loads in kips
indicates loads
Qu:- Do you want the additional Vertical DL to act against the uplift? YES!
F.O.S on uplift and Overturning 1.50
Design assumes self wt of Pad found & user inputed load resists Uplift!
D/6 = 1 Stem/Peir moment induced by max ecc 7.525 kips-ft ecc = 1 inch
e = 0.08 concrete peir/stem wt 4.38 kips
Max Base Pressure 2.839 ksf OK!
Min Base Pressure 2.421 ksf
F.O.S on over turning 37.74 OK!
Plan View
Factor of Safety for design 1.5
Plinth wt kN 1.215
Horiz Shear @ base kN 0
Column Axial load kN 90.3
Max Design Axial Force kN 137.3 (factored loads)
Max Design Bending Moment kNm 11.287 (factored loads)
where Vmax is greater than Critical Shear, more than min links are req'd, ELSE IGNORE!
cl 3.4.5.12 100As/bd from table 3.8, vc = N/mm (this includes fcu increase factor)
formula 6b vc' = N/mm v= N/mm
Min Req'd!! Provide links of 8 mm Dia Bars @ 150 Crs Vert, ( 2 legs) SHT. OF
Plinth Design NOT VALID!! 2 4
CLIENT
Max Stress
REINFORCEMENT DESIGN FOR METRIC UNITS
2.839
lever arms Max Design Bending Moment 17.03 kNm Re-bar strength, fy 420 N/mm
L1 0.925
L2 1.850 User Inputted top steel Moment 0 kNm Re-bar cover 50 mm
Is the edge beam adequatly tied for Uplift? effective depth 1930 mm
Design for a metre width of foundation (depth- cover- tens steel Bar size)
for B/M 17.03 kNm
M/bd = 0.00 for B/M 0 kNm
K=M/bdfcu, K= 0.00013 M/bd = 0.00
z max = 0.95d, 1833.50 K=M/bdfcu, K= 0.00000
K'= 0.156 z max = 0.95d 1833.5
No Comp steel req'd if K<=K', z = 1930
if K<=K', z = 1929.70 z for design = 1834
if K>K', z = 1499.40 if Tens Steel only
z for design = 1833.50 As= 0
if Tens Steel only Min Areas of steel
As= 23.30 As in the comp zone 0
if Comp steel req'd % of Concrete area 0.000%
As= 6613.6 Min % req'd 0.13% Thus
As'= -27381.5 Area of Steel 0
Min Areas of steel
ten steel area to use 23
% of Concrete area 0.001%
Area of Ten Steel 2509 Bottom Steel Req'd 2509.00 mm/m
Area of Comp Steel 0 Top Steel Req'd 0.00 mm/m
Shear Check :- 6240 mm, length lies outwith the critical shear perimeter, no check req'd
Thus, No shear check req'd the Min of 0.8fcu, or 5 = N/mm
100As/bd from table 3.8, vc = N/mm (this includes fcu increase factor)
uniform soil pressure (SL) kN/m max load on side 'only' kN
vmax = V/ud N/mm @ plinth/Pedestal edge, Perimeter, u = mm
assumed the crit per mm Area within C.P m the base area m
Average shear on C.P kN (= the diff in area * soil pressure * f.o.s)
value THUS v = shear on C.P/( crit perimeter * d) N/mm
Since < which is <
20 @ 250
### @ 250
SHT. OF
Base Design NOT VALID!! 3 4
CLIENT
Plan View
Factor of Safety for design 1.6
where Vmax is greater than Critical Shear, more than min links are req'd, ELSE IGNORE!
Min Req'd!! Provide links of # 3 Dia Bars @ 12 Crs Vert, ( 2 legs) SHT. OF
Pedestal Design VALID! 2 4
CLIENT
Max Stress
REINFORCEMENT DESIGN FOR ENGLISH UNITS
2.839
lever arms Max Design Bending Moment 6.71 kip-ft Re-bar strength, 60000 psi
L1 0.583
L2 1.167 User Inputted top steel Moment 0 kip-ft Re-bar cover 2.5 in
Is the edge beam adequatly tied for Uplift? effective depth 20.75 in
Design for a ft width of foundation (depth- cover- tens steel Bar size)
# 6 @ 10 "
# @ "
As' p= in/ft
SHT. OF
3 4
CLIENT
2.5 ft Square
z
#9 bars, 5 Each Face.
2 in
Slab RL
z Ground RL
0.7 ft
#3 bars @ 12 Crs Vert (2 legs).
#0 bars @ 12 Crs Each Way.
6.00 ft
### ft
Lean Mix
Concrete to
Allowable Safe
6.00 ft Square Bearing.
SHT. OF
4 4
CLIENT
load in kips
indicates loads
out of plane Qu:- Do you want the additional Vertical DL to act against the uplift? YES!
base shear F.O.S on uplift and Overturning 1.50
Design assumes self wt of Pad found & user inputed load resists Uplift!
D/6 = 1 Stem/Peir moment induced by max ecc 7.258 kips-ft & 0.975 kips-ft
e = 0.09 concrete peir/stem wt 1.95 kips ecc = 1 inch
Max Base Pressure 2.680 ksf OK!
Min Base Pressure 2.267 ksf
F.O.S on over turning 32.44 OK!
Plan View
Factor of Safety for design 1.5
Plinth wt kN 1.215
Horiz Shear @ base kN 0
Column Axial load kN 87.1
Max Design Axial Force kN 132.5 (factored loads)
Max Design Bending Moment kNm 10.887 (factored loads)
where Vmax is greater than Critical Shear, more than min links are req'd, ELSE IGNORE!
cl 3.4.5.12 100As/bd from table 3.8, vc = N/mm (this includes fcu increase factor)
formula 6b vc' = N/mm v= N/mm
Min Req'd!! Provide links of 8 mm Dia Bars @ 150 Crs Vert, ( 2 legs) SHT. OF
Plinth Design NOT VALID!! 2 4
CLIENT
Max Stress
REINFORCEMENT DESIGN FOR METRIC UNITS
2.680
lever arms Max Design Bending Moment 16.05 kNm Re-bar strength, fy 420 N/mm
L1 0.925
L2 1.850 User Inputted top steel Moment 0 kNm Re-bar cover 50 mm
Is the edge beam adequatly tied for Uplift? effective depth 1930 mm
Design for a metre width of foundation (depth- cover- tens steel Bar size)
for B/M 16.05 kNm
M/bd = 0.00 for B/M 0 kNm
K=M/bdfcu, K= 0.00012 M/bd = 0.00
z max = 0.95d, 1833.50 K=M/bdfcu, K= 0.00000
K'= 0.156 z max = 0.95d 1833.5
No Comp steel req'd if K<=K', z = 1930
if K<=K', z = 1929.70 z for design = 1834
if K>K', z = 1499.40 if Tens Steel only
z for design = 1833.50 As= 0
if Tens Steel only Min Areas of steel
As= 21.90 As in the comp zone 0
if Comp steel req'd % of Concrete area 0.000%
As= 6612.3 Min % req'd 0.13% Thus
As'= -27382.8 Area of Steel 0
Min Areas of steel
ten steel area to use 22
% of Concrete area 0.001%
Area of Ten Steel 2509 Bottom Steel Req'd 2509.00 mm/m
Area of Comp Steel 0 Top Steel Req'd 0.00 mm/m
Shear Check :- 6240 mm, length lies outwith the critical shear perimeter, no check req'd
Thus, No shear check req'd the Min of 0.8fcu, or 5 = N/mm
100As/bd from table 3.8, vc = N/mm (this includes fcu increase factor)
uniform soil pressure (SL) kN/m max load on side 'only' kN
vmax = V/ud N/mm @ plinth/Pedestal edge, Perimeter, u = mm
assumed the crit per mm Area within C.P m the base area m
Average shear on C.P kN (= the diff in area * soil pressure * f.o.s)
value THUS v = shear on C.P/( crit perimeter * d) N/mm
Since < which is <
20 @ 250
### @ 250
SHT. OF
Base Design NOT VALID!! 3 4
CLIENT
Plan View
Factor of Safety for design 1.6
where Vmax is greater than Critical Shear, more than min links are req'd, ELSE IGNORE!
Min Req'd!! Provide links of # 3 Dia Bars @ 12 Crs Vert, ( 2 legs) SHT. OF
Pedestal Design VALID! 2 4
CLIENT
Max Stress
REINFORCEMENT DESIGN FOR ENGLISH UNITS
2.680
lever arms Max Design Bending Moment 9.72 kip-ft Re-bar strength, 60000 psi
L1 0.722
L2 1.443 User Inputted top steel Moment 0 kip-ft Re-bar cover 2.5 in
Is the edge beam adequatly tied for Uplift? effective depth 20.625 in
Design for a ft width of foundation (depth- cover- tens steel Bar size)
# 7 @ 12 "
# @ "
As' p= in/ft
SHT. OF
3 4
CLIENT
1.67 ft Square
z
#7 bars, 2 Each Face.
2 in
Slab RL
Ground RL
z
0.7 ft
#3 bars @ 12 Crs Vert (2 legs).
#0 bars @ 10 Crs Each Way.
6.00 ft
### ft
Lean Mix
Concrete to
Allowable Safe
6.00 ft Square Bearing.
SHT. OF
4 4