xxx.DAT)
All data in data les are in the integer format.
The contents of the file are:
The rst column contains the sample number.
The second column is the time stamp for the data of
that sample number.
The third set of columns contain the data values that
represent analog information.
The fourth set of columns contain the data for the
status channels.
Format : n, timestamp, A1, A2,Ak, D1,
D2,Dm
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Sample Data File
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Obtaining Instantaneous Value
The constants are available in XXX.CFG file
The value is available in XXX.DAT file
The conversion can be as follows :
Let x be the value of a quantity in data file
Let a and b the constants given in configuration file
Then, instantaneous value x is given as
x = ax + b
Example: if x=100, a = 10 and b=1
x = 10*100 + 1 = 1001
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Information File (xxx.INF)
The information le (.INF) is an optional le.
The information le is an ASCII text le that is in a
computer readable specied format.
File contains two type of information which are
classified as public and private respectively.
Public sections contain information in a form that
can be used by equipment and/or software made by
more than one manufacturer.
Private sections contain manufacturer specic
information that is only useful with a specic vendor
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Difference Between Standard of
1999 and 1991
The Header (.HDR) le is explicitly dened as optional.
The Conguration (.CFG) le has been modied.
A eld containing standard revision year has been added.
A eld for a Time Stamp Multiplication Factor has been added.
To assist in conversion of the data, three new scaling elds
(primary, secondary, and primary-secondary) are added.
Conguration elds for Status (Digital) Channel Information
have been expanded to ve elds.
Support for Event Triggered data has been added by the addition
of a new mode for sampling rate Information
The Date/Time Stamps format has been modied
i.e. mm/dd/yy in 1991 to dd/mm/yyyy in 1999
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Difference Between Standard of
1999 and 1991
A new format for a binary data (.DAT) le has
been specied .
A new optional Information le (.INF) has been
added to provide for transmission of extra public
and private information in computer-readable form
All eld descriptions are explicitly dened with
respect to: criticality, format, type,
minimum/maximum length, and
minimum/maximum value.
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Exercise
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Solution
Exercise 1 :
Ans 1: 1999 Ans 1: 1991
Ans 2: Analog = 8 Ans 2: Analog = 10
Digital =17 Digital = 48
Ans 3: 5972 Ans 3: 1605
Ans 4: Time Stamp - Ans 4: 1000 Hz
-Multiplication Factor
Exercise 2 :
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Queries & Discussions
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Thank you
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Tripping Analysis - Methodology
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Contents
Importance
Analysis Approach
Simulation Model
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Importance
Helps in identifying issues related to
Commissioning errors (Eg. CT polarity reversal)
Setting errors
Adequacy of present relaying philosophy
Helps in preventing incorrect operations in
future
Improves effectiveness of the protection
system
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Sources of Data for Analys
COMTRADE files from
Relay
DR
SCADA Data (understanding the operating
scenario)
PMU
Time Synchronized data for sequence of
operation
Observation
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Analysis Approach
Analyze every data to classify it as use full
information for fault analysis
The use full information is studied in greater detail to
derive meaning full results
Aid for analysis
Instantaneous / RMS plots
Phasor Angle Comparison
Harmonic Plot
Relay trajectories (Eg. Impedance and differential)
Reasoning of obtained Waveforms and observations
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Simulation Model
The scenario can be reconstructed in
simulation platform
Electro-Magnetic Transient Study
Transient Stability Study
Validate the analysis results derived using
disturbance data
Can also help to find solution for identified
issues.
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Case Study
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Conclusion and Recommendations
Modification in relay settings
Correction of any commissioning related issues
Enhancement in operating philosophy that can
prevent future occurrence
Recommendations that can help reduce
occurrence of disturbance
If no incorrect operation protection scheme
healthiness can be studied.
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Queries & Discussions
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Thank You
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 2