Design Data
Design Data
OF
DOMESTIC BUILDINGS
Details Lux
Living 300
Dining 150
Study 300
Bedroom: General 300
Dressing 200
Kitchen 200
Bath 100
Staircase 100
Garage 70
Entrance: Hallways 100
Games & Recreation 100
Sewing 300
CINEMA HALLS
Details Lux
Foyers 150
Auditoria 50
Corridors 70
Stairs 100
ASSEMBLE & CONCERT
Details Lux
Foyers 150
Auditoria 50
Corridors 70
Stairs 100
Art Gallery: General 150
Painting 200
Museums 150
INDUSTRIAL BUILDINGS
Details Lux
Entrance 100
Corridors 100
Stairs 100
Outdoor 20
General: Rough work area 150
Medium work 300
Fine work 700
Precision work 1500
Boiler area 100
Control room 300
Conveyers 50
Ware houses 100
Packing & Dispatch 150
Boiler rooms 100
Transformer yard 100
Forges 150
Lab & test room 450
Painting works 300
Sheet metal work 200
Welding (General) 150
Fine welding 300
Soldering 300
TEXTILE MILLS
Details Lux
General, Dyeing 200
Winding, Twisting 200
Spinning 450
Weaving 700
Inspection 700
Bakeries 100
HOSPITAL
Details Lux
(a) Reception & waiting rooms 150
(b) Wards : General 100
Bed 150
(c) Operation Theatres: General 300
Tables & chairs Special lighting
(d) Laboratories 300
(e) Radiology 100
(f) Causality & OP 150
(g) Dispensaries 300
(h) Stairs 100
Doctors Surgeries:
(a) Consulting room 150
(b) Corridors 100
(c) Sight testing 450
Laundries & Dry Cleaning
(a) Receiving, sorting washing, drying 200
(b) Dry cleaning 200
(c) Ironing, mending pressing etc. 300
(d) General offices 300
(e) Drawing offices 450
(f) Kitchens 200
LAMP DATA
ELECTRICAL APPLIANCES
LAMP DATA FOR HALOGEN, SODIUM VAPOUR, MERCURY VAPOUR & FL. TUBES
PROTECTION OF TRANSFORMERS
Capacity of
Method of Secondary side Control &
11 kV/ 433 V Primary side Control & Protection
installation Protection
Transformer
Outdoor AB Switch, L.A., D.O. fuse 800/1200A,25 MVA ACBs
drawout type with 3 O/C +1 E/F
Up to and
Oil SFU/ AB SFUs 250MVA, 400A inbuilt releases and low set E/F
including
Indoor CBs with 2 O/C & one instantaneous Protection using neutral CT, D/C
630 kVA
E/F Relays with D.C. Trip trip or A/C trip with wide range
pick up
1200/1600A,31 MVA ACBs
Above drawout type with 3 O/C +1 E/F
250 MVA 800A CBs preferably VCBs
630 kVA but inbuilt releases and low set E/F
Indoor only with 2 O/C & one instantaneous E/F
below Protection using neutral CT, D/C
Relays with D.C. Trip
1000 kVA trip or A/C trip with wide range
pick up
250 MVA 800A CBs preferably VCBs
1600/2500A,50 kA drawout type
with 2 IDMT O/C Relays with high
ACBs with 3 O/C +1 E/F inbuilt
set elements & instantaneous E/F
1000 kVA and releases and low set E/F
Indoor only Relays, Bucholtz Relays, Oil
above Protection using neutral CT, 2
temperature alarm and trip, winding
O/C +1 E/F Relays, REF Relays
temperature alarm and trip with D.C.
with DC trip.
trip
RATING OF TRANSFORMERS
SWITCH BOARDS
GENERATOR PROTECTION
Capacity Protection
Below 100
MCB / MCCB
kVA
100 kVA to 400
MCCB and low set standby E/F relay using CT in neutral earthing conductor.
kVA
401 kVA to
ACB with thermal O/L and E/F releases, low set standby E/F relay using CT in neutral
below 1000
earthing conductor.
kVA
ACB with thermal O/L, Voltage controlled O/L relay, over voltage, under voltage,
1000 kVA and
negative sequence, low set standby E/F relays and REF/Differential relay with fuel shut
above
off facilities, Over speed protection shall be provided for engine.
FEEDER CABLES
Busbar Size
Switch Board Rating
in mm
Amps
Phase Neutral
100 25x6 25x6
125 25x6 25x6
200 38x6 25x6
250 50x6 25x6
315 63x6 38x6
400 2x38x6 38x6
500 2x50x6 50x6
600 2x63x6 63x6
2x50x9 50x9
800
2x75x6 75x6
2x75x9 75x9
1000
3x50x9 2x50x6
125x12 100x9
1250
2x75x12 1x75x12
2x100x9 1x100x12
1600
3x75x9 2x75x9
2000 2x100x12 1x100x12
2x125x12 1x125x12
2500
3x100x12 2x100x9
3x100x12 2x100x9
3200
2x152x12 1x152x12
4000 4x125x12 2x125x12
CABLE CODE
Constituent Code
Aluminum Conductor A
XLPE insulation 2X
PVC insulation Y
Steel round wire armoured W
Non- Magnetic round wire armoured Wa
Steel strip armoured F
Non- Magnetic strip armoured Fa
Double steel; round wire armoured FF
(b) ALUMINUM CONDUCTOR 3 CORE PVC INSULATED PVC SHEATHED ARMOURED / UNARMOURED CABLES 650 / 1100 VOLTS
(c) ALUMINUM CONDUCTOR 4 CORE PVC INSULATED PVC SHEATHED ARMOURED / UNARMOURED CABLES 650 / 1100 VOLTS
CURRENT CARRYING CAPACITIES AND ASSOCIATED VOLT DROP PER AMP PER METRE
(a) Armoured PVC Insulated Cable with Copper Conductor
FLEXIBLE HOUSE WIRING SINGLE CORE CABLES (WITH COPPER CONDUCTOR 250 /440V)
No & size Thickness Overall Dia.
Conductor Normal Resistance in Current carrying Equivalent Insulation
of wire in Insulation Sheath Unsheathed Sheathed
are in Sq. mm. Ohm/km capacity in Amps. SWG Thickness mm.
mm. mm. mm. mm. mm.
1.0 14/.3 18.89 11 0.9 0.65 3.00 4.55 1/18 0.9
1.6 23/.3 11.50 15 0.9 0.65 3.50 4.80 3/22 0.9
2.0 28/.3 9.42 17 0.9 0.65 3.90 5.40 3/20 0.9
3.0 44/.3 6.00 22 1.0 0.75 4.15 5.55 7/22 0.9
4.5 65/.3 4.06 26 1.0 0.75 4.90 6.10 7/20 1.0
OVERHEAD LINES
SAFETY CLEARANCE
(a) Transmission Lines
* For EHV lines ,the clearance above ground shall not be less than 5.182 metres plus 0.305 metres for every 33kV or part there of by which the voltage of
the line exceeds 33kV
The minimum clearance along or across any street shall not be less than 6.096 metres.
(b) Substations
EHT line (kV) Recommended width of right of way (mm) Min. Clearance between conductors and tress (m)
66 18 3.4
110 22 3.7
220 35 4.6
400 52 5.5
Stranding and Winding Dia. Ultimate Strength Resistance at 20 oC Weght Current rating Aluminum area (Sq.
Code Name
(mm) (mm) (kg) (Ohm/km) (kg/km) (Amps) mm.)
Rose 7/1.96 5.9 415 1.351 57.7 100 21.2
Gnat 7/2.21 6.6 490 1.064 73.4 118 26.8
Iris 7/2.47 7.4 635 0.85 91.8 131 33.6
Lady bird 7/2.79 8.4 740 0.665 117.3 159 42.9
Ant 7/3.1 9.3 890 0.541 144.3 182 52.8
Fly 7/3.4 10.2 1050 0.449 174 207 63.7
Blue Bottle 7/3.66 11 1195 0.388 201 225 73.6
Earwing 7/3.78 11.3 1275 0.263 215.3 28 78.8
Grass
7/3.91 11.7 1355 0.339 229.9 250 84.1
Hopper
May bug 37/4.09 28.6 7289 0.0598 1343 764 473.6
37/4.27 29.9 7878 0.0549 1464 805 518.4
Scorpion
37/4.53 31.8 12200 0.0476 1650 885 597