Frost Protected Shallow Foundations FINAL
Frost Protected Shallow Foundations FINAL
Grade
www.PHRC.psu.edu
PENNSYLVANIA HOUSING RESEARCH CENTER
ASSUMPTIONS AND LIMITATIONS vertical insulation R-value. The footing depth shown is
the minimum required for meeting the structural intent
This document does not address unheated build- of preventing frost heave and may be exceeded by the
ings or crawlspaces. insulation depth requirements from energy code provi-
sions.
Buildings must maintain minimum average monthly
indoor temperature greater than 64F. Figure 2 shows the depth below grade of a monolithic
slab that is designed to meet the FPSF requirements.
FPSF insulation requirements may not meet current
Again, this depth is a minimum. The insulation shown
energy codes; therefore, consult currently enforce-
in Figure 2 must extend to the top of the foundation,
able energy code requirements.
including above-grade portions. This insulation must be
protected by an appropriate covering.
FPSF DESIGN CRITERIA
Table 1 also shows the minimum vertical insulation R-
The simplified approach to FPSF design found in the value for FPSF systems. This is the minimum insulation
2009 IRC is based on variables of Air Freezing Index required to direct building heat loss to the surrounding
(AFI), insulation R-value, and footing depth. soil in order for FPSF systems to function properly. The
Air Freezing Index is a value which indicates the inten- insulation specified to meet these requirements must
sity of below-freezing temperatures occurring during a be suitable for ground contact. Typically, expanded
given heating season. This value is regionally specific. polystyrene (EPS) or extruded polystyrene (XPS) is used
Table 1 shows varying AFI values for each county in for this purpose.
Pennsylvania. All regions within Pennsylvania have an As mentioned previously, the insulation required per
AFI less than 2,000. Many FPSF designs require hori- Table 1 is the minimum amount to be provided in order
zontal insulation extending away from the structure in to ensure the foundation is protected from frost pen-
addition to vertical insulation. In regions with an AFI less etration and frost heave in heated buildings. In many
than 2,000, however, only vertical insulation is neces- instances, this R-value and depth would be exceeded
sary. by currently enforceable energy code requirements. In
Based on the AFI of a specific county in Pennsylvania, all cases, currently enforceable code requirements and
Table 1 also lists the minimum footing depth and the local amendments must be followed.
1
Air Freezing Index by Pennsylvania County
AFI=2000
Berks, Blair, Bradford, Cambria, Cameron, Centre, Clarion,
Clearfield, Clinton, Crawford, Elk, Forest, Huntingdon, Indi- D
ana, Jefferson, Lackawanna, Lycoming, McKean, Pike, Potter,
Susquehanna, Tioga, Venango, Warren, Wayne, Wyoming
AFI=1500 or less
Adams, Allegheny, Armstrong, Beaver, Bedford, Bucks, Butler,
Carbon, Chester, Columbia, Cumberland, Dauphin, Delaware, Figure 2: Frost protected shallow foundation depth and
Erie, Fayette, Franklin, Fulton, Greene, Juniata, Lancaster, insulation placement requirements
Lawrence, Lebanon, Lehigh, Luzerne, Mercer, Mifflin, Mon- Note: Depth below grade = D. Insulation must extend to top
roe, Montgomery, Montour, Northampton, Northumberland, of foundation wall. Depth requirements also apply to stem
Perry, Philadelphia, Schuylkill, Snyder, Somerset, Sullivan, wall construction. Energy code requirements may exceed
Union, Washington, Westmoreland, York insulation depth and R-value requirements shown in Table 1.
www.PHRC.psu.edu Page 2
PENNSYLVANIA HOUSING RESEARCH CENTER
Vertical insulation to
meet energy code and
FPSF requirements
Vertical insula-
tion to meet FPSF
requirements
Horizontal insulation to
meet energy code
requirements
www.PHRC.psu.edu Page 3
PENNSYLVANIA HOUSING RESEARCH CENTER
FPSF WITH HEATED SLABS there is a practical limit to the amount of insulation that
can be placed under the slab before this heat loss is no
In Figures 3 and 4, common scenarios were outlined longer contributing to this effect. In general, under slab
regarding the comparison of FPSF and energy code re- insulation should be limited to R-10 in order to provide
quirements. Another scenario that is common in Penn- an appropriate FPSF. Figure 5 shows this scenario. In
sylvania would involve the inclusion of heating elements this case, R-10 insulation is required for energy code
in the slab adjacent to the FPSF. Energy codes typically provisions, but this insulation must be placed vertically
require the additional placement of insulation under on the outside of the foundation with R-5 insulation
heated slabs. Since FPSF systems rely on heat loss from placed under the heated slab.
the building to raise the surrounding soil temperature,
Horizontal insulation to
meet heated slab
requirements
Vertical insulation to
meet energy code and
FPSF requirements
SUMMARY REFERENCES
International Code Council (ICC). 2009. 2009 International Residential
Frost protected shallow foundations are a feasible and
Code for One-and-Two Family Dwellings. Washington, DC: Interna-
code-approved alternative to traditional deep founda-
tional Code Council.
tions in Pennsylvania. However, the nuances of this ap-
proach, including the stringency of energy codes, leave American Society of Civil Engineers. 2001. Design and Construction of
this as a niche option for a specific set of scenarios. It is Frost-Protected Shallow Foundations (32-01). Reston, VA: American
important to understand the assumptions and limita- Society of Civil Engineers
tions to this approach in order to provide a durable and NAHB Research Center, Inc. 2004. Revised Builders Guide to Frost
energy-efficient foundation assembly. Protected Shallow Foundations. Upper Marlboro, MD: NAHB Research
Center, Inc.