Ansi C37 32 2002

Download as pdf or txt
Download as pdf or txt
You are on page 1of 41

ANSI C37.

32-2002
(Revision of ANSI C37.32-1996)

American National Standard for


High Voltage Switches, Bus Supports,
and Accessories Schedules of Preferred
Ratings, Construction Guidelines, and
Specifications

Approved 20 March 2002


American National Standards Institute, Inc.

The Institute of Electrical and Electronics Engineers, Inc.


3 Park Avenue, New York, NY 10016-5997, USA

Copyright 2003 by the Institute of Electrical and Electronics Engineers, Inc.


All rights reserved. Printed in the United States of America.

Print: ISBN 0-7381-3604-2 SH95098


PDF: ISBN 0-7381-3605-0 SS95098

No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior
written permission of the publisher.

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Approval of an American National Standard requires verification by


AMERICAN ANSI that the requirements for due process, consensus, and other
criteria for approval have been met by the standards developer.
NATIONAL
STANDARD Consensus is established when, in the judgment of the ANSI Board of
Standards Review, substantial agreement has been reached by directly
and materially affected interests. Substantial agreement means much
more than a simple majority, but not necessarily unanimity. Consensus
requires that all views and objections be considered, and that a
concerted effort be made toward their resolution.

The use of American National Standards is completely voluntary; their


existence does not in any respect preclude anyone, whether he has
approved the standards or not, from manufacturing, marketing,
purchasing, or using products, processes, or procedures not conforming
to the standards.

The American National Standards Institute does not develop standards


and will in no circumstances give an interpretation of any American
National Standard. Moreover, no person shall have the right or authority
to issue an interpretation of an American National Standard in the name
of the American National Standards Institute. Requests for
interpretations should be addressed to the secretariat or sponsor whose
name appears on the title page of this standard.

Caution Notice: This American National Standard may be revised or


withdrawn at any time. The procedures of the American National
Standards Institute require that action be taken periodically to reaffirm,
revise, or withdraw this standard. Purchasers of American National
Standards may receive current information on all standards by calling or
writing the American National Standards Institute.

Published by

National Electrical Manufacturers Association


1300 North 17th Street, Rosslyn, VA 22209

Copyright 2002 by the National Electrical Manufacturers Association


All rights reserved including translation into other languages, reserved under the Universal Copyright
Convention, the Berne Convention for the Protection of Literary and Artistic Works, and the
International and Pan American Copyright Conventions.

No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior
written permission of the publisher.

Printed in the United States of America

Copyright 2002 by the National Electrical Manufacturers Association i

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

This page intentionally left blank.

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Contents
Page

Foreword ........................................................................................................................................................ vi

1 Introduction ............................................................................................................................................. 1
1.1 Scope ............................................................................................................................................. 1
1.2 References..................................................................................................................................... 1

2 Definitions ............................................................................................................................................... 2
3 Station class outdoor air disconnect switches ......................................................................................... 2
3.1 Basis of preferred ratings .............................................................................................................. 2
3.2 Preferred ratings ........................................................................................................................... 2
3.3 Dielectric test voltages .................................................................................................................. 3
3.4 Construction specifications ........................................................................................................... 3

4 Distribution class outdoor air disconnect switches................................................................................... 4


4.1 Basis of preferred ratings ............................................................................................................... 4
4.2 Preferred ratings ........................................................................................................................... 4
4.3 Dielectric test voltages ................................................................................................................... 5
4.4 Construction specifications ........................................................................................................... 5

5 Indoor air switches ................................................................................................................................... 5


5.1 Basis of preferred ratings .............................................................................................................. 5
5.2 Preferred ratings ........................................................................................................................... 6
5.3 Dielectric test voltages .................................................................................................................. 6
5.4 Construction specifications ........................................................................................................... 6

6 Grounding air switches............................................................................................................................. 7


6.1 Basis of preferred ratings .............................................................................................................. 7
6.2 Preferred ratings ........................................................................................................................... 7
6.3 Electrical clearances ..................................................................................................................... 7
6.4 Corona and radio influence test voltage limits .............................................................................. 7
6.5 Construction specifications ........................................................................................................... 7

7 Fault initiating switches ........................................................................................................................... 8


7.1 Basis of preferred ratings .............................................................................................................. 8
7.2 Preferred ratings ........................................................................................................................... 8

Copyright 2002 by the National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

7.3 Preferred closing time ................................................................................................................... 8


7.4 Operating life expectancies ........................................................................................................... 8
7.5 Corona and radio influence test voltage limits .............................................................................. 8
7.6 Construction specifications ........................................................................................................... 8

8 Outdoor, indoor, and enclosed interrupter switches ................................................................................ 8


8.1 Basis of preferred ratings .............................................................................................................. 8
8.2 Preferred rated power frequency .................................................................................................. 8
8.3 Preferred rated voltages................................................................................................................. 8
8.4 Preferred rated dielectric withstand ............................................................................................... 9
8.5 Preferred rated currents ................................................................................................................ 10
8.6 Preferred rated switching endurance ............................................................................................ 10
8.7 Preferred rated ice breaking ability ................................................................................................ 10
8.8 Preferred rated control voltage....................................................................................................... 10
8.9 Preferred rated mechanical operations .......................................................................................... 11
8.10 Preferred rated terminal loading................................................................................................... 11
8.11 Construction specifications ........................................................................................................... 11
9 Bus supports ........................................................................................................................................... 11
9.1 Insulators........................................................................................................................................ 11
9.2 Fittings............................................................................................................................................ 11
9.3 Phase spacing................................................................................................................................ 11

10 Switch accessories, operating mechanisms, and switch hooks ............................................................. 11


10.1 Rated control voltages for power-operated mechanisms............................................................. 11
10.2 Hook stick lengths and hook dimensions..................................................................................... 12

Annexes
A Reference data ...................................................................................................................................... 29
B Historical data ........................................................................................................................................ 31
C Bibliography ........................................................................................................................................... 32

Figures
1 Arrangement of bolt holes in terminal pads ............................................................................................ 27
2 Outdoor air switch hook dimensions ....................................................................................................... 28
B1 Typical construction classification of station class outdoor air disconnect switches .............................. 31

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Tables
1 Preferred voltage ratings for station class outdoor air switches............................................................... 13
2 Preferred switching impulse withstand voltage for station class outdoor air switches ............................ 14
3 Preferred continuous and withstand currents for station class outdoor air switches .............................. 14
4 Terminal loadings for high-voltage switches ........................................................................................... 15
5 Phase spacing and ground clearance for station class outdoor air switches and bus supports ............. 16
6 Station class outdoor air switch-pole unit dimensions ............................................................................. 17
7 Station class outdoor air switches preferred mounting hole spacing for 600, 1200,
and 1600 ampere switches ..................................................................................................................... 18
8 Preferred voltage ratings for distribution class outdoor air switches ....................................................... 19
9 Preferred continuous and withstand currents for distribution class outdoor air switches ........................ 19
10 Phase spacing and ground clearance for distribution class outdoor air switches and bus supports ..... 20
11 Distribution class outdoor air switches - pole unit dimensions ................................................................ 21
12 Preferred voltage ratings for indoor air switches .................................................................................... 22
13 Continuous and withstand current for indoor air switches ...................................................................... 22
14 Indoor air switches and bus supports-phase spacing and length of break ............................................ 23
15 Grounding switch electrical clearance .................................................................................................... 24
16 Preferred rated switching currents for interrupter switches..................................................................... 25
17 Preferred rated control voltages and their ranges .................................................................................. 26

Copyright 2002 by the National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Foreword (This Foreword is not part of American National Standard C37.32-2002)

The purpose of this revision is to bring the standard up-to-date and in line with present-day requirements. The
standard is coordinated with the other American National Standards in the field of high-voltage switches:

ANSI/IEEE C37.30, Standard Requirements for High-Voltage Air Switches

IEEE C37.34, Test Code for High-Voltage Air Switches

ANSI/IEEE C37.35, Guide for the Application, Installation, Operation, and Maintenance of High-Voltage Air
Disconnecting and Load Interrupter Switches

ANSI/IEEE C37.36b, Guide to Current Interruption with Horn Gap Air Switches

ANSI/IEEE C37.37, Loading Guide for AC High-Voltage Air Switches

IEEE 1247, Standard for Interrupter Switches for Alternating Current, Rated above 1000 Volts

This revision modifies the document title to allow for future inclusion of other types of High-Voltage Switches
and to harmonize with the direction of the C37.30 series of standards.

This revision includes the changing of the station, distribution and indoor voltage ratings of 8.25 kV, 15.0 kV and
25.8 kV to 8.3 kV, 15.5 kV and 27 kV respectively to harmonize voltage ratings between equipment classes.

Station class voltage ratings of 121 kV, 169 kV and 242 kV have been changed to 123 kV, 170 kV and 245 kV
respectively to harmonize with AC High Voltage Circuit Breakers C37.06-2000 and IEC.

Metrification of the document has continued by placing the metric equivalents first in the text and tables while
retaining the inch - pound system in parentheses.

Circuit switchers are excluded from this standard.

The annexes are for information only and are not considered a part of the standard.

Suggestions for the improvement of this standard will be welcome. They should be sent to the National
Electrical Manufacturers Association, 1300 North 17th Street, Suite 1847, Rosslyn, VA 22209.

This standard was processed and approved for submittal to ANSI by the Accredited Standards Committee on
Power Switchgear, C37. Committee approval of the standard does not necessarily imply that all members voted
for its approval. At the time it approved this standard, the C37 Committee had the following members:

E. Byron, Chairman
A. K. McCabe, Executive Vice-Chairman, HV Standards
J. Scott, Executive Vice-Chairman, LV Standards
D.L. Swindler, Executive Vice-Chairman, IEC Activities
M. Calwise, Secretary

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Organizations Represented: Name of Representative:

Electric Light and Power Group ................................. D.E. Galicia


................................................................................... J.L. Koepfinger
................................................................................... G.J. Martuscello
................................................................................... Y. Musa
................................................................................... E. Worland

Institute of Electrical and Electronics Engineers ........ T. Burse


................................................................................... K. Gray
................................................................................... A. Monroe
................................................................................... B. Puckett
................................................................................... T.E. Royster
................................................................................... R. Garzon (Alt)
................................................................................... J.G. Wood (Alt)

National Electrical Manufacturers Association ........... G. Jones


................................................................................... W. Long
................................................................................... T. Olsen
................................................................................... G. Sakats
................................................................................... D. Stone
................................................................................... E. Byron (Alt)

International Electrical Testing Association ................ A. Peterson

National Electrical Contractors Association ............... D. Harwood

Testing Laboratory Group .......................................... P. Notarian


................................................................................... A. Harkness
Tennessee Valley Authority ........................................ D. Reynolds
U.S. Dept. Of the Army-Office of the Chief of Engineers J.A. Gilson
U.S. Dept. of the Navy-Naval Construction Battalion Center D.L. Mills

Power Switching Equipment Technical Committee SG VI of the National Electrical Manufacturers Association's
Switchgear Section, which revised and approved this standard, had the following personnel at the time of
approval:

R. Brown, Chairman
M. Allen
J. Angelis
M. Beard
M. Dunagin
G. Kamber
R. Reed
R. Reynolds
G. Sakats

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

This page intentionally left blank.


Copyright 2002
Copyright 2003 by
IEEE
theAll RightsElectrical
National ReservedManufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

AMERICAN NATIONAL STANDARD ANSI C37.32-2002

For High Voltage Switches, Bus Supports, and Accessories


Schedules of Preferred Ratings, Construction Guidelines and Specifications

1 Introduction
1.1 Scope

This standard provides the schedules of preferred ratings and construction specifications for high-voltage
disconnect, interrupter, fault initiating, and grounding switches rated above 1000 volts. Switch operator control
voltage ranges (formerly C37.33), bus supports and accessories are also covered by this standard. Switches
included in C37.20.2, C37.20.3, C37.20.4, C37.71, C37.72 and C37.73 are not covered by this standard.

1.2 References

The following standards are referenced by this text or have content relevant to the apparatus covered by this
standard. At the time of publication, the editions indicated were valid. All standards are subject to revision, and
parties to agreements based on this American National Standard are encouraged to investigate the possibility
of applying the most recent editions of the standards indicated below.

ANSI C29.8-1985 (R1995), Wet-Process Porcelain Insulators-Apparatus, Cap and Pin Type

ANSI C29.9-1983 (R1996), Wet-Process Porcelain Insulators-Apparatus, Post Type

NEMA SG 6-2000, Power Switching Equipment

NEMA 107-1987 (R1993) Methods of Measurement of Radio Influence Voltage (RIV) of High-Voltage Apparatus

ANSI/IEEE C37.30-1998, Standard Requirements for High-Voltage Switches

IEEE C37.34-1994, Test Code for High-Voltage Air Switches

ANSI/IEEE C37.35-1996, Guide for the Application, Installation, Operation, and Maintenance of High Voltage
Air Disconnecting and Load Interrupter Switches

ANSI/IEEE C37.36b-1990 (R1996), Guide to Current Interruption with Horn Gap Air Switches

ANSI/IEEE C37.37-1996, Loading Guide for AC High-Voltage Air Switches (in Excess of 1000 Volts)

ANSI/IEEE C37.38-1989, Gas-Insulated, Metal-Enclosed Disconnecting, Interrupter, and Grounding Switches

IEEE 1247-1998, Standard for Interrupter Switches for Alternating Current, Rated Above 1000 Volts

IEEE C37.100-1992, Standard Definitions for Power Switchgear

ANSI/IEEE 142-1991, Practice for Grounding of Industrial and Commercial Power Systems

IEC 815-1986, Guide for the Selection of Insulators in Respect of Polluted Conditions

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 1

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

2 Definitions
The definitions of terms contained in this document, or in other standards referred to in this document, are not
intended to embrace all legitimate meanings of the terms. They are applicable only to the subject treated in this
standard. An asterisk (*) following a definition indicates that at the time this standard was approved, there was
no corresponding definition in C37.100. Refer to C37.100 for additional definitions.

2.1 outdoor switch: Switches designated for operation outside buildings or enclosures. Outdoor switches
may be exposed to the weather. Outdoor switches experience no restriction of heat transfer to the ambient. *

2.2 indoor switch: Switches designated for operation inside buildings or weather-resistant enclosures,
which do not restrict heat transfer to the ambient. *

2.3 enclosed switch: Switches designated for operation within a housing restricting heat transfer to the
external medium.

2.4 station class: A descriptive term used to denote application or restriction or both to generating
stations, switching stations, substations, and transmission lines. *

2.5 distribution class: A descriptive term used to denote application or restriction or both to that part of an
electric system between the substation and the customer. *

3 Station Class Outdoor Air Disconnect Switches


3.1 Basis of preferred ratings

The ratings of station class outdoor disconnect switches shall be based upon the definitive conditions specified
in C37.30.

3.2 Preferred ratings

3.2.1 Voltage and current

The preferred voltage, continuous current, and withstand current ratings at the rated power frequency of 50 or
60 Hz shall be in accordance with tables 1, 2, and 3.

3.2.1.1 Short-time withstand current duration


2
The preferred short-time withstand current test duration is 1, 2, or 3 seconds with allowable I t variations given
in C37.34.

3.2.1.2 Peak withstand current duration

The preferred peak withstand current test duration is 167 milliseconds.

3.2.2 Ice breaking ability

If an outdoor switch has an ice breaking rating, the preferred ratings shall be 10 mm (3/8 inch), and 19 mm (3/4
inch). A switch that has successfully passed the ice test and is rated for a given thickness of ice is also rated for
lesser thickness.

2 Copyright 2003
Copyright 2002IEEE AllNational
by the Rights Reserved
Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

3.2.3 Mechanical operations

The preferred mechanical operation rating shall be 1000 operations: 900 close-open cycles without terminal
loading and 100 close-open cycles with terminal loading as specified in C37.34. Refer to table 17 for rated
control voltages for motor-operated switches and C37.34 for number of operations at minimum and maximum
control voltage.

3.2.4 Terminal loading

The preferred mechanical terminal loadings shall be in accordance with table 4.

3.3 Dielectric test voltages

3.3.1 Energized parts to ground

Outdoor switches in either the open or closed positions shall withstand the voltages specified in table 1,
columns 2, 3, and 4. See note 1 of table 1 and table 2 for switching impulse ratings.

3.3.2 Open gap withstand

The air gap of fully open outdoor air switches shall withstand voltages that are 1.10 times the rated lightning
impulse dry withstand and the power-frequency dry withstand voltages given in columns 2 and 3 of table 1. For
switches rated 362 kV and higher, the open gap shall also withstand the switching impulse voltages specified in
table 2.

Station class outdoor air switches having solid insulation material across the open gap shall withstand 100
percent of the voltages given in table 1 columns 2, 3 and 4.

3.3.3 Corona and radio influence test voltage limits

Switches rated 123 kV and higher when tested under dark conditions at the voltage levels specified in table 1,
column 5 shall be free of visible plumes or spikes. The limits of radio-influence voltage are given in column 6.
Refer to C37.34, and NEMA 107 for testing procedures.

3.4 Construction specifications

3.4.1 Insulators

Insulator units shall have electrical characteristics and leakage distance values equal to or exceeding those
listed for equivalent insulation in C29.8 or C29.9. Refer to C37.35 and IEC 815 for insulator creepage distance
considerations under contaminated conditions. Insulators shall have sufficient mechanical strength to withstand
applicable operating forces, including magnetic forces produced by the rated peak withstand current of the
switches for which they are supplied, as specified in table 3.

3.4.2 Arrangement and size of bolt holes in terminal pads

Bolt hole centerlines in terminal pads, when used, shall be as shown in figure 1. Holes shall accommodate bolts
that are inch (12 mm) in diameter.

3.4.3 Phase spacing (pole spacing)

Phase spacing for outdoor switches and bus supports shall be as specified in table 5.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 3

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

3.4.4 Ground clearance

Ground clearance for outdoor switches and bus supports shall equal or exceed that specified in table 5.

3.4.5 Single-pole switch dimensions

Minimum metal-to-metal, single-pole air gap distances (switch full open position) and centerline-to-centerline
spacings of insulator columns are listed in table 6. The air gap distance is based upon being at least 10 percent
in excess of the minimum clearance to ground as given in table 5. These dimensions may be modified
depending upon dielectric test results (See 3.3.2).

3.4.6 Base mounting holes

Spacing for the base mounting holes for 600, 1200, and 1600 ampere switches should be as specified in table
7. Other spacings can be used. Switches rated through 48.3 kV shall have base mounting holes at least 14 mm
(9/16 inch) in diameter. Switches rated 72.5 kV and above shall have base mounting holes at least 17 mm
(11/16 inch) in diameter.

4 Distribution Class Outdoor Air Disconnect Switches


4.1 Basis of preferred ratings

The ratings of distribution class outdoor air disconnect switches shall be based upon the definitive conditions
specified in C37.30.

4.2 Preferred ratings

4.2.1 Voltage and current

The preferred voltage, continuous current and withstand current ratings at the rated power frequency of 50 or
60 Hz shall be in accordance with tables 8 and 9.

4.2.1.1 Short-time withstand current duration


2
The preferred short-time withstand test current duration is 1, 2 or 3 seconds with allowable I t variations given in
C37.34.

4.2.1.2 Peak withstand current duration

The preferred peak withstand current test duration is 167 milliseconds.

4.2.2 Ice breaking ability

Refer to 3.2.2 for preferred ratings.

4.2.3 Mechanical operations

The preferred number of mechanical operations shall be as specified in 3.2.3.

4.2.4 Terminal loading

The preferred mechanical terminal loading shall be in accordance with table 4.

4 Copyright 2003
Copyright 2002IEEE AllNational
by the Rights Reserved
Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

4.3 Dielectric test voltages

4.3.1 Energized parts to ground

Outdoor switches in either the open or closed positions shall withstand the voltages specified in table 8,
columns 2, 3 and 4.

4.3.2 Open gap withstand

The air gap of fully open outdoor switches shall withstand voltages that are 1.10 times the rated lightning
impulse dry withstand and the power-frequency dry withstand voltages given in columns 2 and 3 of table 8.

Distribution class outdoor air switches having solid insulation material across the open gap shall withstand 100
percent of the voltages given in table 8, columns 2, 3 and 4.

4.3.3 Corona and radio influence test voltage limits

Switches rated below 123 kV have no corona or radio influence voltage requirements.

4.4 Construction specifications

4.4.1 Insulators

Insulators shall have electrical characteristics and leakage distance values such as to coordinate with the
switch dielectric test voltage withstand requirements of 4.3.1. Refer to C37.35 and IEC 815 for insulator
creepage distance considerations under contaminated conditions. The insulators shall have sufficient strength
to withstand the applicable operating force, including magnetic force produced by the rated peak withstand
current of the switch to which they are applied, as specified in table 9.

4.4.2 Arrangement and size of bolt holes in terminal pads

Bolt hole centerlines shall be as shown in figure 1. Holes shall accommodate bolts that are inch (12mm) in
diameter.

4.4.3 Phase spacing (pole spacing)

Phase spacing for distribution class switches and bus supports shall be as specified in table 10.

4.4.4 Ground clearance

Ground clearance for distribution class switches and bus supports shall equal or exceed that specified in table
10.

4.4.5 Single pole switch dimensions

The minimum metal-to-metal single pole air gap distances (switch full open position) shall be as listed in table
11 with possible modifications as noted.

5 Indoor Air Switches


5.1 Basis of preferred ratings

The ratings of indoor air switches shall be based upon the definitive conditions specified in C37.30, except that
they are not subjected to wind loads and they do not have ice breaking ratings.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 5

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

5.2 Preferred ratings

5.2.1 Voltage and current

The preferred voltage, and preferred continuous and withstand current ratings at the rated power frequency of
50 or 60 Hz shall be in accordance with tables 12 and 13.

5.2.1.1 Short-time withstand current duration


2
The preferred short-time withstand current test duration is 1, 2, or 3 seconds with allowable I t variations given
in C37.34.

5.2.1.2 Peak withstand current duration

The preferred peak withstand current test duration is 167 milliseconds.

5.2.2 Mechanical operations

The preferred number of mechanical operations shall be as given in 3.2.3.

5.2.3 Terminal loading

Presently, there are no preferred mechanical terminal loadings for indoor switches.

5.3 Dielectric test voltages

5.3.1 Energized parts to ground

Indoor air switches, in either the open or closed positions, shall withstand the dielectric test voltages specified in
columns 2, 3, and 4 of table 12.

5.3.2 Open gap withstand

The air gap of fully open indoor air switches shall withstand voltages that are 1.10 times the lightning impulse
dry and power-frequency dry withstand test voltages specified in columns 2 and 4 of table 12.

Indoor air switches having solid insulation material across the open gap shall withstand 100 percent of the
voltages given in table 12, columns 2, 3 and 4.

5.3.3 Corona and radio influence test voltage limits

Switches rated below 123 kV have no corona or radio influence voltage requirements.

5.4 Construction specifications

5.4.1 Insulators

Insulator units shall have electrical characteristics and leakage distance values such as to coordinate with the
switch dielectric test voltage withstand requirements of 5.3. The insulators shall have sufficient strength to
withstand the applicable operating force, including the magnetic force produced by the rated peak withstand
current of the switch to which they are applied, as specified in table 13.

5.4.2 Arrangement and size of bolt holes in terminal pads

The arrangement of bolt hole centerlines in terminal pads, when used, shall be as shown in figure 1. Holes shall
accommodate bolts that are inch (12mm) in diameter.

6 Copyright 2003
Copyright 2002IEEE AllNational
by the Rights Reserved
Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

5.4.3 Phase spacing

The minimum metal-to-metal clearance between phases for indoor air switches and bus supports shall be as
specified in table 14.

5.4.4 Single pole switch dimensions

The minimum metal-to-metal single pole air gap distances (switch full open position) shall be as specified in
table 14 with possible exceptions as noted.

6 Grounding Air Switches


6.1 Basis of preferred ratings

The ratings of high-voltage grounding switches shall be based upon the definitive conditions specified in
C37.30.

6.2 Preferred ratings

6.2.1 Voltage and current

The preferred voltage and withstand current ratings at the rated power frequency of 50 or 60 Hz shall be in
accordance with tables 1, 3, 8, 9, 12, and 13. Grounding switches have no continuous current ratings but have
withstand current ratings which may be equal to or less than the disconnect switch rating.

6.2.1.1 Short-time withstand current duration


2
The preferred short-time withstand current test duration is 1, 2 or 3 seconds with allowable I t variations given in
C37.34.

6.2.1.2 Peak withstand current duration

The preferred peak withstand current test duration is 167 milliseconds.

6.2.2 Ice breaking ability

Refer to 3.2.2 for preferred ratings for outdoor switches. Indoor switches have no ice breaking requirements.

6.3 Electrical clearances

The electrical clearance between the grounding blade and the nearest energized part during ground blade travel
shall be equal to or greater than the minimum gap distance listed in table 15. In the fully open position of the
grounding blade, the switch shall withstand the voltages listed in columns 2, 3, and 4 of tables 1, 8, and 12.

6.4 Corona and radio influence test voltage limits

Switches rated 123 kV and higher when tested under dark conditions at the voltage levels specified in table 1,
column 5 shall be free of visible plumes or spikes. The limits of radio-influence voltage are given in column 6.
Refer to C37.34 and NEMA 107 for testing procedures.

6.5 Construction specifications

Construction specifications for grounding switches shall be in accordance with the requirements specified in
3.4, 4.4, or 5.4.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 7

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

7 Fault Initiating Switches


7.1 Basis of preferred ratings

The ratings of high-voltage fault initiating switches shall be based upon the definitive conditions specified in
C37.30.

7.2 Preferred ratings

The preferred fault-making current ratings of fault initiating switches at the rated power frequency of 50 or 60 Hz
shall be 9.5, 12.5, 20, 25 or 38 kA rms symmetrical. Peak withstand current ratings are 24.7, 32.5, 52, 65 and
99 kA respectively for 60 Hz ratings and 23.7, 31.3, 50, 63, and 95 kA respectively for 50 Hz ratings.

7.2.1 Short time withstand current duration


2
The preferred short-time withstand test current duration is 1, 2 or 3 seconds with allowable I t variations given in
C37.34.

7.2.2 Peak withstand current duration

The preferred peak withstand current test duration is 167 milliseconds.

7.3 Preferred closing time

The preferred closing time, which includes blade travel to close the switch, shall not exceed 0.5 seconds.

7.4 Operating life expectancies

The manufacturer should be consulted for operating life expectancies for fault initiating switches.

7.5 Corona and radio influence test voltage limits

Switches rated 123kV and higher when tested under dark conditions at the voltage levels specified in table 1,
column 5 shall be free of visible plumes or spikes. The limits of radio-influence voltage are given in column 6.
Refer to C37.34 and NEMA 107 for testing procedures.

7.6 Construction specifications

Construction specifications for fault initiating switches shall be in accordance with the requirements specified in
3.4, 4.4, or 5.4.

8 Outdoor, Indoor, and Enclosed Interrupter Switches


8.1 Basis of preferred ratings

The ratings of interrupter switches shall be based upon the definitive conditions specified in C37.30.

8.2 Preferred rated power frequency

The preferred rated power frequency of interrupter switches shall be 50 or 60 Hz.

8.3 Preferred rated voltages

8 Copyright 2003
Copyright 2002IEEE AllNational
by the Rights Reserved
Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

8.3.1 Rated maximum voltage

The preferred rated maximum voltage shall be as given in column 1 of tables 1, 8, and 12.

8.3.2 Rated loop splitting voltage

The preferred rated loop splitting voltage is 20 percent of the rated maximum voltage.

8.3.3 Rated differential capacitance voltage range

The preferred limits for the differential capacitance voltage range are 100 volts for the lower limit and 4 percent
of rated maximum voltage for the upper limit.

8.4 Preferred rated dielectric withstand

8.4.1 Preferred rated power frequency withstand voltages

8.4.1.1 Rated live parts-to-ground dry withstand voltage

Live parts-to-ground withstand voltage shall be as given in table 1, column 3; table 8, column 3; and table 12,
column 4.

8.4.1.2 Rated live parts-to-ground wet withstand voltage

Live parts-to-ground wet withstand voltage for outdoor interrupter switches shall be as given in table 1, column
4 and table 8, column 4.

8.4.1.3 Rated live parts-to-ground dew withstand voltage

Indoor and enclosed interrupter switches shall withstand the test voltages specified in column 3 of table 12.

8.4.2 Preferred rated lightning impulse dry withstand voltage

8.4.2.1 Rated live parts-to-ground withstand voltage

These withstand voltages shall conform to table 1, column 2; table 8, column 2; or table 12, column 2.

8.4.3 Preferred rated switching impulse withstand voltage

Interrupter switches rated 362 kV and higher shall withstand switching impulse voltages as specified in table 2,
columns 3 and 4.

8.4.4 Open gap withstand

The air gap of fully open interrupter switches shall withstand voltages that are 1.10 times the rated lightning
impulse dry withstand and the power frequency dry withstand voltages given in table 1, columns 2 and 3; table
8, columns 2 and 3; or table 12, columns 2 and 4. For switches rated 362 kV and higher, the open gap shall
also withstand the switching impulse voltages specified in table 2, columns 3 and 4.

Interrupter switches having solid insulation material across the open gap shall withstand 100 percent of the
voltages given in table 1, columns 2 and 3; table 8, columns 2 and 3; or table 12, columns 2 and 4.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 9

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Outdoor interrupter switches with solid insulation across the open gap shall also withstand the rated wet
withstand voltage given in table 1, column 4 or table 8, column 4.

Indoor or enclosed interrupter switches with solid insulation across the open gap shall also withstand the rated
dew withstand voltage given in table 12, column 3.

8.4.5 Corona and radio influence test voltage limits

Switches rated 123 kV and higher when tested under dark conditions at the voltage levels specified in table 1,
column 5 shall be free of visible plumes or spikes. The limits of radio-influence voltage are given in column 6.
Refer to C37.34 and NEMA 107 for testing procedures.

8.5 Preferred rated currents

8.5.1 Preferred rated continuous current

The continuous current ratings shall be as given in tables 3, 9, and 13.

8.5.2 Preferred rated withstand currents

The rated withstand currents shall be as given in tables 3, 9, and 13.

8.5.3 Preferred rated withstand current duration


2
The preferred short-time withstand current test duration is 1, 2, or 3 seconds with allowable I t variations given
in IEEE 1247.

8.5.4 Preferred peak withstand current duration

The preferred peak withstand current test duration is 167 milliseconds.

8.5.5 Preferred rated fault-making current

The rated fault-making currents shall be as given in 7.2.

8.5.6 Preferred rated switching currents

Rated switching currents for interrupter switches shall be as specified in table 16.

8.6 Preferred rated switching endurance

Rated switching operation endurances for interrupter switches are dependent on the application and the many
different interrupter switch designs. Ratings are established by agreement between user and manufacturer.

8.7 Preferred rated ice breaking ability

The preferred ice breaking ratings shall be as given in 3.2.2. Indoor and enclosed switches have no ice
breaking requirements.

8.8 Preferred rated control voltage

Rated control voltages and their ranges shall be as given in table 17.

10 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

8.9 Preferred rated mechanical operations

Rated mechanical operations of outdoor, indoor, and enclosed interrupter switches shall conform to 3.2.3.

8.10 Preferred rated terminal loading

The preferred rated terminal loadings for outdoor interrupter switches are specified in 3.2.4. Indoor and
enclosed switches have no preferred rated terminal loadings.

8.11 Construction specifications

8.11.1 Phase spacing of interrupter switches

The phase spacing shall be in accordance with tables 5, 10, and 14. Interrupter switches having large lateral
extensions of live parts beyond the insulators or unconfined switching arcs may require greater phase spacings
and the manufacturer should be consulted.

8.11.2 Insulators

Insulators for interrupter switches shall be in accordance with the requirements specified in 3.4.1, 4.4.1, or
5.4.1.

9 Bus Supports
9.1 Insulators

Insulators for bus supports shall be in compliance with the requirements specified in 3.4.1, 4.4.1, or 5.4.1.

9.2 Fittings

The strength classification of fittings for outdoor bus supports, expressed in terms of the gradually applied load
that the fitting shall withstand without failure or fracture of any parts, shall be as follows:

Class designation Load Applicable bolt circle


kN (Ibs) mm (inches)
Standard strength 8.9 (2000) 76 or 127 (3 or 5)
High strength 17.8 (4000) 127 (5)

In all cases, the load shall be applied to the fitting in a plane parallel to its mounting surface, perpendicular to
the length of the conductor at its centerline.

9.3 Phase spacing

The phase spacing of bus supports shall be in accordance with columns 3 and 6 of table 5 and table 10 and
column 2 of table 14.

10 Switch Accessories, Operating Mechanisms, and Switch Hooks


10.1 Rated control voltages for power-operated mechanisms

10.1.1 Control voltages and their ranges

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 11

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

The rated control voltages and their ranges for power-operated mechanisms used on high-voltage air switches
shall be as shown in table 17. Operating, auxiliary, and tripping functions shall perform satisfactorily when
control voltages are within the ranges given in the table.

10.1.2 Voltage range measurement conditions

Voltage measurements shall be made at the control power input terminals of the mechanism. Maximum
voltages are measured at no-load* and minimum voltages with operating currents flowing.

*Maximum voltage at no-load recognizes battery charging and equalizing techniques. Control circuits
must dielectrically withstand the high voltage, which also occurs if maximum voltage is maintained with
operating current flowing. It is not necessary to maintain the high voltage level as long as the voltage
remains within the specified range. This obviates the need for a higher than maximum voltage to
maintain the stated maximum voltage with operating current flowing. However, the minimum voltage
must be maintained with operating current flowing to verify proper operation.

10.1.3 Torque requirements

Power-operated mechanisms shall develop the manufacturers rated torque when operating at the preferred
rated voltages given in table 17.

10.1.4 Power-operated mechanism characteristics

Motor-operating mechanisms for outdoor switches shall have a torque at the output shaft under minimum
operating voltage adequate to operate the switch under rated ice conditions, e.g., 10 mm (3/8 inch) or 19 mm
(3/4 inch) as specified in C37.34. Operating time and torque value required should be in accordance with the
manufacturer's recommendation.

10.2 Hook stick lengths and hook dimensions

The lengths of hook sticks depend on work rules and other regulations not covered by this standard. See
figure 2 for hook dimensions.

12 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 1 Preferred voltage ratings for station class outdoor air switches

Corona & radio


Rated withstand voltages influence voltage
Rated Power frequency
maximum Lightning kV rms Test2 Limit of
voltage impulse1 voltage RIV3
Dry Wet
Line kV rms kV peak 1 minute 10 second kV rms V @ 1 MHz
Number (1) (2) (3) (4) (5) (6)
1 8.3 95 38 30 - -
2 15.5 110 50 45 - -
3 27 150 70 60 - -
4 38 200 95 80 - -
5 48.3 250 120 100 - -
6 72.5 250 120 100 - -
7 3504 175 145 - -
8 123 350 175 145 78 500
9 450 235 190 78 500
10 5504 280 230 78 500
11 145 350 175 145 92 500
12 450 235 190 92 500
13 550 280 230 92 500
14 6504 335 275 92 500
15 170 450 235 190 108 500
16 550 280 230 108 500
17 650 335 275 108 500
4
18 750 385 315 108 500
19 2455 550 280 230 156 500
20 650 335 275 156 500
21 750 385 315 156 500
22 9004 465 385 156 500
23 1050 545 455 156 500
24 362 1050 545 455 230 500
25 13004 610 525 230 500
26 550 1550 710 620 349 500
27 18004 810 710 349 500
28 800 2050 940 830 508 750

NOTES
1 For switches rated 362 kV and higher, see table 2 for values of rated switching impulse withstand voltages.
2 The test voltages are 110 percent of the rated maximum line-to-neutral voltage. It is not necessary to retest switches
previously tested and acceptable at 105 percent. It is not necessary to retest switches previously rated at 121 kV, 169 kV and
242 kV.
3 If equipment of any given rated maximum voltage is used on a circuit of higher voltage rating, the radio influence voltage limit
and test voltage for the equipment shall be that corresponding to the rated maximum voltage of the circuit.
4 Modern arrester technology enables use of lower lightning impulse rated equipment in some applications. The traditional
values are shown in bold font.
5 The switches listed in lines 19 through 28 are intended for application on systems effectively grounded as defined in
ANSI/IEEE 142.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 13

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 2 Preferred switching impulse withstand voltages


for station class outdoor air switches

Rated Rated lightning Switching impulse withstand voltages


Line maximum impulse kV peak
Number voltage To Across
1 2
kV rms kV peak ground open gap
(from table 1) (1) (2) (3) (4)
24 362 1050 750 655 + (295)
25 362 1300 885 825 + (295)
26 550 1550 1050 880 + (450)
27 550 1800 1150 1000+ (450)
28 800 2050 1300 1000+ (650)

NOTES
1 Line-to-ground insulation strength is based upon 97.7 percent probability of withstand where the standard deviation is 6 percent.
See C37.34.
2 Values in parenthesis are 60 Hz bias voltages expressed in kVp units (column 1 voltage x 2 / 3 ). The summation of this
opposite polarity bias voltage and the associated open gap switching impulse voltage is equal to a 97.7 percent probability of line-
to-ground flashover (Critical Flashover + 2). See C37.34.

Table 3 Preferred continuous and withstand currents


for station class outdoor air switches

Withstand currents
Rated continuous Short-time Peak
current
1
Line 60 Hz 50 Hz
Number amperes kA kA kA
(1) (2) (3) (4)
1 600 25 65 63
2 1200 38 99 95
3 1600 44 114 110
4 2000 44 114 110
5 2000 63 164 158
6 3000 63 164 158
7 3000 75 195 188
8 4000 75 195 188

NOTE
1 Peak withstand current (kA) 1.625 times the rms asymmetrical momentary current (kA). Switches previously rated at 40,
61, 70, 100 and 120 kA rms asymmetrical momentary are closely equivalent to the above peak withstand current ratings and
do not require retesting.

14 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 4 Terminal loadings for high-voltage switches

Maximum voltage Current rating F1 and F2 F3 F4


Line kV amperes N (Ibs) N (Ibs) N (Ibs)
Number (1) (2) (3) (4) (5)
1 4.8-72.5 200-1200 400 (90) 130 (30) 130 (30)
2 " > 2000 400 (90) 130 (30) 130 (30)
3 123-170 600-1600 530 (120) 180 (40) 490 (110)
4 " > 2000 530 (120) 180 (40) 1110 (250)
5 245-362 1200-1600 800 (180) 270 (60) 1670 (375)
6 " > 2000 1020 (230) 330 (75) 3040 (685)
7 550 All 2000 (450) 670 (150) 3330 (750)

NOTES
1 Terminal loadings F1, F2, F3, and F4 incorporate considerations for weight of typical connected bus conductors having ice and
wind loads, expansion loads, and limited moment forces. It is recommended that the manufacturer be consulted on forces that
exceed those given in table 4. These higher forces may be due to long bus spans rigidly connected to switches, extra high short
circuit current forces, bus spans other than aluminum tube conductors, and other forces not considered.
2 These loadings were derived for the mechanical operations requirement of C37.34 and do not necessarily represent the
mechanical loading limit on terminals. Consult the manufacturer when actual values are needed.
3 At 245 kV and above, F4 forces may be reduced by 40% for switches with hinged or pivoting type terminals.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 15

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

ANSI C37.32-2002
Table 5 Phase spacing and ground clearance for station class outdoor air switches and bus supports

Centerline-to-centerline phase spacing4


Rated Rated Minimum metal-to-metal Ground clearance3 Vertical break Side break All horn gap
maximum lightning distance disconnecting disconnecting (horizontal break) Switches (vertical
voltage withstand switches, bus supports Recommended Minimum switches disconnecting switches and side break)
voltage1 and rigid conductors2 and bus supports
Line kV rms kV Peak mm (inches) mm (inches) mm (inches) mm (inches) mm (inches) mm (inches)
Number (1) (2) (3) (4) (5) (6) (7) (8)
1 8.3 95 178 (7) 191 (7.5) 152 (6) 457 (18) 762 (30) 914 (36)
2 15.5 110 305 (12) 254 (10) 178 (7) 610 (24) 762 (30) 914 (36)
3 27 150 381 (15) 305 (12) 254 (10) 762 (30) 914 (36) 1220 (48)
4 38 200 457 (18) 381 (15) 330 (13) 914 (36) 1220 (48) 1520 (60)
5 48.3 250 533 (21) 457 (18) 432 (17) 1220 (48) 1520 (60) 1830 (72)
6 72.5 250 533 (21) 457 (18) 432 (17) 1220 (48) 1520 (60) 1830 (72)
7 350 787 (31) 737 (29) 635 (25) 1520 (60) 1830 (72) 2130 (84)
8 123 350 787 (31) 737 (29) 635 (25) 1520 (60) 1830 (72) 2130 (84)
9 450 1120 (44) 991 (39) 846 (34) 1830 (72) 2310 (91) 2620 (103)
Copyright 2003 by the IEEE. All Rights Reserved

10 550 1350 (53) 1190 (47) 1070 (42) 2130 (84) 2740 (108) 3050 (120)
11 145 350 787 (31) 737 (29) 635 (25) 1520 (60) 1830 (72) 2130 (84)
12 450 1120 (44) 991 (39) 846 (34) 1830 (72) 2310 (91) 2620 (103)
13 550 1350 (53) 1190 (47) 1070 (42) 2130 (84) 2740 (108) 3050 (120)
14 650 1600 (63) 1330 (52.5) 1270 (50) 2440 (96) 3350 (132) 3660 (144)
15 170 450 1120 (44) 991 (39) 846 (34) 1830 (72) 2310 (91) 2620 (103)
16 550 1350 (53) 1190 (47) 1070 (42) 2130 (84) 2740 (108) 3050 (120)
17 650 1600 (63) 1330 (52.5) 1270 (50) 2440 (96) 3350 (132) 3660 (144)
18 750 1830 (72) 1560 (61.5) 1470 (58) 2740 (108) 3960 (156) 4270 (168)
19 245 550 1350 (53) 1190 (47) 1070 (42) 2130 (84) 2740 (108) 3050 (120)
20 650 1600 (63) 1330 (52.5) 1270 (50) 2440 (96) 3350 (132) 3660 (144)
21 750 1830 (72) 1560 (61.5) 1470 (58) 2740 (108) 3960 (156) 4270 (168)
22 900 2260 (89) 1930 (76) 1800 (71) 3350 (132) 4870 (192) 4870 (192)
23 1050 2670 (105) 2300 (90.5) 2110 (83) 3960 (156) 5500 (216) 5500 (216)
24 362 1050 2670 (105) 2300 (90.5) 2130 (84) 3960 (156) 5500 (216) 5500 (216)
25 1300 3020 (119) 2690 (106) 2640 (104) 4430 (174) Note 5 6100 (240)
26 550 1550 Note 5 Note 5 3150 (124) Note 5 Note 5 7620 (300)
27 1800 Note 5 Note 5 3660 (144) 7620 (300) Note 5 8230 (324)
28 800 2050 Note 5 Note 5 4220 (166) Note 5 Note 5 15240 (600)

NOTES
1 Close lightning arrester coordination may allow lower lightning impulse values. Traditional values shown in bold font.
2 Minimum metal-to-metal distance may be modified providing proof of performance is substantiated by dielectric tests.
3 Ground clearances for switches with voltages 362 kV and above are based on switching surge voltage levels. Refer to bibliography, Annex C.
4 The phase spacings in columns 6, 7, and 8 are recommended values. Overall width of switch and bus support energized parts, angle of opening of side break switches, etc., may allow a
reduction in phase spacing dependent upon voltage concentration on sharp projections. Resultant metal-to-metal distances between phase energized parts should not be less than that
shown in column 3.
5 Values not yet established.

16 Copyright 2002 by the National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 6 Station class outdoor air switch-pole unit dimensions


Copyright 2002 by the National Electrical Manufacturers Association

Rated Rated lighting Minimum length of break metal-to-metal1 Minimum insulator centerline-to-centerline spacing1
maximum Impulse
voltage withstand Single break insulator strength Double break Insulator strength
voltage Single break distance Double break distance
Standard High Standard High
Line kV rms kV Peak mm (inches) mm (inches) mm (inches) mm (inches) mm (inches) mm (inches)
Number (1) (2) (3) (4) (5) (6) (7) (8)
1 8.3 95 178 (7) Note 2 305 (12) 381 (15) Note 2 Note 2
2 15.5 110 254 (10) " 381 (15) 457 (18) " "
3 27 150 305 (12) " 457 (18) 533 (21) " "
4 38 200 457 (18) 305 (12) 610 (24) 686 (27) 457 (18) 533 (21)
5 48.3 250 559 (22) 381 (15) 762 (30) 838 (33) 585 (23) 610 (24)
6 72.5 250 559 (22) 381 (15) 762 (30) 838 (33) 585 (23) 616 (24)
7 350 813 (32) 559 (22) 1070 (42) 1140 (45) 762 (30) 864 (34)
8 123 350 813 (32) 559 (22) 1070 (42) 1140 (45) 762 (30) 864 (34)
9 450 Note 2 Note 2 1300 (51) 1370 (54) 889 (35) Note 2
10 550 1270 (50) 813 (32) 1520 (60) Note 2 1070 (42) "
11 145 350 813 (32) 559 (22) 1070 (42) 1140 (45) 762 (30) 864 (34)
12 450 Note 2 Note 2 1300 (51) 1370 (54) 889 (35) Note 2
13 550 1270 (50) 813 (32) 1520 (60) Note 2 1070 (42) "
14 650 1520 (60) 965 (38) 1830 (72) 1220 (48) "
15 170 450 Note 2 Note 2 1300 (51) 1470 (54) 889 (35) Note 2
16 550 1270 (50) 813 (32) 1520 (60) Note 2 1070 (42) "
17 650 1520 (60) 965 (38) 1830 (72) " 1220 (48) "
18 750 1730 (68) 1120 (44) 2030 (84) " 1370 (54) "
19 245 550 1270 (50) 813 (32) 1520 (60) Note 2 1070 (42) Note 2
20 650 1520 (60) 965 (38) 1830 (72) " 1220 (48) "
21 750 1730 (68) 1120 (44) 2130 (84) " 1370 (54) "
22 900 2130 (84) 1270 (50) 2440 (96) " 1730 (68) "
23 1050 2640 (104) 1450 (57) 2950 (116) " 1900 (75) "
24 362 1050 2640 (104) 1450 (57) 2950 (116) Note 2 1900 (75) Note 2
25 1300 3050 (120) 1680 (66) 3350 (132) " 2130 (84) "
26 550 1550 Note 2 Note 2 Note 2 Note 2 Note 2 Note 2
27 1800 " " " " " "
28 800 2050 Note 2 Note 2 Note 2 Note 2 Note 2 Note 2

NOTES
1 The design of some switches may be such that minimum metal-to-metal distances and centerline-to-centerline spacing conflicts. Where this occurs, minimum metal-to-metal distance
should be used. Minimum metal-to-metal distances may be modified provided proof of performance is substantiated by dielectric tests.
2 Values not yet established.

ANSI C37.32-2002
17

Copyright 2002 by the National Electrical Manufacturers Association 17

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

ANSI C37.32-2002
18

Table 7 Station class outdoor air switches preferred mounting hole spacing for 600, 1200, and 1600 ampere switches

Rated maximum Hook stick Single side break Vertical break


voltage
A B A B A B
Line kV rms mm (inches) mm (inches) mm (inches) mm (inches) mm (inches) mm (inches)
number (1) (2) (3) (4) (5) (6) (7)
1 8.3 457 (18) 51 or 178 (2 or 7) 610 (24) 76 or 178 (3 or 7) 914 (36) 76 or 178 (3 or 7)
2 15.5 533 (21) 51 or 178 (2 or 7) 610 (24) 76 or 178 (3 or 7) 914 (36) 76 or 178 3 or 7)
3 27 610 (24) 51 or 178 (2 or 7) 686 (27) 76 or 178 ( 3 or 7) 991 (39) 76 or 178 (3 or 7)
4 38 762 (30) 51 or 178 (2 or 7) 838 (33) 76 or 210 (3 or 8-1/4) 1220 (48) 76 or 210 (3 or 8-1/4)
5 48.3 991 (39) 76 or 210 (3 or 8-1/4) 991 (39) 76 or 210 (3 or 8-1/4) 1370 (54) 76 or 210 (3 or 8-1/4)
6 72.5 1290 (51) 76 or 210 (3 or 8-1/4) 1290 (51) 76 or 210 (3 or 8-1/4) 1750 (69) 76 or 210 (3 or 8-1/4)
7 123 1680 (66) 76 or 210 (3 or 8-1/4) 1830 (72) 210 (8-1/4) 2210 (87) 210 (8-1/4)
8 145 1980 (78) 76 or 210 (3 or 8-1/4) 2130 (84) 210 (8-1/4) 2510 (99) 210 (8-1/4)
9 170 2290 (90) 210 (8-1/4) 2440 (96) 210 (8-1/4) 2820 (111) 210 (8-1/4)

NOTES
1 "A" Is the dimension along the length of the base and "B" is the dimension along the width of the base.
2 Dimensions for switches above 170 kV not yet established.
Copyright 2002 by the National Electrical Manufacturers Association

18 Copyright 2002 by the National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 8 Preferred voltage ratings for distribution class outdoor air switches

Rated withstand voltages


Rated
maximum Lightning Power frequency
voltage impulse kV rms
dry wet
Line kV rms kV Peak 1 minute 10 seconds
Number (1) (2) (3) (4)
1 8.3 75 28 24
2 15.5 95 38 30
3 27 125 60 50
4 38 150 70 60

Table 9 Preferred continuous and withstand currents for


distribution class outdoor air switches

Withstand currents
Rated continuous current Short-time Peak
Line 60 Hz 50 Hz
Number amperes kA kA kA
(1) (2) (3) (4)
1 200 or 600 12.5 32.5 31.3
2 600 or 1200 25 65 63
3 1200 38 99 95

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 19

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002
20

ANSI C37.32-2002
Table 10 Phase spacing and ground clearance for distribution
class outdoor air switches and bus supports

Rated Minimum metal-to-metal Centerline-to-centerline phase spacing


Rated lightning distance, all disconnecting Vertical break Side break All horn
Maximum impulse switches, bus supports, Ground clearance disconnecting (horizontal break) gap switches
Line Voltage withstand and switches and disconnecting (vertical and side
Number voltage rigid conductors Recommended Minimum bus supports switches break)
kV rms kV Peak mm (inches) mm (inches) mm (inches) mm (inches) mm (inches) mm (inches)
(1) (2) (3) (4) (5) (6) (7) (8)
1 8.3 75 127 (5) 114 (4.5) 102 (4.0) 305 (12) 457 (18) 610 (24)
2 15.5 95 178 (7) 152 (6.0) 127 (5.0) 457 (18) 559 (22) 711 (28)
3 27 125 229 (9) 191 (7.5) 165 (6.5) 610 (24) 660 (26) 965 (38)
4 38 150 305 (12) 254 (10.0) 229 (9.0) 762 (30) 813 (32) 1,120 (44)

NOTE The phase spacings in columns 6, 7 and 8 are recommended values. It is recognized that at certain points of application these values may be reduced. Overall width of switch and bus
Copyright 2002 by the National Electrical Manufacturers Association

support energized parts, angle of opening of side-break switches, and the like, may allow a reduction in phase spacing, depending on voltage stress concentration on sharp projections.
Minimum metal-to-metal distances may be modified provided proof of performance is substantiated by dielectric tests.

20 Copyright 2002 by the National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 11 Distribution class outdoor air switches-pole unit dimensions


Copyright 2002 by the National Electrical Manufacturers Association

Rated Rated lightning Minimum length of break Minimum insulator centerline-to-centerline


maximum impulse withstand metal-to-metal spacing
voltage voltage Single break Double break Single break Double break
distance distance distance distance
Line kV rms kV Peak mm (inches) mm (inches) mm (inches) mm (inches)
Number (1) (2) (3) (4) (5) (6)
1 8.3 75 127 (5) - 229 (9) -
2 15.5 95 178 (7) - 279 (11) -
3 27 125 229 (9) - 330 (13) -
4 38 150 305 (12) 203 (8) 406 (16) 305 (12)

NOTE The design of some switches may be such that the minimum metal-to-metal distances and the centerline-to-centerline spacing conflict. Where this occurs, the minimum metal-to-metal
distance should be used. Minimum metal-to-metal distances may be modified provided proof of performance is substantiated by dielectric test.

ANSI C37.32-2002
21

Copyright 2002 by the National Electrical Manufacturers Association 21

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 12 Preferred voltage ratings for indoor air switches

Rated withstand voltages


Power frequency
Rated maximum Lightning kV
voltage impulse
Dew Dry
Line kV rms kV Peak 10 seconds 1 minute
Number (1) (2) (3) (4)
1 4.8 60 15 19
2 8.3 75 24 28
3 15.5 95 26 38
4 15.5 110 30 50
5 27 125 40 60
6 38 150 Note 1 80

NOTE
1 Value has not been established. Consult manufacturer.

Table 13 Preferred continuous and withstand currents for indoor air switches

Withstand currents
Rated continuous current Short-time Peak
Line 60 Hz 50 Hz
Number amperes kA kA kA
(1) (2) (3) (4)
1 200 or 400 12.5 32.5 31.3
2 600 25 65 63
3 1200 38 99 95
4 2000 50 130 125
5 3000 63 164 158
6 4000 75 195 188
7 5000 100 260 250
8 6000 125 325 313

22 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 14 Indoor air switches and bus supports-phase spacing and length of break

Rated Minimum phase spacing metal-to- Minimum length of break


maximum metal clearance disconnecting air metal-to-metal single-break
1 2
voltage switches and bus supports Distances
Line kV rms mm (inches) mm (inches)
Number (1) (2) (3)
1 4.8 114 (4.5) 114 (4.5)
2 8.3 152 (6.0) 152 (6.0)
3 15.5 190 (7.5) 190 (7.5)
4 15.5 229 (9.0) 229 (9.0)
5 27 330 (13.0) 330 (13.0)
6 38 457 (18.0) 457 (18.0)

NOTES
1 Barriers may be used to provide additional safety during operation by preventing accidental contact with live parts. The provision
of adequate insulating barriers may allow a modification of these clearances. These minimum clearances may be modified
provided proof of performance is substantiated by dielectric test (with due consideration to the effects of electromagnetic forces)
in accordance with the values shown in columns 2 and 4 of table 12.
2 Minimum metal-to-metal distances may be modified from the values listed above provided proof of performance is substantiated
by the dielectric tests in accordance with C37.34.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 23

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Table 15 Grounding switch electrical clearance

Rated Rated lightning impulse Minimum gap -


maximum voltage withstand voltage grounding switch
to live parts
Line kV rms kV Peak mm (inches)
Number (1) (2) (3)
INDOOR
1 4.8 60 51 (2)
2 8.3 75 51 (2)
3 15.5 95 51 (2)
4 15.5 110 51 (2)
5 27 125 76 (3)
6 38 150 102 (4)
DISTRIBUTION CLASS OUTDOOR
7 8.3 75 51 (2)
8 15.5 95 51 (2)
9 27 125 76 (3)
10 38 150 102 (4)
STATION CLASS OUTDOOR
11 8.3 95 51 (2)
12 15.5 110 51 (2)
13 27 150 102 (4)
14 38 200 152 (6)
15 48.3 250 241 (9.5)
16 72.5 250 241 (9.5)
17 350 367 (14)
18 123 350 367 (14)
19 450 457 (18)
20 550 559 (22)
21 145 350 367 (14)
22 450 457 (18)
23 550 559 (22)
24 650 686 (27)
25 170 450 457 (18)
26 550 559 (22)
27 650 686 (27)
28 750 787 (31)
29 245 550 559 (22)
30 650 686 (27)
31 750 787 (31)
32 900 965 (38)
33 1050 1120 (44)
34 362 1050 1190 (47)
35 1300 1270 (50)
36 550 1550 1910 (75)
37 1800 2160 (85)
38 800 2050 2850 (112)

NOTE These gap distances are not a requirement for grounding blades that operate in a plane perpendicular to the main switch base,

24 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

1
Table 16 Preferred rated switching currents for interrupter switches

Rated Unloaded Line-charging current Isolated Cable-


maximum Load and transformer capacitor charging
voltage loop current current Quick-break Interrupter bank current current

Line kV rms amperes amperes amperes4 amperes5 amperes6 amperes


Number (1) (2) (3) (4) (5) (6) (7)
1 8.3 RCC 2 Note 3 10 10 400 10
2 15.5 RCC 2 Note 3 10 10 400 15
3 27 RCC 2 Note 3 10 10 400 20
4 38 RCC2 Note 3 10 10 250 20
5 48.3 RCC2 10 10 10 250 50
6 72.5 RCC2 10 13 15 630 80
7 123 RCC2 10 10 35 315 90
8 145 RCC2 8 8 50 315 100
9 170 RCC2 8 7 75 400 100
10 245 RCC2 8 5 150 400 115
11 362 RCC2 5 - 350 - -

NOTES
1 Interrupter switches may have one or more specifically assigned switching ratings. Refer to Annex A for typical system values.
2 RCC = rated continuous current from tables 3, 9 or 13.
3 These switches are capable of switching unloaded transformers rated 2500 kVA or less provided the switches have demonstrated
the ability to switch their rated load current. For larger transformers or switches not having load switching ratings, consult
manufacturer.
4 These devices are typically high-velocity whips or rigid arm devices, having unconfined arcs with air as the dielectric medium and
are usually inserted in the circuit during the opening process.
5 These devices are interrupters with gas, vacuum, or oil as the interrupting medium.
6 Values given are for station class switches. Preferred ratings for distribution class switches have not been established. Consult
manufacturer.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 25

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

1,2,3,10
Table 17 Preferred rated control voltages and their ranges
Voltage range, volts
4 5
Rated voltage, volts Operating and auxiliary function Tripping function
6,7
Direct current
8
12 10-14 7-14
8
24 20-28 14-28
8
48 36-56 28-56
125 90-140 70-140
250 180-280 140-280
9
Single-phase alternating current (60 Hz)
120 104-127 -
240 204-254 -
480 416-508 -
9
Poly-phase alternating current (60 Hz)
208Y/120 180Y/104-220Y/127 -
240 208-254 -
480 416-508 -
480Y/277 416Y/240-508Y/292 -

NOTES
I Electrically operated motors, contactors, solenoids, valves, and the like, need not carry a nameplate voltage rating that
corresponds numerically to the rated voltage shown in table 17 as long as these components perform the intended duty cycle
(usually intermittent) in the voltage range specified.
2 Relays, motors, or other auxiliary equipment that function as part of the control for a device shall be subject to the voltage limits
imposed by this standard, whether mounted at the device or at a remote location.
3 Switchgear devices in some applications may be exposed to control voltages exceeding those specified here due to abnormal
conditions such as abrupt changes in line loading. Such applications require specific study, and manufacturer should be
consulted. Also, application of switchgear devices containing solid-state components exposed continuously to control voltages
approaching the upper limits of ranges specified herein require specific attention, and the manufacturer should be consulted
before an application is made.
4 Operating functions include (a) the opening and closing power mechanisms, and (b) the means (coils, contactors, seal-in relays,
and the like) to actuate the power mechanisms. Auxiliary functions include all functions except operating and tripping.
5 Tripping is the release of the holding means that permits stored energy to open a device such as an interrupter switch or close a
device such as a fault initiating switch.
6 It is recommended that the coils of operating, auxiliary, and tripping devices that are connected permanently to one direct-current
potential should be connected to the negative control bus to minimize electrolytic deterioration.
7 Power-operated mechanisms utilizing 12 and 24 V self-contained direct-current control sources shall operate over the range of 85
percent to 115 percent of the rated voltage.
8 12, 24, or 48-volt tripping, operating, and auxiliary functions are recommended only when the device is located near the battery or
where special effort is made in order to provide due consideration to battery location and cable size.
9 Includes heater circuits.
10 For 50 Hz application, consult manufacturer.

26 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

NOTES
1 Two or more interleaved 4-hole pad configurations can be used as shown in figure 1(b).
2 All dimensions are in millimeters and (inches).
3 Holes shall accommodate bolts that are inch (12mm) in diameter.

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 27

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

NOTES
1 All dimensions are in millimeters and (inches).
2 Dimensions that are not shown are optional.

28 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Annex A
(informative)
Reference data

A.1 Peak withstand current replaces momentary current. Short-time withstand current replaces 3
second current. The ratio of the peak withstand current to short time (symmetrical) withstand
current is 2.6 for 60 Hz and 2.5 for 50 Hz.

A.2 Typical system values for cable and line charging currents

Rated Overhead Typical Line Cable


maximum line line charging charging
voltage current length current current
kV rms A/mile miles amperes A/mile
8.3 0.03 10 0.3 1.5
15.5 0.06 10 0.6 2.8
27 0.10 20 2.0 3.2
38 0.14 30 4.2 3.5
48.3 0.17 30 5.1 9.8
72.5 0.28 50 14.0 15.7
123 0.44 80 35.2 18.2
145 0.52 100 52.0 19.4
170 0.61 120 73.2 20.0
245 0.87 170 147.9 22.3
362 1.31 250 327.5 -

A.3 Short-time withstand current and electromagnetic force equations

A.3.1 Calculation of short-time withstand current limits

The following formulas may be used as guides for calculating short-time withstand current capability of uniform conductors
based on thermal capacities assuming no heat loss during the time of current flow.

The formula for aluminum is written for conductivities between 40 to 65 percent of the International Annealed Copper
Standard (IACS). The formula for copper is written for conductivities of 95 to 100 percent IACS.

1 20 + (15150 / G)
I al = 0.144 10 6 A log10 2
t 1 20 + (15150 / G)

1 20 + (25400 / G)
I cu = 0.22 10 6 A log10 2
t 1 20 + (25400 / G)

Where:
Ial = maximum rms amperes for aluminum conductor
Icu = maximum rms amperes for copper conductor
A = cross-sectional area in square inches
t = the duration of constant current flow in seconds
2 = the temperature limit (degrees Celsius)
1 = is the starting temperature (degrees Celsius)
G = the conductivity in percent IACS

NOTES

1 The temperature limit (2) of materials may be determined by mechanical requirements since annealing of heat-treated or
hard drawn material occurs in relatively shorter time as temperature is increased.
For current carrying parts when t = 3 seconds and Ial or Icu = symmetrical rms amperes associated with the short-time
withstand current ratings from table 3, 9 or 13, typical temperature values to minimize annealing are:

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 29

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

2 = 250 oC for heat-treated aluminum alloy


2 = 300 oC for hard-drawn copper
2 1 should be no more than max of C37.30.
3 Other materials available for current-carrying parts may have other values for 1 and 2. Such materials are acceptable
provided it can be demonstrated that the switch meets the short time current requirements of C37.30 and C37.34.

A.3.2 Calculation of electromagnetic forces

The electromagnetic force exerted between two current-carrying conductors is a function of the current, its decrement rate,
the shape and arrangement of conductors, and the natural frequencies of the complete assemblies, including mounting
structure, insulators, and conductors.

Obviously, it is not feasible to cover every case with one simple equation, even if some approximations are made, because
of the large number of variables involved including the wide range of constants for support structures.

The force calculated by the following equation is that produced by the maximum peak current. In most cases, the
calculated force is higher than that which actually occurs due to inertia and flexibility of the systems, and this fact tends to
compensate for the neglect of resonant forces. The equation, therefore, is sufficiently accurate for usual practical
considerations.

5.4 I 2
F = M
S 10
7

F = force in pounds per foot on conductor


M = multiplying factor shown in following table
I = short-circuit current in amperes expressed in terms shown in table
S = spacing between center-lines of conductors in inches

Multiplying factor (M) for calculation of electromagnetic forces

Circuit Amperes (I) expressed as: Multiplying factor (M)


dc maximum peak 1.0
ac, 3-phase maximum peak 0.866
2
ac, 3-phase rms asymmetrical (0.866 x 1.63 ) = 2.3
2
ac, 3-phase rms symmetrical (0.866 x 2.82 ) = 6.9
1 phase of 3-phase or 1 -phase maximum peak 1.0
2
1 phase of 3-phase or 1 -phase rms asymmetrical (1.63 ) = 2.66
2
1 phase of 3-phase or 1 -phase rms symmetrical (2.82 ) = 8.0

30 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Annex B
(Informative)
Historical Data

CopyrightManufacturers
Copyright 2002 by the National Electrical 2003 IEEE All Rights Reserved
Association 31

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.32-2002

Annex C
(Informative)
Bibliography

ANSI C2-1999 National Electrical Safety Code

AIEE Committee Report A Guide for Minimum Electrical Clearances for Standard Basic Insulation
Levels. Part III (PAS) Vol. 73, June 1954.

IEEE Substation Committee Safety Aspects in Substation Voltage Uprating by Substation Committee
Working Group E1: Recommended minimum clearances in substations,
IEEE Transactions on Power Delivery, July 1992, Vol. 7, No. 3, pp. 1250-
1255.

32 Copyright 2003
Copyright IEEE
2002 All Rights
by the Reserved
National Electrical Manufacturers Association

Authorized licensed use limited to: CHILECTRA. Downloaded on October 13,2010 at 18:53:35 UTC from IEEE Xplore. Restrictions apply.

You might also like